TABLE OF CONTENT

Page
1-DESIGN FEATURES------------------------------------------------------- 1-1

2-Model number nomenclature:-


A. Indoor unit------------------------------------------------------------------- 2-1
B. Out door unit -------------------------------------------------------------- 2-2
3-Indoor unit:-
A. Specifications
i. High wall type (CLASSIC) series---------------------------------- 3-1
ii. High wall type (G+) series------------------------------------------ 3-2
iii. Ceiling floor type -------------------------------------------------- 3-3
iv. Ducted type---------------------------------------------------------- 3-4
v. Cassette type--------------------------------------------------------- 3-5
vi. Free stand type------------------------------------------------------ 3-6
B. Dimensions:-
i. High wall type (A) series------------------------------------------ 3-7
ii. High wall type (B) series------------------------------------------ 3-8
iii. Ceiling floor type -------------------------------------------------- 3-9: 3-12
iv. Ducted type---------------------------------------------------------- 3-13: 3-17
v. Cassette type--------------------------------------------------------- 3-18
vi. Free stand type------------------------------------------------------ 3-19
4-Outdoor units:-
A. Specifications---------------------------------------------------------------- 4-1: 4-4
B. Dimensions------------------------------------------------------------------- 4-5: 4-9
5-System specifications:-
A. High wall type (A) series--------------------------------------------------- 5-1
B. High wall type (B) series--------------------------------------------------- 5-2
C. Ceiling floor type------------------------------------------------------------ 5-3
D. Ducted type------------------------------------------------------------------- 5-4
E. Cassette type------------------------------------------------------------------ 5-5
F. Free stand type--------------------------------------------------------------- 5-6
6-Performance:-
A. Cooling performance: -
i. Imperial units: -
a. High wall type (CLASSIC) series------------------------- 6-1: 6-3
b. High wall type (G+) series--------------------------------- 6-4: 6-5
c. Ceiling floor Type------------------------------------------- 6-6: 6-7
d. Ducted type--------------------------------------------------- 6-8: 6-9
e. Cassette Type------------------------------------------------- 6-10
f. Free Stand----------------------------------------------------- 6-11
ii. SI units:-
a. High wall type (CLASSIC) series------------------------- 6-12: 6-14
b. High wall type (G+) series--------------------------------- 6-15: 6-16
c. Ceiling floor Type------------------------------------------- 6-17: 6-18
d. Ducted type--------------------------------------------------- 6-19: 6-20
e. Cassette Type------------------------------------------------- 6-21
f. Free Stand----------------------------------------------------- 6-22
B. Heating capacity:-
i. Imperial units:
a. High wall type (CLASSIC) series------------------------- 6-23
b. High wall type (G+) series--------------------------------- 6-24
c. Ceiling floor type-------------------------------------------- 6-24
d. Ducted--------------------------------------------------------- 6-25
e. Cassette-------------------------------------------------------- 6-26
f. Free stand----------------------------------------------------- 6-26
ii. SI units:
a. High wall type (CLASSIC) series------------------------- 6-27
b. High wall type (G+) series--------------------------------- 6-28
c. Ceiling floor type-------------------------------------------- 6-28
d. Ducted--------------------------------------------------------- 6-29
e. Cassette-------------------------------------------------------- 6-30
f. Free stand----------------------------------------------------- 6-30
7-Fan performance ( Ducted type)---------------------------------------- 7-1: 7-5

8-Unit operation:-
A. Remote Control:-
i. HWC,CFU type---------------------------------------------- 8-1: 8-5
ii. DBC – TFD Type--------------------------------------------- 8-6: 8-8
iii. CAS –Type--------------------------------------------------- 8-9: 8-12
iv. TDF –Type---------------------------------------------------- 8-13: 8-15
B. Touch Pad: - 8-16
i. DBC type------------------------------------------------------ 8-17: 8-20
ii. TFD Type-----------------------------------------------------
C. Mechanical thermostats:-
i. DBC type------------------------------------------------------ 8-21
9-P.C.B advanced functions:-
A. HWC, CUF, DBC, Type-------------------------------------------------- 9-1: 9-4
B. CAS Type-------------------------------------------------------------------- 9-5: 9-8
C. TFD Type-------------------------------------------------------------------- 9-9: 9-11
10-Wiring diagram:-
A. Cool only models:-
i. HWC Plug in type ( HWC009-24) --------------------------------- 10-1: 10-8
ii. HWC wiring connection type ( HWC018-24) -------------------- 10-9: 10-10
iii. HWC wiring connection type ( HWC30-36) --------------------- 10-11: 10-12
iv. CFU plug in type (CFU12-25) -------------------------------------- 10-13: 10-14
v. CFU wiring connection type ( CFU 20-36) ----------------------- 10-15
vi. DBC wiring connection type ( DBC 20-60) ---------------------- 10-16: 10-19
vii. CAS wiring connection type ( CAS20-48) ----------------------- 10-20: 10-22
viii. TDF wiring connection type ( TDF025-048) --------------------- 10-23: 10-26
B.-Heat pump model:-
i. HWC Plug in TYPE ( HWC 009-24) ------------------------------ 10-27: 10-34
ii. HWC wire connection type ( 18-24) ------------------------------- 10-35: 10-36
iii. HWC wire connection type (HWC 030—36) -------------------- 10-37: 10-38
iv. CFU Plug in type ( CFU 012-25) ---------------------------------- 10-39: 10-40
v. CFU wire connection type ( CFU 020-36) ------------------------ 10-41
vi. DBC wire connection type ( DBC 020-60) ----------------------- 10-42: 10-45
vii. CAS wire connection type ( CAS 20-48) ------------------------- 10-46: 10-48
viii. TDF wire connection type ( TDF 025-048)----------------------- 10-49: 10-52
11-Piping:-
A. Capacity correction factor due to piping length --------------------- 11-1
B. Refrigerate additional charge US piping length --------------------- 11-2
C. Max piping length and level difference-------------------------------- 11-3: 11-5
12-Refrigerant piping diagram-------------------------------------------- 12-1: 12-3

13-Outdoor unit service area----------------------------------------------- 13-1


1- Design Features

UNIONAIRE MODELS is designed to provide high quality, economical and reliable cooling or
heating for small and medium size shops, restaurants, offices, showrooms, and residential places.

Indoor Unit Features:


Very elegant design to suit any decoration.
Energy saving with low power consumption.
Ultra quiet operation.
Attractive LCD wireless remote controll with high transmission ability ( HWC,CFU, CAS, TFD).
Advanced-technology PC-board for full control.
“DRY” mode reduces water vapor by computerized dehumidification.
“SLEEP” mode provides suitable sleeping environment with energy saving.
24 hours programmable timer controls the unit operation.
Automatic & manual selection of outlet air direction ( HWC,CFU, CAS, TFD)..
Automatic & manual selection of 3-stage fan speed.
Electronic system provides 3 minutes anti short cycle protection for compressor, which
guaranties total system integrity.
“Hydrophilic” fins in the evaporator.
Self-diagnosis function.
Efficient, easy removable and cleanable air filters.
Optional accessories available upon request::
1. Golden Plasma Air Purifying System “Ionized Filter”.
2. Anti Bacteria filter.
3. Carbon filter.

Outdoor Unit Features:


Fast installation and easy maintenance.
Modern cabinet design to suit the building decorations.
Low noise, high efficiency compressor.
Advanced design allows the use of either “Quick Coupling” or” Flare” connection systems, for
more flexibility in installation.
Heavy gauge galvanized steel with weather resistance electrostatic powder paint.
“Inner-grooved” pipes and “Slit” fins increase the heat exchange rate and decrease Power
consumption.
Available as “Cooling Only” & “Heat Pump” systems.
Operates in high outdoor temperatures, and in low outdoor temperatures in (heat pump only).
Optional accessories available upon request:
1. Low-Ambient control kit.
2. Low-Pressure protection switch.
3. High-Pressure protection switch.
4. Crankcase heater.

1-1
B- OUTDOOR UNIT

Matched Indoor: Power supply:


W: Wall-Mounted. 5: 220 - 240 / 1 / 50
F: Ceiling / Floor unit. 7: 380 - 420 / 3 / 50
D: Ducted unit.
C: Cassette unit. 4: 110 - 115 / 1 / 60
T: Free Stand unit. 6: 208 - 230 / 1 / 60
G: General unit. 8: 380 - 460 / 3 / 60
9: 208 - 230 / 3 / 60

R: High EER.
Unit Size (In 1000 BTU/hr). L: Conventional.

(1)

OR*C XXX XX XXX


Refrigerant Type: Optional List.
R: R22.
Outdoor Unit Name: (2)
ORTC: Cooling Only. Design Generations:
ORHC: Heat Pump. Factory assigned Letter.

(1) * Means cooling only or heat pump.


(2) In this cataloge, series "B" means new generation of the outdoor units. 2-2
3- Indoor Units
A- Specifications
i-High wall type (classic) series

Indoor Unit HWC009*4(6) HWC012*4(6) HWC020*6 HWC024*6 HWC030B6 HWC036B6

Front Panel Color Ivory - White


110-115/1/60
Power Supply 208 - 230 / 1 / 60
(208-230/1/60)
Air Direction Control Manual Vertical (Right, Left) & Automatic horizontal (Upwards and Downwards)
Air Filter One touch and washable
Temperature Control Computerized Control
Hi m3/hr (CFM) 615(360) 1019(600) 1367.5(800)
Air Flow Rate* Med m3/hr (CFM) 523(306) 856(504) 1162 (680)
Low m3/hr (CFM) 444(260) 736(434) 987 (577)
Type Cross Flow
No Used 1
Fan Diameter mm (inch) 97 (3.82) 100(4) 107(4.2)
Length mm (inch) 704 (27.72) 859(33.82) 955(37.6)
Drive Type Direct
Type Hydrophilic Coated aluminum slit fin + Inner grooved copper tube
No of Rows 1 2 3
Coil Fin / Inch 18 16
Face Area m2 (ft2) 0.177 (1.9) 0.223 (2.4) 0.273 (2.926)
Tube Size mm 7 9.5 7
No Used 1
Power Output Watt 12 20 47
Fan Motor
Safety Devices Thermally Protected
Step Control 3

Safety Devices P.C.B Gas leakage / Overheating function to substitute high & low pressure switches

W mm (in) 889 (35) 1100 (43.3) 1200(47.24)


Uncrated Dimensions H mm (in) 295 (11.6) 355 (14) 357(14.1)
D mm (in) 170 (6.7) 223 (8.8) 215(8.5)

W mm (in) 970 (38.2) 1200 (47.25) 1290(50.8)

Crated Dimensions H mm (in) 386 (15.2) 430 (16.96) 430(16.92)

D mm (in) 257 (10.1) 330 (13.0) 285(11.22)

Kg 11.2 16 20
Net Weight
LBS 24.71 35.3 44.1
Noise Level dBA 33 36 39 42
* Air flow rate based on dry coil
Specifications could be changed at any time without prior notice
3-1
ii- High wall type (G+) seriess

Indoor Unit HWC009N4(6) HWC012N4(6) HWC020N6 HWC024N6

Front Panel Color Ivory - White


110-115/1/60
Power Supply 208-230/1/60
(208-230/1/60)
Automatic Vertical (Right, Left) & Automatic horizontal (Upwards and
Air Direction Control
Downwards) ( 2 Swing )

Golden Plasma filter(Ionized filter+Catbon filter+One touch and washable filter) (


Air Filter
Option ) or One touch and washable filter
Temperature Control Computerized Control
Hi m3/hr (CFM) 594 (350) 968 (570)
*
Air Flow Rate Med m3/hr (CFM) 505 (297) 823 (485)
Low m3/hr (CFM) 429 (253) 699 (412)
No. Used 1
Power Output Watt 10 12 20
Fan Motor
Safety Devices Thermally Protected
Step Control 3
No. Used 1
Type Cross Flow
Fan Diameter mm (inch) 94.7(3.73) 100.2(3.94)
Length mm (inch) 622(24.48) 853(33.58)
Drive Type Direct
Type Hydrophilic Coated aluminum slit fin + Inner grooved copper tube
No. of Rows 1 2 2
Coil Fin / Inch FPI 22 14 16
Face Area m2 (ft2) 0.158(1.69) 0.233(2.50)
Tube Size mm 7
P.C.B Gas leakage / Overheating function to substitute high & low pressure
Safety Devices
switches / Thermally motor protected
W mm (in) 824(32.4) 1090(42.9)
Uncrated
H mm (in) 292(11.5) 314(12.4)
Dimensions
D mm (in) 180(7.1) 180(7.1)
W mm (in) 894(35.2) 1160(45.7)
Crated Dimensions H mm (in) 342(13.5) 376(14.8)
D mm (in) 272(10.7) 272(10.7)
Kg 8.9 12.5
Net Weight
LBS 19.6 27.6
Noise Level db 33 36 39
* Air flow rate based on dry coil
Specifications could be changed at any time without prior notice
3-2
iii- Ceiling Floor Type

Indoor Unit CFU012 CFU020 CFU025 CFU030 CFU036

Casing Gray White


Power Supply 208-230 / 1 / 60
Air Filter One touch and washable
Air Direction Control Automatic swings (Right & left), Automatic louver (Upwards & Downwards)
Temperature Control Computerized Control
Hi m3/hr (CFM) 577 (340) 985(581) 1019(600) 1700 (1000) 1780 (1050)
Air Flow
Med m3/hr (CFM) 490 (289) 837(493) 866(510) 1445 (851) 1512 (890)
Rate*
Low m3/hr (CFM) 417 (246) 712(419) 736(434) 1228 (723) 1274 (750)
Type Aluminum fins + Inner grooved copper tube
No. of Rows 2 3 2 3
Coil Fin / Inch FPI 16 14 14 10
Face Area m2 (ft2) 0.134 (1.44) 0.186 (2.00) 0.245 (2.64) 0.285 (3.07) 0.323 (3.48)
Tube Size mm 9.5 (3/8)
Type Centrifugal
No Used 2 3
Fan Diameter mm (inch) 116 (4.56) 143 (5.63)
Width mm (inch) 178 (7.00) 229 (9.02)
Drive Type Direct
No Used 1 2
Power
Watt 30 37 62
Fan Motor Output
Step Control 3
Safety Devices Thermally Protected
W mm (in) 1008 (39.7) 1308 (51.5) 1608 (63.3)
Uncrated Dimensions H mm (in) 608 (24)
D mm (in) 202 (8.1) 235 (9.3)
W mm (in) 1060 (41.7) 1660 (65.4)
Crated Dimensions H mm (in) 665 (26.2)
D mm (in) 260 (10.2)
Kg 33 43 46 52 54
Net Weight
LBS 73 95 101 115 119
Noise Level dBA 43 45 46 48

Electrical Heater Capacity (1) kW 2 3 4.25

* Air flow rate based on dry coil


Specifications could be changed at any time without prior notice 3-3
iv- Ducted Type

Indoor Unit DBC 018 DBC 020 DBC024 DBC 024* DBC 030 DBC 036 DBC 048 DBC 060

Casing Galvanized Steel


Power Supply 208-230/1/60
Air Filter Cleanable High Effiency Filter
Temperature Control Computerized or Mechanical Control
Hi m3/hr (CFM) 993 (585) 951 (560) 1358 (800) 1868 (1100) 2505 (1475) 2717 (1600) 3056 (1800)
Air Flow
Med m3/hr (CFM) 844(497) 809 (477) 1154 (680) 1588 (935) 2130 (1254) 2309 (1360) 2598 (1530)
Rate*
Low m3/hr (CFM) 717 (423) 687 (405) 981 (578) 1350 (795) 1810 (1066) 1963 (1156) 2208 (1300)
Type Aluminum fins + Inner grooved copper tube
No of Rows 3 4
Indoor Coil No of Fins/Inch 12 14 18
Face Area m2 (ft2) 0.138(1.484) 0.155 (1.667) 0.138(1.484) 0.155 (1.667) 0.191 (2.055) 0.217(2.335) 0.367(3.949) 0.455 (4.896)
Tube Size mm (inch) 9.5 (3/8)
Type Centrifugal
No Used 2
Indoor Fan Diameter mm (inch) 143(5.63) 146 (5.75) 143 (5.63) 159 (6.25) 172 (6.75) 229 (9.00)
Width mm (inch) 229(9.02) 178 (7.00) 229 (9.02) 213 (8.38) 156 (6.125) 207 (8.125)
Drive Type Direct
No Used 1 2
Indoor Fan Power Output Watt 65 186 248 373
Motor Safety Devices Thermally Protected
Step Control 3
Electrical Heater Capacity
(Optional) No. x kW - 2 x 1.5 - 2 x 1.5 2 x 2.125 2 x 3.0

W mm (in) 948 (37.3) 1009 (39.7) 1169 (46) 1314 (51.7) 1351.5 (53.2) 1456.5 (57.3)
Uncrated Dimensions H mm (in) 230 (9.06) 280 (11) 350 (13.76) 380 (15)
D mm (in) 316 (12.4) 527 (20.7) 574 (22.56) 574 (22.6)
W mm (in) 1080 (42.5) 1060 (41.7) 1220 (48) 1440 (56.7) 1361.5 (53.51)
Crated Dimensions H mm (in) 470 (18.5) 330 (13) 370(14.54)
D mm (in) 255 (10.03) 703 (27.7) 584 (21.54)
Kg 23.5 26.5 25 30 36 41.5 53
Net Weight
LBS 51.8 58.4 55.1 66.1 79.3 91.5 116.8
Noise Level dBA 42 45 42 45 48 50
* Air flow rate based on dry coil
Specifications could be changed at any time without prior notice
Models DBC015-DBC018-DBC024 for low static pressure applications
* This model for high static pressure applications.
3-4
v- Cassette Type

Indoor Unit CAS024 CAS048

Front Panel Color Gray White


Power Supply 208-230/1/60
Air Direction Control Automatic Swing
Air Filter Cleanable high velocity Filter
Temperature Control Computerized Control
Hi m3/hr (CFM) 1189 (700) 1460 (860)
*
Air Flow Rate Med m3/hr (CFM) 1011 (595) 1241 (731)
Low m3/hr (CFM) 859 (505) 1055 (621)
No. Used 1
Power Output Watt 40 75
Fan Motor
Step Control 3
Safety Devices Thermally Protected
No. Used 1
Type Turbo
Fan Diameter mm (inch) 445(17.52)
Width mm (inch) 167(6.60)
Drive Type Direct

Type Aluminum slit fins + Copper inner-grooved tubes

No. of Rows 2 3
Coil
Fin / Inch FPI 16 14
Face Area m2 (ft2) 0.37
Tube Size mm(inch) 9.5 (3/8)
W mm (in) 950 (37.4)
Front Panel
H mm (in) 950 (37.4)
Dimensions
D mm (in) 80 (3.15)
W mm (in) 830 (32.7)
Uncrated
H mm (in) 830 (32.7)
Dimensions
D mm (in) 290 (11.42)
W mm (in) 1050 (41.34)
Crated
H mm (in) 1050 (41.34)
Dimensions
D mm (in) 340 (13.40)
Kg 25 30
Net Weight
LBS 55.10 66.12
Noise Level db 37 39

* Air flow rate based on dry coil


Specifications could be changed at any time without prior notice
3-5
vi-Free Stand Type

Indoor Unit TFD025 TFD048

Front Panel Color Gray


Power Supply 208-230/1/60
Automatic swings (Right & left), Manual louver (Upwards &
Air Direction Control
Downwards)
Air Filter washable filter
Temperature Control Computerized Control
Hi m3/hr (CFM) 1189(700) 1698(1000)
*
Air Flow Rate Med m3/hr (CFM) 1011(595) 1443(850)
Low m3/hr (CFM) 859(506) 1227(723)
No. Used 1
Power Output Watt 40 90
Fan Motor
No OF Speed 3
Safety Devices Thermally Protected
No. Used 1
Type Centrifugal
Fan Diameter mm (inch) 380(14.96) 298(11.73)
Width mm (inch) 180(7.08) 130(5.11)
Drive Type Direct
Type Aluminum slit fins + Copper inner-grooved pips
No. of Rows 2
Coil Fin / Inch FPI 16 14
Face Area m2 (ft2) 0.24(2.583) 0.436(4.736)
Tube Size mm 9.5 (3/8)
W mm (in) 480(18.89) 600(23.62)
Uncrated
H mm (in) 1680(66.14) 1890(74.41)
Dimensions
D mm (in) 292(11.5) 374(14.72)
W mm (in) 564(22.2) 748(29.4)
Crated
H mm (in) 1852(72.9) 2078(81.7)
Dimensions
D mm (in) 378(14.88) 460(18.11)
Kg 39 53
Net Weight
LBS 85.96 116.81
Noise Level db 35 37

* Air flow rate based on dry coil


Specifications could be changed at any time without pr
3-6
iii - CFU MODELS
CFU 012

Louver Motor Air Outlet

Union aire Air Filter


Swing Motor Air Intake

608 [23,9]
suspension bolt outside mounting

608 [23,9]
527 [20,7]

527 [20,7]
961 [37,8]

30m.m.[1.2 inch] max


202 [8,0]
Intake grill 1008 [39,7]
202 [8,0]

Electrical box

Side View Front View Side View

Hole for refrigerant-piping


suspension bolt inside mounting
850 [33,4]
80 mm[3.14inch] diameter
849 [33,4]

Back air Filtter


608 [23,9]

30m.m.[1.2 inch] max


344 [13,5]

903 [35,6]
1008 [39,7]

903 [35,6]

Rear View Bottom View

3-9
AL Dim. in mm.[inch]
CFU : 020:025

Louver Motor Air Outlet


Swing Motor

Union aire Air Filter


Swing Motor

608 [23,9]
Air Intake
suspension bolt outside mounting
507 [19,9] 1261 [49,6]

1203 [47,4]
Intake grill

30m.m.[1.2 inch] max


235 [9,2]
1308 [51,5]
Electrical box

Side View Front View Side View

Hole for refrigerant-piping


100 m.m.[3.94inch] diameter

1150 [45,3]
Back air Filtter suspension bolt inside mounting
1149.0
608 [23,9]
344 [13,5]

30m.m.[1.2inch] max
1203 [47,4]
1308 [51,5]

1308 [51,5]

Rear View Bottom View

3-10
AL Dim. in mm.[inch]
CFU : 030 - 036

Louver Motor Air Outlet


Swing Motor

Union aire Air Filter


Swing Motor Air Intake
608 [23,9]
507 [19,9]

suspension bolt inside mounting


1449 [57,0]

Intake grill 235 [9,2] 1503 [59,2]

1608 [63,3] Electrical box

30m.m.[1.2inch] max
Side View Front View Side View

Hole for refrigerant-piping


100 m.m.[3.94inch] diameter
1149

suspension bolt outside mounting


Back air Filtter
1561 [61,5]
608

344

30m.m.[1.2inch] max
1503 [59,2]

92.0

1503

1608

Rear View Bottom View

3-11
AL Dim. in mm.[inch]
Fresh air connections

fresh air

Plenuim box

Dim.100[3.94]
(not supplied) Damper

H 200[7.9]

Side View
L

H
Union aire
fresh air

200[7.9]
H

Plenuim box
(not supplied) Damper

Dim.100[3.94]
W

Front View
Side View

3-12
(L*W*H) The Dim.m.m.[inch] of indoor unit
445 [17,5]
1026 [40,4]

49 [1,9]
371 [14,6]
864 [34,0]

191 [7,5]
230 [9,1]

161 [6,3]

230 [9,1]
948 [37,3]
24 [,9] 844 [33,2]

316 [12,4]

316 [12,4]
734 [28,9] 83 [3,3]
900 [35,4]

1026 [40,4]
900 [35,4]
44 [1,7]
734 [28,9] 82 [3,2]
113 [4,4]
230 [9,1]

167 [6,6]
49 [1,9]

266 [10,5] 266 [10,5]


164 [6,5]
527 [20,7]

210 [8,3]
280 [11,0]

205 [8,1]
230 [9,1]
35 [1,4]
450 [17,7] 22 [,9]

1135 [44,7]
425 [16,7] 835 [32,9]

450 [17,7]
996 [39,2]

1171 [46,1]
835 [32,9]
210 [8,3]
280 [11,0]

242 [9,5]
82 [3,2]

271 [10,7] 185 [7,3] 271 [10,7]


1080 [42,5]
210 [8,3]

205 [8,1]
280 [11,0]

230
22 [,9] 35 [1,4]
450 [17,7]
527 [20,7]
1334 [52,5]
1275 [50,2]
975 [38,4]
425 [16,7]

450 [17,7]
1140 [44,9]

1314 [51,7]
975 [38,4]
280 [11,0]
210 [8,3]

242 [9,5]

280 [11,0] 178 [7,0] 280 [11,0]


1225 [48,2]
574 [22,6]
523 [20,6]
1352 [53,2] 425 [16,7]

41 [1,6]
1200 [47,2] 53 [2,1] 363 [14,3]

250 [9,8]
292 [11,5]
350 [13,8]

350 [13,8]

350 [13,8]
50 [2,0]
399 [15,7]
21 [,8]

45 [1,8]

81 [3,2]

45 [1,8]
80 [3,1]
1200 [47,2] 500 [19,7]

1259 [49,6]
1199 [47,2]
1151 [45,3]
574 [22,6]
523 [20,6]
425 [16,7]

158 [6,2] 885 [34,8] 158 [6,2]


1200 [47,2] 99 [3,9]

1352 [53,2]
1200 [47,2] 99 [3,9]
53 [2,1] 158 [6,2] 885 [34,8] 158 [6,2]
187 [7,4]
250 [9,8]
350 [13,8]

80 [3,2] 272 [10,7] 272 [10,7] 81 [3,2]


81 [3,2]

180 [7,1]
574 [22,6]
523 [20,6]
1457 [57,3]

40 [1,6]

19 [,7]

13 [,5]
425 [16,7]
1305 [51,4] 53 [2,1]
363 [14,3] 50 [2,0]

41 [1,6]
250 [9,8]
317 [12,5]
380 [15,0]

380 [15,0]
50 [2,0]

50 [2,0]
21 [,8]
60 [2,4] 101 [4,0]

50 [2,0]

50 [2,0]
111 [4,4]

37 [1,5]
79 [3,1] 1305 [51,4] 399 [15,7]
500 [19,7]

1251 [49,3]
70 [2,8]

191 [7,5] 200 [7,9]

574 [22,6]
355 [14,0]
70 [2,8]

985 [38,8]

1411 [55,6]

1457 [57,3]
1303 [51,3]
272 [10,7] 180
272[7,1]
[10,7]

230 [9,1]
380 [15,0]

985 [38,8]
1305 [51,4]
v i - TFD MODELS
MODEL W H D

TFD 025 480[18.89] 1680[66.1] 29011.4]

TFD 048 600[23.6] 1890[74.4] 370[14.6]

Top View

hole for piping and hole for wiring connection


wiring connection hole for piping connection

Rear View Front View Side View


3 -19
A- Outdoor Unit Specifications:

Outdoor Unit OR*C009 OR*C012 OR*C009 OR*C012 OR*C018 OR*C020 OR*C020(2) OR*C025
(3)
OR*C030 OR*C036(4)

Casing Color White - Gray


Material Metal
Power Supply 110-115/1/60 208-230/1/60
Max Fuse Size A 16 20 10 16 20 25 32 40
Type Rotary Reciprocating
No Used 1
Compressor
Rated Load Amp A 9.00 11.80 4.50 5.30 8.30 12.10 13.50 17.00 18.50
Locked Rotor Amp A 55.00 51.00 28.80 30.00 45.00 62.80 70.5 83.00 100.00
Type Propeller
No Used 1
Fan
Diameter mm (inch) (317.5)12.5 457 (18)
Drive Type Direct
No Used 1
Power Output Watt 30 62 93.2
Fan Motor
Speed rpm 1000 830 900
Rated Load Amp A 0.8 0.5 0.41 0.9
Type Aluminum slit fins + Inner grooved copper tubes
No of Rows 1 2 1 2 1.5 2 1.75 2
Coil Fin / Inch 18 15 18 15 12 15 12 16
Tube Size mm (inch) 9.5(3/8)
2 2 0.244 (2.63) 0.52 (5.66) 0.69 (7.50)
Face Area m (ft )
3 minutes time delay for Compressor
Safety Devices
Internal or External Overload Internal overload - High/Low pressure switches (option)

W mm (in) 595 (23.4) 722 (28.43) 945 (37.2)


Uncrated Dimensions H mm (in) 495 (19.48) 586 (23.07) 649 (25.5) 845 (33.2)
D mm (in) 282 (13.1) 302 (11.89) 356 (14)
W mm (in) 700 (27.56) 840 (33.07) 1040 (41)
Crated Dimensions H mm (in) 560 (22.05) 660 (25.98) 680 (27) 880 (34.65)
D mm (in) 400 (15.75) 425(16.73) 430(16.93)
Kg 32 34 36 43 44 57.5 64 75 88 92
Aprox. Net Weight
LBS 70.53 74.94 79.34 94.77 96.98 126.73 141.06 165.30 193.95 202.77
Noise Level at 1.5 m dBA 46 48 50 53

(1) Same unit with different compressors. (2) Same unit with different motors.
(2) Compressor used in OR*C020 with wall mounted units has (RLA=10.1/LRA=54.0)
(3) Compressor used in OR*C025 with wall mounted units has (RLA=13.5/LRA=70.5)
(4) Compressor used in OR*C036 with wall mounted units has (RLA=24.6/LRA=132)
TEST VOLT : (110V) OR 220V at 60 HZ
Specifications could be changed at any time without prior notice 4-1
Outdoor Unit OR*C012B (NEW) OR*C012B

Casing Color White - Gray


Material Metal
Power Supply 110-115/1/60 208-230/1/60
Max Fuse Size A 20 16
Type Rotary
No Used 1
Compressor
Rated Load Amp A 11.80 5.30
Locked Rotor Amp A 51.00 30.00
Type Propeller
No Used 1
Fan
Diameter mm (inch) (381)15
Drive Type Direct
No Used 1
Power Output Watt 30
Fan Motor
Speed rpm 1000
Rated Load Amp A 0.8
Type Aluminum slit fins + Inner grooved copper tubes
No of Rows 1
Coil Fin / Inch 20
Tube Size mm (inch) 9.5(3/8)
2 2
Face Area m (ft ) 0.301(3.244)
3 minutes time delay for Compressor
Safety Devices
Internal Overload

W mm (in) 677(26.7)
Uncrated Dimensions H mm (in) 540(21.3)
D mm (in) 282(11.1)
W mm (in) 802(31.6)
Crated Dimensions H mm (in) 573(22.6)
D mm (in) 397(15.6)
Kg 32.2
Aprox. Net Weight
LBS 71.0
Noise Level at 1.5 m dBA 50
TEST VOLT : (110V) OR 220V at 60 HZ
Specifications could be changed at any time without prior notice
4-2
Outdoor Unit OR*C 050 OR*C 060

Casing Color White - Gray


Power Supply* 208-230/1/60
Max Fuse Size A 50 60
Type Reciprocating
No Used 1
Compressor
Rated Load Amp A 24.60 30.70
Locked Rotor Amp A 132.00 132.00
Type Aluminum slit fins + Copper inner-groved pipes
No of Rows 1.6 2
Coil No of Fins/Inch 12
Tube Size mm (inch) 9.5(3/8)
Face Area m2 (ft2) 1.07 (11.51)
Type Propeller
No Used 2
Fan
Diameter mm (inch) 457 (18)
Drive Type Direct
No Used 2
Power Output Watt 93.3
Fan Motor
Speed RPM 900
Current A 0.9
Compressor 3minutes time delay in PCB-Internal Overload
Safety Devices High& Low pressure switches (Option)

W mm (in) 945 (37.2)


Uncrated Dimensions H mm (in) 1251 (49.25)
D mm (in) 356 (14)
W mm (in) 1040 (41)
Crated Dimensions H mm (in) 1280 (50.4)
D mm (in) 430 (16.93)
Kg 123 125
Net Weight
LBS 271 276
Noise Level at 1.5 m dBA 56

TEST VOLT : OR 220V at 60 HZ


Specifications could be changed at any time without prior notice
4-3
Outdoor Unit OR*C 050 OR*C 060

Casing Color White - Gray


Power Supply* 380-460 / 3 / 60
Max Fuse Size A 25 32
Type Reciprocating Scroll
No Used 1
Compressor
Rated Load Amp A 10.40 10.00
Locked Rotor Amp A 53.00 74.00
Type Aluminum slit fins + Copper inner-groved pipes
No of Rows 1.6 2
Coil No of Fins/Inch 12 16
Tube Size mm (inch) 9.5(3/8)
2 2
Face Area m (ft ) 1.07 (11.51)
Type Propeller
No Used ]
Fan
Diameter mm (inch) 457 (18)
Drive Type Direct
No Used 2
Power Output Watt 93.3
Fan Motor
Speed RPM 900
Current A 0.9
Compressor 3minutes time delay in PCB-Internal Overload
Safety Devices High& Low pressure switches (Option)

W mm (in) 945 (37.2)


Uncrated Dimensions H mm (in) 1251 (49.25)
D mm (in) 356 (14)
W mm (in) 1040 (41)
Crated Dimensions H mm (in) 1280 (50.4)
D mm (in) 430 (16.93)
Kg 123 125
Net Weight
LBS 271 276
Noise Level at 1.5 m dBA 56

TEST VOLT : OR 220V at 60 HZ


Specifications could be changed at any time without prior notice 4-4
5-System Specifications

i- HWC Models series "classic"

OR*C012W40(3)

OR*C009W60(3)

OR*C012W60(3)

HWC030B6*O

HWC036B6*O
OR*C020W6O
OR*C009W4(3)

OR*C030W60

OR*C036W60
OR*C018W60

OR*C025W60
HWC020*6*0
HWC009*4*0

HWC012*4*0

HWC009*6*0

HWC012*6*0

HWC020*6*0

HWC024*6*0
Models

kW 2.64 3.52 2.78 3.52 5.28 5.72 6.74 8.79 10.26


Nominal Cooling Capacity(1) BTU/hr 9000 12000 9500 12000 18000 19500 23000 30000 35000
KCAL/hr 2268 3024 2394 3024 4536 4914 5796 7560 8821
kW 2.64 3.52 2.78 3.52 5.28 5.72 6.74 8.79 10.84
(1)
Nominal Heating Capacity BTU/hr 9000 12000 9500 12000 18000 19500 23000 30000 37000
KCAL/hr 2268 3024 2394 3024 4536 4914 5796 7560 9325

(1)
CO A 10.64 13.26 5.02 6.50 9.47 9.52 13.34 16.87 21.94
Running Current
HP A 9.67 12.31 4.78 5.57 8.06 8.57 11.86 13.59 19.09
Power Consumption CO W 1100 1400 1050 1330 1980 2000 2700 3600 4585
(1)
HP W 1000 1300 1000 1140 1685 1800 2400 2900 3989

(1)
CO W/W 2.40 2.51 2.65 2.64 2.66 2.86 2.50 2.44 2.24
COP
HP W/W 2.64 2.71 2.78 3.09 3.13 3.18 2.81 3.03 2.72
CO (BTU/hr)/W 8.18 8.57 9.05 9.02 9.09 9.75 8.52 8.33 7.63
EER (1)
HP (BTU/hr)/W 9.00 9.23 9.50 10.53 10.68 10.83 9.58 10.34 9.28
L/hr 1.38 1.84 1.45 1.84 2.75 3.00 3.52 4.60 5.51
Moisture Removal (1)
LBS/hr 3.04 4.06 3.20 4.06 6.06 6.61 7.76 10.14 12.15

Power Supply V/Ph/Hz 110-115/1/60 208-230/1/60


Max Fuse Size A 16 20 10 16 20 25 32 40
Cooling Only : 3 + Sensor Wire + Earth+(1
Cooling Only : 2 Wires + Earth
No of wiring Connections Between Indoor and cranck case heater "Option")
Outdoor Units Heat pump :5 + Sensor Wire + Earth+(1 cranck
Heat pump : 4 Wires + Sensor Wire + Earth
case heater "Option")
Liquid mm (in) 6.4 (1/4) 9.5 (3/8)
Piping Connection Gas mm (in) 9.5 (3/8) 12.7 (1/2) 15.875 (5/8) 19.0 (3/4)
Drain mm (in) 12.7 (1/2)
Type of Connection (2) Flare Connection
Type R22
Refrigerant Kg 0.55 0.90 0.75 0.95 1.20 1.175 1.250 1.50 2.4
LBS 1.21 1.98 1.65 2.09 2.64 2.59 2.76 3.31 5.29

(1) At "ASHRAE" Conditions:


(2) Quick Coupling will be available upon special request.
(3) Available with Plastic casing with the same performance.
- The * in the model name refers to C in Cooling Only models and H in Heat pump models
- Cooling capacity based on high indoor fan speed
5-1
ii- HWC Models series "G+"

OR*C0250W60
HWC009N4*0

HWC009N6*0

HWC012N6*0

HWC020N6*0

HWC020N6*0

HWC024N6*0
OR*C012W6B
OR*C010W60

OR*C018W60

OR*C020W60
OR*C009W4
MODELS

kW 2.64 2.78 3.52 5.28 5.72 6.74


Nominal Cooling Capacity BTU/hr 9000 9500 12000 18000 19500 23000
KCAL/hr 2268 2394 3024 4536 4914 5796
kW 2.64 2.78 3.52 5.28 5.72 6.74
(1)
Nominal Heating Capacity BTU/hr 9000 9500 12000 18000 19500 23000
KCAL/hr 2268 2394 3024 4536 4914 5796
Running Current CO A 10.64 5.02 6.30 9.47 9.52 13.34
(1)
HP A 9.67 4.78 5.38 8.06 8.57 11.86
Power CO W 1100 1050 1290 1980 2000 2700
(1)
Consumption HP W 1000 1000 1100 1685 1800 2400
CO W/W 2.40 2.65 2.73 2.66 2.86 2.50
COP (1)
HP W/W 2.64 2.78 3.20 3.13 3.18 2.81
CO (BTU/hr)/W 8.18 9.05 9.30 9.09 9.75 8.52
EER (1)
HP (BTU/hr)/W 9.00 9.50 10.91 10.68 10.83 9.58
L/hr 1.38 1.45 1.84 2.75 3.00 3.52
Moisture Removal (1)
LBS/hr 3.04 3.20 4.06 6.06 6.61 7.76

Power Supply V/Ph/Hz 110-1-60 220-240/1/60


Max Fuse Size A 10 16 25

CO 2 Wires + Earth 3 + Sensor Wire + Earth+(1 cranck case heater "Option")


No of wiring Connections Between
Indoor and Outdoor Units
HP 4 Wires + Sensor Wire + Earth 5 + Sensor Wire + Earth+(1 cranck case heater "Option")

Liquid mm (in) 6.4 (1/4) 9.5 (3/8)


Piping Connection Gas mm (in) 9.5 (3/8) 12.7 (1/2) 15.875 (5/8)
Drain mm (in) 12.7 (1/2)
Type of Connection (2) Flare Connection
Type R22
Refrigerant Kg 0.625 0.750 0.775 1.2 1.175 1.250
LBS 1.38 1.65 1.71 2.64 2.59 2.76

(1) At "ASHRAE" Conditions - Cooling capacity based on high indoor fan speed
(2) Quick Coupling will be available upon special request.
* Outdoor available with plastic body. 5-2
iii- CFU Models

CFU012/ CFU020/ CFU024/ CFU030/ CFU036/


MODELS
OR*C012 OR*C020 OR*C025 OR*C030 OR*C036

kW 3.52 5.72 6.74 8.79 10.26


Nominal Cooling Capacity BTU/hr 12000 19500 23000 30000 35000
KCAL/hr 3024 4914 5796 7560 8821
kW 3.52 5.72 6.74 8.79 10.26
Nominal Heating Capacity (1) BTU/hr 12000 19500 23000 30000 35000
KCAL/hr 3024 4914 5796 7560 8821
CO A 12.48 9.78 12.92 17.61 23.72
Running Current (1)
HP A 10.64 8.80 11.48 14.75 20.50
Power Consumption CO W 1290 2000 2700 3700 4800
(1)
HP W 1100 1800 2400 3100 4150
CO W/W 2.73 2.86 2.50 2.38 2.14
COP (1)
HP W/W 3.20 3.18 2.81 2.84 2.47
CO (BTU/hr)/W 9.30 9.75 8.52 8.11 7.29
EER (1)
HP (BTU/hr)/W 10.91 10.83 9.58 9.68 8.43
L/hr 1.84 3.00 3.52 4.60 5.35
Moisture Removal (1)
LBS/hr 4.06 6.61 7.76 10.14 11.79
Electrical Heater Capacity (Optional) kW 2.00 3.00 4.25

Power Supply V/Ph/Hz 110-1-60 208-230/1/60


Max Fuse Size A 16 20 25 32 40

CO 3 Wires + Earth
No of wiring Connections Between
Indoor and Outdoor Units
HP 5 Wires + Sensor Wire + Earth

Liquid mm (in) 6.4 (1/4) 9.5 (3/8)


Piping Connection Gas mm (in) 12.7 (1/2) 15.875 (5/8) 19.0 (3/4)
Drain mm (in) 19.0(3/4)
Type of Connection (2) Flare Connection
Type R22
Refrigerant Kg 0.775 1.175 1.250 1.500 2.650
LBS 1.71 2.59 2.76 3.31 5.84

(1) At "ASHRAE" Conditions - Cooling capacity based on high indoor fan speed
(2) Quick Coupling will be available upon special request.
5-3
iv- DBC Models

ORTC020

ORTC020

ORTC025

ORTC025

ORTC030

ORTC036

ORTC050

ORTC060
DBC024*

DBC048*

DBC060*
DBC018

DBC020

DBC024

DBC030

DBC036
MODELS

*
kW 5.28 5.74 7.03 7.56 9.03 10.49 13.92 17.59
Nominal Cooling Capacity BTU/hr 18000 19600 24000 25800 30800 35800 47500 60000
KCAL/hr 4536 4940 6048 6502 7762 9022 11971 15121
kW 5.28 5.74 7.03 7.56 9.03 10.49 13.92 17.59
(1)
Nominal Heating Capacity BTU/hr 18000 19600 24000 25800 30800 35800 47500 60000
KCAL/hr 4536 4940 6048 6502 7762 9022 11971 15121
(1)
CO A 19.95 20.83 25.37 27.98 31.85 39.33 51.98 66.04
Running Current
HP A 18.01 20.09 24.47 25.63 30.71 37.72 51.55 63.68
Power Consumption CO W 2063 2154 2623 2893 3293 4067 5375 6829
(1)
HP W 1862 2077 2530 2650 3175 3900 5330 6585
CO W/W 2.56 2.67 2.68 2.61 2.74 2.58 2.59 2.58
COP (1)
HP W/W 2.83 2.77 2.78 2.85 2.84 2.69 2.61 2.67
CO (BTU/hr)/W 8.73 9.10 9.15 8.92 9.35 8.80 8.84 8.79
EER (1)
HP (BTU/hr)/W 9.67 9.44 9.49 9.74 9.70 9.18 8.91 9.11
(1)
L/hr 2.42 2.61 3.23 3.36 4.07 4.93 7.02 7.69
Moisture Removal
LBS/hr 5.33 5.75 7.11 7.41 8.97 10.87 15.46 16.95
Electrical Heater Capacity (Optional) kW - 2 x 1.5 2 x 2.125 2 x 3.0

Power Supply V/Ph/Hz 208-230/1/60


Max Fuse Size A 16 20 25 32 40 50
(2)
Type of Connection Flare Connection Flare & Brazing
Type R22
Refrigerant
Kg (LBS) 1.6 (3.53) 1.7 (3.74) 2.0(4.41) 2.3 (5.07) 2.8 (6.17) 3.3 (7.27) 4.4 (9.69) 5.5 (12.2)
Liquid mm (in) 9.5(3/8) 12.7 (1/2)
Piping Connection Gas mm (in) 15.875 (5/8) 19.0 (3/4) 22.2 (7/8)
Drain mm (in) 19.0 (3/4)

(1) At "ASHRAE" Conditions - Cooling capacity based on high indoor fan speed
(2) Quick Coupling will be available upon special request.
**option 380-420/3/60 5-4
v- Cassette

CAS024 CAS048

ORHC050**
ORHC020

ORHC025

ORHC030

ORHC036
MODELS

kW 5.74 6.74 8.79 10.26 13.63


Nominal Cooling Capacity BTU/hr 19600 23000 30000 35000 46500
KCAL/hr 4940 5796 7560 8821 11719
kW 5.74 6.74 8.79 10.26 13.63
(1)
Nominal Heating Capacity BTU/hr 19600 23000 30000 35000 46500
KCAL/hr 4940 5796 7560 8821 11719
Running Current CO A 9.99 11.65 15.85 19.03 25.67
(1)
HP A 9.04 11.52 14.52 16.56 24.73
Power CO W 2110 2460 3348 4020 5535
(1)
Consumption HP W 1805 2300 2900 3307 4939
(1)
CO W/W 2.72 2.74 2.63 2.55 2.46
C.O.P
HP W/W 3.18 2.93 3.03 3.10 2.76
CO (BTU/hr)/W 9.29 9.35 8.96 8.71 8.40
EER (1)
HP (BTU/hr)/W 10.86 10.00 10.34 10.58 9.41
L/hr 2.78 3.37 3.91 4.56 7.11
Moisture Removal (1)
LBS/hr 6.13 8.09 5.91 8.09 15.67

Power Supply V/Ph/Hz 208 - 230 / 1 / 60


Max Fuse Size A 20 25 32 40 50
No of Wiring Connections CO 5 Wires + Earth
Between Indoor and Outdoor
Units HP 5 Wires + Sensor Wire + Earth
(2)
Type of Connection Flare Connection
Type R22
Refrigerant Kg 1.200 1.950 2.7 2.5 4.025
(LBS) 2.64 4.30 5.95 5.51 8.87
Liquid mm (in) 9.52 (3/8) 12.7(1/2)
Piping Connection Gas mm (in) 15.875 (5/8) 19.1 (3/4) 22.2 (7/8)
Drain mm (in) 19.1 (3/4)

(1) At "ASHRAE" Conditions - Cooling capacity based on high indoor fan speed
(2) Quick Coupling will be available upon special request.
**option 380-420/3/60
5-5
vi- TFD Models

TFD025 TFD048

ORHC050*
ORHC020

ORHC025

ORHC036
TFD025
MODELS

kW 5.28 7.03 10.55 12.60


Nominal Cooling Capacity BTU/hr 18000 24000 36000 43000
KCAL/hr 4536 6048 9073 10837
kW 5.28 7.03 10.55 12.90
(1)
Nominal Heating Capacity BTU/hr 18000 24000 36000 44000
KCAL/hr 4536 6048 9073 11089
(1)
CO A 11.12 13.27 19.83 25.63
Running Current
HP A 10.15 12.56 14.56 22.97
Power Consumption CO W 2300 2745 4100 5300
(1)
HP W 2100 2597 3010 4750
(1)
CO W/W 2.29 2.56 2.57 2.38
C.O.P
HP W/W 2.51 2.71 3.51 2.71
CO (BTU/hr)/W 7.83 8.74 8.78 8.11
EER (1)
HP (BTU/hr)/W 8.57 9.24 11.96 9.26
(1) L/hr 2.46 3.27 4.82 6.58
Moisture Removal
LBS/hr 5.42 7.21 10.63 14.51

Power Supply V/Ph/Hz 208 - 230 / 1 / 60


Max Fuse Size A 20 25 40 50
6 Wires +
No of Wiring Connections CO 2 Wires 8 Wires + Earth
Earth
Between Indoor and Outdoor
Units 8 Wires +
HP 4 Wires + Sensor Wire 10 Wires + Earth
Earth
Type of Connection (2) Flare Flare & Brazing
Type R22
Refrigerant Kg 1.550 1.900 2.400 2.550
LBS 3.416 4.188 5.290 5.620
Liquid mm (in) 9.52(3/8) 12.7 (1/2)
Piping Connection Gas mm (in) 15.87(5/8) 19.1 (3/4) 22.2 (7/8)
Drain mm (in) 19.1 (3/4)

(1) At "ASHRAE" Conditions - Cooling capacity based on high indoor fan speed
(2) Quick Coupling will be available upon special request.
**option 380-420/3/60
5-6
6-PERFORMANCE
i- IMPERIAL UNITS
a- HIGH WALL TYPE classic,
OR*C009A4 OR*C009A6
HWC009*4 HWC009*6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 8905 5864 6601 7337 8159 867 61.0 9400 6235 7020 7802 8676 827
64.0 9414 4791 5545 6295 7098 906 64.0 9937 5094 5897 6694 7548 865
77
67.0 9675 4048 4808 5590 6353 925 67.0 10213 4305 5112 5945 6755 883
72.0 10468 - 3774 4556 5355 967 72.0 11050 - 4013 4845 5695 923
61.0 8595 5698 6444 7204 8023 955 61.0 9072 6059 6853 7660 8531 911
64.0 9085 4635 5400 6159 6960 994 64.0 9590 4929 5743 6549 7401 949
86
67.0 9338 3905 4666 5451 6212 1013 67.0 9856 4153 4962 5796 6605 967
72.0 10066 - 3649 4426 5218 1055 72.0 10625 - 3880 4707 5548 1007
61.0 8280 5539 6304 7057 7533 1036 61.0 8740 5890 6703 7505 8010 989
64.0 8757 4498 5264 6020 6804 1078 64.0 9244 4783 5597 6401 7235 1029
95
67.0 9000 3778 4537 5316 6075 1100 67.0 9500 4018 4825 5653 6460 1050
72.0 9702 - 3539 4306 5091 1143 72.0 10241 - 3763 4579 5413 1091
61.0 7920 5375 6157 6921 7188 1130 61.0 8360 5716 6548 7360 7644 1078
64.0 8372 4343 5117 5876 6685 1173 64.0 8837 4618 5441 6248 7109 1119
104
67.0 8604 3631 4390 5165 5923 1195 67.0 9082 3861 4668 5492 6299 1140
72.0 9275 - 3407 4163 4940 1242 72.0 9790 - 3623 4427 5253 1185
61.0 7456 5071 5974 6761 6888 1222 61.0 7870 5392 6352 7189 7324 1167
64.0 7881 4158 4940 5713 6530 1269 64.0 8319 4422 5253 6075 6943 1212
115
67.0 8100 3460 4219 4999 5759 1291 67.0 8550 3679 4486 5316 6124 1233
72.0 8732 - 3257 4009 4780 1338 72.0 9217 - 3464 4263 5083 1277
61.0 7038 4755 5787 6234 6427 1321 61.0 7429 5057 6154 6629 6835 1261
64.0 7408 3956 4763 5555 6363 1373 64.0 7820 4207 5065 5907 6766 1311
122
67.0 7614 3276 4048 4838 5600 1396 67.0 8037 3483 4305 5145 5954 1333
72.0 8208 - 3109 3861 4757 1447 72.0 8664 - 3306 4105 5058 1381

OR*C012,A4 OR*C012,A6
HWC012*4 HWC012*6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 11874 7760 8737 9711 10797 1103 61.0 11874 7760 8737 9711 10797 1048
64.0 12552 6340 7339 8332 9394 1154 64.0 12552 6340 7339 8332 9394 1096
77
67.0 12900 5357 6363 7399 8407 1177 67.0 12900 5357 6363 7399 8407 1119
72.0 13958 - 4995 6030 7087 1231 72.0 13958 - 4995 6030 7087 1169
61.0 11460 7541 8529 9534 10618 1215 61.0 11460 7541 8529 9534 10618 1154
64.0 12114 6135 7147 8151 9211 1266 64.0 12114 6135 7147 8151 9211 1202
86
67.0 12450 5169 6175 7214 8221 1289 67.0 12450 5169 6175 7214 8221 1225
72.0 13421 - 4829 5858 6906 1343 72.0 13421 - 4829 5858 6906 1275
61.0 11040 7331 8343 9340 9970 1319 61.0 11040 7331 8343 9340 9970 1253
64.0 11676 5953 6966 7967 9005 1372 64.0 11676 5953 6966 7967 9005 1303
95
67.0 12000 5000 6005 7035 8040 1400 67.0 12000 5000 6005 7035 8040 1330
72.0 12936 - 4684 5698 6738 1455 72.0 12936 - 4684 5698 6738 1382
61.0 10559 7114 8149 9160 9514 1438 61.0 10559 7114 8149 9160 9514 1366
64.0 11162 5748 6772 7777 8848 1492 64.0 11162 5748 6772 7777 8848 1418
104
67.0 11472 4805 5810 6836 7839 1520 67.0 11472 4805 5810 6836 7839 1444
72.0 12367 - 4509 5510 6538 1581 72.0 12367 - 4509 5510 6538 1502
61.0 9941 6711 7906 8948 9116 1555 61.0 9941 6711 7906 8948 9116 1478
64.0 10508 5503 6538 7561 8642 1616 64.0 10508 5503 6538 7561 8642 1535
115
67.0 10800 4579 5584 6616 7622 1644 67.0 10800 4579 5584 6616 7622 1561
72.0 11642 - 4311 5306 6326 1702 72.0 11642 - 4311 5306 6326 1617
61.0 9384 6293 7659 8251 8506 1681 61.0 9384 6293 7659 8251 8506 1597
64.0 9878 5236 6303 7351 8421 1748 64.0 9878 5236 6303 7351 8421 1661
122
67.0 10152 4335 5358 6403 7411 1777 67.0 10152 4335 5358 6403 7411 1688
72.0 10944 - 4115 5110 6296 1842 72.0 10944 - 4115 5110 6296 1750

6-1
OR*C018,A6 OR*C020,A6
HWC020* HWC020*
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 17811 11640 13105 14566 16196 1560 61.0 19295 11858 13350 14838 16498 1576
64.0 18828 9510 11008 12498 14091 1632 64.0 20397 9688 11214 12731 14354 1648
77
67.0 19350 8036 9544 11098 12611 1665 67.0 20963 8186 9722 11305 12846 1682
72.0 20937 - 7492 9045 10631 1740 72.0 22681 - 7632 9213 10830 1758
61.0 17190 11312 12793 14300 15927 1719 61.0 18622 11523 13032 14567 16224 1736
64.0 18171 9202 10721 12227 13817 1790 64.0 19685 9374 10921 12455 14074 1808
86
67.0 18675 7753 9263 10821 12331 1824 67.0 20231 7897 9435 11023 12561 1842
72.0 20132 - 7243 8786 10358 1899 72.0 21809 - 7378 8950 10552 1918
61.0 16560 10996 12515 14010 14954 1865 61.0 17940 11201 12748 14272 15233 1884
64.0 17514 8929 10450 11951 13507 1940 64.0 18974 9095 10645 12174 13759 1960
95
67.0 18000 7500 9008 10553 12060 1980 67.0 19500 7640 9176 10749 12285 2000
72.0 19404 - 7026 8548 10106 2057 72.0 21021 - 7157 8707 10295 2078
61.0 15839 10670 12224 13740 14270 2033 61.0 17159 10869 12452 13996 14537 2054
64.0 16743 8622 10158 11665 13271 2111 64.0 18139 8782 10347 11882 13519 2132
104
67.0 17208 7208 8715 10253 11759 2150 67.0 18642 7342 8878 10445 11978 2172
72.0 18550 - 6763 8264 9807 2235 72.0 20096 - 6889 8418 9990 2258
61.0 14911 10067 11859 13422 13673 2200 61.0 16154 10255 12080 13672 13929 2222
64.0 15763 8255 9808 11341 12962 2285 64.0 17076 8409 9991 11553 13204 2308
115
67.0 16200 6868 8376 9924 11433 2325 67.0 17550 6996 8532 10109 11646 2348
72.0 17464 - 6466 7959 9489 2408 72.0 18919 - 6587 8107 9666 2432
61.0 14076 9440 11489 12376 12760 2378 61.0 15249 9616 11703 12607 12998 2402
64.0 14817 7854 9455 11027 12632 2472 64.0 16052 8001 9631 11233 12868 2497
122
67.0 15228 6503 8037 9604 11116 2513 67.0 16497 6625 8187 9784 11324 2538
72.0 16416 - 6172 7664 9444 2605 72.0 17784 - 6287 7807 9620 2631

OR*C025A6 OR*C030A6
HWC024* HWC030B
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 22758 14274 16070 17862 19861 2128 61.0 29685 19111 21516 23914 26591 2837
64.0 24057 11662 13499 15326 17279 2225 64.0 31379 15614 18073 20518 23134 2966
77
67.0 24725 9855 11704 13609 15465 2271 67.0 32250 13194 15669 18220 20705 3028
72.0 26752 - 9187 11091 13037 2373 72.0 34895 - 12301 14850 17454 3164
61.0 21964 13871 15688 17536 19531 2344 61.0 28649 18571 21004 23478 26149 3125
64.0 23218 11284 13146 14994 16943 2441 64.0 30285 15108 17601 20074 22684 3254
86
67.0 23863 9507 11359 13269 15122 2487 67.0 31125 12728 15207 17765 20246 3316
72.0 25724 - 8882 10775 12702 2589 72.0 33553 - 11892 14426 17006 3452
61.0 21160 13484 15346 17181 18338 2543 61.0 27600 18053 20546 23002 24552 3391
64.0 22379 10949 12814 14655 16564 2646 64.0 29190 14659 17156 19621 22176 3528
95
67.0 23000 9197 11046 12940 14789 2700 67.0 30000 12314 14789 17325 19800 3600
72.0 24794 - 8616 10482 12393 2805 72.0 32340 - 11535 14033 16592 3740
61.0 20239 13085 14990 16849 17500 2773 61.0 26399 17518 20069 22557 23429 3697
64.0 21394 10573 12456 14304 16275 2878 64.0 27906 14155 16677 19151 21789 3838
104
67.0 21988 8839 10688 12574 14419 2932 67.0 28680 11833 14309 16834 19305 3910
72.0 23703 - 8294 10134 12026 3048 72.0 30917 - 11104 13568 16100 4064
61.0 19053 12345 14543 16459 16768 3000 61.0 24852 16528 19470 22036 22449 4000
64.0 20141 10123 12027 13908 15896 3116 64.0 26271 13553 16102 18620 21282 4154
115
67.0 20700 8422 10271 12169 14020 3170 67.0 27000 11276 13751 16293 18770 4226
72.0 22315 - 7929 9760 11637 3283 72.0 29106 - 10616 13067 15579 4378
61.0 17986 11576 14088 15176 15647 3243 61.0 23460 15499 18862 20319 20949 4324
64.0 18933 9631 11595 13522 15491 3371 64.0 24695 12895 15523 18104 20739 4495
122
67.0 19458 7975 9855 11778 13632 3427 67.0 25380 10677 13195 15769 18251 4569
72.0 20976 - 7569 9399 11580 3552 72.0 27360 - 10134 12583 15504 4737

6-2
OR*C036A6
HWC036B
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption
0 0
F F Btu/hr 70 73 77 80 W
61.0 34632 21283 23961 26632 29612 3613
64.0 36609 17388 20127 22850 25763 3778
77
67.0 37625 14693 17450 20291 23058 3856
72.0 40710 - 13698 16537 19438 4030
61.0 33424 20681 23391 26146 29120 3980
64.0 35332 16825 19601 22355 25262 4145
86
67.0 36313 14175 16935 19784 22546 4223
72.0 39145 - 13243 16065 18939 4397
61.0 32200 20105 22881 25616 27342 4319
64.0 34055 16325 19106 21850 24696 4493
95
67.0 35000 13713 16469 19294 22050 4585
72.0 37730 - 12846 15628 18478 4764
61.0 30799 19509 22349 25121 26091 4709
64.0 32557 15763 18572 21328 24265 4888
104
67.0 33460 13178 15935 18747 21499 4979
72.0 36070 - 12365 15110 17930 5176
61.0 28994 18406 21683 24540 25000 5094
64.0 30650 15093 17932 20736 23700 5291
115
67.0 31500 12557 15314 18144 20903 5383
72.0 33957 - 11822 14552 17350 5575
61.0 27370 17260 21005 22628 23329 5507
64.0 28811 14360 17287 20161 23096 5725
122
67.0 29610 11890 14694 17560 20325 5819
72.0 31920 - 11285 14013 17266 6033

6-3
b- HIGH WALL TYPE G+

ORHC009A4 ORHC010A6
HWC009N4 HWC009N6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 8905 5864 6601 7337 8159 867 61.0 9400 6235 7020 7802 8676 827
64.0 9414 4791 5545 6295 7098 906 64.0 9937 5094 5897 6694 7548 865
77
67.0 9675 4048 4808 5590 6353 925 67.0 10213 4305 5112 5945 6755 883
72.0 10468 - 3774 4556 5355 967 72.0 11050 - 4013 4845 5695 923
61.0 8595 5698 6444 7204 8023 955 61.0 9072 6059 6853 7660 8531 911
64.0 9085 4635 5400 6159 6960 994 64.0 9590 4929 5743 6549 7401 949
86
67.0 9338 3905 4666 5451 6212 1013 67.0 9856 4153 4962 5796 6605 967
72.0 10066 - 3649 4426 5218 1055 72.0 10625 - 3880 4707 5548 1007
61.0 8280 5539 6304 7057 7533 1036 61.0 8740 5890 6703 7505 8010 989
64.0 8757 4498 5264 6020 6804 1078 64.0 9244 4783 5597 6401 7235 1029
95
67.0 9000 3778 4537 5316 6075 1100 67.0 9500 4018 4825 5653 6460 1050
72.0 9702 - 3539 4306 5091 1143 72.0 10241 - 3763 4579 5413 1091
61.0 7920 5375 6157 6921 7188 1130 61.0 8360 5716 6548 7360 7644 1078
64.0 8372 4343 5117 5876 6685 1173 64.0 8837 4618 5441 6248 7109 1119
104
67.0 8604 3631 4390 5165 5923 1195 67.0 9082 3861 4668 5492 6299 1140
72.0 9275 - 3407 4163 4940 1242 72.0 9790 - 3623 4427 5253 1185
61.0 7456 5071 5974 6761 6888 1222 61.0 7870 5392 6352 7189 7324 1167
64.0 7881 4158 4940 5713 6530 1269 64.0 8319 4422 5253 6075 6943 1212
115
67.0 8100 3460 4219 4999 5759 1291 67.0 8550 3679 4486 5316 6124 1233
72.0 8732 - 3257 4009 4780 1338 72.0 9217 - 3464 4263 5083 1277
61.0 7038 4755 5787 6234 6427 1321 61.0 7429 5057 6154 6629 6835 1261
64.0 7408 3956 4763 5555 6363 1373 64.0 7820 4207 5065 5907 6766 1311
122
67.0 7614 3276 4048 4838 5600 1396 67.0 8037 3483 4305 5145 5954 1333
72.0 8208 - 3109 3861 4757 1447 72.0 8664 - 3306 4105 5058 1381

ORHC012,A6 ORHC018,A6
HWC012N6 HWC020N6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 11874 7760 8737 9711 10797 1017 61.0 17811 10945 12323 13696 15229 1560
64.0 12552 6340 7339 8332 9394 1063 64.0 18828 8942 10351 11751 13249 1632
77
67.0 12900 5357 6363 7399 8407 1085 67.0 19350 7556 8974 10435 11858 1665
72.0 13958 - 4995 6030 7087 1134 72.0 20937 - 7045 8505 9996 1740
61.0 11460 7541 8529 9534 10618 1120 61.0 17190 10636 12029 13447 14976 1719
64.0 12114 6135 7147 8151 9211 1166 64.0 18171 8653 10081 11497 12992 1790
86
67.0 12450 5169 6175 7214 8221 1188 67.0 18675 7290 8710 10175 11595 1824
72.0 13421 - 4829 5858 6906 1237 72.0 20132 - 6811 8262 9740 1899
61.0 11040 7331 8343 9340 9970 1215 61.0 16560 10340 11767 13174 14062 1865
64.0 11676 5953 6966 7967 9005 1264 64.0 17514 8396 9826 11237 12701 1940
95
67.0 12000 5000 6005 7035 8040 1290 67.0 18000 7052 8470 9923 11340 1980
72.0 12936 - 4684 5698 6738 1340 72.0 19404 - 6606 8037 9503 2057
61.0 10559 7114 8149 9160 9514 1325 61.0 15839 10033 11494 12919 13418 2033
64.0 11162 5748 6772 7777 8848 1375 64.0 16743 8107 9551 10968 12479 2111
104
67.0 11472 4805 5810 6836 7839 1401 67.0 17208 6777 8195 9641 11057 2150
72.0 12367 - 4509 5510 6538 1456 72.0 18550 - 6359 7771 9221 2235
61.0 9941 6711 7906 8948 9116 1433 61.0 14911 9466 11151 12620 12857 2200
64.0 10508 5503 6538 7561 8642 1489 64.0 15763 7762 9222 10664 12189 2285
115
67.0 10800 4579 5584 6616 7622 1514 67.0 16200 6458 7876 9331 10750 2325
72.0 11642 - 4311 5306 6326 1569 72.0 17464 - 6080 7484 8923 2408
61.0 9384 6293 7659 8251 8506 1549 61.0 14076 8876 10803 11637 11998 2378
64.0 9878 5236 6303 7351 8421 1611 64.0 14817 7385 8891 10369 11878 2472
122
67.0 10152 4335 5358 6403 7411 1637 67.0 15228 6115 7557 9031 10453 2513
72.0 10944 - 4115 5110 6296 1697 72.0 16416 - 5804 7207 8880 2605

6-4
ORHC020,A6 ORHC025A6
HWC020N6 HWC024N6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 19295 12102 13625 15144 16839 1576 61.0 22758 14652 16495 18334 20386 2128
64.0 20397 9888 11445 12993 14650 1648 64.0 24057 11971 13856 15731 17736 2225
77
67.0 20963 8355 9923 11538 13112 1682 67.0 24725 10115 12013 13969 15874 2271
72.0 22681 - 7789 9404 11053 1758 72.0 26752 - 9430 11385 13382 2373
61.0 18622 11760 13301 14868 16559 1736 61.0 21964 14238 16103 18000 20047 2344
64.0 19685 9567 11146 12712 14365 1808 64.0 23218 11583 13494 15390 17391 2441
86
67.0 20231 8060 9630 11250 12821 1842 67.0 23863 9758 11659 13620 15522 2487
72.0 21809 - 7531 9135 10769 1918 72.0 25724 - 9117 11060 13038 2589
61.0 17940 11432 13011 14566 15548 1884 61.0 21160 13841 15752 17635 18823 2543
64.0 18974 9283 10864 12425 14043 1960 64.0 22379 11239 13153 15042 17002 2646
95
67.0 19500 7798 9365 10971 12539 2000 67.0 23000 9441 11338 13283 15180 2700
72.0 21021 - 7305 8887 10507 2078 72.0 24794 - 8844 10759 12721 2805
61.0 17159 11094 12709 14285 14837 2054 61.0 20239 13431 15386 17294 17962 2773
64.0 18139 8964 10561 12128 13798 2132 64.0 21394 10852 12786 14683 16705 2878
104
67.0 18642 7494 9061 10660 12225 2172 67.0 21988 9072 10970 12906 14801 2932
72.0 20096 - 7031 8592 10196 2258 72.0 23703 - 8513 10402 12344 3048
61.0 16154 10466 12330 13954 14216 2222 61.0 19053 12671 14927 16894 17211 3000
64.0 17076 8582 10197 11791 13477 2308 64.0 20141 10390 12345 14276 16316 3116
115
67.0 17550 7141 8708 10317 11886 2348 67.0 20700 8645 10542 12491 14391 3170
72.0 18919 - 6723 8275 9866 2432 72.0 22315 - 8139 10018 11944 3283
61.0 15249 9815 11944 12867 13266 2402 61.0 17986 11882 14461 15578 16061 3243
64.0 16052 8166 9830 11464 13133 2497 64.0 18933 9886 11901 13880 15900 3371
122
67.0 16497 6761 8356 9986 11557 2538 67.0 19458 8186 10116 12089 13992 3427
72.0 17784 - 6417 7968 9818 2631 72.0 20976 - 7769 9647 11887 3552

6-5
c- CEILING FLOOR TYPE
OR*C012 OR*C020
CFU012 CFU020
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 11874 7644 8606 9566 10636 1017 61.0 19295 12799 14409 16015 17808 1576
64.0 12552 6246 7229 8207 9254 1063 64.0 20397 10457 12104 13741 15493 1648
77
67.0 12900 5277 6268 7288 8282 1085 67.0 20963 8836 10494 12202 13866 1682
72.0 13958 - 4920 5940 6982 1134 72.0 22681 - 8238 9945 11689 1758
61.0 11460 7428 8402 9391 10459 1120 61.0 18622 12437 14066 15723 17512 1736
64.0 12114 6043 7040 8030 9074 1166 64.0 19685 10118 11787 13443 15191 1808
86
67.0 12450 5091 6083 7106 8098 1188 67.0 20231 8524 10184 11897 13558 1842
72.0 13421 - 4757 5770 6802 1237 72.0 21809 - 7964 9661 11389 1918
61.0 11040 7221 8219 9201 9821 1215 61.0 17940 12090 13760 15404 16442 1884
64.0 11676 5864 6862 7848 8870 1264 64.0 18974 9817 11489 13140 14851 1960
95
67.0 12000 4925 5915 6930 7920 1290 67.0 19500 8246 9904 11603 13260 2000
72.0 12936 - 4614 5613 6637 1340 72.0 21021 - 7725 9398 11112 2078
61.0 10559 7007 8027 9023 9372 1325 61.0 17159 11732 13440 15107 15690 2054
64.0 11162 5662 6671 7661 8716 1375 64.0 18139 9479 11169 12826 14592 2132
104
67.0 11472 4733 5724 6734 7722 1401 67.0 18642 7925 9583 11274 12929 2172
72.0 12367 - 4441 5427 6440 1456 72.0 20096 - 7436 9087 10782 2258
61.0 9941 6611 7788 8814 8980 1433 61.0 16154 11069 13039 14757 15034 2222
64.0 10508 5421 6441 7448 8513 1489 64.0 17076 9076 10783 12470 14252 2308
115
67.0 10800 4510 5500 6517 7508 1514 67.0 17550 7551 9209 10911 12570 2348
72.0 11642 - 4246 5227 6232 1569 72.0 18919 - 7109 8751 10433 2432
61.0 9384 6199 7545 8127 8380 1549 61.0 15249 10379 12632 13607 14029 2402
64.0 9878 5158 6209 7242 8296 1611 64.0 16052 8636 10396 12124 13889 2497
122
67.0 10152 4271 5278 6307 7300 1637 67.0 16497 7150 8836 10560 12222 2538
72.0 10944 - 4053 5033 6202 1697 72.0 17784 - 6786 8427 10383 2631

OR*C025 OR*C030
CFU024 CFU030
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 22758 13986 15746 17501 19460 2128 61.0 29685 19053 21450 23842 26510 2916
64.0 24057 11426 13226 15016 16930 2225 64.0 31379 15566 18018 20456 23064 3049
77
67.0 24725 9655 11467 13334 15152 2271 67.0 32250 13154 15622 18165 20642 3112
72.0 26752 - 9002 10867 12773 2373 72.0 34895 - 12263 14805 17401 3252
61.0 21964 13591 15371 17182 19136 2344 61.0 28649 18515 20940 23407 26070 3212
64.0 23218 11056 12881 14690 16601 2441 64.0 30285 15062 17548 20013 22615 3345
86
67.0 23863 9315 11129 13001 14816 2487 67.0 31125 12690 15161 17712 20184 3408
72.0 25724 - 8703 10557 12445 2589 72.0 33553 - 11856 14382 16955 3548
61.0 21160 13212 15036 16833 17968 2543 61.0 27600 17999 20484 22932 24478 3485
64.0 22379 10728 12555 14359 16229 2646 64.0 29190 14615 17104 19561 22109 3626
95
67.0 23000 9011 10823 12679 14490 2700 67.0 30000 12276 14744 17273 19740 3700
72.0 24794 - 8442 10270 12143 2805 72.0 32340 - 11500 13991 16542 3844
61.0 20239 12820 14687 16508 17146 2773 61.0 26399 17465 20008 22489 23358 3800
64.0 21394 10359 12205 14015 15946 2878 64.0 27906 14112 16626 19093 21723 3944
104
67.0 21988 8660 10471 12319 14128 2932 67.0 28680 11798 14266 16783 19247 4018
72.0 23703 - 8126 9929 11783 3048 72.0 30917 - 11070 13527 16052 4177
61.0 19053 12095 14249 16126 16429 3000 61.0 24852 16478 19411 21969 22381 4111
64.0 20141 9918 11784 13627 15574 3116 64.0 26271 13512 16053 18564 21217 4270
115
67.0 20700 8252 10063 11923 13737 3170 67.0 27000 11242 13709 16243 18714 4344
72.0 22315 - 7769 9562 11401 3283 72.0 29106 - 10584 13027 15532 4499
61.0 17986 11342 13803 14870 15331 3243 61.0 23460 15452 18805 20257 20885 4444
64.0 18933 9437 11360 13249 15177 3371 64.0 24695 12856 15476 18049 20676 4620
122
67.0 19458 7814 9656 11540 13356 3427 67.0 25380 10645 13155 15721 18195 4696
72.0 20976 - 7416 9209 11346 3552 72.0 27360 - 10103 12545 15457 4868

6-6
OR*C036
CFU036
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption
0 0
F F Btu/hr 70 73 77 80 W
61.0 34632 21790 24531 27266 30317 3782
64.0 36609 17802 20606 23394 26376 3955
77
67.0 37625 15043 17866 20774 23607 4037
72.0 40710 - 14024 16931 19900 4219
61.0 33424 21174 23948 26769 29814 4166
64.0 35332 17225 20068 22887 25863 4339
86
67.0 36313 14512 17339 20255 23083 4421
72.0 39145 - 13559 16447 19390 4603
61.0 32200 20583 23426 26226 27993 4522
64.0 34055 16714 19561 22370 25284 4704
95
67.0 35000 14040 16861 19753 22575 4800
72.0 37730 - 13152 16000 18918 4987
61.0 30799 19974 22881 25719 26713 4930
64.0 32557 16139 19014 21835 24843 5117
104
67.0 33460 13492 16314 19193 22011 5213
72.0 36070 - 12660 15470 18357 5419
61.0 28994 18844 22199 25124 25595 5333
64.0 30650 15452 18359 21230 24264 5539
115
67.0 31500 12856 15678 18576 21401 5635
72.0 33957 - 12104 14898 17763 5837
61.0 27370 17671 21505 23166 23885 5765
64.0 28811 14702 17699 20641 23646 5993
122
67.0 29610 12173 15044 17978 20808 6092
72.0 31920 - 11554 14347 17677 6315

6-7
d- DUCTD TYPE
OR*C020 OR*C020
DBC018 DBC020
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 17811 11727 13203 14675 16317 1626 61.0 19394 12959 14589 16216 18031 1697
64.0 18828 9581 11090 12591 14196 1700 64.0 20501 10587 12255 13913 15687 1775
77
67.0 19350 8096 9615 11181 12705 1735 67.0 21070 8946 10625 12355 14040 1812
72.0 20937 - 7548 9112 10711 1813 72.0 22798 - 8341 10069 11835 1893
61.0 17190 11396 12889 14407 16046 1791 61.0 18718 12593 14242 15920 17731 1870
64.0 18171 9271 10801 12318 13920 1865 64.0 19786 10244 11935 13612 15382 1947
86
67.0 18675 7811 9332 10902 12423 1900 67.0 20335 8631 10312 12046 13728 1984
72.0 20132 - 7297 8852 10436 1978 72.0 21921 - 8064 9782 11532 2066
61.0 16560 11078 12608 14115 15066 1943 61.0 18032 12242 13932 15597 16648 2029
64.0 17514 8995 10528 12040 13608 2022 64.0 19071 9940 11633 13304 15037 2111
95
67.0 18000 7556 9075 10631 12150 2063 67.0 19600 8350 10028 11748 13426 2154
72.0 19404 - 7078 8611 10182 2143 72.0 21129 - 7822 9516 11251 2238
61.0 15839 10750 12315 13842 14377 2119 61.0 17247 11879 13608 15296 15887 2212
64.0 16743 8686 10234 11752 13370 2199 64.0 18232 9598 11308 12986 14775 2296
104
67.0 17208 7261 8780 10330 11846 2240 67.0 18738 8024 9703 11415 13090 2339
72.0 18550 - 6814 8326 9880 2329 72.0 20199 - 7529 9200 10917 2432
61.0 14911 10142 11948 13522 13776 2292 61.0 16237 11207 13202 14942 15222 2393
64.0 15763 8316 9881 11426 13059 2381 64.0 17164 9190 10918 12626 14431 2486
115
67.0 16200 6919 8438 9998 11518 2422 67.0 17640 7646 9324 11048 12728 2529
72.0 17464 - 6514 8018 9560 2509 72.0 19016 - 7198 8860 10564 2619
61.0 14076 9511 11574 12468 12855 2478 61.0 15327 10509 12790 13778 14205 2587
64.0 14817 7913 9526 11109 12726 2576 64.0 16134 8744 10526 12276 14063 2690
122
67.0 15228 6552 8097 9676 11199 2618 67.0 16582 7240 8947 10692 12375 2734
72.0 16416 - 6218 7722 9514 2714 72.0 17875 - 6871 8532 10513 2834

OR*C025 OR*C025
DBC024 DBC024*
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 23748 15636 17604 19566 21756 2067 61.0 25529 17058 19204 21345 23734 2280
64.0 25103 12775 14787 16788 18928 2161 64.0 26986 13937 16132 18314 20649 2384
77
67.0 25800 10795 12820 14907 16940 2206 67.0 27735 11776 13986 16263 18481 2433
72.0 27916 - 10064 12150 14281 2306 72.0 30009 - 10979 13254 15579 2543
61.0 22919 15195 17185 19210 21394 2277 61.0 24638 16576 18748 20956 23340 2511
64.0 24228 12361 14401 16424 18560 2371 64.0 26045 13485 15710 17918 20247 2615
86
67.0 24900 10414 12442 14535 16565 2416 67.0 26768 11361 13574 15857 18071 2664
72.0 26842 - 9730 11803 13914 2515 72.0 28855 - 10615 12876 15179 2774
61.0 22080 14771 16811 18820 20088 2471 61.0 23736 16114 18339 20531 21915 2725
64.0 23352 11994 14037 16053 18144 2571 64.0 25103 13084 15313 17513 19794 2835
95
67.0 24000 10075 12100 14175 16200 2623 67.0 25800 10991 13200 15464 17673 2893
72.0 25872 - 9438 11482 13576 2725 72.0 27812 - 10296 12526 14810 3006
61.0 21119 14333 16420 18456 19169 2694 61.0 22703 15636 17913 20134 20912 2971
64.0 22325 11581 13645 15669 17827 2796 64.0 23999 12634 14885 17094 19448 3084
104
67.0 22944 9682 11707 13773 15795 2849 67.0 24665 10562 12772 15026 17231 3142
72.0 24734 - 9085 11101 13173 2961 72.0 26589 - 9911 12111 14371 3266
61.0 19882 13523 15930 18029 18367 2914 61.0 21373 14752 17379 19669 20037 3214
64.0 21017 11089 13174 15235 17412 3027 64.0 22593 12097 14372 16620 18995 3339
115
67.0 21600 9226 11251 13330 15358 3079 67.0 23220 10065 12274 14542 16754 3396
72.0 23285 - 8686 10691 12747 3190 72.0 25031 - 9475 11663 13906 3518
61.0 18768 12681 15432 16624 17140 3150 61.0 20176 13834 16836 18136 18698 3474
64.0 19756 10550 12701 14812 16969 3275 64.0 21237 11510 13856 16159 18511 3612
122
67.0 20304 8736 10796 12902 14932 3329 67.0 21827 9530 11777 14075 16290 3671
72.0 21888 - 8291 10295 12685 3451 72.0 23529 - 9045 11232 13839 3806

6-8
OR*C030 OR*C036
DBC030 DBC036
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 30476 20215 22759 25296 28127 2595 61.0 35424 23048 25948 28840 32068 3205
64.0 32216 16516 19117 21704 24471 2713 64.0 37446 18830 21796 24745 27899 3351
77
67.0 33110 13956 16575 19273 21901 2769 67.0 38485 15911 18897 21973 24970 3420
72.0 35825 - 13011 15707 18463 2895 72.0 41641 - 14834 17908 21050 3575
61.0 29413 19644 22217 24835 27660 2858 61.0 34188 22397 25330 28315 31535 3530
64.0 31092 15981 18618 21234 23995 2977 64.0 36140 18220 21227 24209 27357 3677
86
67.0 31955 13464 16086 18792 21415 3033 67.0 37143 15350 18340 21425 24416 3746
72.0 34447 - 12579 15259 17989 3158 72.0 40040 - 14342 17397 20509 3900
61.0 28336 19096 21733 24331 25971 3102 61.0 32936 21772 24779 27740 29609 3831
64.0 29968 15506 18147 20754 23457 3227 64.0 34833 17679 20690 23662 26744 3986
95
67.0 30800 13025 15643 18326 20944 3293 67.0 35800 14850 17835 20894 23879 4067
72.0 33202 - 12202 14844 17551 3421 72.0 38592 - 13911 16924 20010 4226
61.0 27103 18531 21228 23861 24783 3382 61.0 31502 21127 24203 27204 28255 4177
64.0 28650 14973 17641 20258 23048 3510 64.0 33301 17071 20112 23096 26277 4335
104
67.0 29445 12517 15136 17807 20420 3576 67.0 34225 14271 17256 20302 23282 4417
72.0 31741 - 11745 14352 17031 3718 72.0 36894 - 13391 16363 19417 4592
61.0 25515 17483 20595 23309 23746 3659 61.0 29657 19932 23481 26575 27073 4518
64.0 26972 14336 17032 19696 22511 3800 64.0 31350 16344 19419 22456 25665 4693
115
67.0 27720 11927 14546 17234 19855 3866 67.0 32220 13599 16584 19649 22637 4775
72.0 29882 - 11229 13822 16480 4004 72.0 34733 - 12803 15758 18789 4945
61.0 24086 16394 19952 21493 22159 3955 61.0 27996 18691 22747 24504 25264 4884
64.0 25353 13640 16420 19150 21938 4112 64.0 29469 15551 18721 21833 25011 5078
122
67.0 26057 11294 13957 16680 19305 4179 67.0 30287 12876 15913 19017 22010 5161
72.0 28089 - 10719 13310 16400 4333 72.0 32649 - 12221 15175 18698 5351

OR*C050 OR*C060
DBC048 DBC060
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 47001 29480 33189 36889 41018 4236 61.0 59370 39960 44987 50002 55599 5381
64.0 49684 24085 27879 31651 35685 4429 64.0 62759 32647 37789 42902 48371 5627
77
67.0 51063 20352 24171 28106 31938 4520 67.0 64500 27587 32763 38097 43292 5743
72.0 55250 - 18974 22906 26924 4725 72.0 69789 - 25719 31049 36495 6003
61.0 45361 28647 32400 36216 40336 4666 61.0 57299 38831 43917 49091 54675 5928
64.0 47951 23305 27150 30965 34991 4859 64.0 60569 31589 36802 41973 47430 6173
86
67.0 49281 19634 23458 27404 31230 4950 67.0 62250 26614 31797 37146 42332 6290
72.0 53125 - 18344 22252 26233 5155 72.0 67106 - 24865 30162 35558 6549
61.0 43700 27848 31694 35482 37873 5063 61.0 55200 37748 42960 48095 51336 6433
64.0 46218 22613 26464 30266 34208 5268 64.0 58380 30651 35872 41025 46368 6692
95
67.0 47500 18995 22812 26725 30543 5375 67.0 60000 25747 30922 36225 41400 6829
72.0 51205 - 17794 21647 25595 5585 72.0 64680 - 24119 29342 34693 7095
61.0 41798 27023 30957 34796 36140 5520 61.0 52797 36629 41962 47166 48988 7013
64.0 44184 21835 25725 29542 33611 5730 64.0 55811 29596 34870 40044 45559 7280
104
67.0 45410 18254 22072 25967 29779 5837 67.0 57360 24743 29919 35198 40365 7416
72.0 48952 - 17128 20930 24836 6068 72.0 61834 - 23217 28370 33664 7710
61.0 39350 25495 30034 33991 34629 5972 61.0 49705 34558 40711 46075 46939 7587
64.0 41596 20906 24838 28723 32828 6203 64.0 52542 28337 33668 38933 44498 7881
115
67.0 42750 17394 21212 25132 28954 6310 67.0 54000 23577 28752 34067 39247 8017
72.0 46085 - 16375 20156 24032 6536 72.0 58212 - 22197 27321 32575 8304
61.0 37145 23907 29095 31343 32315 6455 61.0 46920 32406 39438 42484 43802 8202
64.0 39100 19891 23945 27926 31991 6711 64.0 49389 26962 32458 37854 43364 8527
122
67.0 40185 16470 20354 24324 28152 6821 67.0 50760 22324 27589 32971 38160 8667
72.0 43319 - 15632 19410 23916 7072 72.0 54719 - 21188 26310 32418 8985

6-9
e- CASSETTE TYPE
OR*C020 OR*C025
CAS024 CAS024
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0 F) Consumption WBT Capacity at entering DBT (0 F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 19394 12410 13972 15529 17267 1663 61.0 22758 14652 16495 18334 20386 1938
64.0 20501 10139 11736 13324 15023 1739 64.0 24057 11971 13856 15731 17736 2027
77
67.0 21070 8568 10175 11832 13445 1775 67.0 24725 10115 12013 13969 15874 2069
72.0 22798 - 7988 9643 11334 1855 72.0 26752 - 9430 11385 13382 2162
61.0 18718 12060 13639 15246 16980 1831 61.0 21964 14238 16103 18000 20047 2135
64.0 19786 9811 11430 13035 14730 1907 64.0 23218 11583 13494 15390 17391 2224
86
67.0 20335 8266 9875 11536 13147 1943 67.0 23863 9758 11659 13620 15522 2266
72.0 21921 - 7722 9368 11043 2023 72.0 25724 - 9117 11060 13038 2359
61.0 18032 11723 13342 14937 15943 1988 61.0 21160 13841 15752 17635 18823 2317
64.0 19071 9519 11141 12741 14401 2068 64.0 22379 11239 13153 15042 17002 2411
95
67.0 19600 7996 9603 11250 12858 2110 67.0 23000 9441 11338 13283 15180 2460
72.0 21129 - 7491 9113 10775 2192 72.0 24794 - 8844 10759 12721 2556
61.0 17247 11376 13032 14648 15214 2167 61.0 20239 13431 15386 17294 17962 2526
64.0 18232 9192 10830 12436 14149 2249 64.0 21394 10852 12786 14683 16705 2622
104
67.0 18738 7684 9292 10932 12536 2291 67.0 21988 9072 10970 12906 14801 2672
72.0 20199 - 7210 8811 10455 2382 72.0 23703 - 8513 10402 12344 2777
61.0 16237 10733 12643 14309 14578 2344 61.0 19053 12671 14927 16894 17211 2733
64.0 17164 8801 10456 12091 13820 2435 64.0 20141 10390 12345 14276 16316 2839
115
67.0 17640 7322 8930 10580 12189 2477 67.0 20700 8645 10542 12491 14391 2888
72.0 19016 - 6894 8485 10117 2566 72.0 22315 - 8139 10018 11944 2991
61.0 15327 10064 12248 13194 13604 2534 61.0 17986 11882 14461 15578 16061 2954
64.0 16134 8374 10080 11756 13468 2635 64.0 18933 9886 11901 13880 15900 3072
122
67.0 16582 6933 8568 10240 11851 2678 67.0 19458 8186 10116 12089 13992 3122
72.0 17875 - 6580 8171 10068 2776 72.0 20976 - 7769 9647 11887 3237

OR*C030 OR*C036
CAS048 CAS048
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0 F) Consumption WBT Capacity at entering DBT (0 F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 29685 19835 22331 24820 27598 2638 61.0 34632 23141 26052 28957 32198 3168
64.0 31379 16205 18758 21296 24010 2759 64.0 36609 18906 21884 24845 28012 3312
77
67.0 32250 13693 16263 18910 21489 2816 67.0 37625 15976 18973 22062 25071 3381
72.0 34895 - 12766 15412 18115 2943 72.0 40710 - 14894 17981 21135 3534
61.0 28649 19275 21799 24368 27139 2906 61.0 33424 22487 25433 28429 31662 3489
64.0 30285 15680 18268 20834 23543 3027 64.0 35332 18294 21312 24307 27467 3634
86
67.0 31125 13211 15783 18438 21012 3084 67.0 36313 15412 18414 21511 24514 3702
72.0 33553 - 12342 14972 17650 3211 72.0 39145 - 14400 17467 20592 3855
61.0 27600 18737 21325 23873 25482 3154 61.0 32200 21860 24879 27852 29729 3787
64.0 29190 15214 17806 20364 23016 3281 64.0 34055 17750 20774 23758 26852 3940
95
67.0 30000 12780 15349 17981 20550 3348 67.0 35000 14910 17907 20978 23975 4020
72.0 32340 - 11972 14565 17221 3479 72.0 37730 - 13967 16992 20091 4177
61.0 26399 18182 20829 23412 24316 3438 61.0 30799 21212 24300 27314 28369 4129
64.0 27906 14691 17309 19877 22614 3569 64.0 32557 17139 20193 23189 26383 4285
104
67.0 28680 12282 14851 17472 20036 3636 67.0 33460 14329 17326 20384 23376 4366
72.0 30917 - 11524 14082 16710 3780 72.0 36070 - 13445 16429 19495 4539
61.0 24852 17154 20208 22870 23299 3720 61.0 28994 20013 23576 26682 27183 4466
64.0 26271 14066 16712 19326 22088 3864 64.0 30650 16410 19497 22546 25769 4639
115
67.0 27000 11703 14272 16910 19481 3931 67.0 31500 13653 16651 19728 22728 4719
72.0 29106 - 11018 13562 16170 4071 72.0 33957 - 12854 15822 18864 4888
61.0 23460 16086 19576 21088 21742 4021 61.0 27370 18767 22839 24603 25366 4828
64.0 24695 13383 16111 18790 21525 4180 64.0 28811 15614 18796 21921 25112 5019
122
67.0 25380 11081 13695 16366 18942 4249 67.0 29610 12928 15977 19093 22099 5102
72.0 27360 - 10517 13060 16092 4405 72.0 31920 - 12270 15237 18774 5289

OR*C050
CAS048
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0 F) Consumption
0 0
F F Btu/hr 70 73 77 80 W
61.0 46011 28276 31833 35382 39342 4362
64.0 48638 23101 26740 30358 34228 4561
77
67.0 49988 19521 23184 26958 30634 4655
72.0 54086 - 18199 21971 25824 4865
61.0 44406 27477 31076 34737 38688 4804
64.0 46941 22353 26041 29700 33562 5004
86
67.0 48244 18832 22500 26285 29954 5098
72.0 52007 - 17595 21343 25161 5308
61.0 42780 26711 30399 34032 36326 5214
64.0 45245 21689 25383 29030 32810 5424
95
67.0 46500 18219 21880 25633 29295 5535
72.0 50127 - 17067 20763 24549 5751
61.0 40918 25919 29692 33375 34664 5684
64.0 43254 20943 24674 28335 32238 5900
104
67.0 44454 17508 21171 24907 28563 6011
72.0 47921 - 16428 20075 23821 6249
61.0 38521 24453 28807 32603 33214 6149
64.0 40720 20052 23824 27549 31487 6387
115
67.0 41850 16683 20345 24106 27772 6498
72.0 45114 - 15707 19333 23050 6731
61.0 36363 22931 27907 30062 30995 6647
64.0 38277 19078 22967 26786 30685 6911
122
67.0 39339 15797 19522 23330 27003 7024
72.0 42407 - 14993 18618 22939 7282

6-10
f- FREE STAND TYPE
OR*C020 OR*C025
TFD025 TFD025
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 17811 11640 13105 14566 16196 1812 61.0 23748 15521 17473 19421 21595 2163
64.0 18828 9510 11008 12498 14091 1895 64.0 25103 12680 14678 16663 18788 2262
77
67.0 19350 8036 9544 11098 12611 1934 67.0 25800 10715 12725 14797 16815 2309
72.0 20937 - 7492 9045 10631 2022 72.0 27916 - 9990 12060 14175 2413
61.0 17190 11312 12793 14300 15927 1996 61.0 22919 15082 17058 19067 21236 2383
64.0 18171 9202 10721 12227 13817 2079 64.0 24228 12269 14294 16302 18422 2481
86
67.0 18675 7753 9263 10821 12331 2118 67.0 24900 10337 12350 14428 16442 2528
72.0 20132 - 7243 8786 10358 2206 72.0 26842 - 9658 11715 13811 2632
61.0 16560 10996 12515 14010 14954 2167 61.0 22080 14661 16686 18680 19939 2586
64.0 17514 8929 10450 11951 13507 2254 64.0 23352 11905 13933 15934 18010 2690
95
67.0 18000 7500 9008 10553 12060 2300 67.0 24000 10000 12010 14070 16080 2745
72.0 19404 - 7026 8548 10106 2390 72.0 25872 - 9368 11397 13475 2852
61.0 15839 10670 12224 13740 14270 2362 61.0 21119 14227 16298 18319 19027 2819
64.0 16743 8622 10158 11665 13271 2452 64.0 22325 11495 13544 15553 17695 2926
104
67.0 17208 7208 8715 10253 11759 2498 67.0 22944 9610 11621 13671 15678 2981
72.0 18550 - 6763 8264 9807 2597 72.0 24734 - 9018 11019 13075 3099
61.0 14911 10067 11859 13422 13673 2555 61.0 19882 13422 15812 17896 18231 3050
64.0 15763 8255 9808 11341 12962 2654 64.0 21017 11006 13077 15122 17283 3168
115
67.0 16200 6868 8376 9924 11433 2700 67.0 21600 9157 11168 13232 15244 3223
72.0 17464 - 6466 7959 9489 2797 72.0 23285 - 8621 10612 12652 3338
61.0 14076 9440 11489 12376 12760 2762 61.0 18768 12587 15318 16501 17013 3297
64.0 14817 7854 9455 11027 12632 2872 64.0 19756 10472 12607 14703 16843 3427
122
67.0 15228 6503 8037 9604 11116 2919 67.0 20304 8671 10716 12806 14822 3484
72.0 16416 - 6172 7664 9444 3026 72.0 21888 - 8230 10219 12591 3612

OR*C036 OR*C050
TFD048 TFD048
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0F) Consumption WBT Capacity at entering DBT (0F) Consumption
0 0 0
F F Btu/hr 70 73 77 80 W F Btu/hr 70 73 77 80 W
61.0 35622 23489 26445 29393 32682 3231 61.0 42548 28223 31774 35316 39268 4176
64.0 37655 19191 22214 25219 28434 3378 64.0 44977 23058 26690 30301 34163 4367
77
67.0 38700 16216 19259 22394 25448 3448 67.0 46225 19484 23140 26907 30576 4457
72.0 41873 - 15118 18251 21453 3604 72.0 50015 - 18165 21929 25776 4659
61.0 34379 22826 25816 28857 32139 3559 61.0 41064 27425 31018 34672 38616 4600
64.0 36342 18569 21633 24673 27881 3706 64.0 43408 22311 25992 29645 33499 4791
86
67.0 37350 15644 18691 21835 24884 3776 67.0 44613 18797 22458 26235 29898 4881
72.0 40263 - 14616 17730 20902 3932 72.0 48092 - 17562 21303 25114 5083
61.0 33120 22189 25253 28271 30177 3862 61.0 39560 26660 30342 33968 36258 4993
64.0 35028 18018 21086 24116 27256 4018 64.0 41839 21648 25336 28975 32749 5194
95
67.0 36000 15135 18177 21294 24336 4100 67.0 43000 18185 21839 25585 29240 5300
72.0 38808 - 14178 17248 20394 4260 72.0 46354 - 17035 20724 24503 5507
61.0 31678 21532 24666 27725 28796 4211 61.0 37838 25871 29637 33312 34599 5443
64.0 33487 17398 20498 23539 26781 4371 64.0 39998 20903 24628 28282 32177 5650
104
67.0 34416 14544 17587 20690 23728 4453 67.0 41108 17475 21131 24860 28509 5756
72.0 37100 - 13647 16677 19789 4629 72.0 44314 - 16398 20037 23777 5984
61.0 29823 20314 23931 27084 27592 4555 61.0 35622 24408 28753 32542 33152 5888
64.0 31525 16658 19791 22886 26157 4731 64.0 37655 20014 23779 27498 31428 6116
115
67.0 32400 13859 16901 20025 23071 4813 67.0 38700 16652 20307 24061 27720 6222
72.0 34927 - 13048 16060 19149 4986 72.0 41719 - 15677 19297 23007 6445
61.0 28152 19049 23183 24973 25748 4924 61.0 33626 22888 27854 30006 30937 6365
64.0 29634 15849 19079 22251 25490 5119 64.0 35396 19043 22924 26735 30627 6618
122
67.0 30456 13123 16218 19381 22432 5203 67.0 36378 15767 19486 23286 26952 6726
72.0 32832 - 12455 15466 19056 5394 72.0 39215 - 14965 18583 22896 6973

6-11
6-PERFORMANCE
ii- SI UNITS
a- HIGH WALL TYPE classic
OR*C009A4 OR*C009A6
HWC009*4 HWC009*6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 2.61 1.72 1.94 2.15 2.39 867 16.0 2.75 1.82 2.05 2.28 2.54 827
18.0 2.76 1.41 1.63 1.85 2.08 906 18.0 2.91 1.49 1.73 1.96 2.21 865
25
19.5 2.84 1.19 1.41 1.64 1.86 925 19.5 2.99 1.26 1.50 1.74 1.98 883
22.0 3.07 - 1.11 1.34 1.57 967 22.0 3.23 - 1.17 1.42 1.67 923
16.0 2.52 1.67 1.89 2.11 2.35 955 16.0 2.65 1.77 2.01 2.24 2.50 911
18.0 2.67 1.36 1.58 1.81 2.04 994 18.0 2.81 1.44 1.68 1.92 2.17 949
30
19.5 2.74 1.15 1.37 1.60 1.82 1013 19.5 2.88 1.22 1.45 1.70 1.93 967
22.0 2.95 - 1.07 1.30 1.53 1055 22.0 3.11 - 1.14 1.38 1.62 1007
16.0 2.43 1.62 1.85 2.07 2.21 1036 16.0 2.56 1.72 1.96 2.20 2.34 989
18.0 2.57 1.32 1.54 1.77 2.00 1078 18.0 2.70 1.40 1.64 1.87 2.12 1029
35
19.5 2.64 1.11 1.33 1.56 1.78 1100 19.5 2.78 1.18 1.41 1.65 1.89 1050
22.0 2.85 - 1.04 1.26 1.49 1143 22.0 3.00 - 1.10 1.34 1.58 1091
16.0 2.32 1.58 1.81 2.03 2.11 1130 16.0 2.45 1.67 1.92 2.15 2.24 1078
18.0 2.46 1.27 1.50 1.72 1.96 1173 18.0 2.59 1.35 1.59 1.83 2.08 1119
40
19.5 2.52 1.07 1.29 1.52 1.74 1195 19.5 2.66 1.13 1.37 1.61 1.84 1140
22.0 2.72 - 1.00 1.22 1.45 1242 22.0 2.86 - 1.06 1.30 1.54 1185
16.0 2.19 1.49 1.75 1.98 2.02 1222 16.0 2.30 1.58 1.86 2.10 2.14 1167
18.0 2.31 1.22 1.45 1.68 1.92 1269 18.0 2.43 1.29 1.54 1.78 2.03 1212
46
19.5 2.38 1.01 1.24 1.47 1.69 1291 19.5 2.50 1.08 1.31 1.56 1.79 1233
22.0 2.56 - 0.96 1.18 1.40 1338 22.0 2.70 - 1.01 1.25 1.49 1277
16.0 2.06 1.39 1.70 1.83 1.89 1321 16.0 2.17 1.48 1.80 1.94 2.00 1261
18.0 2.17 1.16 1.40 1.63 1.87 1373 18.0 2.29 1.23 1.48 1.73 1.98 1311
50
19.5 2.23 0.96 1.19 1.42 1.64 1396 19.5 2.35 1.02 1.26 1.51 1.74 1333
22.0 2.41 - 0.91 1.13 1.40 1447 22.0 2.54 - 0.97 1.20 1.48 1381

OR*C012,A4 OR*C012,A6
HWC012*4 HWC012*6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 3.48 2.28 2.56 2.85 3.17 1103 16.0 3.48 2.14 2.41 2.68 2.98 1048
18.0 3.68 1.86 2.15 2.44 2.76 1154 18.0 3.68 1.75 2.02 2.30 2.59 1096
25
19.5 3.78 1.57 1.87 2.17 2.47 1177 19.5 3.78 1.48 1.75 2.04 2.32 1119
22.0 4.09 - 1.47 1.77 2.08 1231 22.0 4.09 - 1.38 1.66 1.95 1169
16.0 3.36 2.21 2.50 2.80 3.11 1215 16.0 3.36 2.08 2.35 2.63 2.93 1154
18.0 3.55 1.80 2.10 2.39 2.70 1266 18.0 3.55 1.69 1.97 2.25 2.54 1202
30
19.5 3.65 1.52 1.81 2.12 2.41 1289 19.5 3.65 1.43 1.70 1.99 2.27 1225
22.0 3.94 - 1.42 1.72 2.03 1343 22.0 3.94 - 1.33 1.62 1.90 1275
16.0 3.24 2.15 2.45 2.74 2.92 1319 16.0 3.24 2.02 2.30 2.58 2.75 1253
18.0 3.42 1.75 2.04 2.34 2.64 1372 18.0 3.42 1.64 1.92 2.20 2.48 1303
35
19.5 3.52 1.47 1.76 2.06 2.36 1400 19.5 3.52 1.38 1.66 1.94 2.22 1330
22.0 3.79 - 1.37 1.67 1.98 1455 22.0 3.79 - 1.29 1.57 1.86 1382
16.0 3.10 2.09 2.39 2.69 2.79 1438 16.0 3.10 1.96 2.25 2.53 2.62 1366
18.0 3.27 1.69 1.99 2.28 2.60 1492 18.0 3.27 1.59 1.87 2.14 2.44 1418
40
19.5 3.37 1.41 1.70 2.01 2.30 1520 19.5 3.37 1.33 1.60 1.89 2.16 1444
22.0 3.63 - 1.32 1.62 1.92 1581 22.0 3.63 - 1.24 1.52 1.80 1502
16.0 2.92 1.97 2.32 2.62 2.67 1555 16.0 2.92 1.85 2.18 2.47 2.51 1478
18.0 3.08 1.61 1.92 2.22 2.53 1616 18.0 3.08 1.52 1.80 2.09 2.38 1535
46
19.5 3.17 1.34 1.64 1.94 2.24 1644 19.5 3.17 1.26 1.54 1.82 2.10 1561
22.0 3.42 - 1.26 1.56 1.86 1702 22.0 3.42 - 1.19 1.46 1.74 1617
16.0 2.75 1.85 2.25 2.42 2.50 1681 16.0 2.75 1.74 2.11 2.28 2.35 1597
18.0 2.90 1.54 1.85 2.16 2.47 1748 18.0 2.90 1.44 1.74 2.03 2.32 1661
50
19.5 2.98 1.27 1.57 1.88 2.17 1777 19.5 2.98 1.20 1.48 1.77 2.04 1688
22.0 3.21 - 1.21 1.50 1.85 1842 22.0 3.21 - 1.13 1.41 1.74 1750

6-12
OR*C020A6 OR*C020A6
HWC018* HWC020*
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 5.22 3.28 3.69 4.10 4.56 1560 16.0 5.66 3.64 4.10 4.56 5.07 1576
18.0 5.52 2.68 3.10 3.52 3.97 1632 18.0 5.98 2.98 3.45 3.91 4.41 1648
25
19.5 5.68 2.26 2.69 3.12 3.55 1665 19.5 6.15 2.52 2.99 3.47 3.95 1682
22.0 6.14 - 2.11 2.55 2.99 1740 22.0 6.65 - 2.35 2.83 3.33 1758
16.0 5.04 3.18 3.60 4.03 4.48 1719 16.0 5.46 3.54 4.00 4.48 4.99 1736
18.0 5.33 2.59 3.02 3.44 3.89 1790 18.0 5.77 2.88 3.36 3.83 4.33 1808
30
19.5 5.48 2.18 2.61 3.05 3.47 1824 19.5 5.93 2.43 2.90 3.39 3.86 1842
22.0 5.91 - 2.04 2.47 2.92 1899 22.0 6.40 - 2.27 2.75 3.24 1918
16.0 4.86 3.10 3.52 3.94 4.21 1865 16.0 5.26 3.44 3.92 4.39 4.68 1884
18.0 5.14 2.51 2.94 3.36 3.80 1940 18.0 5.57 2.80 3.27 3.74 4.23 1960
35
19.5 5.28 2.11 2.54 2.97 3.40 1980 19.5 5.72 2.35 2.82 3.30 3.78 2000
22.0 5.69 - 1.98 2.41 2.85 2057 22.0 6.17 - 2.20 2.68 3.16 2078
16.0 4.65 3.00 3.44 3.87 4.02 2033 16.0 5.03 3.34 3.83 4.30 4.47 2054
18.0 4.91 2.43 2.86 3.28 3.74 2111 18.0 5.32 2.70 3.18 3.65 4.15 2132
40
19.5 5.05 2.03 2.45 2.89 3.31 2150 19.5 5.47 2.26 2.73 3.21 3.68 2172
22.0 5.44 - 1.90 2.33 2.76 2235 22.0 5.89 - 2.12 2.59 3.07 2258
16.0 4.37 2.83 3.34 3.78 3.85 2200 16.0 4.74 3.15 3.71 4.20 4.28 2222
18.0 4.62 2.32 2.76 3.19 3.65 2285 18.0 5.01 2.58 3.07 3.55 4.06 2308
46
19.5 4.75 1.93 2.36 2.79 3.22 2325 19.5 5.15 2.15 2.62 3.11 3.58 2348
22.0 5.12 - 1.82 2.24 2.67 2408 22.0 5.55 - 2.02 2.49 2.97 2432
16.0 4.13 2.66 3.23 3.48 3.59 2378 16.0 4.47 2.96 3.60 3.87 3.99 2402
18.0 4.35 2.21 2.66 3.10 3.56 2472 18.0 4.71 2.46 2.96 3.45 3.95 2497
50
19.5 4.47 1.83 2.26 2.70 3.13 2513 19.5 4.84 2.04 2.52 3.01 3.48 2538
22.0 4.82 - 1.74 2.16 2.66 2605 22.0 5.22 - 1.93 2.40 2.96 2631

OR*C025A6 OR*C030A6
HWC024 HWC030B
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 6.67 4.10 4.61 5.13 5.70 2128 16.0 8.70 5.18 5.83 6.48 7.20 2837
18.0 7.05 3.35 3.88 4.40 4.96 2225 18.0 9.19 4.23 4.89 5.56 6.26 2966
25
19.5 7.25 2.83 3.36 3.91 4.44 2271 19.5 9.45 3.57 4.24 4.93 5.61 3028
22.0 7.84 - 2.64 3.18 3.74 2373 22.0 10.22 - 3.33 4.02 4.73 3164
16.0 6.44 3.98 4.50 5.04 5.61 2344 16.0 8.39 5.03 5.69 6.36 7.08 3125
18.0 6.80 3.24 3.77 4.30 4.86 2441 18.0 8.87 4.09 4.77 5.44 6.14 3254
30
19.5 6.99 2.73 3.26 3.81 4.34 2487 19.5 9.12 3.45 4.12 4.81 5.48 3316
22.0 7.54 - 2.55 3.09 3.65 2589 22.0 9.83 - 3.22 3.91 4.61 3452
16.0 6.20 3.87 4.41 4.93 5.27 2543 16.0 8.09 4.89 5.56 6.23 6.65 3391
18.0 6.56 3.14 3.68 4.21 4.76 2646 18.0 8.55 3.97 4.65 5.31 6.01 3528
35
19.5 6.74 2.64 3.17 3.72 4.25 2700 19.5 8.79 3.33 4.00 4.69 5.36 3600
22.0 7.27 - 2.47 3.01 3.56 2805 22.0 9.48 - 3.12 3.80 4.49 3740
16.0 5.93 3.76 4.30 4.84 5.02 2773 16.0 7.73 4.74 5.43 6.11 6.34 3697
18.0 6.27 3.04 3.58 4.11 4.67 2878 18.0 8.18 3.83 4.52 5.19 5.90 3838
40
19.5 6.44 2.54 3.07 3.61 4.14 2932 19.5 8.40 3.20 3.87 4.56 5.23 3910
22.0 6.95 - 2.38 2.91 3.45 3048 22.0 9.06 - 3.01 3.67 4.36 4064
16.0 5.58 3.54 4.18 4.73 4.81 3000 16.0 7.28 4.48 5.27 5.97 6.08 4000
18.0 5.90 2.91 3.45 3.99 4.56 3116 18.0 7.70 3.67 4.36 5.04 5.76 4154
46
19.5 6.07 2.42 2.95 3.49 4.03 3170 19.5 7.91 3.05 3.72 4.41 5.08 4226
22.0 6.54 - 2.28 2.80 3.34 3283 22.0 8.53 - 2.87 3.54 4.22 4378
16.0 5.27 3.32 4.04 4.36 4.49 3243 16.0 6.87 4.20 5.11 5.50 5.67 4324
18.0 5.55 2.77 3.33 3.88 4.45 3371 18.0 7.24 3.49 4.20 4.90 5.62 4495
50
19.5 5.70 2.29 2.83 3.38 3.91 3427 19.5 7.44 2.89 3.57 4.27 4.94 4569
22.0 6.15 - 2.17 2.70 3.32 3552 22.0 8.02 - 2.74 3.41 4.20 4737

6-13
OR*C036A6
HWC036B
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption
0 0
C C KW 21 23 25 27 W
16.0 10.15 6.24 7.02 7.81 8.68 3613
18.0 10.73 5.10 5.90 6.70 7.55 3778
25
19.5 11.03 4.31 5.12 5.95 6.76 3856
22.0 11.93 - 4.02 4.85 5.70 4030
16.0 9.80 6.06 6.86 7.66 8.54 3980
18.0 10.36 4.93 5.75 6.55 7.41 4145
30
19.5 10.64 4.16 4.96 5.80 6.61 4223
22.0 11.48 - 3.88 4.71 5.55 4397
16.0 9.44 5.89 6.71 7.51 8.02 4319
18.0 9.98 4.79 5.60 6.41 7.24 4493
35
19.5 10.26 4.02 4.83 5.66 6.46 4585
22.0 11.06 - 3.77 4.58 5.42 4764
16.0 9.03 5.72 6.55 7.36 7.65 4709
18.0 9.54 4.62 5.44 6.25 7.11 4888
40
19.5 9.81 3.86 4.67 5.50 6.30 4979
22.0 10.57 - 3.62 4.43 5.26 5176
16.0 8.50 5.40 6.36 7.19 7.33 5094
18.0 8.98 4.42 5.26 6.08 6.95 5291
46
19.5 9.23 3.68 4.49 5.32 6.13 5383
22.0 9.95 - 3.47 4.27 5.09 5575
16.0 8.02 5.06 6.16 6.63 6.84 5507
18.0 8.45 4.21 5.07 5.91 6.77 5725
50
19.5 8.68 3.49 4.31 5.15 5.96 5819
22.0 9.36 - 3.31 4.11 5.06 6033

6-14
b- HIGH WALL TYPE G+
OR*C009A4 OR*C010A6
HWC009N4 HWC009N6
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 2.61 1.72 1.94 2.15 2.39 867 16.0 2.75 1.82 2.05 2.28 2.54 827
18.0 2.76 1.41 1.63 1.85 2.08 906 18.0 2.91 1.49 1.73 1.96 2.21 865
25
19.5 2.84 1.19 1.41 1.64 1.86 925 19.5 2.99 1.26 1.50 1.74 1.98 883
22.0 3.07 - 1.11 1.34 1.57 967 22.0 3.23 - 1.17 1.42 1.67 923
16.0 2.52 1.67 1.89 2.11 2.35 955 16.0 2.65 1.77 2.01 2.24 2.50 911
18.0 2.67 1.36 1.58 1.81 2.04 994 18.0 2.81 1.44 1.68 1.92 2.17 949
30
19.5 2.74 1.15 1.37 1.60 1.82 1013 19.5 2.88 1.22 1.45 1.70 1.93 967
22.0 2.95 - 1.07 1.30 1.53 1055 22.0 3.11 - 1.14 1.38 1.62 1007
16.0 2.43 1.62 1.85 2.07 2.21 1036 16.0 2.56 1.72 1.96 2.20 2.34 989
18.0 2.57 1.32 1.54 1.77 2.00 1078 18.0 2.70 1.40 1.64 1.87 2.12 1029
35
19.5 2.64 1.11 1.33 1.56 1.78 1100 19.5 2.78 1.18 1.41 1.65 1.89 1050
22.0 2.85 - 1.04 1.26 1.49 1143 22.0 3.00 - 1.10 1.34 1.58 1091
16.0 2.32 1.58 1.81 2.03 2.11 1130 16.0 2.45 1.67 1.92 2.15 2.24 1078
18.0 2.46 1.27 1.50 1.72 1.96 1173 18.0 2.59 1.35 1.59 1.83 2.08 1119
40
19.5 2.52 1.07 1.29 1.52 1.74 1195 19.5 2.66 1.13 1.37 1.61 1.84 1140
22.0 2.72 - 1.00 1.22 1.45 1242 22.0 2.86 - 1.06 1.30 1.54 1185
16.0 2.19 1.49 1.75 1.98 2.02 1222 16.0 2.30 1.58 1.86 2.10 2.14 1167
18.0 2.31 1.22 1.45 1.68 1.92 1269 18.0 2.43 1.29 1.54 1.78 2.03 1212
46
19.5 2.38 1.01 1.24 1.47 1.69 1291 19.5 2.50 1.08 1.31 1.56 1.79 1233
22.0 2.56 - 0.96 1.18 1.40 1338 22.0 2.70 - 1.01 1.25 1.49 1277
16.0 2.06 1.39 1.70 1.83 1.89 1321 16.0 2.17 1.48 1.80 1.94 2.00 1261
18.0 2.17 1.16 1.40 1.63 1.87 1373 18.0 2.29 1.23 1.48 1.73 1.98 1311
50
19.5 2.23 0.96 1.19 1.42 1.64 1396 19.5 2.35 1.02 1.26 1.51 1.74 1333
22.0 2.41 - 0.91 1.13 1.40 1447 22.0 2.54 - 0.97 1.20 1.48 1381

OR*C012,A6 OR*C018,A6
HWC012N HWC020N
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 3.48 2.28 2.56 2.85 3.17 1017 16.0 5.22 3.21 3.61 4.02 4.47 1560
18.0 3.68 1.86 2.15 2.44 2.76 1063 18.0 5.52 2.62 3.04 3.45 3.89 1632
25
19.5 3.78 1.57 1.87 2.17 2.47 1085 19.5 5.68 2.22 2.63 3.06 3.48 1665
22.0 4.09 - 1.47 1.77 2.08 1134 22.0 6.14 - 2.07 2.49 2.93 1740
16.0 3.36 2.21 2.50 2.80 3.11 1120 16.0 5.04 3.12 3.53 3.94 4.39 1719
18.0 3.55 1.80 2.10 2.39 2.70 1166 18.0 5.33 2.54 2.96 3.37 3.81 1790
30
19.5 3.65 1.52 1.81 2.12 2.41 1188 19.5 5.48 2.14 2.55 2.98 3.40 1824
22.0 3.94 - 1.42 1.72 2.03 1237 22.0 5.91 - 2.00 2.42 2.86 1899
16.0 3.24 2.15 2.45 2.74 2.92 1215 16.0 4.86 3.03 3.45 3.86 4.12 1865
18.0 3.42 1.75 2.04 2.34 2.64 1264 18.0 5.14 2.46 2.88 3.30 3.73 1940
35
19.5 3.52 1.47 1.76 2.06 2.36 1290 19.5 5.28 2.07 2.48 2.91 3.33 1980
22.0 3.79 - 1.37 1.67 1.98 1340 22.0 5.69 - 1.94 2.36 2.79 2057
16.0 3.10 2.09 2.39 2.69 2.79 1325 16.0 4.65 2.94 3.37 3.79 3.94 2033
18.0 3.27 1.69 1.99 2.28 2.60 1375 18.0 4.91 2.38 2.80 3.22 3.66 2111
40
19.5 3.37 1.41 1.70 2.01 2.30 1401 19.5 5.05 1.99 2.40 2.83 3.24 2150
22.0 3.63 - 1.32 1.62 1.92 1456 22.0 5.44 - 1.87 2.28 2.70 2235
16.0 2.92 1.97 2.32 2.62 2.67 1433 16.0 4.37 2.78 3.27 3.70 3.77 2200
18.0 3.08 1.61 1.92 2.22 2.53 1489 18.0 4.62 2.28 2.71 3.13 3.58 2285
46
19.5 3.17 1.34 1.64 1.94 2.24 1514 19.5 4.75 1.89 2.31 2.74 3.15 2325
22.0 3.42 - 1.26 1.56 1.86 1569 22.0 5.12 - 1.78 2.20 2.62 2408
16.0 2.75 1.85 2.25 2.42 2.50 1549 16.0 4.13 2.60 3.17 3.41 3.52 2378
18.0 2.90 1.54 1.85 2.16 2.47 1611 18.0 4.35 2.17 2.61 3.04 3.48 2472
50
19.5 2.98 1.27 1.57 1.88 2.17 1637 19.5 4.47 1.79 2.22 2.65 3.07 2513
22.0 3.21 - 1.21 1.50 1.85 1697 22.0 4.82 - 1.70 2.11 2.60 2605

6-15
OR*C020A6 OR*C025A6
HWC020N HWC024N
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 5.66 3.55 4.00 4.44 4.94 1576 16.0 6.67 4.29 4.83 5.37 5.97 2128
18.0 5.98 2.90 3.36 3.81 4.30 1648 18.0 7.05 3.51 4.06 4.61 5.20 2225
25
19.5 6.15 2.45 2.91 3.38 3.85 1682 19.5 7.25 2.96 3.52 4.09 4.65 2271
22.0 6.65 - 2.28 2.76 3.24 1758 22.0 7.84 - 2.76 3.34 3.92 2373
16.0 5.46 3.45 3.90 4.36 4.86 1736 16.0 6.44 4.17 4.72 5.27 5.87 2344
18.0 5.77 2.81 3.27 3.73 4.21 1808 18.0 6.80 3.39 3.95 4.51 5.10 2441
30
19.5 5.93 2.36 2.82 3.30 3.76 1842 19.5 6.99 2.86 3.42 3.99 4.55 2487
22.0 6.40 - 2.21 2.68 3.16 1918 22.0 7.54 - 2.67 3.24 3.82 2589
16.0 5.26 3.35 3.82 4.27 4.56 1884 16.0 6.20 4.06 4.62 5.17 5.52 2543
18.0 5.57 2.72 3.19 3.64 4.12 1960 18.0 6.56 3.29 3.85 4.41 4.98 2646
35
19.5 5.72 2.29 2.75 3.22 3.68 2000 19.5 6.74 2.77 3.32 3.89 4.45 2700
22.0 6.17 - 2.14 2.61 3.08 2078 22.0 7.27 - 2.59 3.15 3.73 2805
16.0 5.03 3.25 3.73 4.19 4.35 2054 16.0 5.93 3.94 4.51 5.07 5.26 2773
18.0 5.32 2.63 3.10 3.56 4.05 2132 18.0 6.27 3.18 3.75 4.30 4.90 2878
40
19.5 5.47 2.20 2.66 3.13 3.59 2172 19.5 6.44 2.66 3.21 3.78 4.34 2932
22.0 5.89 - 2.06 2.52 2.99 2258 22.0 6.95 - 2.49 3.05 3.62 3048
16.0 4.74 3.07 3.62 4.09 4.17 2222 16.0 5.58 3.71 4.37 4.95 5.04 3000
18.0 5.01 2.52 2.99 3.46 3.95 2308 18.0 5.90 3.04 3.62 4.18 4.78 3116
46
19.5 5.15 2.09 2.55 3.03 3.49 2348 19.5 6.07 2.53 3.09 3.66 4.22 3170
22.0 5.55 - 1.97 2.43 2.89 2432 22.0 6.54 - 2.39 2.94 3.50 3283
16.0 4.47 2.88 3.50 3.77 3.89 2402 16.0 5.27 3.48 4.24 4.56 4.71 3243
18.0 4.71 2.40 2.88 3.36 3.85 2497 18.0 5.55 2.90 3.49 4.07 4.66 3371
50
19.5 4.84 1.98 2.45 2.93 3.39 2538 19.5 5.70 2.40 2.96 3.54 4.10 3427
22.0 5.22 - 1.88 2.34 2.88 2631 22.0 6.15 - 2.28 2.83 3.48 3552

6-16
c- CEILING FLOOR TYPE
OR*C012 OR*C020
CFU012 CFU020
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 3.48 2.24 2.52 2.81 3.12 1017 16.0 5.66 3.75 4.23 4.70 5.22 1576
18.0 3.68 1.83 2.12 2.41 2.71 1063 18.0 5.98 3.07 3.55 4.03 4.54 1648
25
19.5 3.78 1.55 1.84 2.14 2.43 1085 19.5 6.15 2.59 3.08 3.58 4.07 1682
22.0 4.09 - 1.44 1.74 2.05 1134 22.0 6.65 - 2.42 2.92 3.43 1758
16.0 3.36 2.18 2.46 2.75 3.07 1120 16.0 5.46 3.65 4.13 4.61 5.14 1736
18.0 3.55 1.77 2.07 2.36 2.66 1166 18.0 5.77 2.97 3.46 3.94 4.46 1808
30
19.5 3.65 1.49 1.78 2.08 2.38 1188 19.5 5.93 2.50 2.99 3.49 3.98 1842
22.0 3.94 - 1.40 1.69 2.00 1237 22.0 6.40 - 2.34 2.83 3.34 1918
16.0 3.24 2.12 2.41 2.70 2.88 1215 16.0 5.26 3.55 4.04 4.52 4.82 1884
18.0 3.42 1.72 2.01 2.30 2.60 1264 18.0 5.57 2.88 3.37 3.85 4.36 1960
35
19.5 3.52 1.44 1.74 2.03 2.32 1290 19.5 5.72 2.42 2.91 3.40 3.89 2000
22.0 3.79 - 1.35 1.65 1.95 1340 22.0 6.17 - 2.27 2.76 3.26 2078
16.0 3.10 2.06 2.35 2.65 2.75 1325 16.0 5.03 3.44 3.94 4.43 4.60 2054
18.0 3.27 1.66 1.96 2.25 2.56 1375 18.0 5.32 2.78 3.28 3.76 4.28 2132
40
19.5 3.37 1.39 1.68 1.98 2.27 1401 19.5 5.47 2.32 2.81 3.31 3.79 2172
22.0 3.63 - 1.30 1.59 1.89 1456 22.0 5.89 - 2.18 2.67 3.16 2258
16.0 2.92 1.94 2.28 2.59 2.63 1433 16.0 4.74 3.25 3.82 4.33 4.41 2222
18.0 3.08 1.59 1.89 2.18 2.50 1489 18.0 5.01 2.66 3.16 3.66 4.18 2308
46
19.5 3.17 1.32 1.61 1.91 2.20 1514 19.5 5.15 2.22 2.70 3.20 3.69 2348
22.0 3.42 - 1.25 1.53 1.83 1569 22.0 5.55 - 2.09 2.57 3.06 2432
16.0 2.75 1.82 2.21 2.38 2.46 1549 16.0 4.47 3.04 3.71 3.99 4.12 2402
18.0 2.90 1.51 1.82 2.12 2.43 1611 18.0 4.71 2.53 3.05 3.56 4.07 2497
50
19.5 2.98 1.25 1.55 1.85 2.14 1637 19.5 4.84 2.10 2.59 3.10 3.59 2538
22.0 3.21 - 1.19 1.48 1.82 1697 22.0 5.22 - 1.99 2.47 3.05 2631

OR*C025 OR*C030
CFU024 CFU030
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 6.67 4.10 4.61 5.13 5.70 2128 16.0 8.70 5.58 6.28 6.99 7.77 2916
18.0 7.05 3.35 3.88 4.40 4.96 2225 18.0 9.19 4.56 5.28 5.99 6.76 3049
25
19.5 7.25 2.83 3.36 3.91 4.44 2271 19.5 9.45 3.85 4.58 5.32 6.05 3112
22.0 7.84 - 2.64 3.18 3.74 2373 22.0 10.22 - 3.59 4.34 5.10 3252
16.0 6.44 3.98 4.50 5.04 5.61 2344 16.0 8.39 5.42 6.14 6.86 7.64 3212
18.0 6.80 3.24 3.77 4.30 4.86 2441 18.0 8.87 4.41 5.14 5.86 6.63 3345
30
19.5 6.99 2.73 3.26 3.81 4.34 2487 19.5 9.12 3.72 4.44 5.19 5.91 3408
22.0 7.54 - 2.55 3.09 3.65 2589 22.0 9.83 - 3.47 4.21 4.97 3548
16.0 6.20 3.87 4.41 4.93 5.27 2543 16.0 8.09 5.27 6.00 6.72 7.17 3485
18.0 6.56 3.14 3.68 4.21 4.76 2646 18.0 8.55 4.28 5.01 5.73 6.48 3626
35
19.5 6.74 2.64 3.17 3.72 4.25 2700 19.5 8.79 3.60 4.32 5.06 5.78 3700
22.0 7.27 - 2.47 3.01 3.56 2805 22.0 9.48 - 3.37 4.10 4.85 3844
16.0 5.93 3.76 4.30 4.84 5.02 2773 16.0 7.73 5.12 5.86 6.59 6.84 3800
18.0 6.27 3.04 3.58 4.11 4.67 2878 18.0 8.18 4.13 4.87 5.59 6.36 3944
40
19.5 6.44 2.54 3.07 3.61 4.14 2932 19.5 8.40 3.46 4.18 4.92 5.64 4018
22.0 6.95 - 2.38 2.91 3.45 3048 22.0 9.06 - 3.24 3.96 4.70 4177
16.0 5.58 3.54 4.18 4.73 4.81 3000 16.0 7.28 4.83 5.69 6.44 6.56 4111
18.0 5.90 2.91 3.45 3.99 4.56 3116 18.0 7.70 3.96 4.70 5.44 6.22 4270
46
19.5 6.07 2.42 2.95 3.49 4.03 3170 19.5 7.91 3.29 4.02 4.76 5.48 4344
22.0 6.54 - 2.28 2.80 3.34 3283 22.0 8.53 - 3.10 3.82 4.55 4499
16.0 5.27 3.32 4.04 4.36 4.49 3243 16.0 6.87 4.53 5.51 5.94 6.12 4444
18.0 5.55 2.77 3.33 3.88 4.45 3371 18.0 7.24 3.77 4.53 5.29 6.06 4620
50
19.5 5.70 2.29 2.83 3.38 3.91 3427 19.5 7.44 3.12 3.85 4.61 5.33 4696
22.0 6.15 - 2.17 2.70 3.32 3552 22.0 8.02 - 2.96 3.68 4.53 4868

6-17
OR*C036
CFU036
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption
0 0
C C KW 21 23 25 27 W
16.0 10.15 6.39 7.19 7.99 8.89 3782
18.0 10.73 5.22 6.04 6.86 7.73 3955
25
19.5 11.03 4.41 5.24 6.09 6.92 4037
22.0 11.93 - 4.11 4.96 5.83 4219
16.0 9.80 6.21 7.02 7.85 8.74 4166
18.0 10.36 5.05 5.88 6.71 7.58 4339
30
19.5 10.64 4.25 5.08 5.94 6.77 4421
22.0 11.48 - 3.97 4.82 5.68 4603
16.0 9.44 6.03 6.87 7.69 8.21 4522
18.0 9.98 4.90 5.73 6.56 7.41 4704
35
19.5 10.26 4.12 4.94 5.79 6.62 4800
22.0 11.06 - 3.86 4.69 5.55 4987
16.0 9.03 5.86 6.71 7.54 7.83 4930
18.0 9.54 4.73 5.57 6.40 7.28 5117
40
19.5 9.81 3.96 4.78 5.63 6.45 5213
22.0 10.57 - 3.71 4.53 5.38 5419
16.0 8.50 5.52 6.51 7.36 7.50 5333
18.0 8.98 4.53 5.38 6.22 7.11 5539
46
19.5 9.23 3.77 4.60 5.45 6.27 5635
22.0 9.95 - 3.55 4.37 5.21 5837
16.0 8.02 5.18 6.30 6.79 7.00 5765
18.0 8.45 4.31 5.19 6.05 6.93 5993
50
19.5 8.68 3.57 4.41 5.27 6.10 6092
22.0 9.36 - 3.39 4.21 5.18 6315

6-18
d- DUCTD TYPE
OR*C020 OR*C020
DBC018 DBC020
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 5.21 3.43 3.87 4.30 4.78 1626 16.0 5.68 3.80 4.27 4.75 5.28 1697
18.0 5.51 2.81 3.25 3.69 4.16 1700 18.0 6.00 3.10 3.59 4.07 4.59 1775
25
19.5 5.67 2.37 2.82 3.27 3.72 1735 19.5 6.17 2.62 3.11 3.62 4.11 1812
22.0 6.13 - 2.21 2.67 3.14 1813 22.0 6.68 - 2.44 2.95 3.47 1893
16.0 5.03 3.34 3.77 4.22 4.70 1791 16.0 5.48 3.69 4.17 4.66 5.19 1870
18.0 5.32 2.71 3.16 3.61 4.08 1865 18.0 5.79 3.00 3.50 3.99 4.50 1947
30
19.5 5.47 2.29 2.73 3.19 3.64 1900 19.5 5.96 2.53 3.02 3.53 4.02 1984
22.0 5.89 - 2.14 2.59 3.06 1978 22.0 6.42 - 2.36 2.86 3.38 2066
16.0 4.85 3.24 3.69 4.13 4.41 1943 16.0 5.28 3.59 4.08 4.57 4.88 2029
18.0 5.13 2.63 3.08 3.53 3.98 2022 18.0 5.59 2.91 3.41 3.90 4.40 2111
35
19.5 5.27 2.21 2.66 3.11 3.56 2063 19.5 5.74 2.45 2.94 3.44 3.93 2154
22.0 5.68 - 2.07 2.52 2.98 2143 22.0 6.19 - 2.29 2.79 3.29 2238
16.0 4.64 3.15 3.61 4.05 4.21 2119 16.0 5.05 3.48 3.99 4.48 4.65 2212
18.0 4.90 2.54 3.00 3.44 3.91 2199 18.0 5.34 2.81 3.31 3.80 4.33 2296
40
19.5 5.04 2.13 2.57 3.02 3.47 2240 19.5 5.49 2.35 2.84 3.34 3.83 2339
22.0 5.43 - 1.99 2.44 2.89 2329 22.0 5.92 - 2.20 2.69 3.20 2432
16.0 4.37 2.97 3.50 3.96 4.03 2292 16.0 4.76 3.28 3.87 4.38 4.46 2393
18.0 4.61 2.43 2.89 3.35 3.82 2381 18.0 5.03 2.69 3.20 3.70 4.23 2486
46
19.5 4.74 2.03 2.47 2.93 3.37 2422 19.5 5.17 2.24 2.73 3.24 3.73 2529
22.0 5.11 - 1.91 2.35 2.80 2509 22.0 5.57 - 2.11 2.59 3.09 2619
16.0 4.12 2.78 3.39 3.65 3.76 2478 16.0 4.49 3.08 3.75 4.03 4.16 2587
18.0 4.34 2.32 2.79 3.25 3.73 2576 18.0 4.72 2.56 3.08 3.60 4.12 2690
50
19.5 4.46 1.92 2.37 2.83 3.28 2618 19.5 4.86 2.12 2.62 3.13 3.62 2734
22.0 4.81 - 1.82 2.26 2.79 2714 22.0 5.23 - 2.01 2.50 3.08 2834

OR*C025 OR*C025
DBC024 DBC024*
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 6.96 4.58 5.16 5.73 6.37 2067 16.0 7.48 5.00 5.63 6.25 6.95 2280
18.0 7.35 3.74 4.33 4.92 5.54 2161 18.0 7.91 4.08 4.73 5.37 6.05 2384
25
19.5 7.56 3.16 3.76 4.37 4.96 2206 19.5 8.13 3.45 4.10 4.77 5.42 2433
22.0 8.18 - 2.95 3.56 4.18 2306 22.0 8.79 - 3.22 3.88 4.57 2543
16.0 6.71 4.45 5.03 5.63 6.27 2277 16.0 7.22 4.86 5.49 6.14 6.84 2511
18.0 7.10 3.62 4.22 4.81 5.44 2371 18.0 7.63 3.95 4.60 5.25 5.93 2615
30
19.5 7.29 3.05 3.64 4.26 4.85 2416 19.5 7.84 3.33 3.98 4.65 5.30 2664
22.0 7.86 - 2.85 3.46 4.08 2515 22.0 8.46 - 3.11 3.77 4.45 2774
16.0 6.47 4.33 4.92 5.51 5.88 2471 16.0 6.96 4.72 5.37 6.02 6.42 2725
18.0 6.84 3.51 4.11 4.70 5.31 2571 18.0 7.36 3.83 4.49 5.13 5.80 2835
35
19.5 7.03 2.95 3.54 4.15 4.75 2623 19.5 7.56 3.22 3.87 4.53 5.18 2893
22.0 7.58 - 2.76 3.36 3.98 2725 22.0 8.15 - 3.02 3.67 4.34 3006
16.0 6.19 4.20 4.81 5.41 5.61 2694 16.0 6.65 4.58 5.25 5.90 6.13 2971
18.0 6.54 3.39 4.00 4.59 5.22 2796 18.0 7.03 3.70 4.36 5.01 5.70 3084
40
19.5 6.72 2.84 3.43 4.03 4.63 2849 19.5 7.23 3.09 3.74 4.40 5.05 3142
22.0 7.24 - 2.66 3.25 3.86 2961 22.0 7.79 - 2.90 3.55 4.21 3266
16.0 5.82 3.96 4.67 5.28 5.38 2914 16.0 6.26 4.32 5.09 5.76 5.87 3214
18.0 6.16 3.25 3.86 4.46 5.10 3027 18.0 6.62 3.54 4.21 4.87 5.57 3339
46
19.5 6.33 2.70 3.30 3.90 4.50 3079 19.5 6.80 2.95 3.60 4.26 4.91 3396
22.0 6.82 - 2.54 3.13 3.73 3190 22.0 7.33 - 2.78 3.42 4.07 3518
16.0 5.50 3.71 4.52 4.87 5.02 3150 16.0 5.91 4.05 4.93 5.31 5.48 3474
18.0 5.79 3.09 3.72 4.34 4.97 3275 18.0 6.22 3.37 4.06 4.73 5.42 3612
50
19.5 5.95 2.56 3.16 3.78 4.37 3329 19.5 6.40 2.79 3.45 4.12 4.77 3671
22.0 6.41 - 2.43 3.02 3.72 3451 22.0 6.89 - 2.65 3.29 4.06 3806

6-19
OR*C030 OR*C036
DBC030 DBC036
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 8.91 5.91 6.65 7.39 8.22 2595 16.0 10.38 6.75 7.60 8.45 9.40 3205
18.0 9.41 4.83 5.59 6.34 7.15 2713 18.0 10.97 5.52 6.39 7.25 8.17 3351
25
19.5 9.68 4.08 4.84 5.63 6.40 2769 19.5 11.28 4.66 5.54 6.44 7.32 3420
22.0 10.47 - 3.80 4.59 5.39 2895 22.0 12.20 - 4.35 5.25 6.17 3575
16.0 8.59 5.74 6.49 7.26 8.08 2858 16.0 10.02 6.56 7.42 8.30 9.24 3530
18.0 9.09 4.67 5.44 6.20 7.01 2977 18.0 10.59 5.34 6.22 7.09 8.02 3677
30
19.5 9.34 3.93 4.70 5.49 6.26 3033 19.5 10.88 4.50 5.37 6.28 7.15 3746
22.0 10.07 - 3.68 4.46 5.26 3158 22.0 11.73 - 4.20 5.10 6.01 3900
16.0 8.28 5.58 6.35 7.11 7.59 3102 16.0 9.65 6.38 7.26 8.13 8.68 3831
18.0 8.76 4.53 5.30 6.06 6.85 3227 18.0 10.21 5.18 6.06 6.93 7.84 3986
35
19.5 9.00 3.81 4.57 5.36 6.12 3293 19.5 10.49 4.35 5.23 6.12 7.00 4067
22.0 9.70 - 3.57 4.34 5.13 3421 22.0 11.31 - 4.08 4.96 5.86 4226
16.0 7.92 5.41 6.20 6.97 7.24 3382 16.0 9.23 6.19 7.09 7.97 8.28 4177
18.0 8.37 4.38 5.15 5.92 6.73 3510 18.0 9.76 5.00 5.89 6.77 7.70 4335
40
19.5 8.60 3.66 4.42 5.20 5.97 3576 19.5 10.03 4.18 5.06 5.95 6.82 4417
22.0 9.28 - 3.43 4.19 4.98 3718 22.0 10.81 - 3.92 4.79 5.69 4592
16.0 7.46 5.11 6.02 6.81 6.94 3659 16.0 8.69 5.84 6.88 7.79 7.93 4518
18.0 7.88 4.19 4.98 5.76 6.58 3800 18.0 9.19 4.79 5.69 6.58 7.52 4693
46
19.5 8.10 3.49 4.25 5.04 5.80 3866 19.5 9.44 3.98 4.86 5.76 6.63 4775
22.0 8.73 - 3.28 4.04 4.82 4004 22.0 10.18 - 3.75 4.62 5.51 4945
16.0 7.04 4.79 5.83 6.28 6.48 3955 16.0 8.20 5.48 6.67 7.18 7.40 4884
18.0 7.41 3.99 4.80 5.60 6.41 4112 18.0 8.63 4.56 5.49 6.40 7.33 5078
50
19.5 7.61 3.30 4.08 4.87 5.64 4179 19.5 8.87 3.77 4.66 5.57 6.45 5161
22.0 8.21 - 3.13 3.89 4.79 4333 22.0 9.57 - 3.58 4.45 5.48 5351

OR*C050 OR*C060
DBC048 DBC060
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 13.77 8.64 9.73 10.81 12.02 4236 16.0 17.40 11.71 13.18 14.65 16.29 5381
18.0 14.56 7.06 8.17 9.28 10.46 4429 18.0 18.39 9.57 11.07 12.57 14.17 5627
25
19.5 14.96 5.96 7.08 8.24 9.36 4520 19.5 18.90 8.08 9.60 11.16 12.68 5743
22.0 16.19 - 5.56 6.71 7.89 4725 22.0 20.45 - 7.54 9.10 10.69 6003
16.0 13.29 8.40 9.49 10.61 11.82 4666 16.0 16.79 11.38 12.87 14.38 16.02 5928
18.0 14.05 6.83 7.96 9.07 10.25 4859 18.0 17.75 9.26 10.78 12.30 13.90 6173
30
19.5 14.44 5.75 6.87 8.03 9.15 4950 19.5 18.24 7.80 9.32 10.88 12.40 6290
22.0 15.57 - 5.38 6.52 7.69 5155 22.0 19.66 - 7.29 8.84 10.42 6549
16.0 12.81 8.16 9.29 10.40 11.10 5063 16.0 16.17 11.06 12.59 14.09 15.04 6433
18.0 13.54 6.63 7.76 8.87 10.02 5268 18.0 17.11 8.98 10.51 12.02 13.59 6692
35
19.5 13.92 5.57 6.69 7.83 8.95 5375 19.5 17.58 7.54 9.06 10.61 12.13 6829
22.0 15.01 - 5.21 6.34 7.50 5585 22.0 18.95 - 7.07 8.60 10.17 7095
16.0 12.25 7.92 9.07 10.20 10.59 5520 16.0 15.47 10.73 12.29 13.82 14.35 7013
18.0 12.95 6.40 7.54 8.66 9.85 5730 18.0 16.35 8.67 10.22 11.73 13.35 7280
40
19.5 13.31 5.35 6.47 7.61 8.73 5837 19.5 16.81 7.25 8.77 10.31 11.83 7416
22.0 14.35 - 5.02 6.13 7.28 6068 22.0 18.12 - 6.80 8.31 9.86 7710
16.0 11.53 7.47 8.80 9.96 10.15 5972 16.0 14.56 10.13 11.93 13.50 13.75 7587
18.0 12.19 6.13 7.28 8.42 9.62 6203 18.0 15.39 8.30 9.86 11.41 13.04 7881
46
19.5 12.53 5.10 6.22 7.37 8.49 6310 19.5 15.82 6.91 8.42 9.98 11.50 8017
22.0 13.51 - 4.80 5.91 7.04 6536 22.0 17.06 - 6.50 8.01 9.54 8304
16.0 10.89 7.01 8.53 9.19 9.47 6455 16.0 13.75 9.50 11.56 12.45 12.83 8202
18.0 11.46 5.83 7.02 8.18 9.38 6711 18.0 14.47 7.90 9.51 11.09 12.71 8527
50
19.5 11.78 4.83 5.96 7.13 8.25 6821 19.5 14.87 6.54 8.08 9.66 11.18 8667
22.0 12.69 - 4.58 5.69 7.01 7072 22.0 16.03 - 6.21 7.71 9.50 8985

6-20
e- CASSETTE TYPE
OR*C020 OR*C025
CAS024 CAS024
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0 C) Consumption WBT Capacity at entering DBT (0 C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 5.68 3.63 4.09 4.55 5.06 1663 16.0 6.67 4.29 4.83 5.37 5.97 1938
18.0 6.00 2.97 3.44 3.90 4.40 1739 18.0 7.05 3.51 4.06 4.61 5.20 2027
25
19.5 6.17 2.51 2.98 3.47 3.94 1775 19.5 7.25 2.96 3.52 4.09 4.65 2069
22.0 6.68 - 2.34 2.82 3.32 1855 22.0 7.84 - 2.76 3.34 3.92 2162
16.0 5.48 3.53 3.99 4.46 4.97 1831 16.0 6.44 4.17 4.72 5.27 5.87 2135
18.0 5.79 2.87 3.35 3.82 4.31 1907 18.0 6.80 3.39 3.95 4.51 5.10 2224
30
19.5 5.96 2.42 2.89 3.38 3.85 1943 19.5 6.99 2.86 3.42 3.99 4.55 2266
22.0 6.42 - 2.26 2.74 3.23 2023 22.0 7.54 - 2.67 3.24 3.82 2359
16.0 5.28 3.43 3.91 4.37 4.67 1988 16.0 6.20 4.06 4.62 5.17 5.52 2317
18.0 5.59 2.79 3.26 3.73 4.22 2068 18.0 6.56 3.29 3.85 4.41 4.98 2411
35
19.5 5.74 2.34 2.81 3.29 3.77 2110 19.5 6.74 2.77 3.32 3.89 4.45 2460
22.0 6.19 - 2.19 2.67 3.16 2192 22.0 7.27 - 2.59 3.15 3.73 2556
16.0 5.05 3.33 3.82 4.29 4.46 2167 16.0 5.93 3.94 4.51 5.07 5.26 2526
18.0 5.34 2.69 3.17 3.64 4.14 2249 18.0 6.27 3.18 3.75 4.30 4.90 2622
40
19.5 5.49 2.25 2.72 3.20 3.67 2291 19.5 6.44 2.66 3.21 3.78 4.34 2672
22.0 5.92 - 2.11 2.58 3.06 2382 22.0 6.95 - 2.49 3.05 3.62 2777
16.0 4.76 3.14 3.70 4.19 4.27 2344 16.0 5.58 3.71 4.37 4.95 5.04 2733
18.0 5.03 2.58 3.06 3.54 4.05 2435 18.0 5.90 3.04 3.62 4.18 4.78 2839
46
19.5 5.17 2.14 2.62 3.10 3.57 2477 19.5 6.07 2.53 3.09 3.66 4.22 2888
22.0 5.57 - 2.02 2.48 2.96 2566 22.0 6.54 - 2.39 2.94 3.50 2991
16.0 4.49 2.95 3.59 3.86 3.98 2534 16.0 5.27 3.48 4.24 4.56 4.71 2954
18.0 4.72 2.45 2.95 3.44 3.94 2635 18.0 5.55 2.90 3.49 4.07 4.66 3072
50
19.5 4.86 2.03 2.51 3.00 3.47 2678 19.5 5.70 2.40 2.96 3.54 4.10 3122
22.0 5.23 - 1.93 2.39 2.95 2776 22.0 6.15 - 2.28 2.83 3.48 3237

OR*C030 OR*C036
CAS048 CAS048
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
0
DBT WBT Capacity at entering DBT ( C) Consumption WBT Capacity at entering DBT (0 C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 8.70 5.81 6.54 7.27 8.09 2638 16.0 10.15 6.78 7.64 8.49 9.44 3168
18.0 9.19 4.75 5.50 6.24 7.03 2759 18.0 10.73 5.54 6.42 7.28 8.21 3312
25
19.5 9.45 4.01 4.77 5.54 6.30 2816 19.5 11.03 4.68 5.56 6.47 7.35 3381
22.0 10.22 - 3.74 4.52 5.31 2943 22.0 11.93 - 4.37 5.27 6.20 3534
16.0 8.39 5.65 6.39 7.14 7.95 2906 16.0 9.80 6.59 7.46 8.33 9.28 3489
18.0 8.87 4.59 5.35 6.10 6.90 3027 18.0 10.36 5.36 6.25 7.13 8.05 3634
30
19.5 9.12 3.87 4.62 5.40 6.16 3084 19.5 10.64 4.52 5.40 6.31 7.19 3702
22.0 9.83 - 3.62 4.39 5.17 3211 22.0 11.48 - 4.22 5.12 6.04 3855
16.0 8.09 5.49 6.25 6.99 7.47 3154 16.0 9.44 6.41 7.29 8.16 8.71 3787
18.0 8.55 4.46 5.22 5.97 6.74 3281 18.0 9.98 5.20 6.09 6.96 7.87 3940
35
19.5 8.79 3.74 4.50 5.27 6.02 3348 19.5 10.26 4.37 5.25 6.15 7.03 4020
22.0 9.48 - 3.51 4.27 5.05 3479 22.0 11.06 - 4.09 4.98 5.89 4177
16.0 7.73 5.33 6.10 6.86 7.12 3438 16.0 9.03 6.22 7.12 8.01 8.32 4129
18.0 8.18 4.30 5.07 5.82 6.63 3569 18.0 9.54 5.02 5.92 6.80 7.73 4285
40
19.5 8.40 3.60 4.35 5.12 5.87 3636 19.5 9.81 4.20 5.08 5.98 6.85 4366
22.0 9.06 - 3.38 4.13 4.90 3780 22.0 10.57 - 3.94 4.82 5.71 4539
16.0 7.28 5.03 5.92 6.70 6.83 3720 16.0 8.50 5.87 6.91 7.82 7.97 4466
18.0 7.70 4.12 4.90 5.66 6.47 3864 18.0 8.98 4.81 5.72 6.61 7.55 4639
46
19.5 7.91 3.43 4.18 4.95 5.71 3931 19.5 9.23 4.00 4.88 5.78 6.66 4719
22.0 8.53 - 3.23 3.97 4.74 4071 22.0 9.95 - 3.77 4.64 5.53 4888
16.0 6.87 4.71 5.74 6.18 6.37 4021 16.0 8.02 5.50 6.70 7.21 7.44 4828
18.0 7.24 3.92 4.72 5.51 6.31 4180 18.0 8.45 4.58 5.51 6.43 7.36 5019
50
19.5 7.44 3.25 4.01 4.80 5.55 4249 19.5 8.68 3.79 4.68 5.60 6.48 5102
22.0 8.02 - 3.08 3.83 4.71 4405 22.0 9.36 - 3.60 4.47 5.50 5289

OR*C050
CAS048
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0 C) Consumption
0 0
C C KW 21 23 25 27 W
16.0 13.49 8.29 9.33 10.37 11.53 4362
18.0 14.26 6.77 7.84 8.90 10.03 4561
25
19.5 14.65 5.72 6.80 7.90 8.98 4655
22.0 15.85 - 5.33 6.44 7.57 4865
16.0 13.02 8.05 9.11 10.18 11.34 4804
18.0 13.76 6.55 7.63 8.71 9.84 5004
30
19.5 14.14 5.52 6.60 7.70 8.78 5098
22.0 15.24 - 5.16 6.26 7.38 5308
16.0 12.54 7.83 8.91 9.98 10.65 5214
18.0 13.26 6.36 7.44 8.51 9.62 5424
35
19.5 13.63 5.34 6.41 7.51 8.59 5535
22.0 14.69 - 5.00 6.09 7.20 5751
16.0 11.99 7.60 8.70 9.78 10.16 5684
18.0 12.68 6.14 7.23 8.31 9.45 5900
40
19.5 13.03 5.13 6.21 7.30 8.37 6011
22.0 14.05 - 4.82 5.88 6.98 6249
16.0 11.29 7.17 8.44 9.56 9.74 6149
18.0 11.94 5.88 6.98 8.08 9.23 6387
46
19.5 12.27 4.89 5.96 7.07 8.14 6498
22.0 13.22 - 4.60 5.67 6.76 6731
16.0 10.66 6.72 8.18 8.81 9.09 6647
18.0 11.22 5.59 6.73 7.85 8.99 6911
50
19.5 11.53 4.63 5.72 6.84 7.91 7024
22.0 12.43 - 4.39 5.46 6.72 7282
6-21
f- FREE STAND TYPE
OR*C020 OR*C025
TFD025 TFD025
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 5.21 3.41 3.84 4.26 4.74 1812 16.0 6.96 4.55 5.12 5.69 6.33 2163
18.0 5.51 2.78 3.22 3.66 4.13 1895 18.0 7.35 3.71 4.30 4.88 5.50 2262
25
19.5 5.67 2.35 2.79 3.25 3.69 1934 19.5 7.56 3.14 3.73 4.33 4.93 2309
22.0 6.13 - 2.19 2.65 3.11 2022 22.0 8.18 - 2.93 3.53 4.15 2413
16.0 5.03 3.31 3.75 4.19 4.66 1996 16.0 6.71 4.42 5.00 5.59 6.22 2383
18.0 5.32 2.69 3.14 3.58 4.05 2079 18.0 7.10 3.59 4.19 4.78 5.40 2481
30
19.5 5.47 2.27 2.71 3.17 3.61 2118 19.5 7.29 3.03 3.62 4.23 4.82 2528
22.0 5.89 - 2.12 2.57 3.03 2206 22.0 7.86 - 2.83 3.43 4.05 2632
16.0 4.85 3.22 3.66 4.10 4.38 2167 16.0 6.47 4.29 4.89 5.47 5.84 2586
18.0 5.13 2.61 3.06 3.50 3.95 2254 18.0 6.84 3.49 4.08 4.67 5.28 2690
35
19.5 5.27 2.20 2.64 3.09 3.53 2300 19.5 7.03 2.93 3.52 4.12 4.71 2745
22.0 5.68 - 2.06 2.50 2.96 2390 22.0 7.58 - 2.74 3.34 3.95 2852
16.0 4.64 3.12 3.58 4.02 4.18 2362 16.0 6.19 4.17 4.77 5.37 5.57 2819
18.0 4.90 2.52 2.97 3.42 3.89 2452 18.0 6.54 3.37 3.97 4.56 5.18 2926
40
19.5 5.04 2.11 2.55 3.00 3.44 2498 19.5 6.72 2.81 3.40 4.00 4.59 2981
22.0 5.43 - 1.98 2.42 2.87 2597 22.0 7.24 - 2.64 3.23 3.83 3099
16.0 4.37 2.95 3.47 3.93 4.00 2555 16.0 5.82 3.93 4.63 5.24 5.34 3050
18.0 4.61 2.42 2.87 3.32 3.80 2654 18.0 6.16 3.22 3.83 4.43 5.06 3168
46
19.5 4.74 2.01 2.45 2.91 3.35 2700 19.5 6.33 2.68 3.27 3.88 4.47 3223
22.0 5.11 - 1.89 2.33 2.78 2797 22.0 6.82 - 2.53 3.11 3.71 3338
16.0 4.12 2.76 3.36 3.62 3.74 2762 16.0 5.50 3.69 4.49 4.83 4.98 3297
18.0 4.34 2.30 2.77 3.23 3.70 2872 18.0 5.79 3.07 3.69 4.31 4.93 3427
50
19.5 4.46 1.90 2.35 2.81 3.25 2919 19.5 5.95 2.54 3.14 3.75 4.34 3484
22.0 4.81 - 1.81 2.24 2.76 3026 22.0 6.41 - 2.41 2.99 3.69 3612

OR*C036 OR*C050
TFD048 TFD048
Outdoor Indoor Gross Cooling Sensible capacity in Btu/hr Unit Indoor Gross Cooling Sensible capacity in Btu/hr Unit
DBT WBT Capacity at entering DBT (0C) Consumption WBT Capacity at entering DBT (0C) Consumption
0 0 0
C C KW 21 23 25 27 W C KW 21 23 25 27 W
16.0 10.44 6.88 7.75 8.61 9.58 3231 16.0 12.47 8.27 9.31 10.35 11.51 4176
18.0 11.04 5.62 6.51 7.39 8.33 3378 18.0 13.18 6.76 7.82 8.88 10.01 4367
25
19.5 11.34 4.75 5.64 6.56 7.46 3448 19.5 13.55 5.71 6.78 7.88 8.96 4457
22.0 12.27 - 4.43 5.35 6.29 3604 22.0 14.66 - 5.32 6.43 7.55 4659
16.0 10.07 6.69 7.57 8.46 9.42 3559 16.0 12.03 8.04 9.09 10.16 11.32 4600
18.0 10.65 5.44 6.34 7.23 8.17 3706 18.0 12.72 6.54 7.62 8.69 9.82 4791
30
19.5 10.95 4.58 5.48 6.40 7.29 3776 19.5 13.07 5.51 6.58 7.69 8.76 4881
22.0 11.80 - 4.28 5.20 6.13 3932 22.0 14.09 - 5.15 6.24 7.36 5083
16.0 9.71 6.50 7.40 8.29 8.84 3862 16.0 11.59 7.81 8.89 9.95 10.62 4993
18.0 10.27 5.28 6.18 7.07 7.99 4018 18.0 12.26 6.34 7.42 8.49 9.60 5194
35
19.5 10.55 4.44 5.33 6.24 7.13 4100 19.5 12.60 5.33 6.40 7.50 8.57 5300
22.0 11.37 - 4.15 5.05 5.98 4260 22.0 13.58 - 4.99 6.07 7.18 5507
16.0 9.28 6.31 7.23 8.13 8.44 4211 16.0 11.09 7.58 8.68 9.76 10.14 5443
18.0 9.81 5.10 6.01 6.90 7.85 4371 18.0 11.72 6.13 7.22 8.29 9.43 5650
40
19.5 10.09 4.26 5.15 6.06 6.95 4453 19.5 12.05 5.12 6.19 7.28 8.35 5756
22.0 10.87 - 4.00 4.89 5.80 4629 22.0 12.99 - 4.80 5.87 6.97 5984
16.0 8.74 5.95 7.01 7.94 8.09 4555 16.0 10.44 7.15 8.43 9.54 9.71 5888
18.0 9.24 4.88 5.80 6.71 7.67 4731 18.0 11.03 5.86 6.97 8.06 9.21 6116
46
19.5 9.50 4.06 4.95 5.87 6.76 4813 19.5 11.34 4.88 5.95 7.05 8.12 6222
22.0 10.24 - 3.82 4.71 5.61 4986 22.0 12.22 - 4.59 5.65 6.74 6445
16.0 8.25 5.58 6.79 7.32 7.55 4924 16.0 9.85 6.71 8.16 8.79 9.07 6365
18.0 8.68 4.64 5.59 6.52 7.47 5119 18.0 10.37 5.58 6.72 7.83 8.97 6618
50
19.5 8.93 3.85 4.75 5.68 6.57 5203 19.5 10.66 4.62 5.71 6.82 7.90 6726
22.0 9.62 - 3.65 4.53 5.58 5394 22.0 11.49 - 4.39 5.45 6.71 6973

6-22
B- HEATING CAPACITY
i- IMPERIAL UNITS
a- HIGH WALL TYPE (CLASSIC)SERIES

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT 14 23 27 36 45 54
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
64 9081 2.68
HWC009*4 / 68 9000 2.64
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009A4 72 8915 2.55
75 8845 2.49
64 9586 2.83
HWC009*6 / 68 9500 2.78
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009,A6 72 9411 2.69
75 9336 2.63
64 12120 2.76
HWC012*4 / 68 12000 2.71
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC012,A4 72 11899 2.61
75 11797 2.55
64 12840 3.30
HWC012*6 / 68 12000 3.09
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC012,A6 72 12102 2.82
75 11976 2.80
64 18180 3.19
HWC020*6 / 68 18000 3.13
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC018,A6 72 17848 3.02
75 17696 2.95
64 19695 3.24
HWC020*6 / 68 19500 3.18
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC020,A6 72 19326 3.06
75 19157 3.00
64 23276 2.87
HWC024*6 / 68 23000 2.81
0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
ORHC025,A6 72 22727 2.72
75 22513 2.64
64 30360 3.10
HWC030*6 / 68 30000 3.03
0.541 0.812 0.646 0.908 0.726 0.940 0.851 0.977 1.10 1.01
ORHC030,A6 72 29644 2.94
75 29365 2.85
64 37481 2.76
HWC036 / 68 37000 2.72
0.545 0.810 0.650 0.890 0.729 0.940 0.850 0.980 1.10 1.00
ORHC036,A6 72 36641 2.65
75 36278 2.58

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-23
b- HIGH WALL TYPE (G+)SERIES

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT 14 23 27 36 45 54
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
64 9081 2.68
HWC009N4 / 68 9000 2.64
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009A4 72 8915 2.55
75 8845 2.49
64 9586 2.83
HWC009N6 / 68 9500 2.78
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009,A6 72 9411 2.69
75 9336 2.63
64 12840 3.42
HWC012N6 / 68 12000 3.20
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC012,A6 72 12102 2.82
75 11976 2.80
64 18180 3.19
HWC020N6 / 68 18000 3.13
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC018,A6 72 17848 3.02
75 17696 2.95
64 19695 3.24
HWC020N6 / 68 19500 3.18
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC020,A6 72 19326 3.06
75 19157 3.00
64 23276 2.87
HWC024N6 / 68 23000 2.81
0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
ORHC025,A6 72 22727 2.72
75 22513 2.64

c- CEILING/FLOOR TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT 14 23 27 36 45 54
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
64 12108 3.25
CFU012*4 / 68 12000 3.20
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC012A4 72 11887 3.09
75 11793 3.02
64 19695 3.24
68 19500 3.18
CFU020/ ORHC020 0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
72 19326 3.06
75 19157 3.00
64 23276 2.87
68 23000 2.81
CFU024/ ORHC025 0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
72 22727 2.72
75 22513 2.64
64 30360 2.90
68 30000 2.84
CFU030/ ORHC030 0.541 0.812 0.646 0.908 0.726 0.940 0.851 0.977 1.10 1.01
72 29644 2.75
75 29365 2.66
64 35455 2.51
68 35000 2.47
CFU036/ ORHC036 0.545 0.810 0.650 0.890 0.729 0.940 0.850 0.980 1.10 1.00
72 34660 2.41
75 34317 2.34

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-24
d- DUCTED TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT 14 23 27 36 45 54
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
64 18162 2.88
DBC018 / 68 18000 2.83
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 72 17831 2.73
75 17689 2.68
64 19776 2.81
DBC020/ 68 19600 2.77
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 72 19416 2.67
75 19261 2.62
64 24240 2.84
DBC024/ 68 24000 2.78
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC025A6 72 23798 2.68
75 23595 2.62
64 27606 3.05
DBC024* / 68 25800 2.85
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC025,A6 72 26019 2.82
75 25748 2.80
64 31108 2.90
DBC030 / 68 30800 2.84
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC030,A6 72 30540 2.74
75 30280 2.68
64 36158 2.74
DBC036 / 68 35800 2.69
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC036,A6 72 35481 2.59
75 35171 2.54
64 48070 2.67
DBC048 / 68 47500 2.61
0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
ORHC050,A6 72 46937 2.53
75 46495 2.45
64 60720 2.73
DBC060 / 68 60000 2.67
0.541 0.812 0.646 0.908 0.726 0.940 0.851 0.977 1.10 1.01
ORHC060,A6 72 59289 2.59
75 58731 2.51

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-25
e- CASSETTE TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT 14 23 27 36 45 54
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
64 19776 3.23
CAS024 / 68 19600 3.18
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 72 19416 3.07
75 19261 3.01
64 23230 2.99
CAS024/ 68 23000 2.93
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC025A6 72 22806 2.83
75 22612 2.77
64 32100 3.24
CAS048 / 68 30000 3.03
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC030,A6 72 30255 2.82
75 29940 2.80
64 35350 3.16
CAS048 / 68 35000 3.10
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC036,A6 72 34705 2.99
75 34409 2.93
64 46965 2.81
CAS048 / 68 46500 2.76
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC050,A6 72 46085 2.66
75 45683 2.60

f- FREE STAND TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT 14 23 27 36 45 54
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
64 19776 2.78
TFD025 / 68 19600 2.74
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 72 19416 2.64
75 19261 2.59
64 24240 2.76
TFD025/ 68 24000 2.71
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC025A6 72 23798 2.61
75 23595 2.56
64 38520 3.75
TFD048 / 68 36000 3.51
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC036,A6 72 36306 2.82
75 35928 2.80
64 44440 2.77
TFD048 / 68 44000 2.71
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC050,A6 72 43608 2.61
75 43227 2.56

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-26
i- SI UNITS
a- HIGH WALL TYPE (CLASSIC)SERIES

o
Indoor Outdoor DBT ( F) & 80 % Relative Humidity
Unit DBT -10 -5 -3 2 7 12
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
18 2.66 2.68
HWC009*4 / 20 2.64 2.64
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009A4 22 2.62 2.55
24 2.59 2.50
18 2.81 2.82
HWC009*6 / 20 2.78 2.78
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009,A6 22 2.75 2.68
24 2.73 2.63
18 3.56 2.76
HWC012*4 / 20 3.52 2.71
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC012,A4 22 3.49 2.61
24 3.46 2.56
18 3.77 3.30
HWC012*6 / 20 3.52 3.09
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC012,A6 22 3.55 2.82
24 3.51 2.80
18 5.33 3.20
HWC020*6 / 20 5.28 3.13
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC018,A6 22 5.24 3.02
24 5.19 2.96
18 5.78 3.24
HWC020*6 / 20 5.72 3.18
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC020,A6 22 5.67 3.06
24 5.62 3.00
18 6.82 2.87
HWC024*6 / 20 6.74 2.81
0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
ORHC025,A6 22 6.66 2.72
24 6.60 2.64
18 8.90 3.09
HWC030*6 / 20 8.79 3.03
0.541 0.812 0.646 0.908 0.726 0.940 0.851 0.977 1.10 1.01
ORHC030,A6 22 8.69 2.94
24 8.60 2.85
18 10.98 2.76
HWC036 / 20 10.84 2.72
0.545 0.810 0.650 0.890 0.729 0.940 0.850 0.980 1.10 1.00
ORHC036,A6 22 10.73 2.65
24 10.63 2.58

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-27
b- HIGH WALL TYPE (G+)SERIES

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT -10 -5 -3 2 7 12
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
18 2.66 2.68
HWC009N4 / 20 2.64 2.64
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009A4 22 2.62 2.55
24 2.59 2.50
18 2.81 2.82
HWC009N6 / 20 2.78 2.78
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC009,A6 22 2.75 2.68
24 2.73 2.63
18 3.77 3.42
HWC012N6 / 20 3.52 3.20
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC012,A6 22 3.55 2.82
24 3.51 2.80
18 5.33 3.20
HWC020N6 / 20 5.28 3.13
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC018,A6 22 5.24 3.02
24 5.19 2.96
18 5.78 3.24
HWC020N6 / 20 5.72 3.18
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC020,A6 22 5.67 3.06
24 5.62 3.00
18 6.82 2.87
HWC024N6 / 20 6.74 2.81
0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
ORHC025,A6 22 6.66 2.72
24 6.60 2.64

c- CEILING/FLOOR TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT -10 -5 -3 2 7 12
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
18 3.55 3.25
CFU012*4 / 20 3.52 3.20
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC012A4 22 3.49 3.09
24 3.46 3.03
18 5.78 3.24
20 5.72 3.18
CFU020/ ORHC020 0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
22 5.67 3.06
24 5.62 3.00
18 6.82 2.87
20 6.74 2.81
CFU024/ ORHC025 0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
22 6.66 2.72
24 6.60 2.64
18 8.90 2.90
20 8.79 2.84
CFU030/ ORHC030 0.541 0.812 0.646 0.908 0.726 0.940 0.851 0.977 1.10 1.01
22 8.69 2.75
24 8.60 2.66
18 10.39 2.51
20 10.26 2.47
CFU036/ ORHC036 0.545 0.810 0.650 0.890 0.729 0.940 0.850 0.980 1.10 1.00
22 10.16 2.41
24 10.06 2.34

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-28
d- DUCTED TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT -10 -5 -3 2 7 12
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
18 5.33 2.88
DBC018 / 20 5.28 2.84
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 22 5.23 2.74
24 5.19 2.68
18 5.79 2.81
DBC020/ 20 5.74 2.76
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 22 5.69 2.67
24 5.64 2.61
18 7.10 2.83
DBC024/ 20 7.03 2.78
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC025A6 22 6.97 2.68
24 6.91 2.62
18 8.09 3.05
DBC024* / 20 7.56 2.85
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC025,A6 22 7.62 2.82
24 7.54 2.80
18 9.12 2.90
DBC030 / 20 9.03 2.84
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC030,A6 22 8.95 2.74
24 8.88 2.68
18 10.59 2.74
DBC036 / 20 10.49 2.69
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC036,A6 22 10.40 2.59
24 10.31 2.54
18 14.09 2.67
DBC048 / 20 13.92 2.61
0.535 0.817 0.660 0.910 0.730 0.941 0.846 0.980 1.11 1.01
ORHC050,A6 22 13.75 2.53
24 13.63 2.45
18 17.80 2.73
DBC060 / 20 17.59 2.67
0.541 0.812 0.646 0.908 0.726 0.940 0.851 0.977 1.10 1.01
ORHC060,A6 22 17.38 2.59
24 17.22 2.51

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-29
e- CASSETTE TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT -10 -5 -3 2 7 12
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
18 5.79 3.23
CAS024 / 20 5.74 3.18
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 22 5.69 3.07
24 5.64 3.01
18 6.81 2.99
CAS024/ 20 6.74 2.93
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC025A6 22 6.68 2.83
24 6.63 2.77
18 9.41 3.24
CAS048 / 20 8.79 3.03
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC030,A6 22 8.86 2.82
24 8.77 2.80
18 10.36 3.16
CAS048 / 20 10.26 3.10
0.530 0.816 0.670 0.910 0.735 0.930 0.850 0.978 1.10 1.00
ORHC036,A6 22 10.17 2.99
24 10.09 2.93
18 13.77 2.81
CAS048 / 20 13.63 2.76
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC050,A6 22 13.51 2.66
24 13.39 2.60

f- FREE STAND TYPE

Indoor Outdoor DBT (oF) & 80 % Relative Humidity


Unit DBT -10 -5 -3 2 7 12
o
F Hce COPE Hce COPE Hce COPE Hce COPE Hc (BTU/hr) COP Hce COPE
18 5.33 2.55
TFD025 / 20 5.28 2.51
0.545 0.821 0.661 0.908 0.728 0.930 0.850 0.959 1.11 1.00
ORHC020A6 22 5.23 2.43
24 5.19 2.38
18 7.10 2.76
TFD025/ 20 7.03 2.71
0.538 0.816 0.655 0.911 0.721 0.930 0.840 0.965 1.10 1.00
ORHC025A6 22 6.97 2.61
24 6.91 2.55
18 11.29 3.75
TFD048 / 20 10.55 3.50
0.540 0.817 0.656 0.910 0.710 0.925 0.845 0.971 1.11 1.00
ORHC036,A6 22 10.64 2.82
24 10.53 2.80
18 13.03 2.77
TFD048 / 20 12.90 2.72
0.535 0.820 0.670 0.925 0.741 0.928 0.850 0.970 1.10 1.01
ORHC050,A6 22 12.78 2.62
24 12.67 2.56

Hce :Coefficient of Heating Capacity at high indoor fan speed (Heat Pump models only) COPE : Coefficient of COP
Multiply figures in shaded cells by coefficients to calculate heating capacity coefficient of performance at different conditions.
6-30
7- Fan Performance

DBC018
E.S.P
mm wg. 0 3 4 5 6 8
inch wg. 0 0.1 0.15 0.2 0.25 0.3
CFM 585 484 440 401 342
HI 3
m /hr 993 822 748 681 581
Fan Speed

CFM 497 435.6 396 360.9


MED 3
m /hr 844 740 673 613
CFM 423 387.2 352
LOW 3
m /hr 718 658 598

HI
DBC018 MED
LOW
600

550

500
CFM

450

400

350

300
0 0.05 0.1 0.15 0.2 0.25 0.3
E.S.P INCH

7-1
DBC018
E.S.P
mm wg. 0 3 4 5 6 8
inch wg. 0 0.1 0.15 0.2 0.25 0.3
CFM 585 527 474 426 384
Fan Speed HI
m 3/hr 994 894 805 725 652
CFM 497 447.3 402.57 362.313
MED 3
m /hr 844 760 684 616
CFM 423 380.7 342.63
LOW
m 3/hr 718 647 582

HI
DBC018 MED
LOW
600

550

500
CFM

450

400

350

300
0 0.05 0.1 0.15 0.2 0.25 0.3
E.S.P INCH

DBC020/024
E.S.P
mm wg. 0 3 4 5 6 8
inch wg. 0 0.1 0.15 0.2 0.25 0.3
CFM 560 504 454 408 367
HI
Fan Speed

m 3/hr 951 856 770 693 624


CFM 477 429 386 348
MED 3
m /hr 810 729 656 591
CFM 405 365 328
LOW
m 3/hr 688 619 557

HI
DBC020/024 MED
LOW
600

550

500
CFM

450

400

350

300
0 0.05 0.1 0.15 0.2 0.25 0.3
E.S.P INCH

7-2
DBC024B5
E.S.P
mm wg. 0 3 4 5 6 8
inch wg. 0 0.1 0.15 0.2 0.25 0.3
CFM 800 720 648 583 525 472
HI
Fan Speed
m3/hr 1359 1223 1101 991 892 803
CFM 680 612 551 496
MED
m3/hr 1155 1040 936 842
CFM 578 520 468
LOW
m3/hr 982 884 795

HI
DBC024*B MED
LOW
850

800

750

700

650
CFM

600

550

500

450

400
0 0.05 0.1 0.15 0.2 0.25 0.3
E.S.P INCH

DBC030
E.S.P
mm.wg. 0 3 5 8 10 13 15
inch wg. 0 0.1 0.2 0.3 0.4 0.5 0.6
CFM 1100 990 891 802 722 650 585
HI
Fan Speed

m3/hr 1869 1682 1514 1362 1226 1104 993


CFM 935 842 757 682 613
MED
m3/hr 1589 1430 1287 1158 1042
CFM 795 715 644 579
LOW
m3/hr 1351 1215 1094 984

Hi
Med
DBC030
1200 Low

1100

1000

900
CFM

800

700

600

500
0 0.1 0.2 0.3 0.4 0.5 0.6
E.S.P INCH

7-3
DBC036
E.S.P
mm. wg. 0 3 5 8 10 13 15
inch wg. 0 0.1 0.2 0.3 0.4 0.5 0.6
CFM 1475 1328 1195 1075 968 919 873
HI

Fan Speed
3
m /hr 2506 2255 2030 1827 1644 1562 1484
CFM 1254 1128 1016 914 868
MED
m 3/hr 2130 1917 1725 1553 1475
CFM 1066 959 863
LOW
m 3/hr 1811 1629 1467

Hi
DBC036 Med
Low
1600

1500

1400

1300
CFM

1200

1100

1000

900

800
0 0.1 0.2 0.3 0.4 0.5 0.6
E.S.P INCH

DBC048
E.S.P
mm.wg. 0 3 5 8 10 13 15
inch wg. 0 0.1 0.2 0.3 0.4 0.5 0.6
CFM 1600 1440 1296 1166 1050 997 947
HI
Fan Speed

3
m /hr 2718 2446 2202 1982 1783 1694 1610
CFM 1360 1224 1102 991 942
MED
m 3/hr 2311 2079 1872 1684 1600
CFM 1156 1040 936
LOW 3
m /hr 1964 1768 1591

Hi
DBC048 Med
Low
1700

1600

1500

1400
CFM

1300

1200

1100

1000

900
0 0.1 0.2 0.3 0.4 0.5 0.6
E.S.P INCH

7-4
DBC060
E.S.P
mm.wg. 0 3 5 8 10 13 15
inch wg. 0 0.1 0.2 0.3 0.4 0.5 0.6
CFM 1800 1620 1458 1312 1181 1122 1066
HI
Fan Speed

3
m /hr 3058 2752 2477 2229 2006 1906 1811
CFM 1530 1377 1239 1115 1060
MED 3
m /hr 2599 2339 2105 1895 1800
CFM 1300 1170 1053
LOW 3
m /hr 2209 1988 1789

HI
DBC060 MED
LOW
1900

1800

1700

1600

1500
CFM

1400

1300

1200

1100

1000
0 0.1 0.2 0.3 0.4 0.5 0.6

E.S.P INCH

7-5
8- Unit Operation

A- The Remote Control


i- HWC,CFU TYPE

Infra-Red Transmitter: Sends operating signals to PC-


board.

Display Screen: Displays the operating settings of the unit.

O “Temperature Adjustment” buttons: Sets the temperature


F in the range of 16 – 30 oC (60 – 85 oF). Pressing both
O
C buttons at the same time switches the displayed
AM ON temperature from Centigrade to Fahrenheit and vice versa.
PM OFF

“ON/OFF” button: Starts/Stops unit operation.

“Fan Speed” button: Selects the fan speed: Low, Medium,


S C High, Auto.
TIMER ON
FAN MODE “Mode” buttons: Selects the operation mode: Cool, Dry,
S C
Fan, Heat or Auto
TIMER OFF
Sleep Swing Louver
“TIMER ON”: Button (S) adjusts “TIMER ON” settings while
button (C) cancels them.

“TIMER OFF” buttons: Button (S) adjusts “TIMER OFF”


settings while button (C) cancels them.

“Clock Adjustment” buttons: Sets the time of the built-in


clock inside the remote controller.

“LOUVRE” button: Controls the vertical position of the


horizontal blade.

“SWING” button: Used to operate the Air swing.


In case HWC: Not Functioning.

“SLEEP” button: Switches the Sleep operation ON & OFF.

Sliding Cover: Protects buttons and batteries.

8-1
The Display Screen Components
Mode Indication Bar: Shows current mode sign:
Cool Dry Fan Heat Auto
(two symbols
appear together).

Transmission Indicator: Flashes after 3 sec of using


the Remote. The indoor unit beeps as an indication for
receiving the transmission

Fan Speed Indicator: Shows Fan speed sign:


O
F
Low Medium High Auto

O
C “SLEEP ” Indicator: Displayed when “Sleep” operation
AM ON is active.
PM OFF Air Direction Indicator: Displays the current position of
the louvre.

Auto Swing Indicator: Displayed when the Auto Swing


operation is active.
In case HWC: Not Functioning.

“Timer ON” Indicator: Displayed when “TIMER ON”


operation is active.

“Timer OFF” Indicator: Displayed when “TIMER OFF”


operation is active.

“Time” Indicator: Displays Clock settings and also


“TIMER ON” & “TIMER OFF” settings.

“Temperature” Indicator: Displays the adjusted


temperature settings.

Remote Controller Power


The remote controller operates with 2 batteries of size AAA with 1.5 Volts.
Changing Batteries
The batteries have to be changed when the remote does not send its
signals to the indoor unit or when the display screen becomes
unclear.
Open the sliding cover to its full extent and press softly with your
thumb while pulling the cover down till it comes out of its sliding
way showing the battery compartment.
Remove the used batteries and insert a pair of new batteries.
Re-install the sliding cover and test the remote controller work.
If the indoor unit beepis, then the change process was successful
other wise, check battery positioning or replace them.

8-2
Operation Procedures

When you turn the power on using the remote controller, the unit will
automatically operate with the last operating settings.
It is preferable to adjust the operation settings before starting the unit.
When using the remote controller, direct it towards the indoor unit
receiver.
The indoor unit will beep after receiving the remote controller instructions.

“COOL” Mode
Decreases the room temperature and humidity during summer time to comfortable conditions (1).
1 - Set the operation mode to “COOL”.
2 - Select the fan speed (Low, Medium, High, Auto).

3 - Set the desired room temperature.


4 - Adjust the LOUVER position. (2)
5 - Adjust the SLEEP operation. (2)

“DRY” Mode
Decreases water vapor in the room air without significant change in the room temperature.
In this mode, both the fan speed and the SLEEP operation can not be controlled.
1 - Set the operation mode to “DRY”.

2 - Set the desired temperature

3 - Adjust the LOUVER position. (2)

0 0
(1) Recommended comfortable temperature range is 23 – 25 °C.( 73.4 F – 77 F )
(2) Set to ON or OFF according to your needs.
8-3
“FAN” Mode
Moves the room air without changing its temperature.
Both the SLEEP operation and the temperature can not be controlled and the fan speed has 3
speed.
1 - Set the operation mode to “FAN”.
2 - Adjust the fan speed: (Low, Medium, High).
3 - Adjust the LOUVER position. (1)

“HEAT” Mode
Increases the temperature of the room during wintertime.
1 - Set the operation mode to “HEAT”.
2 - Select the fan speed: (Low, Medium, High, Auto).
3 - Set the desired room temperature.
4 - Adjust the LOUVER position. (1)
5 - Adjust the SLEEP operation. (1)

“AUTO” Mode
Automatically change over from “COOL” to “HEAT” and vice versa according to the room temperature in
order to achieve the desired temperature.
1 - Set the operation mode to “AUTO”.
2 - Select the fan speed: (Low, Medium, High, Auto).
3 - Set the desired temperature.
4 - Adjust the LOUVER position. (1)
5 - Adjust the SLEEP operation. (1)

(1) Set to ON or OFF according to your needs.


8-4
“SLEEP” operation

Saves the energy and provides more comfortable conditions.


In Cooling Mode: The temperature increases by 2 °C ( 3.6 F0)above the setting temperature
within 2 hours of turning the operation ON.
In Heating Mode: The temperature decreases by 2 °C ( 3.6 F0 ) below the setting temperature
within 2 hours of turning the operation ON.
To use the “SLEEP” operation: Press the SLEEP button, the “STAR” sign will appear\disappear on
the screen.

“TIMER ON” & “TIMER OFF” Operations


The “TIMER ON” operation operates the unit at a pre-adjusted time if its status was OFF.
The TIMER OFF operation stops the unit at pre-adjusted time if its status was ON.
1 - Press the (S) key to set the time for “TIMER ON”.
The ” ON” symbol will flash and the timer indicator
displays suggested time.

2 - Press the (S) key to set the time for “TIMER OFF”.
The “ OFF” symbol will flash and the timer indicator
displays suggested time.

3 - Press the (C) key to cancel the set order. The symbol will
disappear.

Pressing the (S) key while adjusting the time will increase the suggested time
setting by 30 min.
The change rate of the suggested time settings increases when pressing the
buttons continuously.

Remote Controller’s Clock Setting

The built-in clock inside the remote controller is displayed on the screen and used to determine
when to activate your settings for the “TIMER ON” and “TIMER OFF” operations.
To adjust the remote controller’s clock:
Press one of the two clock adjustment buttons for 3 sec. to activate the process. The displayed
time on the screen will increase (or decrease) by 1min. Continuos pressing on the button will
increase the change rate from 1min to 10 min.

* Receiver for " WALL MOUNTED" G+ Series

Power
Heat
Cool Sleep
Temperature
8-5
ii- For “DBC , TFD 048” Models:

3 2
FAN ON/OFF

TEMP

5 7
SWING SLEEP

6 8
TIME MODE

No COMPONENT DESCRIPTION
1 Transmitter Transmits operating signals to the PC-board of the unit.
2 “ON/OFF” button Starts and stops operating the unit.
3 “Fan” button Toggles the fan speed: Low, Medium, High, or Auto.
Sets the temperature in the range of 16 – 30 oC (60.8 – 86
4 “Temp” buttons o
F).
5 “Auto Swing” button Not Functioning.
Sets the number of operating hours after which the unit will
6 “TIMER” button
stop operating.
7 “Sleep” button Toggles the “SLEEP mode” ON & OFF.

8 “Mode” button Toggles the operation mode: Cool, Dry, Fan, or Heat.

8-6
Changing Batteries
Operates with 1 battery CR2025 type with 3 Volts.
The battery must be changed when the unit does not receive its
signals.
Remove the battery holder out of its place at the bottom of the remote
controller back face.
Remove the used battery and insert new one.
Re-install the holder and test the remote controller.
If the unit beeped, then the change process was successful.

“COOL” Mode
Decreases the room temperature and humidity during summer time to comfortable conditions (1).
1 - Press the ON\OFF button.
2 - Press the mode button till the “COOL” led in the touch pad lights up.
3 - Select the fan speed: (Low, Medium, High, Auto).
4 - Set the desired temperature.
5 - Adjust the SLEEP operation. (2)
6 - Adjust the Timer settings. (2)

“DRY” Mode
Decreases water vapor in the room air without significant change in the room temp .
The fan speed and the sleep operation can not be controlled.
1- Press the ON\OFF button.
2- Press the mode button till the “DRY” led in the touch pad lights up.
3- Set the desired temperature.
4- Adjust the Timer settings. (2)

o
(1) Recommended comfortable temperature range is 23 – 25 °C (73.4 – 77 F).
(2) Set to ON or OFF according to your needs. 8-7
iii- For “CAS” Models:

Infra-Red Transmitter: Sends


operating signals to PC-board.

Display Screen: Displays the


0
operating settings of the unit.
C

“Temperature Adjustment” buttons:


AMPM CLOCK AMPM Sets the temperature in the range of 19
– 30 oC(66 – 86 oF) .

“ON/OFF” button: Starts/Stops unit


operation.
I/O TOO TOO
WARM COOL
“Mode” buttons: Selects the
operation mode: Cool/Dry/Fan/Heat or
Auto Sets.

“SWING” button: Switches the


automatic air swings movement ON &
OFF.

“Fan Speed” button: Selects the fan


speed: Low/Medium/High/Auto

“TIMER ON”: Adjusts “TIMER ON”


HR. MIN. settings.

“TIMER OFF” buttons: Adjusts


“TIMER OFF” settings .

Minute set

Hour set

8-9
The Display Screen Components:

Mode Indication Bar: Shows current mode:


Fan Cool Dry Heat

Transmission Indicator: Flashes after sending


orders..

“Temperature” Indicator: Displays the


0
C adjusted temperature settings.

Fan Speed Indicator: Shows Fan speed:


Low Medium High Auto
AMPM CLOCK AMPM

Auto Swing Indicator: Displayed when “Auto


Swing” operation is active.

“Timer ON” Indicator: Displayed when


“TIMER ON” operation is active.

“Timer OFF” Indicator: Displayed when


“TIMER OFF” operation is active.

“Time” Indicator: Displays Clock settings and


also “TIMER ON” & “TIMER OFF”

Operation Procedures

When you turn the power on using the remote control, the unit will automatically
operate with the last operating settings.
It is preferable to adjust the operation settings before starting the unit.
When using the remote control, direct it towards the indoor unit receiver.
The indoor unit will beep after receiving the remote control instructions.

8 - 10
“COOL” Mode
Decreases the room temperature and humidity during summer time to comfortable conditions (1).
I/O TOO TOO 1 - Set the operation mode to “COOL”.
WARM COOL
2 - Select the fan speed .

3 - Set the desired room temperature.


(2)
4 - Adjust the SWING operation.

HR. MIN.

“DRY” Mode
Decreases water vapor in the room air without significant change in the room temperature. In this
mode, both the fan speed and the SLEEP operation can not be controlled.
I/O TOO TOO 1 - Set the operation mode to “DRY”.
WARM COOL
2 - Set the desired temperature.
(2)
3 - Adjust the SWING operation.

HR. MIN.

“FAN” Mode
Moves the room air without changing its temperature.
temperature can not be controlled and the fan speed has 3 speed.

I/O TOO TOO


WARM COOL
1 - Set the operation mode to “FAN”.
2 - Adjust the fan speed.
(2)
3 - Adjust the SWING operation.

HR. MIN.

“HEAT” Mode
Increases the temperature of the room during wintertime.
I/O TOO TOO 1 - Set the operation mode to “HEAT”.
WARM COOL
2 - Select the fan speed.
3 - Set the desired room temperature.
(2)
4 - Adjust the SWING operation.

HR. MIN.

(1) Recommended comfortable temperature range is 23 – 25 °C.(73.4 – 77 °F)


(2) Set to ON or OFF according to your needs. 8 - 11
“FAN” Mode
Moves the room air without changing its temperature.
The fan speeds are (Low, Medium, High) only and both the sleep option and the temperature can
not be controlled.
1 - Press the ON\OFF button.
2 - Press the mode button till the “FAN” led in the touch pad lights up.
3 - Adjust the fan speed: (Low, Medium, High).
4 - Adjust the Timer settings. (1)

“HEAT” Mode
Increases the temperature of the room during wintertime resulting in conditions that are more
comfortable.
To operate the “HEAT” mode:
1 - Press the ON\OFF button.
2 - Press the mode button till the “HEAT” led in the touch pad lights up.
3 - Select the fan speed: (Low, Medium, High, Auto).
4 - Set the desired temperature.
5 - Adjust the SLEEP operation. (1)
6 - Adjust the Timer settings. (1)

“SLEEP” Function
Saves the energy and provides comfort by adjusting the room temperature (Tr).
In COOLING mode: T ROOM = T SETTING + 2 °C (3.6 °F) within 2 hours of turning it ON.
In HEATING mode, T ROOM = T SETTING - 2 °C (3.6 °F) within 2 hours of turning it ON.

“TIMER” Function
Sets the number of hours after which the unit will start or stop automatically. If the unit is ON while
setting the operation, the Timer will stop it and if it is OFF, the timer will start it.
• When you press the “Timer” key the temperature indicator in the unit displays the
suggested number of hours.
• Each press on the “Timer” key will increase the displayed number of hours by 1 hour.
• To cancel the operation set the number of hours to 0 hours.

(1) Set to ON or OFF according to your needs


8–8
“TIMER ON & TIMER OFF ” Operations

“TIMER ON” operation operates the unit at a pre-adjusted time if its status was OFF.
“TIMER OFF” operation stops the unit at pre-adjusted time if its status was ON.
I/O TOO TOO 1 - Press the ( ) key to set the time for “TIMER ON”. The timer indicator
WARM COOL
displays suggested time. Set the time from the HR. and MIN. Buttons
2 - Press the ( ) key to set the time for “TIMER OFF”. The timer indicator
displays suggested time. Set the time from the HR. and MIN. Buttons

HR. MIN.

Remote Control Power:


Put in two AAA-size batteries. 1
Don’t mistake the "+"/"-" pole.
Changing Batteries
The batteries have to be changed when the remote does not
send its signals to the indoor unit or when the display screen
becomes unclear.
Open the back cover, put in two batteries. - +

Be sure to place the batteries as indicated in the compartment.


Adjust the remote controller clock and operating settings after
changing the batteries.

Remote Controller’s Clock Adjustment:


1- Open the back cover.
2- Press the "RESET" button in the back.
3- Press the "CLOCK SET" button in the back.
4- Press the time setup button to check with present time.
Press the "HOUR SET" button, skip 1 hour each time.
Press the "MINUTE SET" button, skip 1minute each time.
5- Press the "CLOCK SET" button again and put on the back cover.

Press here using a thin


stick

8 - 12
iv- For “TFD” Models:Option

Infra Red Transmitter: Transmits operating


signals to the PC-board of the indoor unit.

Temp. adjustment buttom: Set the disered


temp. in the range of 18 – 30 oC (64.5 – 86 F )
TEMP.
– +
0
C “Timer” button: Adjust “Timer Off” and
CONT TIMER “Timer On” Operation.
OFF “+ & -“ Increase and decrease the period of
ON time 1 hour till 12 hour.
h – +
AUTO “Fan Speed” button: Selects the fan speed:
HI FAN Low, Medium, High, or Auto.
MED
LO
AUTO MODE “Mode” button: Selects the operation mode:
COOL Auto, Cool, Dry or Heat.
DRY
HEAT LOUVER “Louver” button: Controls the vertical
SWING position of the horizontal blade.

“Swing” button: Used to operate the louver.

ON / OFF ON/OFF button: Starts and stops operating


the unit.

Display Screen: Displays the operating


settings of the unit.

8 -13
Operation Procedures

“COOL” Mode

TEMP.
- +
1 - Set the operation mode to “COOL”.
CONTTIMER
OFF 2 - Select the fan speed: (Low, Medium, High, Auto).
ON - +
AUTO
HI FAN 3 - Set the desired room temperature.
MED
LO
AUTO MODE
COOL
DRY
HEAT LOUVER
SWING

ON / OFF

“DRY” Mode
TEMP.
- +
CONTTIMER
OFF
1- Set the operation mode to “DRY”.
ON - +
AUTO
HI FAN 2- Set the desired room temperature.
MED
LO
AUTO MODE
COOL
DRY
HEAT LOUVER
SWING

ON / OFF

“HEAT” Mode
In case of heat pump models".
TEMP. 1- Set the operation mode to “HEAT”.
- +
CONTTIMER
OFF
2- Select the fan speed.
ON - +
AUTO
HI FAN 3- Set the desired temperature.
MED
LO
AUTO MODE
COOL
DRY
HEAT LOUVER
SWING

ON / OFF

“AUTO” Mode

TEMP. 1 - Set the operation mode to “AUTO”.


- +
CONTTIMER
OFF
2 - Select the fan speed.
ON - +
AUTO
HI FAN 3 - Set the desired temperature.
MED
LO
AUTO MODE
COOL
DRY
HEAT LOUVER
SWING

ON / OFF

8 - 14
“TIMER” Operation
When you press the “TIMER” button, the arrow lights up pointed to:
TEMP. 1 - “ON” Timer: Activation of “Timer Operation ON” will start,and the No. of hours will
- +
CONTTIMER
lights up. Press the “+ or –“ will increase or decrease the time by one hour till 12 hour.
OFF
ON - + 2 - “OFF” Timer: Activation of “Timer Operation OFF” will start,and the No. of hours will
AUTO
HI
MED
FAN
lights up. Press the “+ or –“ will increase or decrease the time by one hour till 12 hour.
LO
AUTO MODE
COOL
3 - “CONT.” Timer: Deactivation of “Timer Operation”.
DRY
HEAT LOUVER
SWING

ON / OFF

“FAN” Button
TEMP.
1- The fan speeds are (AUTO, HIGH, MEDIUM LOW).
- +
CONTTIMER
OFF
ON - +
AUTO
HI FAN
MED
LO
AUTO MODE
COOL
DRY
HEAT LOUVER
SWING

ON / OFF

8 - 15
B- The “TOUCH PAD”
i- For “DBC” Models:
Fixed on the wall and connected to the indoor unit with a wire, It consists of the following:

11 6 5 10 4 3

SENSOR

ON/OF 1

AUT COO
HIG FAN
TEM FAN MODE 2
ME DR
LO
D HEA
Y

TIMER SWING SLEEP 7

9 8

No COMPONENT DESCRIPTION

1 “ON/OFF” button Starts and stops operating the unit.


2 “MODE” button Toggles the operation mode: Cool, Fan, Dry, or Heat.
3 “Mode” Led The led of the current mode will be ON.
4 “FAN” button Toggles the fan speed: Low, Medium, High, or Auto.
5 “Fan” Led The led of the current speed will be ON.
6 “TEMP” button Sets the temperature in the range of 16 – 30 oC (60.8 – 86 oF).
7 “SLEEP” button Toggles the “SLEEP” mode ON & OFF.
8 “SWING” button Not Functioning.
Sets the number of operating hours after which the unit will
9 “TIMER” button
stop operating.
10 SENSOR Receives the remote controller’s signal.
Displays the set temperature and displays also the TIMER
11 Display Screen
settings when adjusting it.

Operation Procedures

If you turn the power off using the remote controller or the touch pad, the unit
will automatically operate with the same operation settings next time you turn it
on.
When using the remote controller, direct it towards the touch pad receiver.
The unit will beep after receiving the remote controller instructions.
8-16
ii- For “TFD” Models:
It consists of the following:
(For model TFD 25) Indicator lamp (lights up when
10 operation)

0
A C

ON/OFF
TIME
TIMER MODE
LOUVER TEMP. - TEMP. + FAN
8 1
7 2
6 3
5 4

(For model TFD 48) 10


9

TIME
TIMER MODE
LOUVER TEMP. - TEMP. + FAN
1
8
7 2
6 4 3
5

Indicating the left/right "TIMER" mode display.


louvers at work.

"LOCK" function display. Indicating the auxiliary


electrical heating (not
working).

A "AUTO" mode display. "DRYING" mode display.

"COOLING" mode "HEATING" mode display.


display.

8 - 17
No COMPONENT DESCRIPTION

1 “ON/OFF” button Starts and stops operating the unit.


Select the operation mode: Dry, Fan, Cool, Heat or
2 “MODE” button
Auto.

3 “FAN” button Select the “FAN” speed: Low, Medium, High, or Auto.

4&5 “Temp.” buttons Sets the temperature.

6 "LOUVER" button Controls the vertical position of the horizontal blade.


7 "TIMER" button Activate TIMER function.
Sets the number of operating hours after which the
8 "TIME" button
unit stops or runs automatically.
To Secures the panel (pressing TEMP.-&TEMP.+
9 Lock
together).
Displays the room temp. and also displays both the
10 Display set temp. and the “TIMER” operation setting while
adjusting them.

**For cooling only type, the sign is changed to .

Operation Procedures

“COOL” Mode

Decreases the room temperature and humidity during summer time to comfortable conditions (1).
1 - Press the mode button till the led “COOL” in the
O
C “Pad” lights up.
2 - Select the fan speed.
TIME
ON/OFF
3 - Set the desired temperature.
TIMER MODE (2)
LOUVER
TEMP. -TEMP. +
FAN 4 - Adjust the louver operation.

“DRY” Mode
Decreases water vapor in the room air without significant change in the room temperature.
The fan speed and the sleep operation can not be controlled.
1 - Press the mode button until the led “DRY” in the
O
C “Pad” lights up.
2 - Set the desired temperature.
ON/OFF
TIME
TIMER MODE
LOUVER FAN
TEMP. -TEMP. +

1- Recommended comfortable temperature range is 23 – 25 °C.(73.4 – 77 °F)


2- Set to ON or OFF according to your needs. 8 - 18
“HEAT” Mode "In case of heat pump models".
Increases the temperature of the room during winter time resulting in conditions that are more
comfortable.
To operate the “HEAT” mode:
1 - Press the mode button till the led “HEAT” in the
O
“Pad” lights up.
C

2 - Select the fan speed.


ON/OFF 3 - Set the desired temperature.
TIME
(1)
TIMER
LOUVER FAN
4 - Adjust the louver operation.
TEMP. -TEMP. +

“AUTO” Mode
" In case of heat pump models".
Automatically change from "AUTO" and vice versa according to the room temp. in order to
achieve the desired temp..
1 - Press the mode button till the led “AUTO” A in the
O
C “Pad” lights up.
2 - Select the fan speed.
ON/OFF
TIME 3 - Set the desired temperature.
TIMER MODE (1)
LOUVER
TEMP. -TEMP. +
FAN 4 - Adjust the louver operation.

“TIMER” Mode
1 - Press the "TIMER" button, the led will activate an "1
hour” will be display.
O
C
2 - Press :TIME" button to increase the period of "TIMER
OFF" or "TIMER ON" 1 hour till 12 hour.
ON/OFF
TIME 3 - To cancel "TIMER" action, press the "TIMER” button on
TIMER
LOUVER
TEMP. -TEMP. +
FAN
MODE
the operating panel.
(1)
4 - Adjust the louver operation.

“FAN” Button

The fan speeds are (LOW, MEDIUM, HIGH).

**Note: The preset TIMER OFF (or preset TIMER ON) time will be stored.
When you use it again, the previous preset time will be displayed automatically.

1- Recommended comfortable temperature range is 23 – 25 °C. 8 - 19


Adjustment of louver:

1- Adjustment of louver left/right air deflection:


Fixed air deflection: When the louvers move to the deflection position you desire, just press the
button (LOUVER), the louvers will stop moving and perform fixed air deflection.
Changed air deflection: If you press the button (LOUVER) once, the louvers will give you airflow
to the left and the right alternatively.

2- Adjustment of up/down air deflection:


move the vertical up/down louvers to adjust the up/down airflow angles.
Please hold the two ends of up/down louvers to move them.
Usually during cooling and drying operation, airflow should be adjusted to the front or the up
direction.

Airflow
Airflow

Up/down louvers Up/down louvers

* During heating operation, airflow should be adjusted to Airflow


the down direction.
While the vertical left/right louvers are being adjusted, the Up/down louvers
top louver and bottom louver do not move as well.

** Note: In the HEATING mode, when defrosting and the room temperature is 10C
higher than the preset temperature, the louvers stop moving, when heat air blows out in
the HEATING mode, the control mode of the louvers accord to the "LOUVER" operation
of operating panel.

8 - 20
C- The “MECHANICAL THERMOSTATE” :
i- For “DBC” Models:

o
20 22 24 26 28 30 C

LOW MED HI

HEAT OFF COOL

4 3 2 1

No COMPONENT DESCRIPTION

Operates the unit ON and OFF and also selects the


1 Operation button
operation mode: Either COOL or HEAT.
Selects the indoor fan speed:
2 “Fan” button
Low, Medium or High.
3 Operation LED Indicates the unit operation.
Sets the temperature in the range of
4 “Temperature” Bar
20 – 30 oC (68 – 86 oF)

Mechanical Operation:

o
20 22 24 26 28 30 C

LOW MED HI

HEAT OFF COOL

1 2
3
1 – Adjust the required temperature by moving the indicator to the right and to the left.
2 – Adjust the required indoor fan speed.
3 – Move the selector from the OFF position to the operation mode you require “COOL” or
“HEAT”.
` 8 - 21
9- P.C.B Advanced Functions

a- For “HWC - CFU – DBC” Models:


1) PC-Board Features: 2) “COOL” Mode:
a. Auto-Restart Function: The unit will be “ON” and “OFF” according to
Allows the microprocessor of the PC-board to re- both the room and set temperature.
operate the unit automatically when restoring the The indoor fan motor runs at selected speed.
electrical power as long as the unit is plugged by The compressor will be “ON” when the room
saving the latest user-set operating parameters temperature reaches 0.5 oC (.9 oF) above the
and conditions (such as mode, temperature, set temperature, and will be “OFF” when the it
indoor fan motor speed, various functions like decreases 1 oC (1.8 oF) below the set
sleep, timer,.... ) . temperature.
The 4-way valve will be “OFF” all the time.
b. Compressor ON/OFF Protection:
The compressor must be idle for at least 3 The Outdoor fan will be cycling “ON” and
minutes once it has cut out. This is over ridden by “OFF” according to the compressor status. (1)
a 4-way valve changing. Optional “Low-Ambient control Kit” keeps the
system running with ambient temperature
c. 90 Sec minimum run-time for thermostat: below 20 oC (68 oF) by controlling the outdoor
The compressor incorporate 90 seconds minimum fan speed.
run-time for the thermostat cycle. It cannot be cut
out before running with the current mode for 90 Temp
seconds.
d. Compressor Overload protection
(Heat Pump models only): Ts + ½
2 cases of overload protection are available for Ts Time
the compressor:
- Heating Protection (HEAT mode).
- Cooling Protection (COOL & DRY modes). Ts - 1

Both overload protection cases can be rest


manually by turning the unit OFF and then ON.
Thermostat

ON
Overload will be activated if gas temperature
reaches 68 oC (154.4 oF) inside the coil (outdoor OFF

coil in COOL mode and indoor coil in HEAT


ON
mode).
Indoor

OFF
Fan

The indoor fan remains ON, while compressor


cuts out immediately irrespective of minimum run
Compressor

time protection. 3 min

e. Over heating protection ON

(Heat Pump models only): OFF


In heat pump models in heating mode, if indoor
ON
coil sensor Temp. reach 57 oC (134.6 oF) then
Outdoor 4-Way

OFF
outdoor fan motor will forced to stop.
Valve

f. Low Gas Protection: (1)


The system will consider the gas pressure in the ON
circuit to be low and the system will cut out if the
Fan

OFF
indoor coil temperature ( T coil ) cannot meet the
IN
one of the following conditions for 50 minutes of
Crank-case

operation: ON
Heater

- T coil ≤ 24 oC (75.2 oF) (Cool mode). OFF


IN
- T coil IN ≥ 20 C (68 F)
o o
(Heat mode).

Note: This function is not available in DBC, CFU Models.

(1) If the system is equipped with a low ambient kit, it keeps the
o o
system running even if the outdoor temp. drops below 20 C (68 F)
by controlling outdoor fan speed.
9- 1
3) “HEAT” Mode (Heat Pump Models 4) “DRY” Mode:
Only): When not selected from “COOL” mode, the unit
The unit will be “ON” and “OFF” according to will operate with “COOL” mode continuously either
both the room and set temperature. for 12 minutes or till room temperature reaches 1
o
The indoor fan motor runs at the selected C (1.8 oF) below set temperature.
speed. The “Hot Start” function will avoid Once this condition is fulfilled, The “DRY” mode
introducing cold air to the room. will operate under either A, B, C, or D zones as
If the indoor coil sensor reads 55 oC(131 oF) indicated below:
the indoor fan motor speed will increase with Zone (A): TR > TS + 2 (3.6 oF)
one step. If it reads 68 oC (154.4 oF) the o
compressor overload will be triggered and the
Zone (B): TR ≥ TS + 1 (1.8 F)
unit stops. Zone (C): TS - 1 ≥ TR ≥ TS - 2 (3.6 oF)
≤ TS - 3 (5.4 F)
o
The compressor will be “ON” when the room Zone (D): TR
temperature reaches 1 oC (1.8 oF) below the Other Temperature ranges are dead bands for
set temperature, and will be “OFF” when the zone stability.
room temperature increases 1.5 oC (2.7 oF)
above the set temperature. Temp (oC)
The 4-way valve will be “ON” all the operating +2
time.
+1
The Outdoor fan will be “ON” and “OFF”
Time
according to the compressor and outdoor Ts
temperature.
-1
Crankcase Heater will be “ON” all the time.
-2
Temp (oC)
Ts +1 ½ -3
A B A B C D C
Ts + 1

Ts + ½ Zone “A”
ON
Ts
Time OFF Compressor
Ts - ½
ON
Ts - 1
Indoor Fan
OFF
(low speed)
Zone “B”
Indoor Thermostat

ON
ON
OFF OFF Compressor
Delay by 8 min 4 min
“Hot
Start” ON
ON
Fan

Indoor Fan
OFF
OFF (low speed)
30 Sec. 30 Sec

Zone “C”
Compressor

3 min delay ON
ON 6 min
OFF OFF Compressor
6 min

ON
Indoor Fan
4-Way
Valve

ON OFF (low speed)


OFF 30 Sec. 30 Sec

Zone “D”
Outdoor

ON
ON
Fan

OFF
OFF Compressor
Crank-case

ON
30 Sec. Indoor Fan
Heater

ON
OFF (low speed)
OFF

9-2
5) “AUTO” Mode (Heat Pump Models When the outdoor temperature decreases
Only): below 3 oC(5.4 oF), the defrost controller is
activated and the timer starts counting. The
Depending on both the room temperature and the
time period is used along with the temperature
set temperature, the operation will be changed
to start defrosting at one of the following cases:
automatically from heating to cooling and vise
versa. Temp. ≤ - 8 oC(17.6 oF) for 30 min.
If the present operating mode is cooling: Temp. ≤ - 4 oC(24.8 oF) for 60 min.
Operating Set Temperature is equal to User Set Temp. ≤ - 2 oC(28.4 oF) for 120 min.
Temperature (TOS = TUS). After either case of the above three, the unit
“AUTO” mode will switch from cooling to heating will operate with “COOL” mode and the
when the room temperature decreases below the microprocessor of the PC-board will stop both
operating set temperature by 3.5 oC. the indoor and outdoor fan motors.
TR ≤ TOS – 3.5 oC (6.3 oF) or TR ≤ TUS – Defrost cycle is completed after 10 minutes of
3.5 oC (6.3 oF). starting it or when the outdoor sensor reads 10
o
C which ever is first.
If the present operating mode is heating:
When the defrost cycle is completed, the
Operating Set Temperature is below User Set
operating mode is re-changed to “HEAT”.
Temperature by 1.5 oC (2.7 oF) (TOS = TUS –
1.5 oC (2.7 oF).
“AUTO” mode will switch from heating to cooling Temp (oC)
when the room temperature increases above the
operating set temperature by 3 oC (5.4 oF) +3
TR ≥ TOS + 3 oC (5.4 oF) or TR ≥ TUS + 1.5 oC Time (min)
(2.7 oF). 0
0 30 60 120
-2
6) “DEFROST” Function
(Heat Pump Models Only): -4
Requires an outdoor temperature sensor -6
connected to the PC-board. The function is
activated in the “HEAT” mode to de-ice the -8
outdoor coil when working in low ambient
temperature. The Defrost control is function in
both time and ambient temperature.
When the outdoor sensor reads 3 oC (5.4 oF)
or higher for more than 2 minutes, the defrost
controller is deactivated and its timer is reset.

“AUTO” Mode curve:

+2 Comp. ON
4 W V OFF H
Comp. ON

+1 H Comp. ON Comp. ON
H H
M
TUS M
M
M M M M
Tos
Comp. OFF
Tos
Comp. OFF Comp. OFF
L L
-1 L L M
L L

Comp. OFF Comp. OFF M L


Comp. OFF M Comp. OFF
Tos
M
-2 H H
Comp. ON
Comp. ON

-3 L

Comp. ON
4 W V ON
-4 Indoor Fan OFF

-5

"Cool" mode "Heat" mode "Cool" mode

9-3
7) “HOT START” Function 9) “SLEEP” Function:
(Heat Pump Models Only): Saves energy and provides more comfortable
conditions by changing the set temperature.
Provides a time delay on the indoor fan motor
operation depending on the indoor coil
In “COOL” Mode
temperature.
The temperature increases by 2 oC (3.6 oF) above
The indoor fan motor will not start till the indoor the set temperature within 2 hours.
coil sensor reads above 18 oC (64.4 oF).
The fan motor will run at low speed then Temp (oC)
resume its user set speed when indoor coil
sensor reads above 37 oC (98.6 oF). Ts + 2 //
High
Medium
Indoor Fan
ON Temperature Low speed Low Ts + 1
≤ 18 oC
OFF
Ts + ½
ON Compressor
OFF Time Ts
Time (hr)
0 ½ 1 2
Sleep ON Sleep OFF
8) “ANTI-FREEZE” Function:
Available with “COOL” mode to protect the indoor In “HEAT” Mode
coil from icing when its temperature is less than or The temperature decreases by 2 oC (3.6 oF)below
equal to 0 oC (32 oF)due to low amount of airflow the set temperature with in 2 hours.
rate across the coil. Icing could be caused by
excessive dirt on the coil or clogged air filters.
Temp (oC)
The function is activated when the indoor coil
sensor reads less than or equal to –2 oC Ts
(28.4 oF) for a period of 1 minute while the
compressor is running for at least 10 minutes. Ts - ½
Both the compressor and out door fan motor
are stopped till the ice on the coil is melted. Ts - 1
And they both will be re-operated when the
indoor coil sensor reads more than or equal to
12 oC (53.6 oF)for a period of 1 minute.
Ts - 2 //
Time (hr)

0 ½ 1 2
Sleep ON Sleep OFF

9–4
2 - When room temp. is higher than set
b- For “CAS” Models: temp., compressor runs; if room temp.
is lower than or equal to set temp.,
Control of indoor unit: compressor stops running.
1) “Temperature adjustment” 3 - Compressor stops running under
button ( WARM
TOO TOO ): detection mode or protection function.
COOL
a. when you fell too cool or too warm, you
can set temp. by “Temperature c. Prevent evaporator from frosting in
adjustment” button. When “Temperature order to prevent evaporator from
adjustment” button is pressed, indoor unit frosting, after the compressor has run
o
will make a beep sound. continually for 16 min., when 1 C(1.8
o
b. Press TOO COOL button, set temp. will F) above is detected by pipe temp.
rise by 1 oC(1.8 oF); press “TOO WARM” thermistor, the compressor will stop
button, set temp. will reduce by 1 oC(1.8 running. In any of the following
o
F). conditions, frosting prevention will
end:
2) Cooling operation: 1 - Pipe temp. thermistor attains 10 oC(18
o
Press operation mode switching button to F) or above;
select cooling mode, will appear on 2 - Room temp. is equal to or below set
operation display screen of remote temp;
3 - Cooling mode stops or is converted to
controller.
another mode.
a. Time sequence diagram under cooling Notes: if jumper wire on indoor control
mode: panel is disconnected, initial temp. of
Press down frosting prevention will change from 1 to
“power” 3oC(1.8 to 5.4 oF).
button to Room Temp. Room Temp. Press down
start equal to the higher than the “power” button to
operation. set one. set one. stop operation. d. Frosting protection:
When temp. of evaporator is lower than or
control circuit

equal to 15 oC(27 oF), frosting protection


Temp.

ON will operates as follows:


OFF 1 - Condition of starting up:
After compressor has continued
Set by remote controller. running for 3 min., if evaporator keeps
ON
below or equal to 15 oC(27 oF) for 3
Indoor
Fan

OFF
mi., the frosting protection function is
enabled.
Set by remote controller. 2 - Frosting protection:
motor
Vane

ON The compressor stops running for 6


OFF min., and then restarts. Within the first
10 min. after compressor restarts, if
Auxiliary the starting up condition is met again,
electric OFF the indoor and outdoor unit will stop
heater running and the operating panel will
ON
display this.
Compressor

OFF
3 - Condition of ending:
If within the above time, starting up
condition is not met, or the cooling
*1: At least 3 min. mode ends or is converted to another
mode, the frosting protection function
1:Even room temp. is higher that set temp. is disabled.
during this period, compressor will still
maintain its 3 min. delay. e. Control of indoor fan:
If the fan speed selection button on the
b. Control of compressor: remote controller is pressed down, high or
1 - 3 min. delay: low speed of indoor fan is available. But if
To avoid overload, when compressor abnormity of outdoor unit is detected, the
stops running, it will not restart again indoor fan will reduce to low speed and
unless 3 min. time delay this is independent of remote controller
settings.

9-5
f. Control of air supply vane: • Temp. control circuit open, whatever
Air supply vane is set by remote controller. room tem. is like compressor will stop
g. Detection of outdoor unit abnormity: 10 min..
When compressor has continued running for 3 4 - Frosting protection:
min., if difference between room temp. and During dehumidifying, operation of
evaporator temp. is out of range C and continue frosting protection is same as in
for 1 min., indoor fan speed will turn to low cooling mode.
speed. 5 min. later, if difference is still out of 5 - Frosting prevention:
range C, the outdoor unit is judged to be During dehumidifying, operation of
abnormal in operation. Compressor will stop frosting prevention is not done.
running and the operating panel will display this.
Range C: Temp. of evaporator < room Temp. 5 c. Control of indoor fan:
o
C(41oF). Indoor fan runs at low speed, being
synchronous with compressor.
3) Dehumidifying operation:
Press operation mode switching button to d. Control of air supply vane:
select dehumidifying mode . Same as in cooling mode.
Will appear on operation display screen of
remote controller. e. Detection of outdoor unit
a. Time sequence diagram under abnormity:
dehumidifying mode: In dehumidifying mode, outdoor unit
abnormity detection is disabled.
Indoor Temp. control

ON ON 4) Heating operation:
circuit

OFF OFF Press operation mode switching


Low speed
button to select heating mode, will
appear on operation display screen of
OFF OFF OFF
Fan

remote controller.
In heating operation, warm air stays in the
Compressor
upper part of room, and unit is also
of outdoor OFF OFF
fan installed in upper part, so measured temp.
Compressor and indoor fan run as follows: is slightly higher than actual room temp.,
Auxiliary OFF
heater and the difference is about 4 oC(7.2oF).
So that there should be a 4 oC(7.2oF)
b. Control of Compressor: correction upon measured temp. by room
1 - 3 min. delay: temp. thermistor.3
To avoid overload, when compressor
stops running, it will not restart unit 3 min. a. Time sequence diagram under
later. heating mode:
2 - Compressor stops running under detection Press down
mode or protection function. “power”
3 - Compressor and indoor fan run as follows: button to Room Temp. Room Temp. Press down
When room temp. < 18 oC(64.4oF), start equal to the lower than the “power” button to
operation. set one. set one. stop operation.
compressor will not start up. When room
control circuit

temp. ≥ 18 oC(64.4oF), compressor will


start up and operate intermittently and its ON
on/off time is entirely controlled by on/off
Vane Indoor Temp.

OFF
of temp. control and the following room
temp.. After compressor runs for 3 min.: Control of indoor fan.
ON
• Temp. control circuit closed, and room OFF
motor Fan

tem. > 28 oC(82.4oF): compressor runs 6


min., stops 3 min..
• Temp. control circuit closed, and room ON
Set by remote controller.
tem. > 26 ~ 28 oC(78.8 ~ 82.4oF): OFF
compressor runs 4 min., stops 3 min..
Auxiliary
• Temp. control circuit closed, and room electric
tem. > 24 ~26 oC(75.2 ~ 78.8 oF): heater
compressor runs 2 min., stops 3 min.. ON
Compressor

• Temp. control circuit closed, and OFF


room tem. < 28 oC(82.4oF):
compressor stops 3 min.. *1: At least 3 min.

9-6
b. Control of Compressor: e. Control of air supply vane:
6 - 3 min. delay: See control of air supply vane.
To avoid overload, when compressor
stops running, it can will not restart unit 3 f. Removal of remaining heat:
min. later. Within 1 min. after compressor shuts
7 - When room temp. is lower than set temp.,
down, indoor fan runs at low speed.
compressor runs; if room temp. is higher
than or equal to set temp., compressor
stops running. g. Overheat prevention:
8 - Compressor stops running under detection When room temp. ≥ 60 oC(140 oF),
mode or protection function. auxiliary heater is disabled.
When room temp. ≥ 55 oC(131 oF),
auxiliary heater is enabled.
c. Overheat protection:
1 - Condition of starting up:
When ≥ 70 oC(158 oF) is detected by the 5) Air supply operation:
pipe temp. thermistor, the overheat Press operation mode switching button to
protection function is enabled. select air supply mode, will appear on
2 - Overheat protection: operation display screen of remote
The compressor stops running for 6 min., controller. (only indoor fan runs, outdoor
and then restarts. unit will not run).
Within the first 10 min. after compressor
restarts, if the starting up condition is met 6) Timer operation:
again, the indoor and outdoor unit will stop a. Press ON/OFF button of remote controller
running and the operating panel will to start up air conditioner.
display this. b. Check current time setting, if current time
3 - Condition of ending: is not set, timer will not work.
If within the above time, starting up c. Press timed ON or timed OFF button to
condition is not met, or the heating is select timer operation.
converted to another mode or the temp. Timed ON button.
controller closes, the overheat protection Timed OFF button.
function is disabled. d. Press clock setting buttons “HR” and
“MIN” to set timer.
d. Control of indoor fan: Timer is set by 10 min. when sign “ “ or
Control of indoor fan determined by “ “ appears on display screen, “HR”
and “MIN” button are enabled, sign will
the set temp., room temp. and temp.
stop flashing 1 min. later.
of evaporator. e. Cancellation:
1 - At the beginning of heating mode: Timer setting can be cancelled with timer
If < 35oC(95 oF) is detected by the pipe control button “ “ or “ “.
temp. thermistor, fan will run at ultra low To cancel auto starting up function, press
speed for 5 min.. “ “ again.
If ≥ 35oC(95 oF) is detected by the pipe To cancel auto shutting down function,
temp. thermistor, fan will run at low speed press “ “ again.
for 2 min. and then to be set by remote When timer setting is cancelled, set time
controller. will disappear from screen.
2 - During running: f. Programmed timer:
If temp. of evaporator is higher than room Auto start up and auto shut down can be
temp. by over 5oC(41 oF), indoor fan speed used in combination, “ “ shows the
is set by remote controller. sequence of each step.
If not, the fan will stop.
3 - After compressor stops running:
If temp. of evaporator is higher than room
temp. by over 5oC(41 oF), indoor fan will run
at ultra low speed.
If not, the fan will stop.
4 - During overheat prevention period:
Speed of indoor fan is set by remote
controller.

9-7
7) Control of air supply vane: 10) Function of drain pump:
a. The vane motor of indoor unit is a When cooling or dehumidifying mode
synchronous one, with one micro switch starts, drain pump starts up.
for detecting site of vane. When a failure occurs, or shutting down,
When pressing (vane button), or exiting these two mode, drain pump will
direction of air supply can be selected. run on for 3 min. and then shuts down. In
1 - ( ) appears on remote controller, vane forced operation, drain pump runs.
may swing automatically. • When placing detector of drain pump
2 - ( ) appears on remote controller, vane in air, the drain pump can run
turns to 10o with horizontal and stops. normally.
3 - ( ) appears on remote controller, vane • When placing detector of drain pump
turns to 30o with horizontal and stops. in water for over 1 min., the drain
4 - ( ) appears on remote controller, vane pump is judged to be in failure, see
turns to 60o with horizontal and stops. failure display.
5 - ( ) appears on remote controller, vane
turns to 70o with horizontal and stops.
b. In cooling mode, if fan speed is low, vane
will not able to performance item “3”, but
there is display of item “3” on remote
controller.
c. In cooling or dehumidifying mode, if fan
speed is low, and vane is operating as set
to angle “4” or “5”, after 1 hour, vane will
automatically turn to angle “2” to avoid
condensing.
d. When starting up in heating mode,
however remote controller is set, vane will
stop at angle “2” to avoid cold air from
blowing out, remote controller can be
used some 2 min. later to set operation.

8) Failure display:
When failure occurs in use, air conditioner
will stop automatically and enter self
check mode. When failure occurs,
operation lamp will flash (0.5s on, 0.5s
off). And during detecting period, all
execute components do not work.

9) Time shortening function:


Indoor unit is equipped with a shorting
wire plug. In short circuit, 3 min. delay
protection of compressor is shortened to
3s. Time of other operations turns from
X min. To Xs.

9-8
c- For “TFD” Models:
2) “COOL” Mode:
The unit will be “ON” and “OFF” according to
both the room and set temperature.
1) PC-Board Features:
The indoor fan motor runs at selected speed.
In Auto fan speed, the indoor fan will run as
a. Compressor ON/OFF Protection:
folllow:
The 4-way valve is ceased for 2 minutes to
prevent the refrigerants abnormanl noise when High speed when Tr ≥ Ts+40C()
the heating operation is off or switched to other Medium speed when Tr ≥ Ts+20C()
operation modes. Low speed when Tr < Ts+20C()
The compressor will be “ON” when the room
b. 120 Sec. minimum run-time for 4W-valve: temperature reaches 1 oC (1.8 oF) above the
The compressor incorporate 90 seconds minimum set temperature, and will be “OFF” when the it
run-time for the thermostat cycle. It cannot be cut decreases 1 oC (1.8 oF) below the set
out before running with the current mode for 90 temperature.
seconds. The 4-way valve will be “OFF” all the time.
The Outdoor fan will be cycling “ON” and
c. Overload protection “OFF” according to the compressor status. (1)
(Heat Pump models only): Optional “Low-Ambient control Kit” keeps the
system running with ambient temperature
During heating operation, overheating protection below 20 oC (68 oF) by controlling the outdoor
system controls both of compressor and outdoor fan speed.
fan motor to restrain the rise in high pressure.
Over heating system will be activated if indoor Temp
pipe sensor sence as following:
If the Tcoil IN > 610C() the Outdoor fan motor will be
ON. If the Tcoil IN < 53 0C() the Outdoor fan motor Ts + ½
will be OFF.
Ts Time
If the Tcoil IN > 630C() for 15 second the
compressor will be OFF. If the Tcoil IN < 53 0C()
for 6 minutes the compressor will be ON. If the
Tcoil IN exceeds 630C again within 10 minutes the Ts - 1
unit will be turned off and can not recover
automatically.
Thermostat

ON
OFF
d. Low Gas Protection:
The system will consider the gas pressure in the circuit
ON
to be low and the system will cut out if the indoor coil
Indoor

temperature ( T coil IN ) cannot meet the one of the OFF


Fan

following conditions for 15 minutes of operation:


Compressor

3 min
- T coil ≤ 24 oC (75.2 oF) (Cool mode).
IN
- T coil IN ≥ 20 oC (68 oF) (Heat mode). ON
OFF

ON
Outdoor 4-Way

OFF
Valve

(1)
ON
Fan

OFF
Crank-case

ON
Heater

OFF

(1) If the system is equipped with a low ambient kit, it keeps the
o o
system running even if the outdoor temp. drops below 20 C (68 F)
by controlling outdoor fan speed.

9-9
3) “HEAT” Mode (Heat Pump Models 4) Dry Mode:
Only):
The setting temperature ranges from 180C(64.50F)
The unit will be “ON” and “OFF” according to to 300C(860F)
both the room and set temperature.
The indoor fan motor runs at the selected The unit will operate with in “Dry” Mode under
speed. The “Hot Start” function will avoid indicated zones below:
introducing cold air to the room. In Auto fan Zone A: Tr>280C(65.50F)
speed, the indoor fan will run as folllow:
Zone B: 280C(65.50F)>Tr>260C(630F)
High speed when Tr ≥ Ts-40C()
Medium speed when Tr ≥ Ts-20C() Zone C: 260C(630F)>Tr>240C(750F)
Low speed when Tr < Ts-20C() Zone D: Tr<Ts
The compressor will be “ON” when the room
temperature reaches 1 oC (1.8 oF) below the
set temperature, and will be “OFF” when the
room temperature increases 1.5 oC (2.7 oF) Temp (oC)
above the set temperature. +2
The 4-way valve will be “ON” all the operating
time. It is ceased for 2 minutes when the +1
heating operation is “OFF” Time
Ts
The Outdoor fan will be “ON” and “OFF”
according to the compressor and outdoor -1
temperature.
-2
Crankcase Heater will be “ON” all the time.
-3
Temp (oC) A B A B C D C
Ts +1 ½

Ts + 1 Zone “A”
ON
Ts + ½
OFF
9 min 3 min
Compressor
Ts
ON
Time
Ts - ½ Indoor Fan
OFF

Ts - 1
Zone “B”
ON

OFF Compressor
Thermostat

7 min 3 min
ON
OFF ON
Delay by
“Hot
Indoor Fan
OFF
Start”
Indoor

ON
Fan

OFF Zone “C”


ON
3 min
Compressor

3 min delay
OFF Compressor
5 min
ON
ON
OFF Indoor Fan
OFF
4-Way
Valve

ON
OFF Zone “D”
ON

OFF Compressor
Outdoor

ON
Fan

OFF
ON
Indoor Fan
OFF
Crank-case

4) “DRY
Heater

ON
OFF

9 - 10
8) “ANTI-FREEZE” Function:
5) “AUTO” Mode:
Available with “COOL” mode to protect the indoor
Depending on the room temperature at starting coil from icing when its temperature is less than 1
operation, the operation mode and set o
C (oF)due to low amount of airflow rate across
temperature are set automatically as following: the coil. Icing could be caused by excessive dirt
Tr ≥ 250C() : The cooling mode operation started, on the coil or clogged air filters.
the 240C() is slected automatically.
The function is activated when the indoor coil
210C<Tr<250C : The dry mode operation start, the sensor reads less than 1oC ( oF) while the
230C set temperature is selected automatically. compressor is running for at least 16 minutes.
Tr ≤ 210C() : Both the compressor and out door fan motor
A) “Cooling Only” Models: The fan mode are stopped till the ice on the coil is melted.
operation started on the user setting And they both will be re-operated when the
speed. indoor coil sensor reads more than or equal to
B) “Heat Pump” Models: The heating mode 10 oC (53.6 oF) while the compressor has been
operation started, the 230C() set “OFF” for 3 minutes.
temperature is selected automatically.

6) “DEFROST” Function
(Heat Pump Models Only):
Requires an outdoor temperature sensor
connected to the PC-board. The function is
activated in the “HEAT” mode to de-ice the
outdoor coil when working in low ambient
temperature. The Defrost control is function in
both time and temperature.
When the outdoor sensor reads -5 oC (oF) the
defrost controller is activated.
The compressor, outdoor fan motor and
indoor fan motor are turned “OFF”. 40
seconds later the 4W-valve is the turned
“OFF”, 10 second later the compressor is
turned “ON”.
Defrost cycle is completed after 8 minutes of
starting it or when the outdoor sensor reads 8
o
C which ever is first.
When the defrost cycle is completed, the
operating mode is re-changed to “HEAT”.
The Compressor is turned “OFF”, outdoor fan
motor is turned “ON”, the indoor fan motor is
controlled by “Hot start” function.

7) “HOT START” Function


(Heat Pump Models Only):
Provides a time delay on the indoor fan motor
operation depending on the indoor coil
temperature.
The indoor fan motor will not start till the indoor
coil sensor reads above 26 oC (oF).
The fan motor will run at low speed till the
indoor coil sensor reeds above 350C() then
resume its user set speed.
High
Low speed Medium
ON
Indoor Fan
Low
OFF Temperuature
Temperature >350C
<26 oC Compressor
ON
OFF Time 9 - 11
A - Capacity Correction Factor Related Piping Length :

Ref. PIPING length (One Way)


Mode COOLING HEATING
Model
m(ft) 4(13) 12(40) 16(54) 20(66) 24(80) 30(100) 34(113) 40(133) 4(13) - 24(80) 30(100) 34(113) 40(133)
HWC009/OR*C009 0.960
HWC012/OR*C012 0.958
HWC020/OR*C018 0.973 0.960
HWC020/OR*C020(1) 1.000 0.971 0.961 0.945 0.935 1.000
HWC024/OR*C025 0.969 0.958 0.943 0.935
HWC030B/OR*C030 0.969 0.951 0.913 0.900 0.978
0.935
HWC036B/OR*C036 0.977 0.961 0.930 0.910 0.979

HWC 009 N/OR*C009 0.959


HWC 012 N/OR*C012 0.961
1.000 1.000
HWC 020 N/OR*C020(1) 0.965 0.961 0.945 0.935
HWC 024 N/OR*C025 0.964 0.958 0.943 0.935

CFU013/OR*C012
CFU018/OR*C018 0.963
0.975
CFU020/OR*C020 0.962 0.950 0.942
1.000 1.000
CFU025/OR*C025 0.961 0.945 0.935
CFU030/OR*C030 0.972 0.959 0.916 0.975
0.941 0.930
CFU036/OR*C036 0.977 0.961 0.928 0.978

DBC018/OR*C018 0.969 0.951


DBC020/OR*C020 0.983 0.971 0.963 0.953
DBC024/OR*C025 0.984 0.974 0.964 0.954
DBC030/OR*C030 1.000 0.978 0.962 0.948 0.934 0.888 1.000 0.978
DBC036/OR*C036 0.970 0.950 0.931 0.912 0.896 0.977
DBC048/OR*C050 0.973 0.966 0.959 0.948 0.930 0.914 0.902 0.978 0.971 0.968
DBC060/OR*C060 0.972 0.967 0.954 0.941 0.934 0.923 0.908 0.975 0.969 0.966

CAS024/OR*C020 0.983 0.976 0.962


CAS024/OR*C025 0.975 0.945 0.935
CAS048/OR*C030 1.000 0.927 0.910 1.000 0.977
0.961
CAS048/OR*C036 0.977 0.935 0.920 0.910 0.978
CAS048/OR*C050 0.925 0.916 0.905 0.900 0.975 0.968 0.967

TFD025/OR*C020 0.983 0.976 0.962


TFD025/OR*C025 0.975 0.945 0.935
TFD048/OR*C036 1.000 0.927 0.910 1.000 0.977
0.961
TFD048/OR*C050 0.977 0.935 0.920 0.910 0.902 0.890 0.978 0.969 0.966
TFD050/OR*C050 0.925 0.916 0.905 0.900 0.976 0.968 0.965
(1) This model works with Reciprocating compressor, for rotary compressor the maximum equavilant length is 20 meter.
e.g: Cooling Capacity of HWC 020 at 35 0C outdoor and 27 DBT 0C, 19.5 indoor condition is ( 19500 BTU ) with 4 meter piping.
In case of 12 meter piping Capacity =19500 x 0.971 =18934 BTU 11-1
B- Additional R22

Additional R22 (gm/m)


HWC009/OR*C009 20
HWC012/OR*C012 25
HWC020/OR*C018
HWC020/OR*C020(1) 30
HWC024/OR*C025
HWC030B/OR*C030
45
HWC036B/OR*C036

HWC 009 N/OR*C009 20


HWC 012 N/OR*C012 25
HWC 020 N/OR*C020(1)
30
HWC 024 N/OR*C025

CFU013/OR*C012 20
CFU018/OR*C018
25
CFU020/OR*C020
CFU025/OR*C025
30
CFU030/OR*C030
CFU036/OR*C036 35

DBC018/OR*C018
DBC020/OR*C020
30
DBC024/OR*C025
DBC030/OR*C030
DBC036/OR*C036 35
DBC048/OR*C050 40
DBC060/OR*C060 45

CAS024/OR*C020 20
CAS024/OR*C025 25
CAS048/OR*C030
30
CAS048/OR*C036
CAS048/OR*C050 35

TFD025/OR*C020 20
TFD025/OR*C025 25
TFD048/OR*C036 30
TFD048/OR*C050 35
11-2
CASE A CASE B CASE C

Outdoor Unit Indoor Unit H L H L H L


OR*C009 HWC009 6 (20) 12 (40) 5 (17) 12 (40) 0 12 (40)

OR*C012N
HWC012N 6 (20) 12 (40) 5 (17) 12 (40) 0 12 (40)
series "G+"

HWC012 * 0
OR*C012 7.5 (25) 12 (40) 6 (20) 12 (40) 12 (40)
CFU013 0

HWC020 0
OR*C018 CFU018 7.5 (25) 16 (54) 6 (20) 16 (54) 0 16 (54)
DBC018 0

HWC020 works with rotary


20 (67) 20 (67) 0 20 (67)
compressor

HWC020 series"classic" & /"G+" 24 (80) 24 (80) 0 24 (80)


OR*C020 CFU020 7.5 (25) 20 (67) 6 (20) 20 (67) 0 20 (67)
DBC020 0
CAS024 20 (67) 20 (67) 0 20 (67)
TFD025 0

HWC024 series"classic" & "G+" 0

CFU025 0
OR*C025 7.5 (25) 24 (80) 6 (20) 24 (80) 24 (80)
DBC024 0
CAS024 0
TFD025 0

HWC030 0
OR*C030 CFU030 10 (32) 30 (100) 8.5 (28) 30 (100) 0 30 (100)
DBC030 0

HWC036 0
CFU036 0
OR*C036 DBC036 10 (32) 30 (100) 8.5 (28) 30 (100) 0 30 (100)
CAS036 0
TFD048 0

DBC048 0
OR*C050 CAS048 10 (32) 40 (133) 8.5 (28) 40 (133) 0 40 (133)
TFD048 0

OR*C060 DBC060 10 (32) 40 (133) 8.5 (28) 40 (133) 0 40 (133)

All Dim. In m (ft) 11-4


Field Refrigerant Piping
Piping Diameter:

Equivalent M 1-6 6 - 12 12 - 16 16 - 20 20 - 24 24 - 30 30 -36 30 - 40


Length ft 3 - 20 20 - 40 40 - 54 54 - 66 66 - 80 80 - 100 100 - 133 100 - 133
Model Name S L S L S L S L S L S L S L S L

Wall Mounted classic


HWC009(*4/*6)/OR*C009 9.5(3/8") 12.7(1/2") 6.4(1/4")
6.4(1/4")
HWC012(*4/*6)/OR*C012 12.7(1/2")
HWC020/OR*C018
15.9(5/8") 9.5(3/8")
HWC020/OR*C020 15.9(5/8") 9.5(3/8") 19(3/4") 9.5(3/8")
19(3/4") 9.5(3/8") 19(3/4") 9.5(3/8")
HWC024/OR*C025
HWC030/OR*C030
19(3/4") 9.5(3/8") 19(3/4") 9.5(3/8") 22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2")
HWC036/OR*C036

Wall Mounted Series "G+"


HWC009(N4/N6)/OR*C009 9.5(3/8") 12.7(1/2") 6.4(1/4")
6.4(1/4")
HWC012(N4/N6)/OR*C012 12.7(1/2")
HWC020/OR*C020 15.9(5/8") 9.5(3/8")
15.9(5/8") 9.5(3/8") 19(3/4") 9.5(3/8")
HWC024/OR*C025 19(3/4") 9.5(3/8") 19(3/4") 9.5(3/8")

CFU013/OR*C012 12.7(1/2") 6.4(1/4") 12.7(1/2")


CFU018/OR*C018
CFU020/OR*C020 15.9(5/8") 15.9(5/8")
9.5(3/8") 19(3/4") 9.5(3/8") 19(3/4") 9.5(3/8") 19(3/4") 9.5(3/8")
CFU025/OR*C025 9.5(3/8")
CFU030/OR*C030
19(3/4") 19(3/4") 22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2")
CFU036/OR*C036 22.2(7/8") 12.7(1/2")

DBC018/OR*C018 15.9(5/8")
DBC020/OR*C020 15.9(5/8") 15.9(5/8")
9.5(3/8") 19(3/4") 9.5(3/8") 19(3/4") 9.5(3/8")
DBC024/OR*C025 9.5(3/8") 9.5(3/8") 19(3/4")
DBC030/OR*C030
19(3/4") 19(3/4") 22.7(7/8") 22.7(7/8") 22.7(7/8")
DBC036/OR*C036 22.2(7/8")
12.7(1/2") 12.7(1/2") 12.7(1/2")
DBC048/OR*C050 12.7(1/2")
22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2") 28.5(1 1/8") 28.5(1 1/8") 28.5(1 1/8") 28.5(1 1/8") 28.5(1 1/8") 12.7(1/2") 28.5(1 1/8") 12.7(1/2")
DBC060/OR*C060

CAS024/OR*C020C
15.9(5/8") 15.9(5/8")
CAS024/OR*C025C
9.5(3/8") 9.5(3/8") 19(3/4") 9.5(3/8") 22.2(7/8")
CAS048/OR*C030C 12.7(1/2") 22.2(7/8")
19(3/4") 19(3/4") 12.7(1/2") 22.2(7/8")
CAS048/OR*C036C 12.7(1/2")
CAS048/OR*C050C 22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2") 28.5(1 1/8") 12.7(1/2") 28.5(1 1/8") 28.5(1 1/8") 28.5(1 1/8") 28.5(1 1/8") 12.7(1/2") 28.5(1 1/8") 12.7(1/2")

TFD025/OR*C020
15.9(5/8") 15.9(5/8")
TFD025/OR*C025 9.5(3/8") 9.5(3/8") 19(3/4") 9.5(3/8") 22.2(7/8")
12.7(1/2") 22.2(7/8")
TFD048/OR*C036 19(3/4") 19(3/4") 12.7(1/2") 22.2(7/8")
12.7(1/2")
TFD048/OR*C050 22.2(7/8") 12.7(1/2") 22.2(7/8") 12.7(1/2") 28.5(1 1/8") 12.7(1/2") 28.5(1 1/8") 28.5(1 1/8") 28.5(1 1/8") 28.5(1 1/8") 12.7(1/2") 28.5(1 1/8") 12.7(1/2")

L: Liqued
S: Suction 11-5