2.Chemical
3.Electrical
Dielectric dissipation
factor at 100C % D 924 0,3 0,1
Breakdown voltage
- Before treatment kV D 877 30 55
- After treatment kV D 1816 (0.04" gap) 28 35
Gassing tendency l/min D 2300B +30 <0
4.Oxidation Stability
After 72 h: D 2440
Sludge wt% 0,15 <0,02
Neutralization No mg KOH/g 0,5 0,15
After 164 h:
Sludge wt% 0,3 0,03
Neutralization No mg KOH/g 0,6 0,19
Nytro 10GBN is an uninhibited transformer oil, meeting the specifications ASTM D3487 type I, IEC 60296 (03)
General specifications and AS 1767.1-1999.