Bf1 fac= 1344.087
y
fac,cal= 13.146
fbc= 1618.467
D1 fbc,cal= 40.875
x x
Area= 213.000
Lamda < 120 Safe in Buckling
Tf1 Safe in Bending
Safe in Axial Compression
Safe in Axial Compression & Bending
y
Stress factor= 0.035
Safe in Deflection
Flanges Tf = 25.00 mm
Bf= 250.00 mm
Webs tw = 16.00 mm
d= 550.00 mm
Area= 213.00 cm2 xc = 30.00 cm
Ixx= 125503.65 cm 4
xt = 30.00 cm
Iyy= 6529.19 cm 4
Zxc = 4183.45 cm3
rx= 24.27 cm Zxt = 4183.45 cm3
ry= 5.54 cm
l-x= 43.46
l-y= 4.52
l max = 43.46 Lamda < 120 Safe in Buckling
d/tw= 34.38
T/t= 1.56
D/T= 24.00
file:///conversion/tmp/scratch/365022959.xlsx 09/07/2017
SECTION : STRUCTURAL PROJECT : BSSL : J-26
DESIGN CALCULATION NO. COMPUTED : Prakash
WI NO. /ZONE / SEC. CODE/NO CHECKED :
MEC/Q269/02/SA/001 DATE :
SHEET ________ OF __________
c1= 30.00
c2= 30.00
Value of k2 : as w = Iytf / ( Iytf + Iybf ) = 0.13
k2= 0.0 See Table 6.4
Value of k1 : as s = area of flanges at support/area of flanges at max.BMpt
No Curtailment s= 1.0
Refer Table 6.3
k1= 1.0
Y= 129708.67
X= 129823.64 MPA
fcb= 129823.64 MPA fy= 250.00 MPA
fbc= 1618.47 kg/cm