You are on page 1of 7

Proceedings o f 1998 IEEE IAS Industrial & Commercial Power Systems Conference

SHORT-CIRCUIT CURRENTS TO PERFORM A


PROTECTIVE DEVICE COORDINATION STUDY

HERBERT A. FLECK FRANK J. MERCEDE


Kvaemer Davy Elcctrical& Computer Engineering
One Oliver Plaza , Villanova University
Pittsburgh. PA 15222 Villanova. PA 19085
-
Abstract There are two types of short-circuit studies of interest A few words of caution before we proceed. The risk of injury to
to the power engineer. The results of the first type are used to select personnel and damage to power system apparatus is high if a
the withstand and interrupting capabilities of switchgear; whereas, short-circuit study is performed by someone who is unqualified or
the rcsults of the second type are used to properly select the settings inexperienced. Simply reading the literature on the subject does not
of overcurrent protective devices. Oftentimes, the engineer is in certify nor qualify an engineer to perform power system studies in
possession of conimercial software for the first type of short-circuit practice. Although commercial software is the quickest and most
study. Thus, a natural question is whether its output can also be efficient means of performing a short-circuit study, it is important
applicd to the second type. The purpose of this paper is to address that the engineer know how to perform these calculations by hand in
this question, in accordance with Chapter 4 of the IEEE Red Book conjunction with using the commercial software. The results of a
I 11, by comparing the two types of short-circuit studies. The basis computer-aided short-circuit study are susceptible to errors. The
for the comparison is the complex impedance network method. A most common ones are human errors (e.g., data input errors,
sample industrial power system is used to clarify the findings. misinterpretation of results, etc.); although, occasionally the
software is the culprit. Neverthess, the engineer. not the software
Key Words: power system protection, short-circuit currents, vendor, is responsible for the accuracy of the study.
short-circuit analysis, coordination of protective devices.
11. BACKGROUND [4]
1. INTRODUCI'ION
This section provides only a brief background on the fundamentals
There are two types of short-circuit studies of interest to the power of short-circuit analysis to serve the purpose of this paper.
engineer. The first type of study determines the first-cycle References 1 through 5 provide further details.
(momentary) and contact-parting (intempting) short-circuit current
duties (i.e., asymmetrical rms or peak currents) at the buses of the Fig. 1 illustrates a typical short-circuit current waveform for one
power system, which are used to select the short-circuit withstand phase of a three-phase synchronous generator, previously unloaded,
and intempting capabilities of switchgear [I. Chap. 41. To insure which has been subjected to a balanced, three-phase fault across its
safety of personnel and to prevent damage of power system accessible terminals. In general, an asymmetrical short-circuit
apparatus, this type of short-circuit study is performed under current waveform is produced by a balanced, three-phase fault.
worst-case assumptions. These assumptions include selecting the
worst-case fault location at the switchgear bus (which receives all "Asymmetrical altemating currents when treated as a single current
possible short-circuit current contributions) and fault typc (usually a wave are difficult to interpret for circuit breaker applications and
bolted, three-phase fault) [I. Sec. 43.21. relay-setting purposes. Complicated formulas are required to
calculate their magnitude unless resolved into components. The
The second type of short-circuit study determines the subtransicnt asymmctrical altemating currents are, for circuit breaker applications
and transient short-circuit currents that an overcurrent protective and relay-setting purposes, arbitrarily divided into simple
device will sense, in order to initiate the prompt removal of the components, which makes it easy to calculate the short-circuit
affected portion of the power system by its circuit interrupter [2. magnitude at certain significant times after the short-circuit occurs."
Sec. 1.51. These short-circuit currents are necessary to properly 15, pp. 15 and 161
selcct the instantaneous and time delay settings of the overcurrent
protective dcviccs [ I , Chap. 51 12, Chap. 141 13, Chap. 91 [5, For this reason, the asymmetrical short-circuit current waveform of
Chap. 91. Fig. 1 has been decomposed into two components: an unidirectional
(dc) component and a symmetrical ac component. The dc component
Oftentimes, the engineer is in possession of comniercial software for exponentially decays to zero, and the amplitude of the symmetrical
the first type of short-circuit study. To perform the computations, ac component eventually decays to a constant amplitude in the
many of the algorithms employ either reduction of the complex steady-state. The sum of these two components at any time instant
impedance network representation of the power system 12, Sec. 2.61 is cqual to the total asymnictrical short-circuit current at that instant
or else reductions of separate reactance and resistance networks [I, Furthermore, it is important to note that the asymmetrical
Chap. 41. Thus, a nntunl question is whcthcr the output from such short-circuit current wavcfonns of thc other phascs. which are not
a computer-aidcd short-circuit study can also be applied to the shown in Fig. I , differ only in their dc components. The dc
second type of study. The purpose of this paper is to address this coiiiponcnts have different initial values but exponentially decay at
question by comparing the two types of short-circuit stitdies. The the same rate. The rate of exponential decay (i.e., time constant) of
basis for the comparison is the complex impedance network method. the dc component is related to the short-circuit XEQ / REQ ratio,
The organization of the paper is the following. Sec. 11 provides a where XEQ and REQ are the equivalent reactance and resistance at
brief background on the fundamentals of short-circuit analysis. the fault location, respectively. The envelope of the symmetrical ac
Next. Sec. I l l discusses how various types of phase overcurrent component is identical for all three phases.
protective dcvices respond to the short-circuit current waveform.
Based on this discussion, Sec. IV specifies which short-circuit To simplify the analysis, steady-state ac circuit theory is exploited to
currents are necessary to perform a protective device coordination calculate a worst-case (i.e., initial) root-mean-square (rms)
study. SCC.V then coinpares the two types of short-circuit studies, magnitude of the symmetrical ac component to characterize a
based on the complex impedance network representation of the particular time interval of the fault-on time period. There are three
power system. The results of the comparison are used in Sec. VI to time intervals of interest: " ... the subtransient period. lasting
present reconimendations on how the results of a computer-aided only for the first few cycles [at 60 Hz] during which the current
short-circuit study to compute short-ciruit current dutics can be dccrcincnt 1i.c.. decay of the asymmctrical short-circuit currcnt
applied to determine the short-circuit currents that are necessary to waveform] is very rapid; the transient period. covering a
select the settings of phase overcurrent protective dcviccs. Enally, relatively longer time [i.e., beyond six cycles1 during which the
a sample industrial power system is provided in Sec. VI1 to clarify current decrement is more moderate; and finally t h e steady-state
the recommendations. period [i.e.. beyond thirty cycles] __. " (6, Sec. 6-6J T o simplify

0-7803-4509-6/98/$10.00 1998 IEEE


165
id$) iap impedance that is related to the magnitude of decaying generator
short-circuit current at the specificed calcualtion time [ I , Sec.
4.5.431; and. all motor contributions are omitted in the transient
unidirectional dc network.
component
+ At this point. we have only accounted for the ac component of the
asymmetrical short-circuit current waveform. "Calculation of the
precise rms value of an asymmetrical current at any time after the
inception of a short-circuit may be very involved. Accurate
decrement factors to account for the d c component at any time are
required, as well as factors for the rate of change of the apparent
reactances of the gcncraton. This prccisc mcthod may be uscd. if
desired, but simplified methods have evolved whereby the d c
component is accounted for by simple multiplying factors. The
multiplying factor converts symmetrical rms current into
asymmetrical rms current, which accounts for both the dc and ac
components." [5, p. 201
asymmetrical waveform The short-circuit currents which are necessary to select the settings
of an overcurrent protective device must reflect the operating
characteristics and operating times of the device. The response of
the protective device to subtransient asymmetrical rms current andor
subtransient asymmetrical peak current must be known. On the
other hand, it is unnecessary to account for the negligible dc
component over the transient period; so that, only the transient
symmetrical rms current is necessary.

T h e subtransient asymmetrical rms current is calculated by


multiplying the subtransient symmetrical rms current by an
Fig. 1 - Phase current of a short-circuited generator. asymmetry multiplying factor. Strictly speaking, the asymmetry
verbage. the expression "worst-case (i.e.. initial) rms magnitude of multiplying factor depends on the short circuit XEQ / REQ ratio of
the symmetrical a c component" is hereafter shortened to the Thevenin equivalent impedance. &Qat the location 141 171 191.
"symmetrical rms current." in practice, a multiplying factor of 1.6 is used on medium-voltage
systems (> loo0 volts) and 1.5 on low-voltage systems IS,p. 5481.
Thus, the purpose of the analysis is to calculate: The exception for medium-voltage systems is to use the smaller
ld = subtransient symmetrical m s current multiplying factor of 1.5 on systems of 2.4 kV to 5 kV when there
are transformers or appreciable line resistance between the fault
Id = transient symmetrical rms current point and the source [S. Section .54, p. 21. It is important to note
Id = steady-state symmetrical rms current that these figures may have to be increased in order to avoid
nuisance tripping.
In order to perform these calculations, a constant reactance for each
time period is assigned to every machine: 111. PROTECTIVE DEVICE OPERATION UNDER
X' - direct-axis subtransient reactance SHORT-CIRCUIT CURRENT WAVEFORM
P-
x d = direct-axis transient reactance The operating characteristic of a phase overcurrent protective device
Q = direct-axis synchronous reactance dictates how i t responds to the asymmetrical short-circuit current
waveform. For a static relay, it is important to know whether it is
On the other hand, the utility generaton are usually remote from the programmed to sense rms, average, or peak current and calibrated
plant. Their short-circuit current contnbutions to the remote plant for rms current.
appear to them as a small increase in load current. Furthermore,
these current contributions tend to remain constant during the entire Induction-type relays are affected only by the ac component of the
fault-on time period. Therefore, the utility tie is often modeled by a short-circuit current waveform. Generally, the time-current
constant (Le., Thevenin equivalent) impedance over the entire characteilstic curve of such a device is not plotted beyond the
fault-on time period, which is dctcrmincd by knowing the available subtransient symmetrical rms current that it will experience.
short-circuit contribution which can be delivered to the plant.
Finally, the passive apparatus of the system (i.e.. transformers, There are other instantaneous phase overcurrent protective devices
cables, busway, reactors, etc.) are modeled by impedances that are that are affected by both the dc and a c components of the
constant over the entire fault-on time period. short-circuit current waveform and respond within the first
half-cycle. Consequently, subtransient asymmetrical rms current is
The problem of calculating symmetrical rms current can be a crucial factor i n setting these devices.
summarized as follows ( I ) Construct an impedance network by
interconiiecting the appropriate impedances of the apparatus i n Finally, the transient symmetrical rms current is used to vcrify the
accordance with the one-line diagram. (2) Impose the fault location coordination of time-delay phase overcurrent protective devices that
on the network. ( 3 ) Use the series. parallel. and delta-wye are set to operate slower than 0.1 second (i.e., 6 cyclcs).
transformation formulas to reduce the network to an equivalent
impedance, ZEQ ( 4 ) Use Ohm's Law to divide into the rms The following list has been adapted from Sec. 4.5.43of Ref. I ; pp.
magnitude of the prefault phase-to-neutral voltage at the faulted bus 548-9of Ref. 5;and Table 2, Section 3 1 of Ref. 8. It summarizes
to yield the symmetrical rms current. which short-circuit currents affect the operation of specific types of
phase overcurrent protective devices.
In order to apply the above procedure to calculate subtransient
symmetrical rms current, use direct-axis subtransient reactances for S u b t r a n s i e n t Synlnletrical RMS C u r r e n t : High-speed,
all of the rotating machines i n the subtransient networh. T o apply induction-type relays that operate in less than 3 cyclcs (0.05
the procedure to calculate transicnt symmetrical rms current for second); short-time induction relays that are set to opcntc faster than
several cycles (i e , beyond 6 cycles) after fault inception, the 0.1 second (6 cycles); generator, transformer, and bus differential
generator modcl utilizes either its transient reactance or else a larger relays; power-line currcnt balance relays; pilot-wire relays.

2
166
Subtransient Asymmetrical R M S Current: lnstantancous tiniedclay phase overcurrent protective device within a satisfactory
(i.e.. magnetic) functions of thermal-magnetic molded or insulated time. The minimal power system configuration for the transient
case circuit breakers; plunger or hinged armature type instantaneous network may apply at night or whcn production lincs are down for
relays; fast-melting-time zone (< 0. I second) of fuses; instantaneous any reason, and it is often defined under minimum power supply.
and short-time delay functions that are set to operate faster than 0.1
second on electromagnetic or static (i.e., solid-state or The following list summarizes the short-circuit currents which
microprocessor-based) direct-acting trips of low- and should be calculated in order to perform a coordination study.
medium-voltage circuit breakers.
Maximal & Minimal Subtransient Symmetrical RMS
Transient Symmetrical RMS Current: Timedelay induction- Currents: High-speed phase overcurrent protective devices that
type relays that are set to operate slower than 0.1 second; fuse are responsive only to the ac component of the short-circuit current.
operation, under sustained fault current, in melting-time portion of
characteristic that is slower than 0.1 second; long-time and Maximal Subtransient Asymmetrical & Minimal
short-time delay functions that are set to operate slower than 0.1 Subtransient Symmetrical RMS Currents: Instantaneous
second on electromagnetic o r static (i.e., solid-state or phase overcurrent protective devices that are responsive to both the
microprocessor-based) direct-acting trips of low- and dc and ac components of the short-circuit current (cf. Sec. 111).
medium-voltage circuit breakers.
Maximal Subtransient and Maximal & Minimal Transient
IV. SHORT-CIRCUIT CURRENTS TO SELECT Symmetrical RMS Curmnts: Time-delay phase overcurrcnt
SFlTlNGS OF PROTECTIVE DEVICES protective devices that are responsive only to the ac component of
the short-circuit current (cf. Sec. Ill) and are set to operate slower
Based on the previous discussion, the subtransient symmetrical rms than 6 cycles at 60 Hz.
short-circuit current under the maximal power system configuration
should be calculated at the appropriate fault location of every phase V. COMPARISON OF STUDIES
overcurrent protective device. T h e maximal power system
configuration for the subtransient network includes all possible Let us first consider the short-circuit study whose results are used to
short-circuit current sources (i.e., utility service supply, in-plant select the short-circuit withstand and interrupting capabilities of
gencration, and motors). Generally. the time-current characteristic medium-voltage and low-voltage circuit breakers and fuses from
curve of an induction-type relay is not plotted beyond the maximal manufacturers' tables. For this application, there are two types of
subtransient symmetrical rms current nor the pick-up setting of an networks to calculate symmetrical rms current: First-Cycle
instantaneous phase overcurrent relay in the same circuit, whichever (Momentary) Network and Contact-Parting (Interrupting) Network.
is smaller.
The first-cycle (momentary) network is identical to the subtransient
Knowledge of the maximal subtransient asymmetrical rms current is network, and it is used to calculate the symmetrical rms current over
necessary to determine the settings of instantaneous phase the subtransient time interval of the fault-on time period. An
overcurrent protective devices that are responsive to both the dc and appropriate asymmetry multiplying factor is then used to convert
ac components of the short-circuit current waveform. Minimum first-cycle (momentary) symmetrical rms current into first-cycle
settings are required to allow motor locked-rotor current or (momentary) asymmetrical rms current. The withstand capability of
transformer magnetic in-rush current. Higher settings are not a mcdium-voltage circuit breakcr, the interrupting capability of a
necessary but can be used. Coordination of instantaneous phase fuse, and the interrupting capability of a low-voltage circuit breaker
overcurrent devices in series at the same voltage level is not possible must exceed the first-cycle (momentary) asymmetrical rms current
unless there is significant impedance between buses, caused by long [l, Chap. 41.
cable runs or by current-limiting reactors. In this case, the pickup
setting of the upstream device has to be about twice the pickup The contact-parting (interruptin.) network is used to calculate the
setting of the downstream device. A more accurate criterion is that symmetrical rms current for circ$t breaker minimum contact-parting
the subtransient asymmetrical rins current for a fault at the times of 1.5 to 4 cycles after the inception of the short-circuit. For
downstream device is less than the instantaneous setting of the this network, direct-axis subtransient reactances are used for the
upstream protective device. in-plant synchronous turbine-generators, synchronous motor
reactance is calculated by multiplying its direct-axis subtransient
If the subtransient asymmetrical rms current under the minimal rcactance by a rotating machine reactance multiplicr of 1.5, and
power system Configuration is less than the pickup setting of an induction motor contributions are included in accordance with
instantaneous overcurrent relay, the relay will not operate and Tables 4-1 and 4-2 of the IEEE Red Book 11I. An appropriate
protection will depend upon time-delay phase overcurrent relays. asymmetry multiplying factor is then used to convert contact-parting
This situation requires calculation of minimal subtransient (interrupting) symmetrical rms current into contact-parting
Symmetrical rms current in order to determine if the time-delay (interrupting) asymmetrical rms current. The interrupting capability
overcurrent relays will provide adequate protection. The minimal of a medium-voltage circuit breaker must exceed the contact-parting
power system configuration for the subtransient network may apply (interrupting) asymmetrical rms current.
at night or when production lines are down for any reason. Note
that this network still uses direct-axis subtransient reactances for all Let us now compare the two types of short-circuit studies. The
of the rotating machines in use. basis for the comparison is the complex impedance network
representation of the power system.
The transient symmetrical rms short-circuit current under the
maximal power system configuration is calculated at the appropriate Although the first-cycle (momeatary) network is identical to the
fault location of cvcry timedelay phase overcurrent protective device subtransient network. fault location is the principle reason why the
that is set to operate slower than 0.1 second (i.e., 6 cycles). The first-cycle (monientary) symmetrical rms current is nor the same
maximal power system configuration for the transient network value as the subtransient symmetrical rms current.
neglects motor contributions but includes all other short-circuit
current sources (i.c., utility scrvicc supply and in-plant generation). In order to select the short-circuit withstand and interrupting
Knowledge of the maximal transient symmetrical rms current is capabilities of circuit breakers and fuses at a switchgear bus. a
necessary to establish the coordination time intervals for conservative practice is to assume the maximal power system
electromagnetic (i.e., induction-disc) or static (i.e., solid-state or configuration and to locate the three-phase short-circuit at the
microprocessor-bascd) time-delay phase overcurrent relays with switchgear bus so as to receive all possible short-circurt current
other phase overcurrent protective devices. contributions. The maximal power system configuration for the
first-cycle network includes all possiblc short-circuit current sources
Finally, it may be important to calculate the transient symmetrical (i.e., utility service supply, in-plant generation and motors).
r m s current under the minimal power system configuration (i.e..
miniimal transient symmetrical rms current) in order to investigate On the other hand, to select the time-current characteristics and
whether sufficient fault current is available IOcause operation of a settings of a phase overcurrent protective device. the three-phase

167
SUM OF CONTRIBUTIONS SUM OF CONTRIBUTIONS
FROM REMAINING FROM REMAINING
SHORT-CIRCUTT CURRENT SHORT-CIRCUIT CURRENT
SOURCES OF SYSTEM. SOURCES OF SYSTEM.

4.16 kV - Sub K3 -4.16 kV - S u b #


r
*

+
SI IORT-CIRCUIT
11 1-
I

M5 MOTOR BACKFEED.

F3
MAIN FAULT LOCATION
RECEIVES SUM OF
- CONTRIBUTIONS FROM
ALL POSSIBLE

Jf I
SHORT-CIRCUIT CURRENT
SOURCES IN POWER SYSTEM.

f
1M5 IM3
CONIWBUTIONS -
FROM INDUCTION
MOTORS

INDUCTION INDUCTION INDUCTION INDUOION


EACH 1500HP 2 0 H P EACH 1500HP 2WHP
x>=o.16p~ X(h=O.I6pu X$=O.I6pu X(h=O.I6pu

Fig. 2: Three-phase fault location to Fig. 3: Fault location to select time-


select interrupting capabilities current characteristic of fuse.
short-circuit is located at the terminal of the device (i.e., or its determined by: (I:) J f: IL - If;ls. Finally, as stated previously,
current transformers) which causes the largest short-circuit current
to flow through it. (For a radial power system, this fault location is (Id)! is multiplied by an appropriate asymmetry multiplying factor
the load-side terminal of the protective device o r its current to yield the subtransient asymmetrical rms current.
transformcrs.)
Note that the difference between the subtransient symmetrical rms
Let us consider a specific example to better illustrate the distinction current (to delineate the time-current characteristic of the power
between these two types of fault locations. Fig. 2 presents the fuses) and the first-cycle (momentary) symmetrical rms current (to
designations and illustrates the directions of the short-circuit current select the short-circuit interrupting capabilites of the power fuses) is
contributions to the three-phase fault location, F3, at the 4.16 kV the short-circuit (i.e., first-cycle symmetrical rms) current
Substation #3 bus. The purpose of this fault location is to calculate contribution of induction motor M 5 (i.e., motor backfeed). For this
example, the motor backfeed is approximated by:
the first-cycle (momentary) symmetrical rms current. In Fig. 2. I[
denotes the phasor representation of the short-circuit current
contribution; and the superscript, f, refers to the first-cycle network.
bfJ
Finally, ~ f=, F .is multiplied by an appropriate asymmetry
= 1804 amperes @ 4.0 kV
multiplying factor [ I , Chap. 41, based on the equivalent short-circuit (a
C)
S 0.16(4.0)
X / R ratio at the fault location, to yield the first-cycle (momentary)
asymmetrical rms current. The short-circuit interrupting capabilities Finally, the principle difference between the contact-parting
of the medium-voltage power fuses at this bus must exceed the (interrupting) network and the transient network is time. Circuit
first-cycle (momentary) asynimetncal rms currcnt. breaker minimum contact-parting times arc 1.5 to 4 cyclcs after the
inception ofthe short-circuit, and motor contributions are included
Next. Fig. 3 shows the three-phase fault location, J, at the load-side in the contact-parting (interrupting) network. The transient period
terminal of the power fuse for induction motor M5. The purpose of covers a relatively longer time period, beyond 6 cycles; so that,
this location is to calculate the subtransient asymmetrical rms motor contributions are ignored in the transient network. Therefore,
current, which is then used to delineate the upper (i.e., right-most) the contact-parting (interrupting) symmetrical rms current is larger
current limit of the fuses time-current charactenstic curve. by motor contributions than the transient symmetrical rms current.

Now. the firstxycle network is predominantly reactive. because the VI. RECOMMENDATIONS
short-circuit X / R ratios of its apparatus are relatively large. Thus, In this section we present recommendations on how to apply the
as an approximation, the magnitudes of the phasor currents can be
added and subtracted without regard to their phase angles (which are results of a computer-aided short-circuit study that selects withstand
and interrupting capabilities of switchgear lo dcterniine the
all in the neighborhood of %lo). Therefore, referring to Fig. 3 . the short-circuit currents (i.e., maximal and minimal subtransient and
subtransient symmetrical rms current at fault location J can be transient symmetrical rms currents) to properly select the

4
168
time-current characteristics and settings of phasc overcurrent three-phase bolted fault at that bus.'ln addition, an iniportant table is
protcctivc dcviccs. I t is vcry important to note that thcsc provided that lists all of the branch flows of first-cycle symmetrical
recommendations arc based on the complex impedance network rms currcnt for a thrcc-phax bolted fault at cvcry bus.
representation of the power system.
The first run of the' program was performed under the niaximal
First and foremost, it is important to use the appropriate fault power system configuration. The information from the print-out
location and account for motor backfeed. Imposing the appropriate was used to dcterminc thc maximal subtransient symmetrical rnis
fault location and accounting for motor backfeed on thc subtransient currents at the fault locations (i.e., locations A through K) of the
and fint-cycle networks, the subtransient symmetrical rms current is phase overcurrent protective devices.
equal to the first-cycle (momentary) symmetrical r m s current, which
can be calculated by the procedure in Chap. 4 of the IEEE Red Book As a n example, consider fault location D i n fig. 4. Note that the
I11. In turn, the subtransient asymmetrical r m s current is calculated current transformers for the Motor M2 overcurrent relays will not
by multiplying the first-cycle (momentary) symmetrical rms current sense the M2 niotor backfeed for a thrcc-phase fault at location D.
by an appropriate asymmetry multiplying factor, in accordance with Consequently, the maximal stibtransicnt symmetrical rms current at
the rules in Sec. 11. fault location D. used to select the settings of the Motor M2
overcurrent relays, is the following:
As mentioned previously, the transient symmetrical nns current is
different (i.e., smaller by motor contributions) than the
(I"J$X *fmax Ifinax
contact-parting (interrupting) symmetrical rms current. However, E 2BI - 2BS12-2B1
the principal use of the maximal transient symmetrical rms current is
to establish the coordination time interval for a time-delay phase = 13.537 - 1.506 = 12.031 kA Q 13.8 kV
overcurrent relay (i.e., set beyond 6 cycles) with another phase fmax
overcurrcnt protcctive device. T o establish this timc interval at a where 12, i s the total first-cycle symmetrical r m s current for a
larger value of short-circuit current is a conservative practice insofar three-phase bolted fault at the 13.8 kV main bus 2B 1 and
as coordination is conccmcd. Howcvcr, a coordination time interval lfniax
which is too conservative may not be desirable from the standpoint 2Bs 12-2B I is the branch flow of first-cycle symmetrical rms current
of limiting equipment damage; because, in the event that the from Motor M2 bus 2BS12 to bus 2B1 under a three-phase bolted
downstream protective device fails to operate, the upstream fault at bus 2Bl.
(back-up) protective device may take too long to operate. I n
summary, with regards to coordination, it is permissible 12, Sec. The same rationale is used to derive the following equations to
14.2.21 to use the maximal contact-parting (interrupting) calculate the maximal subtransient symmetrical rms currents at the
symmetrical rms current (instead of the maximal transient other fault locations. The results are tabulated at the end of this
symmetrical rms current) to establish the coordination time interval. section (cf. Table 1).
Finally, it is permissible [ I , Secs. 4.5.4.3 and 4.6.51 to use the
approximate 30-cycle network (instead of the minimal power system
configuration for the transient network) in order to investigate rfmax Ifmax
whether the minimum symmetrical rms current is sufficient to cause (I;):AX = 1B1 - 281-181
satisfactory operation of a time-delay current-actuated relay. The
=
-
Ifmax finax fmax
approximate 30-cycle network is a minimum source representation 2 81 2BS 11-2BI - '2,s 12-2B 1
that may apply at night or whcn production lines arc down for any
reason. Some of the source circuit breakers may be open. and all Ifmax fmax
motors are omitted. In-plant generators use direct-axis transient - 2BS13-2Bl-I2BS14-2Bl
lfmax - {max
reactance or a larger reactance related to the magnitude of decaying
generator short-circuit current at the specified calculation time. The
(1i)C"""= 2B1 2BSll-2B1
dc component will have decayed to near zero and is not considered.
(IJyX =
fmax Ifmax
'2B1 - 2BS13-2B1
VII. EXAMPLE
(I;):AX =
fmax fmax
l2BS 1 11 - '4B 1-2BS 1 11
The preceeding recommendations are applied to the sample industrial lfmax - lfmax Ifma
power system of Fig. 4. Fig. 4 shows the appropriate fault =
locations (i.e., labeled A through K) of the phasc overcurrent 4B 1 4BS 13-4B1- 4BS 1 4 4 B 1
protective devices and provides the input data and the labeling of fmax ,fmax
(I,);"" = '3B1 - 3BSll-3B1
buses for the computer-aided short-circuit study. The commercial
software is designed to compute the first-cycle (momentary) and fmax fmax
contact-parting (interrupting) short-circuit current duties (i.e., -'3BS12-3Bl - '3BS13-3Bl
asymmetrical r m s currents) at the buses of the power system, which
arc used to select the short-circuit withstand and intcrrupting (I;)yAX= fmax fniax
'4BS14- '4BS1414BS14
capabilities of switchgear. The algorithm of the software employs
complex impedance network reduction. lfmax fmax
= 3B1 - '3BSI 1-3BI
The program was run under three different power system
configurations: maximal power system configuration, minimal
(lipx =
fmax Ifmax
'4B1 - 4BS W 4 B 1
power system configuration. and approximate 30-cycle
configuration. The maximal power system configuration includes In addition, another column of the print-out lists for each bus the
all possible short-circuit current sources. The minimal power total contact-parting (interrupting) symmetrical r m s current for a
system configuration is defined for this example to exclude (i.e., three-phase bolted fault at that bus. However, this particular
out-of-scrvicc) the 1500 hp M4 induction motor load and the loads software package does not provide a table of the branch flows of
of low-voltage Substation #2. Finally, the only sources of contact-parting (interrupting) symmetrical rms current for a
short-circuit current under the approximate 30-cycle network three-phase bolted fault at every bus. (It only provides a table of the
branch flows of first-cycle symnictrical r m s currcnt.) Without this
configuration are the utility tie and in-plant generator; and the information. it is not uossible to use similar eauations to those
in-plant gencrator is represented by its direct-axis transient reactance
instead of the subtransient reactancc.
Appendix A provides a summary of the essential results from the maximal transient symmetrical mis cuirents at the fault locations of
print-outs. The program was run for each power system the phase overcurrent protective devices. Of course. if the motor
configuration. For each run, one column of the print-out lists for
each bus the total first-cycle symmetrical rms current for a backfeed Gy12-2B1
is a negligiblc fraction of 1% then

5
169
34.5 kV Utility Line

1520125 MVA
9375 kVA 63 0.8 PF OA/FA/K)A Class

SYNCH.MOTOR
5OOO HP @ 0.8 PF

INDUOTON = loo0 HP INDUCrrION = 1500 HP.

INDUCTION
EACH 1
4.0 kV, X I R = 30. 4.0 kV, X I R = 32,
INDUCIlON = 350 HP ?::0.16PU 2;=0.16PU

LARGEST INDUCTION:
150 HP

Figure 4. Labeling of buses for computer-aided short-circuit study.


6

170
t MAX
lmax
12B1 would not tx an ovcrly conservativeapproximation of(1d)D .
A second run of the software was performed under the minimal
power system configuration. The print-out of the run provided the
same types of results as before, and similar equations to those above
were used to calculate the minimal subtransient symmetrical rms
currents at the fault locations of the phase overcurrcnt protective
devices. The results are tabulated at the end of this section.
A third run of the software was performed under the approximate
30-cycle network configuration. Recall that the only sources of
short-circuit current under the approximate 30-cycle network
configuration are thc utility tie and in-plant generation, and the
in-plant generators are represented by direct-axis transient reactances
instead of their subtransient reactances. Since this version of the
software only provides a tablc of tlic branch flows of first-cyclc
symmetrical rms current, a simple trick was employed to produce a
table of the branch flows of approximate 30-cycle symmetrical rms
current for a three-phase bolted fault at every bus. The trick was
simply to replace the previous input data of the generator's ' Faulted Prefault Maximal Minimal Maximal Approx.
subtransient reactance with the value of its transient reactance (i.e.,
13.5 9%) and rcrun the program under the approximate 30-cycle Bus Voltage Erst-Cycle Erst-Cycle Interrupt 30-Cycle
network configuration. The output of the run provided the same 1BI 34.5 kV 34.821 34.775 34.787 34.233
types of results as before, and similar equations to those above were 2B1 13.8kV 13.537 13.091 13.204 9.338
used to approximate the minimal transient symmetrical rms currents 2BSlll 13.8kV 13.493 13.049 13.163 9316
at tlic fault locations or tlic pliasc ovcrcurrciit protcctivc dcviccs. 3t31 4.16kV 14.258 12.749 12.357 8.683
The remaining results are tabulated below. 481 4 8 o V 36.871 36.796 36.871 28.099
TABLE 1 4BS14 48OV 12.692 12.687 12.692 9.399
Computer-Aided Short-circuit Study Results
ymmetrical RMS Currents at Fault Locations of Protective Devices
protective maximal, minimal, maximal, minimal, Branch Flows of Symmetrical RMS Kiloamperes
subtransient subtransient transient transient for Bolted Three-phase Faults
device
fault symmetrical symmetrical symnietrical symmetrical I From-To Faulted Maximal Minimal Amrox.
rmsM rmskA rmskA rmskA Busses Bus First-Cycle First-Cycle 3cii3ycle
location

A 33.414
(GyN
33.413
(Id)MAX
N.A.
(I;)"
33.413
2B1-1B1
2BSll-2Bl
2BS12-2B1
1B1
2B1
2BI
1,407
0.419
1.506
1.362
0.220
1.505
0.820
0
0
B* 6.434 6.434 (6.436) 6.436 2BS13-2B1 2B1 1.053 0.807 0
C* 13.I18 12.871 (12.263) 9.338 2BS14-2B1 281 4.125 4.125 2.902
D* 12.03 1 I I .S86 ( 1 1.324) 9.338 4 B 1 - 2 B S l l l 2 B S l l l 0.219 0.219 0
E* 12.484 12.284 ( 11S 2 7 ) 9.338 3BSll-3Bl 3B1 1.967 1.966 0
F* 13.274 12.830 ( 12.263) 9.3 16 3BS12-3B1 3B1 1.476 0 0
G 28.989 28.9 14 N.A. 28.099 3BS13 -3B1 381 1.475 1.475 0
H 9.340 9.307 N.A. 8.683 4BS13-4B1 4B1 5.408 5.408 0
I I I .662 1 I .657 N.A. 9.399 4BS14-4B1 4B1 2.474 2.474 0
J 12.29 1 10.783 N.A. 8.683 4BS141 -4BS14 4BS14 1.030 1.030 0
K 34.397 34.322 N.A. 28.099
111 IEEE Std 141-1993, IEEE Recoiiiinended Prucrice for Electric
Power Dislribufionfor Industriul Plaius (IEEE Red Book), first
N.A. -
not available from computer-aided short-circuit study.
printing. IEEE, Piscataway, NJ, Chapter4, 1994
* - computer results validated with hand calculations.
( ) - result of hand calculations.
121 IEEE Std 242-1986, IEEE Recoinmentled Pructice f o r
Protection and Coordinution of Industrial and Coininerciul
Power Sysfems (IEEE Buff Book), sixth printing. IEEE,
Hand calculations were performed to validate the results of the Piscataway, NJ, Chapter 14, June 1994
computer-aided short-circuit study at fault locations B, C, D, E and
13I IEEE Std 241- 1990, IEEE Recoininended Practice for Elecwic
F. Unfortunately, space restriction disallowed the inclusion of these Power Svstems in Co/mrerciul Bitifdings ( I EEE Gray Book),
hand calculations in the paper. first printing, IEEE, Piscataway. NJ, Chapter 9, Sept. 1991
141 Frank J. Mercede, Fault Culculurionc oflndusrriul/Coiiuiierciul
VIII. CONCLUSIONS Power Systcnis. IEEE Self-Study Course. IEEE Order No.
HL0459-8, IEEE Educational Activities Board, Piscataway,
There are two types of short-circuit studies of interest to the power NJ, 1994
engineer. The results of thc first type are used to select the Donald Beeman, InduLlstriui Power Sy.tfeni.tHandbook, first
withstand and interrupting capabilities of switchgear: whereas, the edition, McGraw-Hill, New York, 1955
results of the second type arc used to properly select the settings of A.E. Fitzgerald, C. Kingsley, Jr. and S.D. Umans. Electric
overcurrent protective devices. This paper presents a comparison of Muchinery, fifth edition, McGraw-Hill. New York, 1990
these short-circuit studies. The results of the comparison are then Craig N. Hartnian, "Understanding asymmetry." IEEE
used to formulate recommendations on how the results of a Transactions on Industry Applicationss, vol. IA-21, no. 4. pp.
computer-aided short-circuit study of the first type can be applied to 842-8, July I Aug. 1985
determine the short-circuit currents of the second type. I81 General Electric Co.; Indu.wiul Power S ~ S I C I IDurcr
I S Book;
Schenectady, N Y ;p. 2, S e c . .54 and Table 2 , Sec. . 5 4 1 ; 1955
I t is imperative that the engineer clearly understand the solution 191 A.A. Regotti, "Calculating short-circuit currents for systems
algorithm of the software. T o perform the computations, many of without ac decav." 1982 IEEE Industrial and Coniniercial
the algorithms employ either reduction of the complex impedance Power Systems '(I&CPS) Conference. 82CH 1740-0. May
network representation of the power system or else reductions of 1982, Philadelphia, PA, pp. 1 IS-9

7
17 I

You might also like