You are on page 1of 3

REV. NO.

:
SHEET :
DATA SHEET DATE :
WATER CHILLER DOC. NO. :
BY :

Service : Air Conditioning System Tag. No. :


OPERATION CONDITIONS
Item Designation Required Proposed Item Designation Required Proposed
1 Cooling Capacity (kw) 615 4 Outside Air Temperature (Cdb/Cwb) 35/29
kW/ton at 100 % capacity <0.79 5 Cooling Condenser Water :
2 Chilled Water - Operating tem 37.5/32
- Operating Temperature in/out (C) 12.7/7.2 - Flow rate (m/h) 125.0
- Flow Rate (m/h) 96.0 6 Location indoor/outdoor indoor
3 Type of Control and Part load 7 Position of control sensor
- Micro Computer Control Center Yes on chilled water :
- Part load >30 % - Chilled water outlet Yes
(Operate more than 10 hrs/day) - Chilled water inlet Yes
GENERAL DATA FOR EVAPORATOR
8 Manufacturer 15 Head Loss of Water circuit (m WG) <7.5
9 Country of Origin 16 Exchange Area (m)
10 Type 17 Fouling Factor (mC/kW) 0.01761
11 No of Pass 2 18 Test Pressure (bar)
12 Model 19 Insulation Type Close Cell Foam UL apporved 2 " thick
13 Evaporation Temperature (C)
14 Maximum Operation Pressure (bar) 10 20 Marine Water Box none
GENERAL DATA FOR CONDENSER
21 Manufacturer 28 Head Loss of Water Circuit (m WG) <7.5
22 Country of Origin 29 Exchange Area (m)
23 Type 30 Fouling Factor (m C/ kW) 0.04403
24 Number of Pass 2 31 Test Pressure (bar)
25 Model 32 Marine Water Box none
26 Condensation Temperature (C) 33 Water Condenser Pipe
27 Maximum Operation Pressure (bar) 10 34 Finned Tubes Air Condenser
GENERAL DATA FOR COMPRESSOR
35 Country of Origin import model 42 Number of Compressors
36 Model 43 Number of stages
37 Type Screw 44 Casing Heating Resistance (W)
38 Rotation Speed (rpm) 45 Refrigerant Type 134 a
39 Drive Ratio 46 Antivibration Mounting
40 Number of Refrigerant Circuits 47 Anti Short Cycle Safety
41 Power Supply - Duration (mn)
- Full load amp - Initialization of the Anti-short
- Locked rotor amp 48 Sound encloser for absorb compressor sound Required
GENERAL DATA FOR REFRIGERANT CIRCUIT
48 Liquid Reserve (L) 56 Low Pressure Controlled and
49 Test Pressure (bar) Manometers
50 Safety Valve 57 High Pressure Controlled and
51 Liquid Pressure Indicator Manometers
52 Humidity Indicator 58 Oil Pressurestats and Manometers
53 Oil Indicator 59 Antifreeze Thermostat
54 Dehydrator Filter 60 Valve Soleniod
55 Pressure Reducing Valve :
- Manufacturer
- Type
- Model

(Doc.NO. : 363385855.xls)
REV. NO. :
SHEET :
DATA SHEET DATE :
WATER CHILLER DOC. NO. :
BY :

GENERAL DATA FOR STRUCTURE


Item Designation Required Proposed Item Designation Required Proposed
61 Hydraulic Connections 65 Operating Weight
- Chilled Water Port - Total Weight of Group (kg.)
- Refrigerated Port - Compressor + Evaporator
- Flanges or Gas Type Thread 66 Chilled Water Flow Rate Control
62 Refrigerated Flow Rate 67 Weight of Air Condenser (kg.)
Control
63 Frame on Antishook Plots
GENERAL DATA FOR ELECTRICAL MOTOR
Item Description Compressor Ventilation Ventilation
Required Proposed Required Proposed Required Proposed
68 Number
69 Manufacturer
70 Supply Voltage (V) 380
71 Phase/Frequency (Ph/Hz) 3/50
72 Rotation Speed (rpm)
73 Rated Power (kw) 113.75
74 Rated Current (Amp)
75 Power Factor (Cos j)
76 Thermal Protection
- Ipsotherme
- Thermal Relay
- Other
77 Reference
Item Description Compressor Ventilation Ventilation
Required Proposed Required Proposed Required Proposed
78 Protection Index :
- Enclosed
- Other
79 Isolating Class
80 Cooling Mode
81 Start-up Type
82 Authorized Number of Start-up Per Hour
83 Weight of Motor (kg.)

ACOUSTICAL POWER (according to std NF S 31 025)


Hz 63 125 250 500 1000 2000 4000 8000
Compressors (dB)
Ventilators (dB)
Chilled water protection unit (dB)
References of annexed vendors documents :
Remark :Required sound encloser or silencer jecket for absorb compressor sound
Rev. Description By Check Date Approved Date
5
4
3
2
1
0 Issued for bidding

(Doc.NO. : 363385855.xls)
(Doc.NO. : 363385855.xls)