systems (UETTRDSB03A)
Certificate IV in ESI Substation Resources (UET40206)
Learner Guide
E
PL
M
SA
E
Introduction....................................................................................................................8
Hazards Associated with DC Systems...........................................................................8
Environmental Considerations.......................................................................................9
Performance Characteristics of DC Systems .................................................................9
Storage Battery Principles..............................................................................................9
Primary Cells .............................................................................................................9
Install and maintain substation DC systems Learner Guide -3- NSW DET 2009
Principle of Impedance Testing ...........................................................................25
Student Activity: Discharge and Impedance Testing...........................................26
Recycling Secondary Battery Cells .............................................................................26
DC Testing ...............................................................................................................27
Student Activity: DC Testing...............................................................................27
DC Lighting Systems...................................................................................................27
First Aid ...................................................................................................................28
DRABC................................................................................................................28
Electric Shock ......................................................................................................29
Acid and Alkali Spills..........................................................................................29
Muscle Strain .......................................................................................................30
E
Learning Tasks and Practical Exercises.......................................................................31
PL
M
SA
Install and maintain substation DC systems Learner Guide -4- NSW DET 2009
Introduction
DC systems are installed in substations to supply power for control, protection,
alarms, communications, and other critical auxiliary circuits where maximum
reliability of supply is essential.
AC supplies can be unreliable, whether it is obtained from the local supply or from
on-site alternator sets. In the event of AC supply failure, DC electricity is stored in
batteries with sufficient capacity to provide enough power until the AC supply
becomes available again.
Different DC voltages are used within substations depending upon equipment
E
requirements. Common voltages are 50, 120 and 400.
The storage batteries may be of a few main types: lead-acid, alkaline, and nickel-
cadmium; each type with its own characteristics.
Substation staff need to have an understanding of how batteries are maintained, the
principles of charging and discharging of batteries, how to recognise and diagnose
PL
battery faults, and how to diagnose faults which may occur in the DC distribution
network. Installation in the context of this Learning Module refers to replacement
of defective units. (Installation and commissioning of battery banks will be generally
performed by contractors from the supplier.)
The principles contained within this module are also appropriate to other electrical
and electronic fields that use DC storage systems, including telecommunications,
security, computer and renewable energy.
Hazards Associated with DC Systems
There are a number of hazards that may be present when working with DC systems in
M
electrical substations. These include:
Electrical shock DC voltages and large currents may be high enough to cause
severe burns or electrocution.
Acids and alkalis Can burn skin and eyes.
Large mass batteries and cells are very heavy and can cause injury if not lifted
SA
Install and maintain substation DC systems Learner Guide -8- NSW DET 2009
Environmental Considerations
As you will learn, battery cells may be constructed using the heavy metals of lead or
cadmium. Both of these metals are known to be detrimental to the environment, and
if absorbed by the human body they can be very detrimental to health. If nickel
cadmium cells are carelessly disposed of in landfills the cadmium eventually
dissolves and the toxic substance can seep into the water supply, causing serious
health problems.
Cells which have reached the end of their life or are faulty are returned to the
manufacturer on an exchange basis for replacement new cells, or are sent to specialist
recycling facilities where the metals are recovered and reused.
E
Battery rooms must be kept clean. Liquid spills or leaking electrolyte must be
cleaned up.
Battery rooms should be bunded to prevent harmful chemicals entering the
environment. Bunding is a method of sealing the flooring and walls so that liquids
cannot escape into the environment. Any signs of damage to the proofing membrane
PL
(cracking, flaking etc) should be reported.
All waste associated with DC Systems should be disposed of correctly, in accordance
with your organisational guidelines.
Further detail on environmental management can be found in the Learning Module:
UETTDRIS23A - Implement and monitor environmental and sustainable energy
management policies and procedures.
The battery should be able to be recharged from its design end-of-discharge voltage to
full charge in 5 hours.
Install and maintain substation DC systems Learner Guide -9- NSW DET 2009
common metal rusting is a type.) The common zinc-carbon dry cell and alkaline dry
cell is an example of this type of battery. A typical voltage of such a primary cell is
1.5 volts. Lithium dry cells may have voltages higher to 3 volts due to the higher
electrochemical potential of this metal and its compounds. The name dry cell is
given because the electrolyte is in a paste-form rather than liquid form.
Primary cells must not be recharged as they may explode.
Secondary Cells
Also called storage or accumulator cells, these battery cells can be recharged because
the chemical reaction that occurs during discharge can be reversed by applying a
reverse current into the cell. The cell can be discharged and recharged many times
E
(often many thousand times) before it is degraded to the point where it can no longer
provide reliable service.
PL
This is perhaps the most common type of rechargeable battery,
especially in substation environments. It is also called a wet-cell
or flooded-cell battery because the electrolyte is in a liquid form.
They are vented batteries because the charging process can
produce gasses of hydrogen and oxygen which needs to be able to
escape from the confines of the battery case.
In its charged state the cathode (positive plates) are lead peroxide,
the anode (negative plates) are lead, and the electrolyte is dilute
sulphuric acid. As the cell is discharged the plates are converted to
lead sulphate and the electrolyte becomes water. The chemical
M
reaction looks like this:
The open circuit voltage of a fully charged lead acid cell is between 2.3 volts and 2.4
volts. Under load the voltage will typically be between 2.0 volts and 2.2 volts.
Lead acid batteries have reduced life expectancy if they are left in a discharged
condition. Ordinarily they do not deal well with deep discharge cycles, although
recent advances in design have produced lead acid batteries more suitable to such
tasks.
Install and maintain substation DC systems Learner Guide - 10 - NSW DET 2009
Often a number of cells are packaged together in one case to give a battery of higher
terminal voltage. Other common voltages for lead acid batteries are 6 volts and 12
volts.
E
Figure 2 A number of cells
can be combined to provide a
battery of greater voltage and
energy capacity.
PL
Sulphation
Sulphation is a natural occurrence in all lead/acid batteries including sealed and gel-
cel batteries. It the prime cause of early battery failure and is when the sulphur in the
sulphuric acid forms sulphur crystals attach to the lead plates and then act as an
"insulation" keeping the battery from accepting a charge.
Terminal Corrosion
Lead acid batteries suffer from terminal corrosion because of the corrosive
M
atmosphere created by the misting of sulphuric acid which is vented from the
battery. Most people are familiar with the corrosion that forms around the terminals
of a cars lead acid battery. The crystals that form are often yellow in colour
(sulphur) and bluish-green (copper salts). To minimise this corrosion it is common
practise to use petroleum jelly to create a barrier between the sulphuric acid and the
metal terminals and connectors.
SA
Install and maintain substation DC systems Learner Guide - 11 - NSW DET 2009
Sealed Lead Acid (SLA) Batteries
This is a particular type of lead acid battery which is becoming more common
because of the reduced maintenance requirements. More correctly, they should be
called a valve regulated lead-acid battery, because they do have a valve to release
internal gas build up which can result from overcharging. The electrolyte has been
jellified making the battery more resistant to
extreme temperatures, vibration and shock.
This is also why they are sometimes called
Gel Cells. They also have calcium included
in the plate construction which reduces the
E
gassing effects, minimising loss of electrolyte.
PL
Nickel Iron/ Nickel Alkaline
Figure 4 A valve-regulated lead acid
(VRLA) battery.
Also abbreviated to NiFe cell (or simply written as Nife). This type of battery cell is
becoming far less common, however can still be found in some older substations.
Manufacturing of this type of battery has almost ceased.
It uses a nickel oxide (Ni2O3) cathode, an iron anode, and an electrolyte of potassium
hydroxide, which is alkaline.
M
NiFe cells have a nominal voltage of 1.2 volts (1.4 volts open circuit).
They have advantages of being very robust, lifetimes in excess of 30 years are
possible, and can be deep cycled.
Disadvantages include excessive weight, steep voltage drop off with state of charge,
high self-discharge rates, can only be charged slowly, and are only able to be
SA
discharged slowly.
Nickel Cadmium Cells
Most of us are aware of the round sealed nickel cadmium rechargeable batteries used
in many of todays consumer items. Although they appear very physically different
they use a similar chemical reaction to the
vented stationery batteries used in
substations and other standby power
arrangements. Sometimes referred to by
the abbreviation NiCad, although strictly
speaking this is a copyrighted name to one
particular manufacturer.
Nickel cadmium cells cost as much as five
times more than lead acid batteries,
however they have the advantage of large
capacities and discharge rates. Vented Figure 5 Vented wet cell nickel
cadmium cells.
Install and maintain substation DC systems Learner Guide - 12 - NSW DET 2009
nickel cadmium cells are not normally damaged by excessive rates of overcharge,
discharge or even reverse charging. Oxygen and hydrogen are released through the
vent, and this explains the need to top up the water levels of vented nickel cadmium
cells. (Note: Sealed nicads are damaged by such adverse actions.)
The nominal voltage of a nicad cell is 1.2 volts.
Can deliver very high currents.
They can be left for long periods in a discharged state without damage (unlike
lead acid cells).
The electrolyte in a nicad is potassium hydroxide (alkaline - similar to the nickel
E
iron cell), and cross contamination from sulphuric acid must be avoided. It does
not change
(Like nickel iron cells) the specific gravity of nickel cadmium cells is unchanged by
the charging-discharging process.
Identification of Battery Type
PL
The external appearance of lead acid and alkaline (nickel cadmium or nickel iron)
batteries can be very similar. However the electrolyte is not interchangeable, and it is
important that when doing any testing or servicing that correct identification of
battery type is undertaken. Generally a label will be placed on the battery container to
indicate its type.
Internal Resistance
Electrically a battery cell appears as a voltage source with a resistor in series. The
actual output voltage at the battery terminals will be less than the voltage source
SA
depending upon the value of the internal resistance and the current being drawn. As
the internal resistance of the battery increases, then Ohms Law tells us that as current
(load) increases then the available terminal voltage will drop, eventually making the
battery useless for the intended purpose. However, with little to no load, the voltage
at the terminals will not be significantly different from the internal voltage source. It
can be deceptive to decide the serviceability of a battery simply by measuring its
terminal voltage it is only under load conditions that we can truly know if its
internal resistance is satisfactorily low.
The principle of internal resistance
applies to both non-rechargeable and
rechargeable batteries. It is an
important concept and measurement
in determining whether a battery is
still serviceable or not.
E
The lead acid cell does not perform well at a 1C discharge rate. To obtain a
reasonably good capacity reading, manufacturers commonly rate these batteries at
0.1C or less (10 hour discharge). For example, a 40Ah battery is reckoned to be able
to provide 4 amps for 10 hours. If, however, the current is doubled to 8 amps, the
time to discharge would be less than half somewhere around 4 hours. The effect
PL
is more dramatic as the discharge current increases ten times the current (40 amps)
would reduce the capacity such that it would only supply current for 30 minutes. The
capacity would in effect have been reduced to the equivalent of 20Ah.
120
Capacity vs Load - Lead/Acid Cell
100
Percentage of available capacity
M
80
60
40
SA
20
0
0.1 1 10 100 1000
Figure 7 In the case of a lead acid cell, as the discharge rate is increased
its available capacity decreases.
Referring to the Capacity vs Load Chart for a lead acid cell we can see how the
capacity is reduced as the current drawn from the cell is increased.
This derating of lead acid battery capacity needs to be taken into consideration when
designing DC power supply systems. This is to ensure that the required capacity is
available for the expected load and duration that the cell must be able to provide
power.
Install and maintain substation DC systems Learner Guide - 14 - NSW DET 2009
Install and maintain substation DC
systems (UETTRDSB03A)
Certificate IV in ESI Substation Resources (UET40206)
Trainer Guide
E
PL
M
SA
E
Learning Outcomes......................................................................................................10
Topics Covered in this Learning Module ....................................................................10
Hazards Associated with DC Systems.........................................................................11
Environmental Considerations.....................................................................................11
Performance Characteristics of DC Systems ...............................................................13
Storage Battery Principles............................................................................................13
Install and maintain substation DC systems Trainer Guide -3- NSW DET 2009
Timing Instructional Content Notes to Trainer
E
Introduction
DC systems are installed in substations to supply power for control, protection, Display Slide 2 & 3
alarms, communications, emergency lighting, and other critical auxiliary circuits
where maximum reliability of supply is essential.
PL
AC supplies can be unreliable, whether it is obtained from the local supply or from
on-site alternator sets. In the event of AC supply failure DC electricity is stored in
batteries with sufficient capacity to provide enough power until the AC supply
becomes available again.
While the battery provides the reserve of stored energy, this is only normally used
in an emergency, or for supplying the short time heavy current drain of circuit
breaker closing solenoids. Under normal conditions the station load and the small Some ESI organisations may use other
current required to maintain the battery in a fully charged state is supplied by the voltages such as 20VDC and 30VDC.
battery charger. Furthermore, there may be some
Different DC voltages are used within substations depending upon equipment tolerance around the actual voltage
Install and maintain substation DC systems Trainer Guide -9- NSW DET 2009
Learning Outcomes Display Slide 4
E
(As per those listed on Page 5 of this Trainer Guide.)
PL
Primary and secondary cells
Lead-acid cells
Alkaline cells
Cell capacity
Battery maintenance
Battery testing
Earth fault detection
M
SA
Install and maintain substation DC systems Trainer Guide - 10 - NSW DET 2009
E
Hazards Associated with DC Systems Display Slide 6
There are a number of hazards that may be present when working with DC
systems in electrical substations. These include:
Electrical shock DC voltages and large currents may be high enough to cause
severe burns or electrocution.
PL
Acids and alkalis Can burn skin and eyes.
Large mass batteries and cells are very heavy and can cause injury if not
lifted and transferred using appropriate techniques.
Confined spaces gases from battery cells can build up and require ventilation
before battery rooms can be entered.
This list is not definitive. A risk assessment should always be performed before
commencing any activity. The work method statement for your organisation can
also provide guidance about how to work safely.
M Treatment of these injuries is covered in the section on First Aid later in this
Learning Guide.
For more detail on working safely in electrical substations refer to Learning
Module: UETTDRIS22A - Implement and monitor the organisational OHS
policies, procedures and programs.
Install and maintain substation DC systems Trainer Guide - 11 - NSW DET 2009
manufacturer on an exchange basis for replacement new cells, or are sent to
specialist recycling facilities where the metals are recovered and reused.
E
Battery rooms must be kept clean. Liquid spills or leaking electrolyte must be
cleaned up.
Battery rooms should be bunded to prevent harmful chemicals entering the
environment. Bunding is a method of sealing the flooring and walls so that liquids
cannot escape into the environment. Any signs of damage to the proofing
PL
membrane (cracking, flaking etc) should be reported.
All waste associated with DC Systems should be disposed of correctly, in
accordance with your organisational guidelines.
Further detail on environmental management can be found in the Learning
Module: UETTDRIS23A - Implement and monitor environmental and sustainable
energy management policies and procedures.
M
SA
Install and maintain substation DC systems Trainer Guide - 12 - NSW DET 2009
E
Performance Characteristics of DC Systems
The battery is required to supply the electrical requirements of the system
substation when there is no output from the battery charger. This may be due to a
loss of the A.C. supply to the substation or a fault in the battery charger or its
supply. Under these conditions the battery is required to supply the loads it is The period that the battery is required to
connected to for a period of 10 hours. supply DC power, and the re-charge
PL
period, may vary from organisation to
organisation, and this figure should be
The battery should be able to be recharged from its design end-of-discharge treated as typical or modified for the
voltage to full charge in 5 hours. organisation that training is occurring in.
Primary Cells
Install and maintain substation DC systems Trainer Guide - 13 - NSW DET 2009
Secondary Cells
E
Also called storage or accumulator cells, these battery cells can be recharged Display Slide 9
because the chemical reaction that occurs during discharge can be reversed by
applying a reverse current into the cell. The cell can be discharged and recharged
many times (often many thousand times) before it is degraded to the point where it
can no longer provide reliable service.
PL
Lead Acid Batteries Most people would be aware of lead acid
batteries used in automobiles.
This is perhaps the most common type of rechargeable battery, especially in
substation environments. It is also called a wet-cell or flooded-cell battery
because the electrolyte is in a liquid form. They are vented batteries because the Display Slide 10
charging process can produce gasses of hydrogen and oxygen which needs to be
able to escape from the confines of the battery case.
In its charged state the cathode (positive plates) are lead peroxide, the anode
(negative plates) are lead, and the electrolyte is dilute sulphuric acid. As the cell is
M discharged the plates are converted to lead sulphate and the electrolyte becomes
water. The chemical reaction looks like this:
+ve plate
Cell charged
-ve plate
Cell discharged
+ve plate -ve plate Display Slide 11
SA
PbO2 + Pb + 2H2SO4 PbSO4 + PbSO4 + 2H2O
The open circuit voltage of a fully charged lead acid cell is between 2.3 volts and
2.4 volts. Under load the voltage will typically be between 2.0 volts and 2.2 volts. Display Slide 12
Lead acid batteries have reduced life expectancy if they are left in a discharged
Install and maintain substation DC systems Trainer Guide - 14 - NSW DET 2009
condition. Ordinarily they do not deal well with deep discharge cycles, although Automobile batteries have 6 cells
recent advances in design have produced lead acid batteries more suitable to such connected in series providing an output
E
tasks. voltage of 12 volts loaded and closer to
Often a number of cells are packaged together in one case to give a battery of 13.8 volts unloaded.
higher terminal voltage. Other common voltages for lead acid batteries are 6 volts
and 12 volts.
Sulphation
PL
Sulphation is a natural occurrence in all lead/acid batteries, including sealed and
Display Slide 13
gel-cell type batteries. It the prime cause of early battery failure. It occurs when
the sulphur in the sulphuric acid forms hard sulphate crystals attach to the lead
plates. These crystals then act as an insulator, keeping the battery from accepting
a full charge.
Terminal Corrosion
Display Slide 14
Lead acid batteries suffer from terminal corrosion because of the corrosive
atmosphere created by the misting of sulphuric acid which is vented from the
battery. Most people are familiar with the corrosion that forms around the
M terminals of a cars lead acid battery. The crystals that form are often yellow in
colour (sulphur) and bluish-green (copper salts). To minimise this corrosion it is
common practise to use petroleum jelly to create a barrier between the sulphuric
acid and the metal terminals and connectors.
Install and maintain substation DC systems Trainer Guide - 15 - NSW DET 2009
Nickel Iron/ Nickel Alkaline
E
Also abbreviated to NiFe cell (or simply written as Nife). This type of battery cell Display Slide 16
is becoming far less common, however can still be found in some older
substations. Manufacturing of this type of battery has almost ceased.
The electrolyte of a NiFe cell IS NOT
It uses a nickel oxide (Ni2O3) cathode, an iron anode, and an electrolyte of compatible with a lead acid battery.
potassium hydroxide, which is alkaline. Contamination of the two different types of
PL
NiFe cells have a nominal voltage of 1.2 volts (1.4 volts open circuit). electrolyte must be avoided.
They have advantages of being very robust, lifetimes in excess of 30 years are Unlike a lead-acid cell, the electrolyte is
possible, and can be deep cycled. not changed during charging and
discharging of a NiFe cell. It remains as
Disadvantages include excessive weight, steep voltage drop off with state of potassium hydroxide (2KOH). Therefore
charge, high self-discharge rates, can only be charged slowly, and are only able to specific gravity testing will not indicate the
be discharged slowly. state of battery charge.
M Most of us are aware of the round sealed nickel cadmium rechargeable batteries
used in many of todays consumer items. Although they appear very physically
different they use a similar chemical reaction to the vented stationery batteries
used in substations and other standby power arrangements. Sometimes referred to
by the abbreviation NiCad, although strictly speaking this is a copyrighted name
to one particular manufacturer.
Nickel cadmium cells cost as much as five times more than lead acid batteries,
Display Slide 17
SA
however they have the advantage of large capacities and discharge rates. Vented
nickel cadmium cells are not normally damaged by excessive rates of overcharge,
discharge or even reverse charging. Oxygen and hydrogen are released through
the vent, and this explains the need to top up the water levels of vented nickel
cadmium cells. (Note: Sealed nicads are damaged by such adverse actions.)
The nominal voltage of a nicad cell is 1.2 volts.
Can deliver very high currents.
Install and maintain substation DC systems Trainer Guide - 16 - NSW DET 2009
Install and maintain substation DC
systems (UETTRDSB03A)
Certificate IV in ESI Substation Resources (UET40206)
Assessment Guide
E
Instructions to Assessors
This Assessment Guide is part of a suite of resources that have been developed to
support 8 core units of competency from the Certificate IV in ESI Substation
PL
(UET40206) as follows:
UETTDRIS05A
UETTDRIS22A
UETTDRIS23A
UETTDRSB01A
UETTDRSB02A
Perform substation switching operation to a given schedule
Implement and monitor the organisational OHS policies,
procedures and programs
Implement and monitor environmental and sustainable energy
management policies and procedures
Diagnose and rectify faults in power systems substation
environment
Carry out substation inspections
UETTDRIS03A Install and maintain substation DC systems
M
UETTDRIS04A Maintain HV power system circuit breakers
UETTDRIS05A Maintain HV power system transformers and instruments
This Assessment Guide together with a Trainer Guide and a Learner Guide are
designed for UETTDRSB03A Install and maintain substation DC systems. This
guide is intended to provide some direction to assessors who are determining
competence of students who have completed the theoretical and practical instruction
SA
in this learning module. Assessors are expected to use their own judgement in
designing appropriate assessment questions and tasks and putting them into context
for the assessment candidate. At all times the evidence requirements as set out in the
unit and the principles of assessment, that is, validity, reliability, flexibility and
fairness must be complied with.
Use these guidelines to assist in preparing your own assessment instruments and tools.
The checklist should be treated as a starting point. You may choose to add more
checkpoints to highlight particular aspects of knowledge and skill that you want to see
evidence of. This could be through practical tasks or problem-based questions.
Evidence Required
Evidence for competence in this unit shall be considered holistically. Each element
and associated Performance Criteria shall be demonstrated on at least two occasions in
accordance with the Assessment Guidelines UET06. Evidence must also reflect
the critical aspects of evidence which includes the following:
E
reported in accordance with the preferred approach; namely a percentile graded
result, where required by the regulated environment.
Demonstrate an appropriate level of skills enabling employment.
Conduct work observing the relevant Anti Discrimination legislation, regulations,
polices and workplace procedures.
PL
To be deemed as competent in this Unit, the candidate must provide sufficient
evidence of being able to maintain and repair the range of DC systems within the
electrical substation.
Where summative (or final) assessment is used it is to include the application of the
competency in the normal work environment or, at a minimum, the application of the
competency in a realistically simulated work environment. In some circumstances,
assessment in part or full can occur outside the workplace. However, it must be in
accordance with industry and regulatory policy. (For more detail on assessment
practices you are advised to refer to the Training Package and the Evidence Guide
for this Unit of Competence, especially where longitudinal competency development
M
and Profiling has been used).
This assessment guide covers all tasks and equipment included in the section of the
Unit: Critical aspects for assessment and evidence required to demonstrate
competency in this unit, as shown in the table below.
on which skill is to be
demonstrated.
At least one of the Nickel cadmium batteries
following: Sealed/unsealed lead acid batteries
At least one of the Main batteries
following: Communication batteries
Pilot isolation batteries
All of the following: Battery chargers
DC control circuits
At least two of the Cell voltage test
following: Hydrometer/specific gravity test
Battery discharge and capacity tests
Impedance testing
Install and maintain substation DC systems Assessment Guide 2 NSW DET 2009