Auto-transformer starters 8
Star-delta starters 9
Summary 11
There are many misconceptions about motor starting. It is often believed that the
start current of a motor under full voltage conditions depends on the driven load,
but this is totally incorrect.
The start current of the motor depends on the For many induction motors the current does
motor design, rotor speed and stator voltage not fall significantly until the motor speed is
from zero speed until full speed is reached. over 90%.
The load only influences the time taken for the
Starting an unloaded motor DOL is just as
motor to reach full speed. The current/speed
severe on the supply as starting a fully loaded
curve of the motor is independent of
motor, except that the overload is for a shorter
all external influences other than
time. NB: Some clamp type ammeters with
stator voltage.
slow response times do not show the true
The motor will always initially draw locked start current.
rotor current (LRC) when started direct-on-
line (DOL). The current will stay at LRC as the
motor begins to accelerate, and fall as the
motor approaches full speed.
The simplest form of motor starter is the Full voltage starting also causes a torque
full voltage direct-on-line (DOL) or transient from zero to locked rotor torque
across-the-line starter, consisting of an (LRT) at the instant of contactor closure. The
isolation contactor and motor overload instantaneous torque application results
protection device. In some industries DOL in a severe mechanical shock to the motor
starters are used extensively. However in drive system and the machine. The damage
many situations full voltage starting is not from the torque transient
Run contactoris more severe
Thermal
and start overload
permitted by the power authority due to than the damage from the maximum torque
resistors
the high starting currents and the voltage amplitude.
disturbances they cause.
Start Start
Current Torque
6 x FLC
5 x FLC
4 x FLC
3 x FLC
2 x FLC
FLC
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Rotor Speed
Three traditional methods of reduced voltage Switching to full voltage at 80% speed results
starting are commonly used: in a current of typically 75% LRC, or 500%
FLC. At 50% speed, the current would be
-- Primary resistance starting
90% LRC. The maximum current will be
-- Auto-transformer starting
significantly reduced only if the changeover
-- Star-delta starting
occurs at a rotor speed of 90% or more.
Reduced voltage starting is used extensively The speed of the motor at changeover
and in many areas is mandatory. The use of depends on the torque of the motor at the
reduced voltage starting has been promoted reduced voltage, and the speed/torque curve
as a means of reducing power supply voltage of the load. If the time in the reduced voltage
disturbances resulting from motor starting. is too short, the motor may not have time to
accelerate to the speed where the available
In reality the benefits are marginal due to the
torque equals the load torque, resulting in a
misapplication of reduced voltage starters.
premature transition to full voltage.
Many installations would suffer fewer
disturbances if a full voltage starter replaced The two controllable parameters which
the poorly applied reduced voltage starting determine the reduced voltage starters
system. performance are therefore start time and
start voltage. If either of these parameters
The reduced voltage starter must be able
is not correctly set, then the reduced voltage
to accelerate the motor to almost full speed
starter is of limited advantage.
before stepping to full voltage. A step to full
voltage at much less than rated motor speed The transition from the reduced voltage to full
will result in a current step that can be very voltage can be open transition switching or
close to LRC. closed transition switching.
2 x FLT
6 x FLC 2 x FLT 6 x FLC
5 x FLC 5 x FLC
CURRENT
4 x FLC 4 x FLC
FLT
FLT
3 x FLC 3 x FLC
CURRENT
2 x FLC 2 x FLC
TORQUE
FLC FLC
TORQUE
FAN SPEED/TORQUE CURVE FAN SPEED/TORQUE CURVE
10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Motor Start
contactor (B)
Run Start Start
contactor contactor (B) contactor (A)
Closed transition 3 auto-transformer
2 x FLT
6 x FLC 2 x FLT
6 x FLC
5 x FLC 5 x FLC
4 x FLC 4 x FLC
FLT
3 x FLC 3 x FLC FLT
CURRENT
2 x FLC 2 x FLC
CURRENT
TORQUE
10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Start Start
Current Torque
2 x FLT
6 x FLC
5 x FLC
4 x FLC
FLT
3 x FLC
CURRENT
2 x FLC
TORQUE
FLC
FAN SPEED/TORQUE CURVE
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Rotor Speed