TOR-APP F-5

Attachment 2

Workflow for Formwork Structure (1/2)

Contractor submits PE-endorsed Contractor submits Method


design calculations & drawings. Statement & Risk Assessment

QP(S) review calculations


(WSH Regs. Factor of Safety = 2.0)
QP(S) review DESIGN &
CHECKING

Accepted? Accepted?
NO NO
YES YES

Formwork structure materials


delivered to site

Contractor PM/CM, Formwork Supervisor, QP(S)/SRE/RE &


LTA (PM/SPE/SO Rep) check material quality (checklist used)

Defective material NO
rejected Accepted?

YES

Material capacity
NO Appropriate material
factor & design
revised capacity factor used?

YES

Formwork structure installed by


Scaffold Contractors
Formwork Supervisor and
Trained & Certified Scaffold Erectors
INSTALLATION
Site adjustments
made
Contractor PM/CM, Formwork Supervisor, QP(S)/SRE/RE
& LTA (PM/SPE/SO Rep) inspection (checklist used)
& INSPECTION

NO
YES
NO
Is redesign required? Accepted?

YES

PE inspection

NO
Accepted?

YES
PE issues COS for formwork structure
(1) for reinforcement to be installed

CONTRACT RD276
TOR-APP F-6

Attachment 2

Workflow for Formwork Structure (2/2)

Installation of reinforcement

Contractor PM/CM, Formwork Supervisor, QP(S)/SRE/RE


& LTA (PM/SPE/SO Rep) re-inspection (checklist used)

Adjustments NO
made Accepted?
REBAR FIXING
YES &
PE re-inspection (<24 hrs before concreting)
RE-INSPECTION
NO
Accepted?

YES
PE issues COS for formwork structure (2) for
concreting to commence

Concreting proceeds. Formwork Supervisor


checks formwork structure during concreting

NO Leaks
End or adjustments required?

YES

NO
<300mm depth poured?

YES

Formwork Supervisor/
PE/QP(S)/Contractor/LTA(PD)
to assess if safe to enter

YES
Safe to enter?
Concreting stops for minor
repairs & adjustments
CONCRETING
NO
&
No entry allowed.
MONITORING
No repairs allowed.

Formwork Supervisor/
PE/QP(S)/Contractor/LTA(PD)
to advise on whether safe to
continue concreting

YES Safe to
continue concreting?

NO

Concreting stops.
PE to advise on way
forward (concrete to be
washed out?)

CONTRACT RD276