06C1-E-0004a
Fuji Vacuum Circuit Breaker
for Safe Operation, Easy Handling and Compactness
Vacuum circuit breakers are compact designed for safe operation, Scope of VCB basic type
high reliability and easy maintenance, and are widely used for External view Internal view
Rated voltage [kV] 3.6/7.2
various types of high voltage circuits.
Rated breaking current
Fuji HS series vacuum circuit breakers (VCB) have been [kA]
20 25 31.5 40 50
developed through the use of our many years of successful 600
Rated
experience and advanced technology. They are compact and current 1200
light-mass (weight), and are available in a number of current [A] 2000
ratings. 3000
4000
handle
2100
ZCT
CB
The excellent insulation recovery characteristics of the vacuum 20kA
interrupter allow it to react quickly from small current to short- 600A Closing
spring Closing
circuit currents, and also to exhibit a stable interrupting lever
charge
performance in double earth fault and out-of-phase currents. CT
indicator
SA
Tripping push Aux.
ZCT button circuit
plug
50
N89-6317-4
1800 Closing push Tripping spring Closing spring
button charge indicator Gear unit
Hole for manual
charging handle
[Unit: mm]
1 2
Ratings and Specifications
3 4
Type designations
Type HS4010 HS4010 HS5010 HS5010 HS1220 HS1620 HS2520 HS4020 HS2530
- Mf-NA - Mf-N - Mf-NA -30Mf-N - Mf-EA - Mf-E - Mf-E - Mf-N - Mf-N HS2010Y-06M f -E
Ratings Voltage [kV] 12 24 36
Normal current JEC [A] 1200, 2000 3000, 4000 1200, 2000 3000 600, 1200 600, 1200, 2000 1200, 2000, 3000 600, 1200, 2000
IEC [A] 1250, 2000 3000, 4000 1250, 2000 3000 630, 1250 630, 1250, 2000 1250, 2000, 3000 630, 1250, 2000
Basic type
Short-circuit breaking current [kA] 40 50 12.5 16 25 40 25
3.6/7.2kV, 20 to 40kA : HS E
Short-circuit breaking capacity [MVA] 830 1040 520 665 1000 1660 1600 3000A max. and
(reference value) 12kV, 12.5 to 31.5kV
Short-circuit making current [kA] 100 125 31.5 40 63 100 63 2000A max.
(peak value) 24kV, 16, 25kA
24kV, 12.5kA : HS EA
Short-time JEC, 2s [kA] 40 50 12.5 16 25 40 25
withstand IEC, 1s*1 [kA] 40 50 12.5 16 25 40 25 3.6/7.2kV, 50kA 1200/2000A and : HS NA
current 12kV, 40, 50kA 1200/2000A
Except for the above ratings : HS N
Breaking time [cycle] 5 3 5 3
Short-circuit breaking current
Rated withstand 1 min power JEC [kV] 28 50 70
Rated [kA] Symbol
voltage frequency IEC [kV] 28 50 70
12.5 12
Impulse (1.2 x 50s) [kV] 75 125 170 16 16
No-load closing time [s] 0.1 0.04 0.1 0.1 20 20
25 25
Rated operating sequence JEC O-1min-CO-3min-CO, CO-15s-CO or O-0.35s-CO-1min-CO
31.5 31
IEC O-3min-CO-3min-CO, CO-15s-CO or O-0.3s-CO-3min-CO
40 40
Opening time JEC [s] 0.04 0.07 0.03 0.07 0.04 50 50
(4000A: 0.07)
IEC [s] 0.04 0.03 0.07 0.04
Voltage
Operating Closing system Motor-spring stored-energy (rapid auto-reclosing) (M)
Rated [kV] Symbol
system
Operating voltage and current 100V 6A 100V 2A 100V 2.5A 100V 6A 3.6/7.2 06
for closing AC, DC 200V 3A 200V 1A 200V 1.7A 200V 3A 12 10
Control voltage and current 100V 4A 100V 4A 100V 5A 100V 4A 24 20
for closing AC, DC 200V 2A 200V 2A 200V 2.5A 200V 2A 36 30
Tripping system*2 Shunt trip (f) Installation
Operating voltage and current 100V 4A Type Symbol
for tripping DC 200V 2A Fixed type P
Draw-out type for HS2530 M
Draw-out unit type for class CW X, U
Draw-out unit type Y
No. of auxiliary switches (for external circuit) 4NO+4NC, switching capacity 100/200V AC: 20/10A, 100/200V DC: 5/3A
for class MW or PW
Service life Mechanical [time] 10000
Normal current
Rated normal current switching [time] 10000 Rated [A] Symbol
Installation P, Y P, Y (3000A) P, Y P, X, Y P, Y P, M, X 600, 630 06
X (4000A) 1200, 1250 12
Mass (for draw-out type main unit only) [kg] 210 320 (3000A) 240 320 120 (P, X, 600A) 190 (Y, 600, 1200A) 280 (1200, 2000A) 280 (M, X, 600, 2000 20
400 (4000A) 130 (P, X,1200A) 200 (Y, 2000A) 350 (3000A) 1200A) 3000 30
135 (Y) 300 (M, X, 2000A) 4000 40
Connection daiagrams (page 11) C A B C Closing system*
System Symbol
Dimensions (pages 12 to 16) F 3000A: J F G K K L 1200, 2000A: M O
(typical example *3) 4000A: E 3000A: N Motor-spring stored-energy M
(rapid auto-reclosing)
Notes :*1 Contact Fuji for the information concerning to the 3s time rating of IEC.
*2 If capacitor tripping mechanism is required, connect a capacitor trip unit VCB-T1PB, T1A or VCB-T2PB, T2A (optional accessory) to an AC power supply. Tripping system*
*3 Contact Fuji for dimensions of the types not listed here. System Symbol
Shunt trip f
Note :* For closing and tripping systems, specify the type and operating
vlotage.
5 6
Construction
110
90
18
The closing mechanism is simple in design and provides high automatically after closing. This breaker model is suitable for rapid 7 6
auto-reclosing duty. It can be used for reclosing since the charging 2-M5
reliability. The circuit breakers use a motor-spring stored-energy 110 15
closing mechanism of the rapid auto-reclosing type. time for the motor mechanism is 15s or less. Shunt trip (f) 17 83 18
52a
SW C2 Terminal M4
P 100/110V or C
SA
900.2
200/220V DC
1
N Shunt trip
92
5 7 9
r2 r3 coil
Operating mechanism
45
Protective 52T Earth
relay Rf P1 r1 45
R S T terminal M4 2-7
N, NA types 900.2
8 6 View from P holes
Panel cutting
9 5 8
VCB-T1A, T2A types
52T 52a
Capacitor trip unit VCB 3-7 holes for mounting
N, NA types
20
Pilot
VCB-TK lamp
Breaker shaft (Mounting plate fittings for mounting in the cubicle.
190
230
Closing spring
130 50
Tripping coil 90 35 52
Closing coil 27
Shaft shaft
Breaker 80 124
120
92
90
90
130
Tripping spring
Closing spring Hole for cable inlet: 28
Tripping coil 70 2-7 Rubber bush inside
4-7
Closing coil dia.: 23
Shaft
Tripping spring Specifications
Open position Open position Closed position Closed position
(spring free) (spring charged) (spring free) (spring charged) Name Type Rated input Effective time for tripping VCB shunt
E, K types voltage AC [V] trip coil DC [V]
Capacitor VCB-T1PB, T1A 100/110 Within 30s after AC 100/110
Open position Open position Closed position Closed position trip unit power disappeared
(spring free) (spring charged) (spring free) (spring charged) Closing spring VCB-T2PB, T2A 200/220 200/220
E, K types Tripping spring Installation
Closing cam
Installation Fixed type M draw-out type Draw-out unit type
Closing ratch
Breaker spring
Closing shaft X U Y
ratch
Tripping spring
Operating
Closing cammotor
Closing ratch
Breaker shaft
Tripping ratch
Operating motor
Open position Open position Closed position Closed position
(spring free) (spring charged) (spring free) (spring charged) Type HS...P HS...M (for HS2530) HS...X HS...U HS...Y
Main circuit Screw Plug
connection
Terminal
Open position Open position Closed position Closed position Aux. circuit Connector
(spring free) (spring charged) (spring free) (spring charged) Earth (ground) Screw Shoe
Insulation shutter With
Interlock With draw-out interlock
7 8
Vacuum Interrupter Accessories
: Provldod
Standard accessories are listed in table below. Optional accessories are available on request. : Not provlded
In the vacuum interrupter, there is a pair of cup contacts, each having oblique slots.
This contact structure allows a current to flow along a winding path as shown by "1" in the
Service life Fuji VCB type Motor-spring stored-energy (rapid auto-reclosing)
HS2006, HS2506 All VCBs except for models on the left
Remarks
illustration below. Judgement of vacuum condition Installation Fixed type Draw-out unit type Fixed type Draw-out unit type
Name P X U Y P X Y
When the contacts open, the arc deflects in the direction shown by "2" and rotates in the The vacuum condition in the vacuum
Standard Mounted on Operating counter Mounted on VCB
direction shown by "3". interrupter is an important factor for accessories VCB Closing spring charge indicator
The arc is driven round the contact surface without arc stagnation, and is extinguished in a operation of the VCB. Main circuit connecting bolt
short time. This prevents local overheating of the contact surface and uneven wear of the The interrupter of Fuji VCB is designed Fixing parts
contacts, thereby providing a longer service life. to maintain a high vacuum for a long Mounted on Main circuit isolating fixed contact In case of
Since the contacts are made of a special material, chopping current flowing into the period of time. It is factory tested to insure cradle Insulating shutter installation type
contacts is reduced to 3.5A. reliable performance. Draw-out-guide * * X, U and Y, these
Cradle mounted on cradle
When checking the vacuum condition, use
Accessories Aux. circuit plug
the following procedure.
Manual charging handle 1 per 5 VCB
With VCB in the "open" condition, apply a
Draw-out handle
commercial frequency voltage (ex.22kV Optional Mounted on Limit switch for closing spring charge Mounted on VCB
Insulator effective value for VCB rated at 7.2kV) for accessories VCB indication (ON "a" contact)
1min time across the poles of the same Limit switch for indication of service Mounted on cradle (2
Fixed contact and isolated positions max. SPDT "c"contact)
phase. When the vacuum interrupter
withsatnds this voltage, the vacuum Au. plug-in interlock
Shield
Separate Capacitor trip unit
Moving contact
condition is normal.
mount, option Mounting plate In case of mounted
in the cubicle for
Bellows Mechanical life VCB-T1PB, T2PB
The VCB has a simple and excellent Connector with external lead wire Length 3m
operating mechanism, so the mechanical Testing jumper
Vacuum condition tester
Guide
stress developed at the time of operation
Lifter
remains the constant and hence the
Notes :* Except for "E" and "EA" type
mechanical characteristic is kept stabilized
for many years of use. For the mechanical Capacitor trip unit Lifter (Manufacturer :FUJI INDUSTRY MFG.,LTD.)
life, refer to the table on pages 3 to 6. Type Mount type Rated input voltage Type Carrying VCB type Remark
AF96-32 Fuji VCB is equipped with an operating VCB-T1PB Flush mounting 100/110V AC L-2HNB HS2006-E Other available
counter for check of the mechanical life. VCB-T1A Surface mounting HS2506-E equipment
VCB-T2PB Flush mounting 200/220V AC HS2010-06, 12-E MULTI. VCB
VCB-T2A Surface mounting HS2510-06, 12-E VMC (HN46A)
Function of contact structure Electrical life HD type truck
The electrical life of the vacuum interrupter Vacuum condition tester L-2HS40E HS3106-12, 20-E
is determined by the switching of load as HS4006-12, 20-E
Type Available VCB type Remark HS1210-20-E
shown in the table on pages 3 to 6. It can VC-1A 3.6/7.2kV type VCB HS1610-20-E
be checked by observing the amount of VC-2A 12 to 36kV type VCB HS2010-20-E
wear of the contacts which is indicated by HS2510-20-E
the wear indication mark (for "N" and " HS3110-12, 20-E
NA" types). The indication mark can be Capacitor trip unit Vacuum condition L-4HS30E HS3106-30-E VCBs for L-2HS40E can
HS4006-30-E also be mounted.
visually checked from the front of the VCB tester
L-4HS43N HS5006-12, 20-NA
(except for "E" and "EA" types) without VCB-T1PB, T2PB VCB-T1A, T2A VC-1A HS4010-12, 20-NA
removing it from the switchgear. (Flush mounting) (Surface mounting) HS5010-12, 20-NA
HS4020-12, 20-N
L-4HS44N HS4006-40-N VCBs for L-4HS43N can
HS5006-30-N also be mounted.
HS3110-30-N
HS4010-30, 40-N
1 2 3 HS5010-30-N
HS4020-30N
The current path bends as The arc receives the force The arc is driven in the L-4HS12K HS1220-06, 12-EA
shown by both arrows. in the arrow direction. arrow direction, and HS1620-06, 12-E
it rotates without arc AF94-108 SH27 L-4HS22E HS2520-06, 12, 20-E
stagnation.
9 10
Connection Diagrams Outline Drawings [Unit: mm]
A HS2006, HS2506, HS1210-06, 12, HS1610-06, 12, HS2010-06, 12, HS2510-06, 12, HS1220, HS1620
Closing Closing Tripping
A HS2006Y..........E(600, 1200A), HS2506Y..........E(600, 1200A)
15 min
408
(1) LS2 1 2 10 e*
Red B B
10
(2) 12 6 8 4-11
(1) LS1
(1) LS3 (1)
(2) (2) (2) 52X
(150)
(3) 52Z
(69)
175
22
40
52Z (6)
(21)
(1)(3) (6) 52 52 Yellow a*20 P
(4) (7) (20)
220
52 (6) 23 24 25
M
35
35
533
473
533
576
(3) 52X
220
52 (8) Q
(32) 26 27 28 2-11
4 35
(33) Blue
187
(1) a*35
187
0
(6) 52X
A
29 34 35
52C 52Z 52T
53
(8) (7)
36 37 38 300
300 162 184 116
Green 12
4-4-12 500
VCB 39 50 51 425 35
35 500 22 Details of Q View from P
holes
12 2 8 23 25 27 29 35 37 39 51 E 649 130
() () () 4NO 4NC Aux. circuit plugs
contacts View from front of VCB
Draw-out stroke
control operation control
(+) (+) (+) 500
on off Protective relay 180 433
Aux. switches 514 40
FI
10 1 6 22 24 26 28 34 36 38 50 457 e* 3M12
d*20
10
36
55
(1)
12
LS2 1 2 10 145 145
Red
12
0
(2) LS1 12 6 8
(1) (1)
(1) LS3 (2) (2)
(2)
(3) 52X
164
(3) 52Z
673
695
(1) LS4 P
240
(6) (21) (6) 22 a*20
625
(2) (1) Black 52 52 Yellow
630
(4) 52Z (20) (6)
(7) 23 24 25
185 121
185 121
52 52X M
473
(3)
240
52 (8) Red
(32) 120 Q
243
(6) 26 27 28 a*35
0
(33) (1) (7) Blue M12
52X 29 34 35 140
52C 52Z 52T d*20
(8) 300 164 199 For 2-screw
36 37 38 12
4-4-12 35 500 23
Green 478 Details of Q View from P
VCB 39 50 51 holes
12 2 8 23 25 27 29 35 37 39 51 563 660 130
() () () 4NO 4NC Aux. circuit plugs
contacts View from front of VCB Min. distance for safe
10
(+) LS2 12 10
(NC)
(+)
(+) LS1 8 6 P
(+) LS3 (NC) (NC)
(NO) 52Z 23 22
245
(6) 52 52
(4) 52Z (2) (21)
(6) 25 24 180 180
688
810
810
(1) (20) 52 M 27 26
(3)
a*38
52
20
(32) 29 28
(33) (a)
A
(+) LS1 35 34
5
a*27 27.5 27.5
52C 52Z (NC)
(b)
52T 37 36
39 38 3-M10 80
400 35 500
500
VCB 51 50 d*20
12 2 8 582 12 679 115
23 25 27 29 35 37 39 51
4-
4-12 View from P
() () () 666 15 holes
4NO 4NC Aux. circuit plugs
contacts 681
View from front of VCB
Note* a: approx. d: depth e: elec. parts egual to earth potential h: height p: pitch
11 12
D HS3106Y(3000A), HS4006Y(3000A)
Draw-out stroke
G HS5006Y(3000A), HS5010Y(3000A)
1000
Draw-out stroke
660 775
760 200 605
200 570 155
275 275
30
38
550 2-14
2-14
P p*550
P
365
470
1200
950
1203
100
Ventilation hole
784
160
20 55 20
220 220
324
100
5
a*27
35
383
250
200 130
100
A 180 205 A
25
25
35 35 900
35
500* 280* 130 3-M10 275 275
100
44
44
540
540
12 35
35 600
600 405 405 900 155 3-M10 View from P Section A A
4-
4-12
700 320 20 55 20 960 d*20
holes 3-14
3-14 14
2-2-14 3-14
3-14
390 390 15 850 View from P p*405 p*200 p*405
E HS4006X(4000A), HS4010X(4000A)
Draw-out stroke
H HS1210Y(600, 1200A), HS1610Y(600, 1200A), HS2010Y(600, 1200A), HS2510Y(600, 1200A)
Min. distance Draw-out stroke
760 for safe
200 945 650 200 482
275 275 100 155 500 315
20 55 20 P
15min
40 30 408 40 15min 94
C20
40 30
e*
10
240
60
40
90
200 150 65
1205
470
180
65 65
1095
905
270
681
736
90
20
10
Ventilation hole
681
613
500
a*
180
40
2-14
40
493
145 40
2-12 pin
385
271
a*35 40 20
185
185
15
0
200 20 300 250 290 260
4.5
Draw-out stroke
HS5006, 5010 245 459 141
615
200 605 HS4010 291 413 155 Min. distance for safe 200 459
210 210 Current A
55 38
30
30
e* 1200A 363
2000A 359
R17.5
10
50 P 3-M12, d*20
View from P P
(HS5006, HS5010)
245
180 180
820
953
950
820
688
B
20
210 210
a*38
5 27.5 27.5
A
a*27
35 35
100
80
25
400 d*20
20 35 500
3-M10 View from P
44
130
275 275 210 210 310 810 2-M12, d*20
HS3110 438
30
200
HS4010 383
550 2-14 100
p*550 Ventilation hole 30 35
P Cardle top view
160
55
1203
30 R60
470
1200
Ventilating hole
1205
470
with removable
1100
50 cover
275 275
150
A
35 35
25
25
100
385
99 31
3-M10
211 310
200 180 205 668 20 55 20 d*20
78
44
44
100
10
lifter
80 80
400
1205
40
100
470
P
1100
470
2-M12, d*20 P
1098
1148
30 35 A Section A-A
A
385
20
55 55
160
70 150
200
55
6M10
423
50
10
d*25
35 35
R6
100
100
30 30 683.5
0
1400
470
566
1295
1130
2-M12, d*20
1203
1283
230 230
30 35
View from P
586
160
455
55
a*38
R6
30
0
5 50 420
692 a*42100 350 350 230 10 510
830 735
285 50 920
937 15 6-14 783 30
950
holes 1110 400 View from P 878
Note* a: approx. d: depth e: elec. parts egual to earth potential h: height p: pitch Note* a: approx. d: depth e: elec. parts egual to earth potential h: height p: pitch
15 16
Ordering Information Application Guide of Surge Absorber
HS f E
The high surge voltage by the VCB that injures the insulation of Connection of surge absorber
Basic type Closing system Frequency the machines and apparatus is generated under certain specific The surge absorber should be connected between the VCB and
conditions. The necesstiy of surge protection depends on the its load (device) as shown ; connect each phase betwwen the
3.6/7.2kV, 20 to 40kA : HS........ E Motor-spring stored-energy :M 50/60Hz : C1 dielectric strength of the device used as a load. power line and the earth.
3000A max. and (rapid auto-reclosing) Special (50Hz) : C2 The application guide given below is based on the results of
12kV, 12.5 to 31.5kV Ditto (60Hz) : C3 switching surge tests. When the dielectric strength of the device is
low, use of a surge absorber is recommended.
2000A max.
24kV, 16, 25kA Tripping system
Surge absorber application guide VCB
24kV, 12.5kA : HS...... EA
Voltage 3.3kV 6.6kV 11kV 22kV
3.6/7.2kV, 50kA 1200/2000A : HS...... NA Shunt trip :f Environmental ambient condition Load
*4
and Rotating OCR
machine C-R C-R C-R I >
12kV, 40, 50kA 1200/2000A Basic : D1 suppressor suppressor suppressor
Except for the above ratings : HS........ N Closing operation voltage Special (to tropical area) : D2 Molded *2, *3 *2, *3
*3 *3
*1
AC : Acceptable transformer C-R Gapless
suppressor arrester
or gapless
Closing cotrol voltage arrester
Short-circuit breaking current AC : Acceptable (BIL45kV) (BIL60kV) (BIL55kV) (BIL95kV)
L
imit switch for indication of service Oil-immersed *2, *3 *2, *3 *2, *3 *2, *3 Surge protection
*1
transformer (BIL45kV) (BIL60kV) (BIL90kV) (BIL150kV)
[kA] 12.5 16 20 25 31.5 40 50 Tripping control voltage and isolating positions Load device
device
*3 *3 *3 *3
Symbol 12 16 20 25 31 40 50 AC : Non-acceptable Dry-type
*1
transformer C-R C-R C-R Gapless
Without provision : F1 suppressor suppressor
suppressor arrester
DC [V] 100 110 200 220 Special (1 SPDT in each) : F2 or gapless
Symbol 1 2 3 4 arrester
Ditto (2 SPDT in each) : F4
(BIL25kV) (BIL35kV) (BIL55kV) (BIL95kV) When using a C-R suppressor, it may be necessary to use a
Voltage AC [V] 100 110 200 220 Special
Notes:
: Protection device is required. directional relay as a ground fault protection relay. Note that the
Symbol 5 6 7 8 9 : Protection device is not required. C-R suppressor may be damaged due to higher harmonics.
[kV] 3.6/7.2 12 24 36 *1 W
hen apply the gapless arrestor, the withstand voltages (impulse) of
Symbol 06 10 20 30 transformer must exceed the values listed above.
L
imit switch for closing spring *2 W
hen interrupting a magnetizing inrush current, it is recommended
No. of aux. contacts charged indication that a protection device be used.
A standard lightning arrester is sufficient.
4NO, 4NC :1 *3 S
emiconductor device must be provided with suitable protection
Without provision : G01 devices when a semiconductor is installed on the load side of
Installation Special (6NO, 6NC) :2 Special (with) : G15 transformer, since a surge on the low voltage side will also cause a
Ditto (9NO, 9NC) :3 voltage appear on the load side, depending on the turns ratio.
*4 C
ontact Fuji for further information.
Fixed type :P
Draw-out type for HS2530 :M
Draw-out unit type for class CW : X, U Aux. plug-in interlcok
Draw-out unit type :Y
for class MW or PW Without : A1
Special (with) : A2
17 18