SINGLE PHASE UPS SIZING GUIDE 1/Nov/13

UPS Full Load(%)


Mdl Rating UPS Load Chassis 20% 30% 40% 50% 60% 70% 75% 80% 90% 100% (Full Load)
Ref (VA) Ver (W) WF TW RK VA W Runtime VA W Runtime VA W Runtime VA W Runtime VA W Runtime VA W Runtime VA W Runtime VA W Runtime VA W Runtime VA W Runtime

1,000 B 800 Sine Y 200 160 53:48 300 240 33:02 400 320 24:37 500 400 18:44 600 480 13:54 700 560 11:26 750 600 10:12 800 640 9:29 900 720 8:14 1,000 800 7:00
+1 (HB)EBM 126:19 89:08 58:39 48:59 38:05 29:11 27:33 25:52 22:30 19:07
+1 (B)EBM 201:03 138:38 105:34 84:43 61:16 53:12 49:38 45:56 38:33 31:10

1,000 LB 800 Sine Y 200 160 300 240 400 320 500 400 600 480 700 560 750 600 800 640 900 720 1,000 800
+2 (B)EBM 403:32 188:07 144:52 114:53 97:18 79:52 71:13 62:16 55:10 49:38
+3 (B)EBM 670:03 307:28 223:44 179:13 151:30 124:02 115:56 109:59 98:03 86:07
+4 (B)EBM 952:33 458:36 328:04 247:51 205:48 173:29 163:15 152:41 131:33 115:56

2,000 B 1,600 Sine Y 400 320 78:56 600 480 51:34 800 640 35:49 1,000 800 27:15 1,200 960 22:08 1,400 1,120 17:01 1,500 1,200 14:48 1,600 1,280 13:52 1,800 1,440 12:02 2,000 1,600 10:12
+1 (HB)EBM 172:23 119:04 93:38 69:38 54:35 46:11 41:58 37:56 29:58 27:33
+1 (B)EBM 274:42 190:04 145:43 114:53 96:47 78:41 69:38 60:56 54:56 49:38

2,000 LB 1,600 Sine Y 400 320 600 480 800 640 1,000 800 1,200 960 1,400 1,120 1,500 1,200 1,600 1,280 1,800 1,440 2,000 1,600
+2 (B)EBM 418:51 265:56 197:52 161:23 129:18 110:22 103:34 97:03 84:04 71:13
+3 (B)EBM 704:07 463:07 476:10 247:51 204:42 172:05 161:23 151:06 130:39 115:56
ITYS 2 (Online Double Conversion)

+4 (B)EBM 978:05 677:48 330:53 382:35 287:04 234:07 219:25 205:15 178:27 163:15

3,000 B 2,400 Sine Y 600 480 48:54 900 720 28:15 1,200 960 21:19 1,500 1,200 14:58 1,800 1,440 12:16 2,100 1,680 9:49 2,250 1,800 9:10 2,400 1,920 8:29 2,700 2,160 7:08 3,000 2,400 5:46
+1 (HB)EBM 114:46 74:55 53:14 42:42 30:56 26:46 25:02 23:11 19:29 15:46
+1 (B)EBM 179:02 118:25 93:54 71:13 55:38 47:55 44:07 40:04 31:57 28:07

3,000 LB 2,400 Sine Y 600 480 900 720 1,200 960 1,500 1,200 1,800 1,440 2,100 1,680 2,250 1,800 2,400 1,920 2,700 2,160 3,000 2,400
+2 (B)EBM 247:20 167:38 124:11 104:46 85:45 67:05 59:21 56:18 50:13 44:07
+3 (B)EBM 440:48 263:07 198:27 163:15 133:18 113:11 107:03 100:29 87:23 74:16
+4 (B)EBM 621:59 403:12 277:41 221:59 180:47 158:22 147:29 135:52 116:53 107:03

6,000 B 5,400 Sine Y 1,200 1,080 63:08 1,800 1,620 41:00 2,400 2,160 27:05 3,000 2,700 20:56 3,600 3,240 14:57 4,200 3,780 12:43 4,500 4,050 11:36 4,800 4,320 10:26 5,400 4,860 9:04 6,000 5,400 7:55
+1 (HB)EBM 153:42 102:00 76:11 57:59 49:38 41:25 37:22 33:04 27:51 24:30
+1 (B)EBM 234:31 158:54 114:17 92:31 77:43 64:02 58:55 56:03 50:18 44:33

6,000 LB 5,400 Sine Y 1,200 1,080 1,800 1,620 2,400 2,160 3,000 2,700 3,600 3,240 4,200 3,780 4,500 4,050 4,800 4,320 5,400 4,860 6,000 5,400
+2 (B)EBM 347:40 216:00 160:20 121:43 104:40 89:17 84:13 78:50 68:04 58:55
+3 (B)EBM 523:34 361:59 245:16 195:26 163:07 138:15 125:59 117:00 105:57 94:55
+4 (B)EBM 794:11 474:00 365:55 273:09 221:47 187:36 174:56 165:09 145:34 125:59

10,000 B 9,000 Sine Y 2,000 1,800 42:00 3,000 2,700 23:51 4,000 3,600 15:52 5,000 4,500 12:02 6,000 5,400 8:56 7,000 6,300 6:56 7,500 6,750 6:06 8,000 7,200 5:32 9,000 8,100 4:29 10,000 9,000 3:42
+1 (HB)EBM 90:00 58:04 43:41 29:46 24:09 19:10 17:34 16:02 13:53 12:13
+1 (B)EBM 140:00 92:45 67:48 53:37 43:56 34:15 29:46 27:58 24:22 20:48

10,000 LB 9,000 Sine Y 2,000 1,800 3,000 2,700 4,000 3,600 5,000 4,500 6,000 5,400 7,000 6,300 7,500 6,750 8,000 7,200 9,000 8,100 10,000 9,000
+2 (B)EBM 190:00 122:09 93:14 74:16 58:27 51:12 47:34 44:04 37:06 30:11
+3 (B)EBM 310:00 195:58 145:06 112:20 93:43 80:19 74:16 68:26 58:44 54:08
+4 (B)EBM 435:00 273:57 197:01 156:52 123:52 107:41 100:42 93:58 83:52 75:14

All runtime are based on approximate values only.

SOCOMEC UPS Single Phase Product Selection Guide v2.2.xls/ ITY2 1-10kVA/ 12/11/2013