Amrita Institute of Medical Science at Faridabad Schedule of Quantities

S.No Description Unit Qty. Price Amount

SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF UPS &


I.
BATTERY SYSTEM
Sub Head-I : 500 kVA/kW UPS each with minimum 3 no. of battery
A. strings (Minimum 288000 VAH per UPS for 15 Min Battery backup)

Supply, unloading, shifting, installation, testing & commissioning of micro


processor controlled 500 kVA/kW UPS operating in parallel redundant
mode for 100% load, IGBT based rectifier to achieve input THDI < 3% and
input power factor of greater than 0.99 at 100% loading with AC to AC
Efficiency> 94.5% . True Online Double Conversion (VFI as per IEC 62040-
1 3) UPS using PWM IGBT technology , 3 Phase input and 3 phase 415 V
output UPS system; and comprising of the following complete as required
and as per specification:

Fully rated Rectifier cum charger unit and 100% rated Inverter unit
a
Integrated in UPS module
Fully rated Inbuilt static switch at the inverter output and 100% rated Inbuilt
b static switch at the static bypass line integrated in UPS module

Web-enabled Monitoring and Management through SNMP protocols for


c No. 4
multi-OS environments with below features :
External Load bank of 500 kVA / UPS along with input & output cables and
Breakers for Testing UPS Performance before putting up plant load incase
d UPS does not have Smart Power Testing Feature as mentioned in Specs.

Giving notifications like e-mail, paging notification, broadcast notification,


battery replacement notification, run event-based scripts

Event logging, data logging and action logging (with date, time, description

of fault and event)
Run the battery diagnostic test
Automated unattended shutdown of computers
Local notification through audible alarm
RS-485 port with BUS/MODBUS card, communication protocol to integrate

the UPS with building management system
Life Cycle Monitoring System required to predict health of consumables

AC/DC Capacitors, Battery Bank & Cooling Fans.

KCB & Associates UPS System


Amrita Institute of Medical Science at Faridabad Schedule of Quantities

S.No Description Unit Qty. Price Amount


2 Battery Banks & Associated Infrastructure
Battery Banks comprising of Valve Regulated Lead Acid Sealed
Maintenance Free batteries of minimum 5 years design life to provide 15
minutes backup at full load i.e. 500 kVA/KW, 1.7 ECV & 0.9 pf with
individual UPS (Minimum VAH: 288000 VAH per UPS). The batteries shall
be installed on open racks for quick replacement and servicing. The
temperature sensor shall be provided in the battery section for
temperature compensated charging. The bank of batteries shall comprise
of required numbers of batteries connected in series and there should be
atleast two banks connected in parallel to provide redundancy with each
UPS so that incase of failure of one battery bank, the other bank shall
2.1
provide reduced backup time for the particular UPS.

(Vendor to provide complete details of make of Batteries, ampere hour


ratings, no. of Batteries, Expected life, Final discharge voltage, Nominal
float voltage, Battery recharge time & configuration of back up time, Battery
sizing Calculations)
Set 4

Supply, unloading, installation, testing & commissioning of open type MS


racks to house SMF batteries for 500 kVA UPS system along with suitable
interconnecting links, moulded case circuit breaker having thermal,
2.2 magnetic & automatic U/V trip mechanisms Protection of Battery Banks
etc. complete as required & as per specifications

Supply, laying, testing & commissioning of NYVIN Type Glass Wool


Insulated cable for interconnections between UPS to UPS, UPS to
2.3 batteries, complete as required for 500 kVA UPS (Approx 10 mtr spacing to
be considered between UPS & batteries Bank placed in two separate
room.

3.0 External Galvanic Isolation Transformer


A external Isolation transformer, k1 rated Copper wound at the complete No. 4
Input of the UPS system (As per IEEE 1100-2005). Transformer rating shall
be 110% of the UPS rating i.e. 550 kVA/KW.
3.1
Please note*: Inbuilt Transformer in the UPS sytem is not acceptable.

Total

Sub Head-II : 250 kVA/kW UPS each with minimum 3 no. of battery
B. strings (Minimum 288000 VAH per UPS for 30 Min Battery Backup)

Supply, unloading, shifting, installation, testing & commissioning of micro


processor controlled 250 kVA/kW UPS operating in parallel redundant
mode for 100% load, IGBT based rectifier to achieve input THDI < 3% and
input power factor of greater than 0.99 at 100% loading with AC to AC
Efficiency > 94.5% . True Online Double Conversion (VFI as per IEC
1 62040-3) UPS using PWM IGBT technology , 3 Phase input and 3 phase
415 V output UPS system; and comprising of the following complete as
required and as per specification:

Fully rated Rectifier cum charger unit and 100% rated Inverter unit
a
Integrated in UPS module

KCB & Associates UPS System


No. 4 -
Amrita Institute of Medical Science at Faridabad Schedule of Quantities

S.No Description Unit Qty. Price Amount

Fully rated Inbuilt static switch at the inverter output and 100% rated Inbuilt
b static switch at the static bypass line integrated in UPS module

Web-enabled Monitoring and Management through SNMP protocols for


c No. 4 -
multi-OS environments with below features :
External Load bank of 250 kVA / UPS along with input & output cables and
Breakers for Testing UPS Performance before putting up plant load incase
d UPS does not have Smart Power Testing Feature as mentioned in Specs.

Giving notifications like e-mail, paging notification, broadcast notification,


battery replacement notification, run event-based scripts

Event logging, data logging and action logging (with date, time, description

of fault and event)
Run the battery diagnostic test
Automated unattended shutdown of computers
Local notification through audible alarm
RS-485 port with BUS/MODBUS card, communication protocol to integrate

the UPS with building management system
Life Cycle Monitoring System required to predict health of consumables

AC/DC Capacitors, Battery Bank & Cooling Fans.
2 Battery Banks & Associated Infrastructure
Battery Banks comprising of Valve Regulated Lead Acid Sealed
Maintenance Free batteries of minimum 5 years design life to provide 30
minutes backup at full load i.e. 250 kVA/KW, 1.7 ECV & 0.9 pf with
individual UPS (Minimum VAH: 288000 VAH per UPS). The batteries shall
be installed on open racks for quick replacement and servicing. The
temperature sensor shall be provided in the battery section for
temperature compensated charging. The bank of batteries shall comprise
of required numbers of batteries connected in series and there should be
atleast two banks connected in parallel to provide redundancy with each
UPS so that incase of failure of one battery bank, the other bank shall
2.1
provide reduced backup time for the particular UPS.

(Vendor to provide complete details of make of Batteries, ampere hour


ratings, no. of Batteries, Expected life, Final discharge voltage, Nominal
float voltage, Battery recharge time & configuration of back up time, Battery
sizing Calculations)
Set 4 -

Supply, unloading, installation, testing & commissioning of open type MS


racks to house SMF batteries for 250 kVA/kW UPS system along with
suitable interconnecting links, moulded case circuit breaker having thermal,
2.2 magnetic & automatic U/V trip mechanisms Protection of Battery Banks
etc. complete as required & as per specifications

Supply, laying, testing & commissioning of NYVIN Type Glass Wool


Insulated cable for interconnections between UPS to UPS, UPS to
2.3 batteries, complete as required for 250 kVA/kW UPS (Approx 10 mtr
spacing to be considered between UPS & batteries Bank placed in two
separate room.

3.0 External Galvanic Isolation Transformer

KCB & Associates UPS System


Amrita Institute of Medical Science at Faridabad Schedule of Quantities

S.No Description Unit Qty. Price Amount

A external Isolation transformer, k1 rated Copper wound at the complete No.


Input of the UPS system (As per IEEE 1100-2005). Transformer rating shall
be 110% of the UPS rating i.e. 275 kVA/kW.
3.1 4
Please note*: Inbuilt Transformer in the UPS sytem is not acceptable.

Total -

Sub Head-III : 250 kVA/kW UPS each with minimum 2 no. of battery
C. strings (Miniumum 144000 VAH per UPS for 15 Min Battery Backup)

Supply, unloading, shifting, installation, testing & commissioning of micro


processor controlled 250 kVA/kW UPS operating in parallel redundant
mode for 100% load, IGBT based rectifier to achieve input THDI < 3% and
input power factor of greater than 0.99 at 100% loading with AC to AC
Efficiency >94.5%. True Online Double Conversion (VFI as per IEC 62040-
1 3) UPS using PWM IGBT technology , 3 Phase input and 3 phase 415 V
output UPS system; and comprising of the following complete as required
and as per specification:

Fully rated Rectifier cum charger unit and 100% rated Inverter unit
a
Integrated in UPS module
Fully rated Inbuilt static switch at the inverter output and 100% rated Inbuilt
b static switch at the static bypass line integrated in UPS module

Web-enabled Monitoring and Management through SNMP protocols for


c No. 2 -
multi-OS environments with below features :
External Load bank of 250 kVA / UPS along with input & output cables and
Breakers for Testing UPS Performance before putting up plant load incase
d UPS does not have Smart Power Testing Feature as mentioned in Specs.

Giving notifications like e-mail, paging notification, broadcast notification,


battery replacement notification, run event-based scripts

Event logging, data logging and action logging (with date, time, description

of fault and event)
Run the battery diagnostic test
Automated unattended shutdown of computers
Local notification through audible alarm
RS-485 port with BUS/MODBUS card, communication protocol to integrate

the UPS with building management system
Life Cycle Monitoring System required to predict health of consumables

AC/DC Capacitors, Battery Bank & Cooling Fans.
2 Battery Banks & Associated Infrastructure

KCB & Associates UPS System


Amrita Institute of Medical Science at Faridabad Schedule of Quantities

S.No Description Unit Qty. Price Amount

Battery Banks comprising of Valve Regulated Lead Acid Sealed


Maintenance Free batteries of minimum 5 years design life to provide 15
minutes backup at full load i.e. 250 kVA/KW, 1.7 ECV & 0.9 pf with
individual UPS (Minimum VAH: 144000 VAH per UPS). The batteries shall
be installed on open racks for quick replacement and servicing. The
temperature sensor shall be provided in the battery section for
temperature compensated charging. The bank of batteries shall comprise
of required numbers of batteries connected in series and there should be
atleast two banks connected in parallel to provide redundancy with each
UPS so that incase of failure of one battery bank, the other bank shall
2.1
provide reduced backup time for the particular UPS.

(Vendor to provide complete details of make of Batteries, ampere hour


ratings, no. of Batteries, Expected life, Final discharge voltage, Nominal
float voltage, Battery recharge time & configuration of back up time, Battery
sizing Calculations)
Set 2 -

Supply, unloading, installation, testing & commissioning of open type MS


racks to house SMF batteries for 250 kVA UPS system along with suitable
interconnecting links, moulded case circuit breaker having thermal,
2.2 magnetic & automatic U/V trip mechanisms Protection of Battery Banks
etc. complete as required & as per specifications

Supply, laying, testing & commissioning of NYVIN Type Glass Wool


Insulated cable for interconnections between UPS to UPS, UPS to
2.3 batteries, complete as required for 250 kVA/kW UPS (Approx 10 mtr
spacing to be considered between UPS & batteries Bank placed in two
separate room.

3.0 External Galvanic Isolation Transformer


A external Isolation transformer, k1 rated Copper wound at the complete No.
Input of the UPS system (As per IEEE 1100-2005). Transformer rating shall
be 110% of the UPS rating i.e. 275 kVA.
3.1 Please note*: Inbuilt Transformer in the UPS sytem is not acceptable. 2

Total -

KCB & Associates UPS System


Description Amount
S.No

Sub Head-I : 500 kVA/kW UPS each with minimum 3 no. of battery strings
A.
(Minimum 288000 VAH per UPS for 15 Min Battery backup)

Sub Head-II : 250 kVA/kW UPS each with minimum 3 no. of battery strings
B.
(Minimum 288000 VAH per UPS for 30 Min Battery Backup)

Sub Head-III : 250 kVA/kW UPS each with minimum 2 no. of battery strings
C.
(Miniumum 144000 VAH per UPS for 15 Min Battery Backup)

Grand Total
288000