You are on page 1of 2

Jupiter

Close control unit

Customer benefits Options


Compact design: space savings in plant rooms Electric reheat/hot water reheat
Accuracy: accurate temperature and humidity control for High pressure centrifugal fans
any size of application Electrode boiler humidifier
High performance: lowest energy consumption. EC fan High efficiency filters
motor (option) Fresh air module with filter
Air suction from the front, rear or base (upflow
Range description configuration only)
Unit with AC motor and forward curved fan
Accessories
JDCC: Chilled water downflow
Dirty filter alarm (differential pressure switch)
JUCC: Chilled water upflow
Temperature and humidity sensor
JDAC: Air-cooled direct expansion downflow
Base frames and plenums (intake or discharge) for easier
JUAC: Air-cooled direct expansion upflow
integration
JDWC: Water-cooled direct expansion downflow External sensors for high ambient temperature and
JUWC: Water-cooled direct expansion upflow humidity alarm signals
Unit with EC motor and backward curved fan Fire and/or smoke detector
JDCV: Chilled water downflow Water leak detector with one sensor
DX Unitary
Systems

JUCV: Chilled water upflow Excess pressure damper


JDAV: Air-cooled direct expansion downflow
JUAV: Air-cooled direct expansion upflow Control
JDWV: Water-cooled direct expansion downflow mP40 microprocessor control module with easy-to-use LCD
JUWV: Water-cooled direct expansion upflow graphic display
Temperature and humidity control and recording system
Main features Complete alarm signaling and recording system
Designed for environments in which high-tech equipment Automatic restart
is the predominant heat source and comfort applications Remote auto off function
(offices) On-site language selection
Front access for total unit maintenance Connectivity with the most common communication
Double inlet galvanized steel centrifugal fans with forward protocols (BACnet/LonTalk/Modbus/...) or local
curved blades RS485 network

This description may not include all options and accessories available. For full technical information, visit www.trane.com/litweb or contact your local sales office.
Chilled water units

JDCC / JDCV / JUCC / JUCV 0020 0025 0030 0040 0060


Net cooling capacity (total/sensible) (1) (kW) 7.2 / 6.6 9.9 / 8.9 10.9 / 10.0 13.7 / 13.0 22.3 / 20.5
Supply airflow (m3/h) 1610 2280 2305 3265 5035
Maximum external static pressure (Pa) 191 59 37 144 82
Sound pressure level at 2m (downflow version) (dB(A)) 49 50 50
Weights and dimensions (Operating)
Length (mm) 550 850 850 850 1200
Width (mm) 450 450 450 450 450
Height (mm) 1740 1740 1740 1740 1740
Weight (kg) 105 135 135 145 220
Electrical data
Power supply (V/Ph/Hz) 200/1/50 - 400/3/50

Direct expansion air-cooled units

JDAC / JDAV / JUAC / JUAV 0115 0125 0133 0135 0150 0160
Net cooling capacity (total/sensible) (2) (kW) 6.2 / 5.8 7.6 / 6.3 10.1 / 10.1 12.7 / 11.4 16.8 / 15.5 18.1 / 16.1
Total power input (indoor+outdoor unit) (kW) 2.4 3.0 3.7 4.7 5.7 6.3

Direct expansion water-cooled units

JDWC / JDWV / JUWC / JUWV 0115 0125 0133 0135 0150 0160
Net cooling capacity (total/sensible) (3) (kW) 6.4 / 5.8 8.2 / 6.5 10.4 / 10.4 13 / 11.5 17.4 / 15.6 18.4 / 16.1
Total power input (kW) 2.4 3.0 3.7 4.7 5.7 6.3

General data - Direct expansion units


Number of refrigerant circuits 1 1 1 1 1 1
Number of compressors / capacity steps 1 1 1 1 1 1
3
Supply airflow (m /h) 1645 1731 3205 3440 4500 5202
Maximum external static pressure (Pa) 193 155 178 123 153 40
Weights and dimensions - Direct expansion units
Length (mm) 550 850 850 850 1200 1200
Width (mm) 450 450 450 450 450 450
Height (mm) 1740 1740 1740 1740 1740 1740
Weight (kg) 105 135 135 145 220 220
Electrical data - Direct expansion units
Power supply (V/Ph/Hz) 200/1/50 - - - -
Power supply (V/Ph/Hz) 400/3/50

(1) Based on 24C/50% relative humidity (return air), intake water temperature: 7C, outlet water temperature: 12C, glycol: 0%
(2) Based on 24C/50% relative humidity (return air), outdoor air temperature: 35C
(3) Based on 24C/50% relative humidity (return air), intake water temperature: 30C, leaving water temperature 35C, glycol: 30%

DX Unitary
Systems