HERMETIC SCROLL
GS560418
70 - 175 TON
246 - 545 Kw
60 Hz
200-3-60
230-3-60
315-3-60
460-3-60
575-3-60
MODELS ONLY
FORM 150.72-RP1 (809)
WARNING
HIGH VOLTAGE
Is used in the operation of this equipment.
DEATH OR SERIOUS INJURY
may result if personnel fail to observe safety precautions.
Work on electronic equipment should not be undertaken unless the individual(s) have been
trained in the proper maintenance of equipment and is (are) familiar with its potential hazards.
Shut off power supply to the equipment before beginning work and follow lockout procedures.
When working inside equipment with power off, take care to discharge every capacitor likely to
hold dangerous potential.
Be careful not to contact high voltage connections when installing or operating this equipment.
LOW VOLTAGE
DO NOT be misled by the term low voltage. Voltages as low as 50 volts may cause death.
2 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
YLAA0091SE46XAA
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATOR REFRIGERANT VOLTAGE/STARTER DESIGN/DEVELOPMENT LEVEL
38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54
EVAP. FIELD CONDENSER FIELD CABINET FIELD
X :150# PSI DWP X : Aluminum 1 : Wire (Full Unit) Encl. Panels (factory)
3 :300# PSI DWP C : Copper 3 : Wire/Louvered Encl. Panels (factory)
D :Double Thick Insulation B : Black Fin 5 : Louvered (Cond. Only) Encl. Panels (factory)
V :Victaulic Flange P : Phenolic 7 : Louvered (Full Unit) Encl. Panels (factory)
S :One Flow Switch X : TEAO Fan 9 : End Louver (Hail Guard) Enc. Panels (factory)
T :Two Flow Switches Motors B : Acoustic Sound Blanket
U :Three Flow Switches E : Acoustic Enclosure
D :One Diff. Press. Switch L : Ultra Quiet Fans
E :Two Diff. Press. Switches G : High Airow Fans
F :Three Diff. Press. Switches H : High Static Fans
A :ASME Press Vessel Codes T : Two Speed Fans
E :PED Press Vessel Codes 1 : 1" Deection
R :Remote Cooler 61 S : Seismic
PLANT OF MANUFACTURE N : Neoprene Pads
R : Monterrey
S : Sabadell
CUR : Curitiba, Brazil
MEX : Mexico, ES
MTY : Monterrey. BE
NOTES:
SAT : San Antonio, Texas
1. Q :DENOTES SPECIAL / S.Q.
2. # :DENOTES STANDARD
3. X :w/in OPTIONS FIELD, DENOTES NO OPTION SELECTED
4. Agency Files (i.e. U.L. / ETL; CE; ARI; ETC.) will contain info. based on the rst 14 characters only.
5. Plant of manufacture to include PIN 56 upon entering the chiller order.
JOHNSON CONTROLS 3
FORM 150.72-RP1 (809)
EVAPORATOR COMPONENTS
Evaporator
Service Note:
Pin location 38 in Model Number will be "X" for 150# DWP Cooler .
Pin location 38 in Model Number will be "3" for 300# DWP Cooler
Service Note:
Standard 150# DWP Cooler Flow Switch - 024-26116-000
Optional 300# DWP Cooler Flow Switch - 024-12144-000
Differential Pressure Switch - 025-30919-000 (Optional)
Evaporator
TABLE 1 EVAPORATOR COMPONENTS - 150 PSIG (SEE FIG. 1, PAGE 4)
QTY
ITEM UNIT MODEL UNIT MODEL
PER DESCRIPTION DWP
NUMBER YLAA0070 YLAA0080
UNIT
Cooler, Fully Insulated with
375-75061-001 375-75064-001
1 1 Heater ALL
Cooler, less Heater & Insulation 375-75062-000 375-75065-000
2 1 Head, Connection End ALL 375-71203-000 375-67289-000
3 1 Head, Back End ALL 075-71205-000 075-65741-003
4 1 Bafe, Connection End ALL 375-71206-000 375-67287-000
5 1 Bafe, Back End ALL 375-71208-000 375-67288-000
6 8 Gasket, Bafe and Head ALL 075-71210-000 075-65741-004
1 Heater, Cooler 180 Watt 025-22690-000 025-22690-000
7 ALL
1 Heater, Cooler 280 Watt 025-22691-000 025-22691-000
9 2 Well, Thermo ALL 026-32328-000 026-32328-000
- Insulation (3/4"x49"x65") 010-05997-000 010-05997-000
10 ALL
- Insulation (1 1/2"x49"x65") 010-05998-000 010-05998-000
11 2 Sensor, Water Temperature ALL 025-29964-000 025-29964-000
12 1 Adhesive (Use with #6) ALL 013-03311-000 031-03311-000
UNIT MODEL
QTY YLAA0091,
ITEM UNIT MODEL
PER DESCRIPTION DWP 0100, 0101,
NUMBER YLAA0090
UNIT 0115 AND
YLAA0125
Cooler, Fully Insulated with
375-75058-001 375-75055-001
1 1 Heater ALL
Cooler, less Heater & Insulation 375-75059-000 375-75056-000
2 1 Head, Connection End ALL 375-67628-000 375-71454-000
3 1 Head, Back End ALL 075-67624-002 075-71457-000
4 1 Bafe, Connection End ALL 375-67626-000 375-71458-000
5 1 Bafe, Back End ALL 075-67627-000 375-71460-000
6 4 Gasket, Bafe and Head ALL 075-67624-003 075-71467-000
1 Heater, Cooler 180 Watt 025-22690-000 025-22690-000
7 ALL
1 Heater, Cooler 280 Watt 025-22691-000 025-22691-000
9 2 Well, Thermo ALL 026-32328-000 026-32328-000
- Insulation (3/4"x49"x65") 010-05997-000 010-05997-000
10 ALL
- Insulation (1 1/2"x49"x65") 010-05998-000 010-05998-000
11 2 Sensor, Water Temperature ALL 025-29964-000 025-29964-000
12 1 Adhesive (Use with #6) ALL 013-03311-000 031-03311-000
JOHNSON CONTROLS 5
FORM 150.72-RP1 (809)
QTY
ITEM UNIT MODEL
PER DESCRIPTION DWP
NUMBER YLAA0175
UNIT
Cooler, Fully Insulated with
375-76135-001
1 1 Heater ALL
Cooler, less Heater & Insulation 375-76136-000
2 1 Head, Connection End ALL 375-67887-000
3 1 Head, Back End ALL 075-67892-002
4 1 Bafe, Connection End ALL 375-67888-000
5 1 Bafe, Back End ALL 375-67891-000
6 8 Gasket, Bafe and Head ALL 075-84276-000
7 2 Heater, Cooler 280 Watt ALL 025-22691-000
9 2 Well, Thermo ALL 026-32328-000
- Insulation (3/4"x49"x65") 010-05997-000
10 ALL
- Insulation (1 1/2"x49"x65") 010-05998-000
11 2 Sensor, Water Temperature ALL 025-29964-000
12 1 Adhesive (Use with #6) ALL 013-03311-000
6 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
Condenser
2 2
77926-000-3
8
375-77926-000 = W/ RECEIVER (RIGHT PIPES)
375-77926-001 = W/O RECEIVER
375-77926-002 = W/O RECEIVER (SPLIT SYSTEM)
375-77926-003 = W/ RECEIVER (LEFT PIPES)
3 4
Condenser
7 7
77926-000-1a
BACK
6
-000
5 ONLY
-003
ONLY
8 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
Condenser
77927-2a
JOHNSON CONTROLS 9
FORM 150.72-RP1 (809)
10 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
FAN COMPONENTS
Service Note:
Fan Hub to Shaft Joint should be
sealed with protective coating - use
RUST VETO 344 - a solvent type, 71386-000
rust preventative coating.
4 6
5
3
Piping
8
2
9
1
Service Note: Pin Location 52 in Model Number will be
X for Standard Fan, or L for Low Noise Fan.
FIG. 3 FAN COMPONENTS See page 3.
S
= Recommended Spare Parts
JOHNSON CONTROLS 11
FORM 150.72-RP1 (809)
123 148
148 105
141 123
202
203
141
200 123
201
Piping
77937-004a
118
119
122 116
112 115
12 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
ITEM
SYS. DESCRIPTION YLAA0070 YLAA0080 YLAA00090
NO.
105 Both Valve, Ball (Discharge) 022-08883-000 022-08883-000 022-08883-000
112s 1 Valve, Thermal 025-40666-000 025-40666-000 025-40681-000
113s 2 Expansion 025-40666-000 025-40681-000 025-40681-000
114 Both Moisture Indicator 026-14125-000 026-14125-000 026-14125-000
115 Both Valve, Liquid Stop 022-10022-000 022-10022-000 022-10022-000
116 Both Valve, Solenoid 025-41743-000 025-41743-000 025-41743-000
118 Both Dehydrator, Body 026-43984-002 026-43984-002 026-43984-002
119s Both Core, Dehydrator 026-37540-000 026-37540-000 026-37540-000
122 Both Valve, Angle Stop 022-03836-000 022-03836-000 022-03836-000
Piping
123 Both Valve, Charging 022-09754-000 022-09754-000 022-09754-000
141 Both Valve, Ball (Suction) 022-09753-000 022-09753-000 022-09753-000
148 Both Valve, Transducer 022-11735-000 022-11735-000 022-11735-000
200 Both Valve, Relief (400 psi) 022-11704-000 022-11704-000 022-11704-000
201 Both Tube, Relief 375-37978-000 375-37978-000 375-37978-000
202 All Valve, Relief (650 psi) 022-10682-001 022-10682-001 022-10682-001
203 All Tube, Relief 375-37975-000 375-37975-000 375-37975-000
S
= Recommended Spare Parts
JOHNSON CONTROLS 13
FORM 150.72-RP1 (809)
YLAA0141,
ITEM YLAA0170 AND
SYS. DESCRIPTION YLAA0135 0150, 0155 AND
NO. YLAA0175
YLAA0156
1 022-08883-000 022-08883-000
105 Valve, Ball (Discharge) 022-09752-000
2 022-09752-000 022-09752-000
112s 1 Valve, Thermal 025-40900-004 025-40900-004
025-40900-004
113s 2 Expansion 025-40681-000 025-40900-008
1 026-14125-000 026-14125-000
114 Moisture Indicator 026-20574-000
2 026-20574-000 026-20574-000
1 022-10022-000 022-10022-000
Piping
S
= Recommended Spare Parts
14 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
18
Piping
11
9 7
SYSTEM PIPING YLAA 76061-000-2
JOHNSON CONTROLS 15
FORM 150.72-RP1 (809)
COMPRESSOR
-
2-M2
2-M1
1-M2
72257-001c
1-M1
SYSTEM #2
SYSTEM #1
2-M2 2-M1
1-M3 72257-002c
1-M2 1-M1
SYSTEM #2
SYSTEM #1
YLAA0090, YLAA0101, YLAA0135, YLAA0150 and YLAA0155
SYSTEM #2
SYSTEM #1
JOHNSON CONTROLS
YLAA0070 -40 015-04055-102 ZP154KCE 3 015-04055-102 ZP154KCE 3 N/A N/A N/A
-46 015-04055-104 3 015-04055-104 3
-58 015-04055-105 3 015-04055-105 3
-17 015-04045-101 3 015-04055-101 3
-28 015-04045-101 3 015-04055-101 3
YLAA0080 -40 015-04045-102 ZP180KCE 3 015-04055-102 ZP154KCE 3 N/A N/A N/A
-46 015-04045-104 3 015-04055-104 3
-58 015-04045-105 3 015-04055-105 3
-17 015-04045-101 3 015-04052-101 1 015-04045-101 1
-28 015-04045-101 3 015-04052-101 1 015-04045-101 1
YLAA0090 -40 015-04045-102 ZP180KCE 3 015-04052-102 ZP385KCE 1 015-04045-102 ZP180KCE 1
-46 015-04045-104 3 015-04052-104 1 015-04045-104 1
-58 015-04045-105 3 015-04052-105 1 015-04045-105 1
-17 015-04052-101 2 015-04045-101 2
-28 015-04052-101 2 015-04045-101 2
YLAA0091 -40 015-04052-102 ZP385KCE 2 015-04045-102 ZP180KCE 2 N/A N/A N/A
-46 015-04052-104 2 015-04045-104 2
-58 015-04052-105 2 015-04045-105 2
COMPRESSOR (CONTD)
17
Compressor
Compressor
18
TABLE 5 (CONT'D) COMPRESSOR PART NUMBERS - R-410A (SEE FIG. 5, PAGE 16)
JOHNSON CONTROLS
FORM 150.72-RP1 (809)
FORM 150.72-RP1 (809)
COMPRESSOR (CONTD)
TABLE 5A RECOMMENDED COMPRESSOR OIL TYPE
S
= Recommended Spare Parts
COMPRESSOR PART HEATER PART QUANTITY PER SOUND BLANKET QUANTITY PER
NUMBER NUMBER COMPRESSOR PART NUMBER COMPRESSOR
015-04045-xxx 025-37888-000 1 010-06507-002 1
015-04055-xxx 025-40351-000 1 010-06507-007 1
015-04052-xxx 025-37853-000 1 010-06507-000 1
Compressor
TABLE 5C COMPRESSOR COMPONENTS
Discharge
Connection
Pressure
Equalization
Suction
Connection
1. TERMINAL BLOCKS
2. CIRCUIT BREAKERS
3. NON-FUSED DISCONNECT SWITCHES
The most basic chiller power wiring conguration uses TERMINAL BLOCKS in the power panels, and an options
panel with no power wire termination hardware. The model pin number locations 16 and 17 would be X and X to
reect this basic combination. Identify model pin number locations 16 and 17 to identify the chiller power wiring
connections and hardware listed below.
PIN 16 & 17
LETTER CODE OPTION PANEL AND POWER PANEL CONFIGURATIONS
IDENTIFIERS
S X Single Point Supply Terminal Block
S D Single Point Supply Non-Fused Disconnect Switch
B X Single Point Supply Circuit Breaker
1
1 2
2
Control & Power Panel
20 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
SINGLE POINT
SINGLE POINT NON-FUSED
SINGLE POINT SINGLE POINT
NON-FUSED DISCONNECT
VOLTAGE TERMINAL CIRCUIT
MODEL DISCONNECT SWITCH w/ IND.
CODE BLOCK BREAKER
SWITCH SYS. CIRCUIT
(SX) (BX)
(SD) BREAKERS
(DB)
17 371-05245-101 371-05245-201 371-05245-301 371-05245-401
28 371-05245-102 371-05245-202 371-05245-302 371-05245-402
YLAA0070 40 371-05245-103 371-05245-203 371-05245-303 371-05245-403
46 371-05245-104 371-05245-204 371-05245-304 371-05245-404
58 371-05245-105 371-05245-205 371-05245-305 371-05245-405
17 371-05245-107 371-05245-207 371-05245-307 371-05245-407
28 371-05245-108 371-05245-208 371-05245-308 371-05245-408
YLAA0080 40 371-05245-109 371-05245-209 371-05245-309 371-05245-409
46 371-05245-110 371-05245-210 371-05245-310 371-05245-410
58 371-05245-111 371-05245-211 371-05245-311 371-05245-411
17 371-05246-101 371-05246-201 371-05246-301 371-05246-401
28 371-05246-102 371-05246-202 371-05246-302 371-05246-402
YLAA0090 40 371-05246-103 371-05246-203 371-05246-303 371-05246-403
46 371-05246-104 371-05246-204 371-05246-304 371-05246-404
JOHNSON CONTROLS 21
FORM 150.72-RP1 (809)
SINGLE POINT
SINGLE POINT NON-FUSED
SINGLE POINT SINGLE POINT
NON-FUSED DISCONNECT
VOLTAGE TERMINAL CIRCUIT
MODEL DISCONNECT SWITCH w/ IND.
CODE BLOCK BREAKER
SWITCH SYS. CIRCUIT
(SX) (BX)
(SD) BREAKERS
(DB)
17 371-05244-107 371-05244-207 371-05244-307 371-05244-407
28 371-05244-108 371-05244-208 371-05244-308 371-05244-408
YLAA0115 40 371-05244-109 371-05244-209 371-05244-309 371-05244-409
46 371-05244-110 371-05244-210 371-05244-310 371-05244-410
58 371-05244-111 371-05244-211 371-05244-311 371-05244-411
17 371-05244-107 371-05244-207 371-05244-307 371-05244-407
YLAA0120 28 371-05244-108 371-05244-208 371-05244-308 371-05244-408
AND 40 371-05244-109 371-05244-209 371-05244-309 371-05244-409
YLAA0125 46 371-05244-110 371-05244-210 371-05244-310 371-05244-410
58 371-05244-111 371-05244-211 371-05244-311 371-05244-411
17 371-05246-113 371-05246-213 371-05246-313 371-05246-413
YLAA0135 28 371-05246-114 371-05246-214 371-05246-314 371-05246-414
AND 40 371-05246-115 371-05246-215 371-05246-315 371-05246-415
YLAA0141 46 371-05246-116 371-05246-216 371-05246-316 371-05246-416
Control & Power Panel
22 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
*Service Note:
Locate the PANEL NUMBER sticker on the upper right hand corner of the power
panel, see Figure 7, then refer to the appropriate parts list for that number.
JOHNSON CONTROLS 23
Control & Power Panel
24
4A 2B
2B 4B
4C
8A 8A
8B 8B
2A 2A
2C 2C
5A 5A
3A 3A
POWER PANEL COMPONENTS (CONTD)
9A 9A
3B 3B
4D
211028-3
JOHNSON CONTROLS
FIG. 7A POWER PANEL COMPONENTS - (REF. TABLE 7, PAGES 25-35)
FORM 150.72-RP1 (809)
TABLE 7 POWER PANEL COMPONENTS - YLAA0070 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
JOHNSON CONTROLS
371-05245-10x 371-05245-20x 371-05245-30x 371-05245-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
Fan Contactor (-17, -28 & -40) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2Bs 4
Fan Contactor (-46 & -58) 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)**
2C 13 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
6 Compressor Contactor (-17) 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
2 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3A Compressor Contactor (-28)
4 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
6 Compressor Contactor (-40, -46 & -58) 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
3B 6 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
1 Terminal Block 025-39410-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34424-000 N/A
1
4A Circuit Breaker (-40, -46 & -58) N/A N/A 025-34419-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-30965-000 N/A 024-30965-000
1
Non-Fused Disc. Sw. (-40, -46 & -58) N/A 024-30963-000 N/A 024-30963-000
4B 3 Safety Cover (use w/ TB) 025-39393-000 N /A N/A N /A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34089-000
1 Ind. Sys. Circuit Breaker (Sys. 1) N/A N/A N/A 025-34419-000
5A
1 Ind. Sys. Circuit Breaker (Sys. 2) N/A N/A N/A 024-31842-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
9A 4 Ground Bar 025-35685-000 025-35685-000 025-35685-000 025-35685-000
s
Recommended Spare Part
**Service Note:
Make a visual inspection of the contactors in
order to select the correct replacement part.
024-35441-000 (9A) RI1-D0910-G7
Note:
POWER PANEL COMPONENTS (CONTD)
25
Control & Power Panel
Control & Power Panel
26
TABLE 7 POWER PANEL COMPONENTS - YLAA0080 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05245-10x 371-05245-20x 371-05245-30x 371-05245-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
Fan Contactor (-17, -28 & -40) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2Bs 4
Fan Contactor (-46 & -58) 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)**
2C 13 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
6 Compressor Contactor (-17) 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
4 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
Compressor Contactor (-28)
2 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
3A
3 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
Compressor Contactor (-40)
3 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
6 Compressor Contactor (-46 & -58) 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
3B 6 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
1 Terminal Block 025-39410-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34424-000 N/A
1
Circuit Breaker (-40, -46 & -58) N/A N/A 025-34419-000 N/A
4A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-30965-000 N/A 024-30965-000
1 Non-Fused Disc. Sw. (-40) N/A 024-30964-000 N/A 024-30964-000
Non-Fused Disc. Sw. (-46 & -58) N/A 024-30963-000 N/A 024-30963-000
4B 3 Safety Cover (use w/ TB) 025-39393-000 N /A N/A N /A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34089-000
1 Ind. Sys. Circuit Breaker (Sys. 1) N/A N/A N/A 025-34419-000
5A
1 Ind. Sys. Circuit Breaker (Sys. 2) N/A N/A N/A 024-31842-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
9A 4 Ground Bar 025-35685-000 025-35685-000 025-35685-000 025-35685-000
POWER PANEL COMPONENTS (CONTD)
s
Recommended Spare Part
**Service Note:
Service Note:
Make a visual inspection of the contactors in order to select the correct replacement part.
Lug Kits for Circuit Breakers or Non-Fused Disconnect
024-35441-000 (9A) RI1-D0910-G7 024-35467-000 (65A) RI1-D6511-G7
Switches - See LUG KIT TABLE on Page 36.
024-35444-000 (12A) RI1-D1210-G7 024-35470-000 (80A) RI1-D8011-G7
*Service Note: 024-35447-000 (18A) RI1-D1810-G7 024-35473-000 (95A) RI1-D9511-G7
Locate the PANEL PART NUMBER sticker on the upper right hand corner of the power 024-35451-000 (25A) RI1-D2510-G7 024-34294-000 (150A) TE-LC1D150-F7
JOHNSON CONTROLS
panel, see Figure 7, PAGE 23, then refer to the appropriate parts list for that number. 024-35462-000 (50A) RI1-D5011-G7
FORM 150.72-RP1 (809)
TABLE 7 POWER PANEL COMPONENTS - YLAA0090 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05246-10x 371-05246-20x 371-05246-30x 371-05246-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
JOHNSON CONTROLS
Fan Contactor (-17, -28 & -40) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2Bs 4
Fan Contactor (-46 & -58) 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)**
2C 14 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
4 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
Compressor Contactor (-17)
1 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
4 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
Compressor Contactor (-28)
1 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
3A
4 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
Compressor Contactor (-40)
1 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
4 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
Compressor Contactor (-46 & -58)
1 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 5 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34424-000 N/A
1
4A Circuit Breaker (-40, -46 & -58) N/A N/A 025-34419-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-30965-000 N/A 024-30965-000
1 Non-Fused Disc. Sw. (-40) N/A 024-30964-000 N/A 024-30964-000
Non-Fused Disc. Sw. (-46 & -58) N/A 024-30963-000 N/A 024-30963-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N /A N/A N /A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34089-000
1 Ind. Sys. Circuit Breaker (Sys. 1) N/A N/A N/A 025-34419-000
5A
1 Ind. Sys. Circuit Breaker (Sys. 2) N/A N/A N/A 024-31842-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
POWER PANEL COMPONENTS (CONTD)
27
Control & Power Panel
Control & Power Panel
28
TABLE 7 POWER PANEL COMPONENTS - YLAA0091 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05244-10x 371-05244-20x 371-05244-30x 371-05244-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
Fan Contactor (-17, -28 & -40) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2Bs 6
Fan Contactor (-46 & -58) 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)**
2C 13 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
2 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
Compressor Contactor (-17 & -28)
2 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
2 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
3A Compressor Contactor (-40)
2 024-35473-000 (D9511)** 024-35473-000 (95A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
2 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
Compressor Contactor (-46 & -58)
2 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 4 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34425-000 N/A
1
4A Circuit Breaker (-40, -46 & -58) N/A N/A 025-34424-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-30965-000 N/A 024-30965-000
1 Non-Fused Disc. Sw. (-40) N/A 024-30964-000 N/A 024-30964-000
Non-Fused Disc. Sw. (-46 & -58) N/A 024-30963-000 N/A 024-30963-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N /A N/A N /A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N /A N /A N /A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34089-000
1 Ind. Sys. Circuit Breaker (Sys. 1) N/A N/A N/A 025-34419-000
5A
1 Ind. Sys. Circuit Breaker (Sys. 2) N/A N/A N/A 025-34419-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
9A 4 Ground Bar 025-35685-000 025-35685-000 025-35685-000 025-35685-000
POWER PANEL COMPONENTS (CONTD)
s
Recommended Spare Part **Service Note:
Service Note: Make a visual inspection of the contactors in order to select the correct replacement part.
Lug Kits for Circuit Breakers or Non-Fused Disconnect 024-35441-000 (9A) RI1-D0910-G7 024-35467-000 (65A) RI1-D6511-G7
Switches - See LUG KIT TABLE on Page 36. 024-35444-000 (12A) RI1-D1210-G7 024-35470-000 (80A) RI1-D8011-G7
*Service Note: 024-35447-000 (18A) RI1-D1810-G7 024-35473-000 (95A) RI1-D9511-G7
Locate the PANEL PART NUMBER sticker on the upper right hand corner of the power 024-35451-000 (25A) RI1-D2510-G7 024-34294-000 (150A) TE-LC1D150-F7
JOHNSON CONTROLS
panel, see Figure 7, PAGE 23, then refer to the appropriate parts list for that number. 024-35462-000 (50A) RI1-D5011-G7
FORM 150.72-RP1 (809)
TABLE 7 POWER PANEL COMPONENTS - YLAA0100 & YLAA0101 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05246-10x 371-05246-20x 371-05246-30x 371-05246-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
4 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-17, -28 & -40)
JOHNSON CONTROLS
1 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
2Bs
3 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-46 & -58)
2 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)**
2C 14 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
3 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
Compressor Contactor (-17 & -28)
2 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
3 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
3A Compressor Contactor (-40)
2 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)**
3 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
Compressor Contactor (-46 & -58)
2 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 5 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34425-000 N/A
1 Circuit Breaker (-40 & -46) N/A N/A 025-34424-000 N/A
4A
Circuit Breaker (-58) N/A N/A 025-34419-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-30965-000 N/A 024-30965-000
1 Non-Fused Disc. Sw. (-40 & -46) N/A 024-30964-000 N/A 024-30964-000
Non-Fused Disc. Sw. (-58) N/A 024-30963-000 N/A 024-30963-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N /A N/A N /A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N/A N/A N/A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34089-000
1 Ind. Sys. Circuit Breaker (Sys. 1) N/A N/A N/A 025-34419-000
5A
1 Ind. Sys. Circuit Breaker (Sys. 2) N/A N/A N/A 025-34424-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
POWER PANEL COMPONENTS (CONTD)
29
024-35462-000 (50A) RI1-D5011-G7
30
TABLE 7 POWER PANEL COMPONENTS - YLAA0115 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05244-10x 371-05244-20x 371-05244-30x 371-05244-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
4 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-17 & -28)
2 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
2Bs
6 Fan Contactor (-40) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
6 Fan Contactor (-46 & -58) 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)**
2C 13 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
4 Compressor Contactor (-17 & -28) 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
3A 4 Compressor Contactor (-40) 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)**
4 Compressor Contactor (-46 & -58) 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 4 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34425-000 N/A
4A 1
Circuit Breaker (-40, -46 & -58) N/A N/A 025-34424-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-31889-000 N/A 024-31889-000
1
Non-Fused Disc. Sw. (-40, -46 & -58) N/A 024-30964-000 N/A 024-30964-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N /A N/A N /A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N/A N/A N/A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34085-000
2 Ind. Sys. Circuit Breaker (-17 & -28) N/A N/A N/A 025-34424-000
5A
2 Ind. Sys. Circuit Breaker (-40, -46 & -58) N/A N/A N/A 025-34419-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
9A 4 Ground Bar 025-35685-000 025-35685-000 025-35685-000 025-35685-000
s
Recommended Spare Part
POWER PANEL COMPONENTS (CONTD)
Service Note:
Lug Kits for Circuit Breakers or Non-Fused Disconnect **Service Note:
Switches - See LUG KIT TABLE on Page 36. Make a visual inspection of the contactors in order to select the correct replacement part.
*Service Note: 024-35441-000 (9A) RI1-D0910-G7 024-35467-000 (65A) RI1-D6511-G7
Locate the PANEL PART NUMBER sticker on the upper right hand corner of the power 024-35444-000 (12A) RI1-D1210-G7 024-35470-000 (80A) RI1-D8011-G7
panel, see Figure 7, PAGE 23, then refer to the appropriate parts list for that number. 024-35447-000 (18A) RI1-D1810-G7 024-35473-000 (95A) RI1-D9511-G7
024-35451-000 (25A) RI1-D2510-G7 024-34294-000 (150A) TE-LC1D150-F7
JOHNSON CONTROLS
024-35462-000 (50A) RI1-D5011-G7
FORM 150.72-RP1 (809)
TABLE 7 POWER PANEL COMPONENTS - YLAA0120 & YLAA0125 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05244-10x 371-05244-20x 371-05244-30x 371-05244-40x
JOHNSON CONTROLS
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
4 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-17 & -28)
2 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
2Bs
6 Fan Contactor (-40) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
6 Fan Contactor (-46 & -58) 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)** 024-35441-000 (9A)**
2C 13 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
4 Compressor Contactor (-17 & -28) 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
3A 4 Compressor Contactor (-40) 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)**
4 Compressor Contactor (-46 & -58) 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 4 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34425-000 N/A
4A 1
Circuit Breaker (-40, -46 & -58) N/A N/A 025-34424-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-31889-000 N/A 024-31889-000
1
Non-Fused Disc. Sw. (-40, -46 & -58) N/A 024-30964-000 N/A 024-30964-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N /A N/A N /A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N/A N/A N/A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34085-000
2 Ind. Sys. Circuit Breaker (-17 & -28) N/A N/A N/A 025-34424-000
5A
2 Ind. Sys. Circuit Breaker (-40, -46 & -58) N/A N/A N/A 025-34419-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
9A 4 Ground Bar 025-35685-000 025-35685-000 025-35685-000 025-35685-000
s
Recommended Spare Part
POWER PANEL COMPONENTS (CONTD)
Service Note:
Lug Kits for Circuit Breakers or Non-Fused Disconnect
Switches - See LUG KIT TABLE on Page 36. **Service Note:
Make a visual inspection of the contactors in order to select the correct replacement part.
*Service Note:
024-35441-000 (9A) RI1-D0910-G7 024-35467-000 (65A) RI1-D6511-G7
Locate the PANEL PART NUMBER sticker on the upper right hand corner of the power
024-35444-000 (12A) RI1-D1210-G7 024-35470-000 (80A) RI1-D8011-G7
panel, see Figure 7, PAGE 23, then refer to the appropriate parts list for that number.
024-35447-000 (18A) RI1-D1810-G7 024-35473-000 (95A) RI1-D9511-G7
024-35451-000 (25A) RI1-D2510-G7 024-34294-000 (150A) TE-LC1D150-F7
024-35462-000 (50A) RI1-D5011-G7
FORM 150.72-RP1 (809)
31
Control & Power Panel
Control & Power Panel
32
TABLE 7 POWER PANEL COMPONENTS - YLAA0135 & YLAA0141 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05246-10x 371-05246-20x 371-05246-30x 371-05246-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
3 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-17 & -28)
3 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
2Bs 4 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-40)
2 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
6 Fan Contactor (-46 & -58) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2C 14 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
4 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
Compressor Contactor (-17 & -28)
1 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
4 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)**
3A Compressor Contactor (-40)
1 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)** 024-35467-000 (65A)**
4 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
Compressor Contactor (-46 & -58)
1 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)** 024-35462-000 (50A)**
3B 5 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34473-000 N/A
1
4A Circuit Breaker (-40, -46 & -58) N/A N/A 025-34424-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-31889-000 N/A 024-31889-000
1 Non-Fused Disc. Sw. (-40) N/A 024-30965-000 N/A 024-30965-000
Non-Fused Disc. Sw. (-46 & -58) N/A 024-30964-000 N/A 024-30964-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N/A N/A N/A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N/A N/A N/A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34086-000
2 Ind. Sys. Circuit Breaker (-17 & -28) N/A N/A N/A 025-34424-000
5A
2 Ind. Sys. Circuit Breaker (-40, -46 & -58) N/A N/A N/A 025-34419-000
POWER PANEL COMPONENTS (CONTD)
JOHNSON CONTROLS
024-35444-000 (12A) RI1-D1210-G7 024-35470-000 (80A) RI1-D8011-G7
FORM 150.72-RP1 (809)
*Service Note:
Locate the PANEL PART NUMBER sticker on the upper right hand corner of the power 024-35447-000 (18A) RI1-D1810-G7 024-35473-000 (95A) RI1-D9511-G7
panel, see Figure 7, PAGE 23, then refer to the appropriate parts list for that number. 024-35451-000 (25A) RI1-D2510-G7 024-34294-000 (150A) TE-LC1D150-F7
024-35462-000 (50A) RI1-D5011-G7
TABLE 7 POWER PANEL COMPONENTS - YLAA0150 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05246-10x 371-05246-20x 371-05246-30x 371-05246-40x
JOHNSON CONTROLS
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
4 024-35447-000 (18A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-17 & -28)
2 024-35451-000 (25A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
2Bs 4 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-40)
2 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
6 Fan Contactor (-46 & -58) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2C 14 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
5 Compressor Contactor (-17 & -28) 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
3A 5 Compressor Contactor (-40) 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)**
5 Compressor Contactor (-46 & -58) 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 5 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34473-000 N/A
4A 1
Circuit Breaker (-40, -46 & -58) N/A N/A 025-34424-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-31889-000 N/A 024-31889-000
1
Non-Fused Disc. Sw. (-40, -46 & -58) N/A 024-30965-000 N/A 024-30965-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N/A N/A N/A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N/A N/A N/A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34086-000
2 Ind. Sys. Circuit Breaker (-17 & -28) N/A N/A N/A 025-34424-000
5A 1 N/A N/A N/A 025-34419-000
Ind. Sys. Circuit Breaker (-40, -46 & -58)
1 N/A N/A N/A 025-34420-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
9A 4 Ground Bar 025-35685-000 025-35685-000 025-35685-000 025-35685-000
POWER PANEL COMPONENTS (CONTD)
s
Recommended Spare Part
**Service Note:
Service Note:
Make a visual inspection of the contactors in order to select the correct replacement part.
Lug Kits for Circuit Breakers or Non-Fused Disconnect
024-35441-000 (9A) RI1-D0910-G7 024-35467-000 (65A) RI1-D6511-G7
Switches - See LUG KIT TABLE on Page 36.
024-35444-000 (12A) RI1-D1210-G7 024-35470-000 (80A) RI1-D8011-G7
*Service Note: 024-35447-000 (18A) RI1-D1810-G7 024-35473-000 (95A) RI1-D9511-G7
Locate the PANEL PART NUMBER sticker on the upper right hand corner of the power 024-35451-000 (25A) RI1-D2510-G7 024-34294-000 (150A) TE-LC1D150-F7
panel, see Figure 7, PAGE 23, then refer to the appropriate parts list for that number. 024-35462-000 (50A) RI1-D5011-G7
FORM 150.72-RP1 (809)
33
Control & Power Panel
Control & Power Panel
34
TABLE 7 POWER PANEL COMPONENTS - YLAA0155 & YLAA0156 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
371-05246-10x 371-05246-20x 371-05246-30x 371-05246-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
4 024-35447-000 (18A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-17 & -28)
2 024-35451-000 (25A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
2Bs 4 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-40)
2 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
6 Fan Contactor (-46 & -58) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2C 14 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
5 Compressor Contactor (-17 & -28) 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
3A 5 Compressor Contactor (-40) 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)**
5 Compressor Contactor (-46 & -58) 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 5 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34473-000 N/A
4A 1
Circuit Breaker (-40, -46 & -58) N/A N/A 025-34424-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-31889-000 N/A 024-31889-000
1
Non-Fused Disc. Sw. (-40, -46 & -58) N/A 024-30965-000 N/A 024-30965-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N/A N/A N/A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N/A N/A N/A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34086-000
2 Ind. Sys. Circuit Breaker (-17 & -28) N/A N/A N/A 025-34424-000
5A 1 N/A N/A N/A 025-34419-000
Ind. Sys. Circuit Breaker (-40, -46 & -58)
1 N/A N/A N/A 025-34420-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
POWER PANEL COMPONENTS (CONTD)
JOHNSON CONTROLS
panel, see Figure 7, PAGE 23, then refer to the appropriate parts list for that number. 024-35462-000 (50A) RI1-D5011-G7
FORM 150.72-RP1 (809)
TABLE 7 POWER PANEL COMPONENTS - YLAA0170 & YLAA0175 (SEE FIG. 7A, PAGE 24)
Single Point Non-Fused
Single Point Terminal Single Point Non-Fused Single Point Circuit Disconnect Switch w/
Item
Qty. Description Block (SX) Disconnect Switch (SD) Breaker (BX) Ind. System Circuit
No.
Breakers (DB)
JOHNSON CONTROLS
371-05246-10x 371-05246-20x 371-05246-30x 371-05246-40x
2As 3 Fan Control Relay 024-35526-000 024-35526-000 024-35526-000 024-35526-000
4 024-35447-000 (18A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-17 & -28)
2 024-35451-000 (25A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
2Bs 4 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
Fan Contactor (-40)
2 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)** 024-35447-000 (18A)**
6 Fan Contactor (-46 & -58) 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)** 024-35444-000 (12A)**
2C 14 Surge Supressor 031-00808-000 031-00808-000 031-00808-000 031-00808-000
5 Compressor Contactor (-17 & -28) 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)** 024-34294-000 (150A)**
3A 5 Compressor Contactor (-40) 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)** 024-35473-000 (95A)**
5 Compressor Contactor (-46 & -58) 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)** 024-35470-000 (80A)**
3B 5 Ground Lug 025-34088-000 025-34088-000 025-34088-000 025-34088-000
Terminal Block (-17 & -28) 025-32536-000 N/A N/A N/A
1
Terminal Block (-40, -46 & -58) 025-34910-000 N/A N/A N/A
Circuit Breaker (-17 & -28) N/A N/A 025-34473-000 N/A
4A 1
Circuit Breaker (-40, -46 & -58) N/A N/A 025-34424-000 N/A
Non-Fused Disc. Sw. (-17 & -28) N/A 024-31889-000 N/A 024-31889-000
1
Non-Fused Disc. Sw. (-40, -46 & -58) N/A 024-30965-000 N/A 024-30965-000
Safety Cover (use w/ TB -17 & -28) 025-39397-000 N/A N/A N/A
4B 3
Safety Cover (use w/ TB -40, -46 & -58) 025-39393-000 N/A N/A N/A
4C 1 Oper. Mech. (use w/ CB or NFDS) N/A 024-31878-000 024-31878-000 024-31878-000
4D 1 Ground Lug 025-34089-000 025-34089-000 025-34089-000 025-34086-000
2 Ind. Sys. Circuit Breaker (-17 & -28) N/A N/A N/A 025-34424-000
5A 1 N/A N/A N/A 025-34419-000
Ind. Sys. Circuit Breaker (-40, -46 & -58)
1 N/A N/A N/A 025-34420-000
8A 2 Fuse Holder 025-37863-000 025-37863-000 025-37863-000 025-37863-000
8B 6 Fuse See Fuse Table on Page 36
POWER PANEL COMPONENTS (CONTD)
35
Control & Power Panel
FORM 150.72-RP1 (809)
36 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
CONTROL PANEL
PANEL DIVIDER
(PARTIAL VIEW)
MICROPROCESSOR
4A 1FU BOARD
031-02550-000
4B
LOAD
4T
1 2A
2B
CTB1
203741-1b
5
6
7
LD05167b
38 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
SENSOR HARNESSES
2-BSP
1-BSP
BAMB
75213-001h
1-BDP
2-BDP
75213-001g
3
BECT EEH
75213-000
BLCT
75213-001-l
8 1
EVAPORATOR HEATER
HARNESS = 575-72382-211
9-PIN
12 Pin Plug (025-28383-000)
(025-21196-000)
15 Pin Plug
(025-28385-000)
45622-003
TABLE 9A SENSOR HARNESS WIRING - YLAA0091, 0115 & YLAAA0120 (SEE FIGS. 9,
JOHNSON CONTROLS 41
FORM 150.72-RP1 (809)
1-BSP
2-BSP
BAMB
1-BDP
Y2RSI-2D-
1 21
2-BDP
21
75213-001g sensor
Control & Power Panel
FIG. 10 TRANSDUCERS, PRESSURE CUTOUTS AND TEMP SENSORS (REF. TABLE 10)
Item
Qty Description Models Part Number
Number
1s 1 Sensor, Outside Air Temperature All 025-28663-001
2s 1 Sensor, Entering Water Temp. (Not Shown) All 025-29964-000
3s 1 Sensor, Leaving Water Temp. (Not Shown) All 025-29964-000
4 - Compound, Heat Conductive* All 013-00898-000
20s 2 Transducer, Suction Pressure (0-400psi) All 025-41756-002
21s 2 Transducer, Discharge Pressure (0-650psi) All 025-41756-003
42 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
A B
A B
3 C
7 4
8 5
END VIEW
OF PLUG
9 6
02492-2c
JOHNSON CONTROLS 43
FORM 150.72-RP1 (809)
VIBRATION ISOLATORS
392 to 605 lbs. 178 to 274 kg. Y2RSI-2D-710 DARK BROWN 029-25336-008
605 to 741 lbs. 274 to 336 kg. Y2RSI-2D-870 RED 029-25336-009
741 to 1021 lbs. 336 to 463 kg. Y2RSI-2D-1200N RED/BLACK 029-25336-010
1021 to 1438 lbs. 463 to 652 kg. Y2RSI-2D-1690 PINK 029-25336-011
1438 to 2245 lbs. 652 to 1018 kg. Y2RSI-2D-2640N PINK/GRAY 029-25336-012
2245 to 2619 lbs. 1018 to 1188 kg. Y2RSI-2D-2870N PINK/GRAY/ORANGE 029-25336-013
2619 to 3740 lbs. 1188 to 1697 kg. Y2RSI-2D-3280N PINK/GRAY/DARK BROWN 029-25336-014
* Note: One Inch Deection Spring Isolators must all be of the same class for the entire unit. Must use
C2P's at all locations on a selected unit, or all CP's.
44 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
JOHNSON CONTROLS 45
FORM 150.72-RP1 (809)
LOUVERED LOUVERED
MODEL WIRE /
WIRE LOUVERED ENCLOSURE ENCLOSURE
NUMBER LOUVERED
ENCLOSURE ENCLOSURE CONDENSER HAIL GUARD
YLAA- ENCLOSURE
ONLY ONLY
0070
0080 475-75917-301 475-75918-301 475-75917-303 475-75918-303
0090
0091
0100
475-75918-201
0101 475-75917-201 475-75917-203 475-75918-203
0115
0120 475-75918-202
475-75918-104
0125
475-75917-101 475-75918-101 475-75917-103
0135
0141 475-75917-102 475-75918-102 475-75917-104 475-75918-103
0150 475-75917-101 475-75918-101 475-75917-103
0155 475-75917-102 475-75918-102 475-75917-104
0156
475-75918-401
0170 475-75917-401 475-75917-403 475-75918-403
0175 475-75918-402
Chiller Options
46 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
21 1
5 4
5
22
FRONT RIGHT
3 3 21
1
4 22
5 5
REAR 75917-300-1
LEFT
JOHNSON CONTROLS 47
FORM 150.72-RP1 (809)
5 28 27
5
29
FRONT 28 RIGHT
3 25
3 1
26
4
5 5
REAR LEFT
FIG. 13 LOUVERED ENCLOSURE (REF. TABLE 16)
75918-300-1
YLAA0070, 0080 & YLAA0091, ,0110, 0101, YLAA0125, 0135, 0141, YLAA0156, 0170 &
WIRE ENCLOSURE
YLAA0090 0115 & YLAA0120 0150 & YLAA0155 YLAA0175
ITEM # DESCRIPTION 475-75918-30x QTY 475-75918-20x QTY 475-75918-10x QTY 475-75918-40x QTY
Chiller Options
48 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
Chiller Options
All parts should be purchased from your local JOHNSON CONTROLS Sales and Service Center.
JOHNSON CONTROLS 49
FORM 150.72-RP1 (809)
NOTES
50 JOHNSON CONTROLS
FORM 150.72-RP1 (809)
NOTES
JOHNSON CONTROLS 51
Copyright 2009 Johnson Controls, Inc. Printed in USA 150.72-RP1 (809)
P.O. Box 423, Milwaukee, WI 53203 Supercedes: 150.72-RP1 (1008)