You are on page 1of 4

TM

Electronic Motor C&S


Protection Relays Controls & Switchgear

C UL
R

UL
R

TM

Marketed by Controls & Switchgear Co. Ltd.


Manufactured by
LG Industrial Systems Co. Ltd.
ELECTRONIC MOTOR PROTECTION RELAY

Inverse TIme Characteristics Type Definite Time Characteristics Type


Features Features
z Multiple protection over current / Phase Manual test & reset
z z Small size
failure / Stall / Asymmetry / Phase reverse function available (auto z Over current & phase failure
z Compact design & Elegant outlook reset option) protection
z Various current adjustment z Reverse phase & phase z Definite type characteristics
z Common use of the screw type & unbalance protection are z Wide current adjustment range
Tunnel type optional z Screw or Din-rail mounting
z Applicable to the inverter circuit z Time adjustment (0~30 sec) z Looping option can be used for
z Screw or 35mm Din-rail mounting range lower current
available z Certification : UL, CUL, CE z Delay time ( 0~30 ) & operating time
z Fault diaganose by LEDs indication in (0~15sec) setting
short time z Test & reset function available
z UL, CE & CUL certified product
Various Production
z Over current
z Phase current

Various Protection Functions


Protection GMP60T
Model Over Phase Stall Asymmetry Reverse TEST/ RESET button
current failure phase O.L LED
2S / 2T z z z - -
3S / 3T z z z z - D- TIME Knob
3SR / 3TR z z z z z
O - TIME Knob

Trouble shooting

RC (A) Knob

Trouble shooting

Ordering information (Type designations)

GMP 22 2 P R 220

Frame Current setting value Type CT No. Wring method Reverse phase Operational power
0.3~1.5A 2 2CT - Without reverse phase - AC100~260V
22 1~5A 3 3CT S Screw type protection 220 AC220V
Direct /
4.4~22A T Tunnel type R With reverse phase 110 AC110V
Screw / protection
4~20A Tunnel
40 8~40A
80 16~80A Screw

Frame Current setting value Type Operational power


0.5~6A 110 AC85~120V
60 3~30A Tunnel 220 AC180~260V
5~60A
DIGITAL MOTOR PROTECTION RELAY

Features
z MCU based compact Design & Elegant outlook z Parameter setting & Storing facilities
z Multiple protection z Use on single phase / 3 phase load / Motor
z Digital Ammetor
z Trouble shooting / Trip cause display on relay z Screw type and tunnel type both connection available
z Manual instance / Elect remote reset z Unit type & Extension type both models available
z Fail safe operation z Certification : UL, CE, CUL, CSA, Lloyd register
z Alert function ( 60~110% )
z Confirm standard IEC-60947-1
Inverse / Definite time characteristics
z C.T ratio setting in 05 type only
Multiple Protection
Protection DMP - S DMP -SZ DMP -SI DMP -SE DMP -SEZ DMP -SEI DMP -T DMP -TZ DMP -TI DMP -TE DMP -TEZ DMP -TEI
Wiring Screw type Tunnel type
Panel mount Unit type Extension type Unit type Extension type
Over current
Under current
Stall
Lock
Phase failure
Reverse phase
Asymmetry
Grount fault
Short circuit

Protect Function
Over current Depend on setting time Selectable the inverse/definite
Phase loss Within 3seconds Over 70% of the rate of unbalance
Phase unbalance Within 5seconds Over 50% of the rate of unbalance
Phase reverse Within 0.1seconds Function enable R Phase Digital display
Stall Within 5seconds Over 180% of the setting current S Phase
Lock Within 0.5seconds Setting 200~900% of rated current Bar graph
T Phase
Under current Within 3seconds Setting 30~70% of rated current
Instantaneous current Within 50m seconds Setting 300~1800% of rated current Display button
Test/Reset
Ground fault Within 1Second Setting 100~ 2500mA of rated current button
) Lock protection is operated after setting D-time in case of definite time type Set button
Function selection
FUNC
Function Selection Function Note button Time Knob
Inverse or definite time Default inverse time Current
characteristics characteristics Knob

Set the O-time For D-time setting,


(Definite time only) Use the time knod

Reverse phase protection Default is Off

Under current protection Default is Off (Note1)

Alarm function Default is Off


(With pre-alarm function)
Stall function Default is Off

Lock function Default is Off

CT ratio Default is 1:1 (Note2)

Phase failure Default is On

Ground fault Default is Off


Alert Function
) 2.dEF is only displayed when dEF is selected in a 1.CHA mode

DMP 06 - SEZ 220


DMP
06 S E Z 220

Current Setting range Wiring method Type Optional Operational power


06 0.5 ~ 6A S Screw - Unit Z Ground fault 220 AC220V
60 5 ~ 60A T Tunnel E Extension I Short circuit 110 AC110V

S
Stockist
TCG/PUB/PM65/EMP-RELAY/REV-2/24032003

TM Controls & Switchgear Co. Ltd.


Central Marketing Office : 222, Okhla Industrial Estate, New Delhi - 110 020
Tel. : +91-11-2691 8834-37, 2683 8291, Fax: +91-11-2684 8241, 2684 7342
email : info@controlsindia.com, gurmeet@controlsindia.com
Corporate Office : 222, Okhla Industrial Estate, New Delhi - 110 020
Tel. : +91-11-2684 8242-45, 2683 6171, Fax: +91-11-2684 7154, 2682 9063
W e b s i t e : w w w. c o n t r o l g r o u p . o r g