Professional Documents
Culture Documents
net
9500 Series Pilot Operated Safety Relief Valve Sizing Program
POINT MOUSE ON RED ARROW TO VIEW DISCLAIMER
To use the Mercer Valve sizing program, the information on "DATA ENTRY" sheet must be comple
ENTRY" sheet, notice the red arrows thoughout the sheet. Point on these arrows for more infom
information may help entering correct data into the program. Enter data into the shaded boxes
boxes to choice different options. When all information is entered and correct, the program w
choose a valve size to meet given conditions. The pull down menus at the bottom of the scree
appropriate accessories. After your selection process is complete the data entry sheet can be
"Printout" a data sheet for the Pilot Operated Valve can be viewed and printed. . This informat
selection, quoting, and ordering of the valve. Thank you for using Mercer Valve
NAME: PHONE:
COMPANY: FAX:
LOCATION:
TAG NUMBER: REFERENCE #:
1) Select information from boxes below. Relieving Temperature only used for Sizing Calculation
Sizing Method: ASME, Section VIII, Div. 1 System Type:
Select 9500 Series Type: Gas API Letter Orifices Rupture Disk Installed Under Main Valve: No
Compressiblity Factor: 1
4) Pressure 5) Temperature
Constant: 0 psig
Orifice Size: D Orifice
Built-Up Back Pressure Selected Orifice Area: 0.151 in
Variable: 0 psig Selected Orifice Flow: 374.751 scfm
Inlet Size: 1x2 Pilot Body Material: CF3M SS Body and Crbn Stl Bonnet
Disclaimer
#N/A
Note: This sizing program does not take material compatibility or pressure and temperature limitations into account for choosing
materials. Please verify all material choices with Mercer Valve Company, Inc.
00000008/22/2017 16:09:46
Customer Name:
Company:
Location:
Phone:
Fax:
Reference #:
Valve Tag Number:
FLUID FLUID STATE Natural Gas GAS/VAPOR
MOLECULAR WEIGHT SPECIFIC GRAVITY 17.4 0.6
Fluid Data
GAS CONSTANT k-RATIO OF SPECIFIC HEATS 344.1 1.27
COMPRESSIBILITY FACTOR REQUIRED CAPACITY 1.000 100.000 scfm
SUPERIMPOSED CONST BP SUPERIMPOSED VARIABLE BP 0.000 psig 0.00 psig
BUILT-UP BP TOTAL BACK PRESSURE 0.000 psig 0.00 psig
OPERATING TEMP RELIEVING TEMPERATURE 60.0 Fahrenheit 60.0 Fahrenheit
OPERATING PRESSURE ATMOSPHERIC PRESSURE 0.00 psig 14.70 psia
SET PRESSURE FLOWING PRESSURE 100.00 psig 124.70 psia
CDTP OVER PRESSURE 100 psig 10.00 psig
DISCHARGE COEFFICIENT AND AREAS ASME, Section VIII, Div. 1
VALVE CERTIFICATION / DESIGN CODE ASME BOILER AND PRESSURE VESSEL CODE, SECTION VIII, DIVISION 1
SYSTEM TYPE
REQUIRED AREA FLOW COEFFICIENT 0.040 in 0.870
SELECTED ORIFICE 0.151 in D Orifice
Sizing Results MAXIMUM CAPACITY OF VALVE AT OVER PRESS. 374.751 scfm
TAG CAPACITY 300.3 SCFM AIR
DECIBEL LEVEL SINGEL OUTLET REACTION FORCE 94 dB @ 100ft (30m) 41 lbF w/OUTLET PRESS=OVER PRESS
Disclaimer #N/A
Comments
00000008/22/2017 16:09:46
ENG-711000CUST v6.4CUST
31-Jul-14
SAK
Customer Name:
Company:
Location:
Phone:
Fax:
Quote #:
Reference #:
Tag Number:
60 x Q x w TxZ
A =
K x C x P M
K x C x P x A M
Q =
60 x w TxZ
Note:
1) ALL UNITS ARE CONVERTED TO PSI, SCFM, IN, AND RANKINE.