2. Strut-like buckling:
Su = Qf / C1
Where,
1/ 2
2
a
2
L
C1 2 2
n 1 2 n n 4 x i x
p s s w 2n p j
1 w1
a = Diaphragm width
n1 = Total number of end connectors over the section width a
1
Diaphragm Action at P&B Endwall
Calculations :
Factor of safety = 2
Zamil wall panels are properly fastened to the supporting structural units framing and are capable of
resisting loads through in-plane shear resistance. This shear resistance is causing a shear transfer of these
loads to the foundation with practically no deflection.
The resistance of wall sheeting acting as a diaphragm is approximately 4.8 kN/m2. The minimum effective
lengths of sheeting required for a standard wind load of 1.0 kN/m2 are shown in the following table so as to
eliminate sag rods and diagonals. The effective lengths shall be exclusive of any framed openings for
accessories etc.
Explanation: Eave height of the building is 8.0 m and the endbay of the building is 6.1 m, then the
minimum sheeting length along the width of the building is 5.08 m in each endwall column bay.
This is obtained as: (6.1/2)x1.0x8/4.8=5.08m < End wall bay spacing (O.K)