Product Checks
Visual Inspection
Rating information correct for installation?
Case earth installed?
External wiring checked against diagram?
Test block connections checked?
4.Watchdog Contact:-
6. Setting checks:-
10.Non Directional Definite Time Earth Fault over current Protection (50N):-
Delay type: DMT
IN>
Setting 10*Is
TMS
(Is) 2*Is 5*Is
(Amps)
Calculated Measured Calculated Measured Calculated Measured
N 0.200 1.0 10.029 10.15 4.279 4.318 2.97 3.010
Pickup current tolerance: 1.05*Is 5% Operating time tolerance: 5% or 40ms which ever is greater
Functionality Check
Item Description Result
1
Relay contact Output checks
2
Relay Digital Input Checks
3
Relay LED Checks
6
Master Trip Relay Checks
Remarks:-