1MRK 505 031-BEN
Page 1
Revision B
Issued: November 2003
Data subject to change without notice
)HDWXUHV High speed general differential protection. Stability is ensured for through faults, even
Minimal operating time around 10 ms with heavy CT saturation, and a maximum
remanence in the CT core at high-speed
No interposing CTs are required, easy
auto-reclosing
installation in existing stations for improved
power network stability Different CT ratios can be used in all bays.
Although any CT ratio difference can be
Numerical design with advanced features
accommodated a difference larger than
Three-phase version of the terminal with 10:1 is not practically viable.
one measuring zone for up to six three-
One hardware version for 1A and 5A CTs
phase CT inputs
No switching in CT circuits
One-phase version of the terminal with two
measuring zones for up to eighteen CT No separate check zone or extra measur-
inputs. Three terminals per protection ing criteria are necessary. The algorithm
scheme are usually required, one for each provides full stability for open CT circuit
phase. condition
Cost effective summation type differential Software functionality ensures simple
principle is available with one-phase ver- adaptation to buses with the CT on only
sion of the terminal. one side of the bus-section or bus-coupler
circuit breaker
General differential protection can be used
for protection of: Fixed, factory pre-configured input/output
configuration
- meshed corners
Display of analog service values for each
- T-connections
phase and zone of protection
- reactors
Event list with the last sixteen events
- autotransformers
Continuous self monitoring and diagnostics
- generators
Front mounted menu driven display with a
- motors key pad for simple setting of the terminal
- HV capacitor banks Remote data communication via LON bus
- Busbars with up to six bays per protec- Available for 19 inch rack mounting, sur-
tion zone (three-phase version) face mounting or flush mounting
- Busbars with up to eighteen bays per Hardware characteristics:
protection zone (one-phase version) - Fixed binary input and output modules
Low CT requirement, only 2 milliseconds to
saturation needed for correct operation - Optional separate COMBITEST test
switch for reliable and safe testing
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 2
&
(
ZA
ZB
(&
1 2 6
1 2 3 4 5 6
&
(
&
(
& &
(
(
ZA BS ZB
(& (&
1 2 3 4 5 1 2 3 4 5
Fig. 8 Two Single Busbar Sections with Bus-Section Breaker and up to five feeder bays on each side
For each of the six three-phase current possible to block the differential function
inputs, the rated CT primary current can with an external binary signal.
be set. In this way adaptation to different
CT ratios is provided in the simplest way. The innovative measuring algorithm pro-
The minimum pick-up value for the differ- vides stability also for the open CT circuit
ential current is then set to give a suitable condition, which means that no separate
sensitivity for all internal faults. Multi- check zone is necessary. Pick-up current
phase as well as single phase faults are level for open CT detection can usually
detected and tripped at high speed in sol- be set to detect the open circuit condition
idly or low resistance earthed systems. for the smallest CT. This built-in feature
For busbar protection applications typi- allows the protection terminal to be set
cal setting value for the minimum differ- very sensitive, lower than maximum
ential operating current is from 50% to through-load current. At detection of
100% of the biggest CT. However for open circuits, the differential protection
other types of applications, for example will be instantly blocked and an alarm is
generator differential, this value can be given. When the fault has been cor-
set more sensitive, down to 5% of the rected, a manual reset must be given.
biggest CT. This can be done locally from the front
HMI, via the LON communication or via a
All current inputs are indirectly provided binary input.
with a restraint feature. The operation is
based on the well proven RADSS per- Each CT input can be included or
centage restraint stabilization principle, excluded from the differential function in
with an extra stabilization feature to stabi- software. This can be done by setting or
lize for very heavy CT saturation. Stability activated externally via a binary input.
for external faults is guaranteed if a CT is This feature gives a simple control over
not saturated for at least two milliseconds the connected current inputs for multi-
during each power system cycle. It is also zone applications. At the same time it
gives the possibility for disconnection of
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 4
region
d
I
ZA ZA
&
(
&
(
(&
&
(
&
(
(&
(&
ZB
1 2 18
1 2 18
&
(
Fig. 10 Single Busbar Section with up to nine or Fig. 12 1 Breaker Station with up to 18 diameters
eighteen bays (one or two AIM modules)
ZA ZB
&
(
&
(
&
(
1 2 8 1 2 8
Fig. 13 Two Single Busbar Sections with Bus-Sectionalising Disconnector and up to eight feeder bays
on each side of the switchgear
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 6
ZA BS ZB
&
(
&
(
&
(
1 2 8 1 2 8
Fig. 14 Two Single Busbar Sections with Bus-Section Breaker and up to eight feeder bays
on each side of the switchgear
ZA BS ZB
&
( &
(
&
( &
(
&
( &
(
1 2 17 1 2 17
Fig. 15 Two Single Busbar Sections with Bus-Section Breaker and up to seventeen feeder bays
on each side of the switchgear
For each of the eighteen current inputs, external faults is guaranteed if a CT is not
the CT rated primary current can be set. saturated for at least two milliseconds
In this way adaptation to different CT during each power system cycle. Both
ratios is provided in the simplest way. The protection zones can be individually
minimum pick-up value for the differential blocked with external binary signals.
current is then set to give a suitable sen-
sitivity for all internal faults. Multi-phase The innovative measuring algorithm pro-
as well as single phase faults are vides stability also for open CT circuit
detected and tripped at high speed in sol- condition, which means that no separate
idly or low resistance earthed systems. check zone is necessary. Pick-up current
For busbar protection applications typi- level for open CT detection can usually
cal setting value for the minimum differ- be set to detect the open circuit condition
ential operating current is from 50% to for the smallest CT. This built-in feature
100% of the biggest CT. allows the protection terminal to be set
very sensitive, lower than maximum
All current inputs are indirectly provided through-load current. At detection of
with a restraint feature. The operation is open circuits, the differential protection
based on the well proven RADSS per- will be instantly blocked and an alarm is
centage restraint stabilization principle given. This feature can however not be
with an extra stabilization feature to stabi- fully utilised when the summation princi-
lize for heavy CT saturation. Stability for ple is used.
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 7
Id [Primary Amps]
front HMI, via the LON communication or
via a binary input.
Operate
in
I
=
region
Each CT input can be included or
d
I
excluded from two differential functions in
software. This can be done by setting or 'LII2SHU/HYHO
activated externally via binary input. This s=0.53
feature gives a simple control over the Iin [Primary Amps]
connected current inputs for multizone
en01000028.vsd
applications. At the same time it gives the
possibility for disconnection of the CT
cores for bus-section or bus-coupler bays Fig. 16 Diff. Function Operating Characteristic
with a CT only on one side of the circuit
breaker. This ensures correct and fast The settings can be changed only from
fault clearance of faults between the CT the front human-machine-interface (HMI).
and the circuit breaker within these bays. It is possible to block any setting changes
via an external binary signal.
A load transfer functionality is included
into the design, which allows very simple 6FKHPHHQJLQHHULQJ
applications for double busbar sections.
Load transfer is automatically started The one-phase RED 521 terminal allows
when any of the CT inputs 3 to 18 is con- an effective scheme solution for applica-
nected at the same time to both differen- tions on larger busbars, due to the soft-
tial zones. It is also possible to start load ware feature, which allows simple control
transfer externally via a binary input. over the connected CT inputs.
When load transfer is started, CT inputs 3
to 18 are all included simultaneously into Overall scheme engineering is quite sim-
both zones. However CT inputs 1 and 2 ple and very much standardised. Princi-
are at the same time disconnected from ple drawings, for typical protection
both zones. Therefore the CT inputs 1 schemes, are available from ABB.
and 2 shall be dedicated as the bus-cou-
pler CT inputs for these applications. The simple engineering and factory made
configuration combined with the high
3DUDPHWHUVHWWLQJV speed tripping has made RED 521 a nat-
ural choice as additional protection for
RED 521 terminal has wide setting facili- substations for improved power system
ties to ensure application flexibility. The stability.
settings are organized as the configura-
tion settings and the differential protec- Future switchgear extensions can be
tion function settings. One setting group either pre-engineered in the original
is available. scheme design or the auxiliary equip-
ment can be easily added at a later
Under configuration settings data, the CT stage. If the overall required number of
primary rated currents and the way how CT inputs are included in RED 521 hard-
each CT input is connected to the protec- ware at the ordering stage, no software
tion zones are entered. changes are required within the RED 521
terminals to facilitate these extensions.
Under settings for the differential func-
tion, the minimum operate current and ,QGLFDWLRQVHYHQWVDQGVHUYLFHYDOXHV
sensitivity for open CT detection are
entered. Both settings are made directly Internal relay supervision, open CT detec-
in primary amperes. These two settings tion and trip indications are available on
are common for both differential functions the front HMI LEDs (green, yellow & red
within the terminal. The operating slope LED respectively). The time-tagged event
for the differential function is fixed to 53% list with resolution of 1 ms is available on
in the algorithm. the front HMI or from another location
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 8
'HVLJQ The physical design of the RED 521 ter- the terminal with one or two analog input
minal is in line with the other products in modules. Each analog input module has
the REx 5xx series. It is housed in nine current inputs. The analog input
painted sheet steel enclosure, suitable for module contains analog to digital convert-
different mounting by use of particular ers (AD-converters). Some digital low-
mounting accessories. Wire connections pass filtering of AC input signals is per-
are made at the rear side of the terminal. formed on the AIM module as well.
All wires are connected by compression
type of terminal tightened by a screw. 0DLQ SURFHVVRU PRGXOH does the ana-
Optical fibres for data communication are log and digital data processing for the
also connected at the rear side. On the protection functions. A communication
front there is an HMI-panel with the com- interface for connection to a station con-
mon look and feel with the other 500 trol system (SCS) via LON bus can be
series terminals. included as well.
Behind the front cover, there is an inter- 3RZHUVXSSO\PRGXOH with DC/DC con-
connection board (motherboard) to which verter supplies all power required by the
printed circuit boards (PCBs) are plugged internal electronic circuits and provides
in from the rear side. The input module the required barrier against electromag-
for analog AC quantities is fixed mounted netic disturbances.
and the connection terminal for these cir-
cuits are also fixed mounted. The con- %LQDU\LQSXWRXWSXWPRGXOHV can be of
nection terminals for the DC contact two different types. Binary input module,
circuits are of the multi-pole detachable BIM, with 16 optocoupler inputs and a
type, to facilitate easy disconnection for binary output module, BOM, with 24 out-
exchange of PCBs. put relay contacts.
7HFKQLFDOGDWD
7DEOH (QHUJL]LQJTXDQWLWLHVUDWHGYDOXHVDQGOLPLWV
4XDQWLW\ 5DWHGYDOXH 1RPLQDOUDQJH 2SHUDWLYHUDQJH
Rated Current Ir = 1 A or 5 A (0,2-30) x Ir (0,03-100) x Ir
Burden < 0,25 VA at Ir (0,2-4) x Ir continuously 100 x Ir for 1 s*
Frequency fr = 50/60 Hz 2,5 Hz 5 Hz
Auxiliary DC voltage EL EL = (24-60) V 20% 20%
EL = (90-250) V 20% 20%
Power consumption
basic terminal 33 W
Binary input (16) module
DC voltage RL RL24 = 24/30 V 20% 20%
RL48 = 48/60 V 20% 20%
RL110 = 110/125 V 20% 20%
RL220 = 220/250 V 20% 20%
power consumption
each I/O board 0,5 W
RL24 = 24/30 V max. 0,05 W/input
RL48 = 48/60 V max. 0,1 W/input
RL110 = 110/125 V max. 0,2 W/input
RL220 = 220/250 V max. 0,4 W/input
Binary output (24/12)
module
power consumption
each output board 1W
each output relay 0,25 W
Ambient temperature 20C -5C to +55C -20C to +70C
Ripple in dc auxiliary voltage max. 2% max. 12% Full wave rectified
Relative humidity 10-90% 10-90% 0-95%
* Max 350 A for 1 s when COMBIFLEX test switch is used
7DEOH ,QIOXHQFLQJIDFWRUV3HUPLVVLEOHLQIOXHQFH
'HSHQGHQFHRQ :LWKLQQRPLQDOUDQJH :LWKLQRSHUDWLYHUDQJH
Ambient temperature 0,01%/1C Correct function
Ripple in auxiliary DC voltage negligible Correct function
Interruption in auxiliary DC voltage
without resetting 50 ms 50 ms
no unwanted function 0- 0-
7DEOH ,QVXODWLRQWHVWV
7HVW 7\SHWHVWYDOXHV 5HIHUHQFHVWDQGDUGV
Dielectric test 2,0 kV AC 1 min IEC 60255-5
Impulse voltage test 5 kV, 1,2/50 s, 0,5 J IEC 60255-5
Insulation resistance > 100 MOhm at 500 V DC IEC 60255-5
7DEOH 0HFKDQLFDOWHVWV
7HVW 7\SHWHVWYDOXHV 5HIHUHQFHVWDQGDUGV
Vibration Class I IEC 60255-21-1
Shock and bump Class I IEC 60255-21-2
Seismic Class I IEC 60255-21-3
7DEOH &RQQHFWLRQV\VWHP
0D[LPXP 0D[LPXPORDG 0D[LPXPORDG
&RQQHFWRUW\SH 5DWHGYROWDJH VTXDUHDUHD FRQWLQXRXV V
Binary input/output 250 V AC 2,5 mm2 10 A 30 A
module voltage com- 2 x 1 mm2
pression
Analog input module 250 V AC 4 mm2 20 A 500 A
voltage/current com-
pression
Fiber connectors Glass: Bayonet ST
Plastic: Snap in Simplex Latching
7DEOH $GGLWLRQDOJHQHUDOGDWD
Dimensions
Width 483 mm (1/1 of 19 rack)
Height 6U = 266 mm
Depth 245 mm
Storage temperature -40C to +70C
7DEOH (YHQW/LVW
)XQFWLRQDOLW\ %LQDU\9DOXH5HFRUGHGRQ&KDQJH
Time tagging resolution 1 ms (relative time)
Number of Event List entries 16
7DEOH 5DWHGSRZHUV\VWHPIUHTXHQF\
4XDQWLW\ 3DUDPHWHU 9DOXHRU5DQJH
Rated frequency fr 50 or 60 Hz
7DEOH *HQHUDOG,IIHUHQWLDOSURWHFWLRQ
)XQFWLRQ 3DUDPHWHU 9DOXHRU5DQJHDQGVWHS
Differential current operating level Diff Oper Level 1 - 10000 A; in step of 1A
Stabilizing slope s 53% fixed
Open CT sensitivity Open CT Level 1 - 5000 A; in step of 1A
Operate time 12 ms, typically
Trip Reset Time 10 cycles, typically
7DEOH &7LQSXWFRQILJXUDWLRQSDUDPHWHUV
)XQFWLRQ 3DUDPHWHU 9DOXHRU5DQJHDQGVWHS
Set CT rated primary current CT Prim Inp x -10000 - +10000 A; in step of 1A
Determine the way how CT input is con- ZoneSelection / CTx Contact Ctrl / Fixed to ZA /
nected to the protection zone (Fixed to ZB)
( ) only available in one-phase
version of the terminal
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 12
7HUPLQDOGLD 7KUHHSKDVHWHUPLQDO
JUDPV
RED 521
(en00000672.eps)
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 13
7HUPLQDOGLD 2QHSKDVHWHUPLQDO
JUDPV
RED 521
(en00000673_1)
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 14
RED 521
(en00000673_2)
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 15
2UGHULQJ6KHHW The numerical, three-phase, general differential terminal RED 521 is designed for fast and
IRU7KUHH3KDVH selective protection of meshed corners, T-connections, generators, motors, reactors, HV capac-
7HUPLQDO itor banks, smaller busbars etc. Up to six three-phase bays can be included in the measuring
zone. One 16 channel input board and one 24 channel output board with fixed configured
inputs respectively outputs are provided. One or two AIM boards, each equipped with three,
three-phase analog inputs, can be selected. A CIM board for PPH communication can be addi-
tionally provided. No CAP or SMS modules are available for this version.
+DUGZDUHEDVHPRGXOHV
6RIWZDUHEDVHIXQFWLRQV
Service value reading for differential current and incoming (i.e. bias) current
Configuration of the three-phase RED 521 terminal is fixed with inputs and outputs according
to the terminal diagram 1MRK 002 002-AA
2UGHULQJ1XPEHU 4XDQWLW\
%DVLFGDWD
Nominal frequency: 50/60 Hz (selectable by setting)
Rated CT input current 1/5 A (selectable by tap)
Rated auxiliary dc voltage EL 24-60 V 90-250 V
for Power Supply Module
Select rated dc voltage RL 24/30 V 48/60 V 110/125 V 220/250 V
for optocoupler binary inputs
&RPPXQLFDWLRQPRGXOH
6HULDO/21FKDQQHOPRGXOHIRUUHPRWHFRPPXQLFDWLRQ
Plastic 1MRK 001 608-AA
Glass 1MRK 001 608-CA
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 16
0HFKDQLFDORSWLRQV
)LUVWWHVWVZLWFK
COMBITEST test switch module RTXP 24 No 1 for the first AIM. 1MRK 000 371-EA
6HFRQGWHVWVZLWFK
COMBITEST test switch module RTXP 24 No 2 for the second AIM. 1MRK 000 371-EB
127(
The test switches have external star point connection of three-phase CT groups.
Each RTXP 24 test switch module will be mounted in a separate RHGS 6 case with window door.
One test switch per analog input module (AIM) is required so two test switches are needed if two analog input
modules are used. Connections between the AIMs and test switches are not made in the factory. These connec-
tions have to be done by the user.
2SWLRQDOPRXQWLQJGHWDLOV
Mounting details with IP40 degree of protection from the front for protection terminal case and if needed for extra test
switch case(s):
Protection One Test Two Test
terminal switch case switch cases
19 rack 1MRK 000 020-CA 1MRK 000 020-BE 1MRK 000 020-BB
Wall mounting 1MRK 000 020-DA 1MRK 000 020-DA 1MRK 000 020-DA
Flush mounting 1MRK 000 020-Y 1MRK 000 020-Y 1MRK 000 020-Y
Additional sealing for IP54 1MKC 980 001-2
(Only available for flush
mounted terminal)
No mounting details
$FFHVVRULHV 4XDQWLW\
Users Guide for RED 521 1MRK 505 031-UEN
For our reference and statistics we would be pleased if we are provided with the following application data:
2UGHULQJ6KHHW The one-phase RED 521 general differential protection terminal can be used for protection of
IRU2QH3KDVH larger busbars with up to 18 bays. Two measuring zones (one phase) are available in each ter-
7HUPLQDO minal. Usually three terminals per protection scheme are required, one for each phase. One or
two AIM modules, each equipped with nine current analog inputs, can be included. The one-
phase RED 521 terminal is also equipped with two or three 16 channel input boards (depending
on number of ordered AIM modules) and one 24 channel output board. All these boards are
with fixed configuration. In addition, a CIM board for PPH communication can be provided.
No CAP or SMS modules are available for this version.
+DUGZDUHEDVHPRGXOHV
6RIWZDUHEDVHIXQFWLRQV
Service value reading for the differential current and the incoming (i.e. bias) current.
Configuration of the one-phase RED 521 terminal is fixed with inputs and outputs according to
the terminal diagram 1MRK 002 004-AA.
2UGHULQJ1XPEHU 4XDQWLW\1RWH1RUPDOO\PXOWLSOHRI
LHHWF
bays 1MRK 002 003-AA
bays 1MRK 002 003-BA
%DVLFGDWD
Nominal frequency: 50/60 Hz (selectable by setting)
Rated CT input current 1/5 A (selectable by tap)
Rated auxiliary dc voltage EL 24-60 V 90-250 V
for Power Supply Module
Select rated dc voltage RL 24/30 V 48/60 V 110/125 V 220/250 V
for optocoupler binary inputs
&RPPXQLFDWLRQPRGXOH
6HULDO/21FKDQQHOPRGXOHIRUUHPRWHFRPPXQLFDWLRQ
Plastic 1MRK 001 608-AA
Glass 1MRK 001 608-CA
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 18
$X[LOLDU\VXPPDWLRQ&7 4XDQWLW\
3 pcs SLCE 8-1 summation transformers on apparatus plate (2U high) 1/1 A 1MRK 000 643-EA
3 pcs SLCE 8-1 summation transformers on apparatus plate (2U high) 5/1 A 1MRK 000 643-FA
0HFKDQLFDORSWLRQV
)LUVWWHVWVZLWFK
COMBITEST test switch module RTXP 24 No 1 for the first AIM. 1MRK 000 371-EA
6HFRQGWHVWVZLWFK
COMBITEST test switch module RTXP 24 No 2 for the second AIM. 1MRK 000 371-EB
127(
The test switches have external star point connection of three-phase CT groups.
Each RTXP 24 test switch module will be mounted in a separate RHGS 6 case with window door.
One test switch per analog input module (AIM) is required so two test switches per each terminal are needed, if 18
bays version is used. Therefore if three terminals are ordered six test switches will be delivered. Connections between
the AIMs and the test switches are not made in the factory. These connections have to be done by the user.
2SWLRQDOPRXQWLQJGHWDLOV
Mounting details with IP40 degree of protection from the front for protection terminal case and if needed for extra test switch
case(s):
Protection One Test Two Test
terminal switch case switch cases
19 rack 1MRK 000 020-CA 1MRK 000 020-BE 1MRK 000 020-BB
Wall mounting 1MRK 000 020-DA 1MRK 000 020-DA 1MRK 000 020-DA
Flush mounting 1MRK 000 020-Y 1MRK 000 020-Y 1MRK 000 020-Y
Additional sealing for IP54 1MKC 980 001-2
(Only available for flush
mounted terminal)
No mounting details
$FFHVVRULHV 4XDQWLW\
Users Guide for RED 521 1MRK 505 031-UEN
For our reference and statistics we would be pleased if we are provided with the following application data:
6DPSOH Numerical differential protection terminal minal shall occur for CT open circuit con-
VSHFLILFDWLRQ is intended for the selective, reliable and dition and an alarm shall be issued to the
fast protection of busbars, T-connections, supervisory system. Stability of the differ-
meshed corners, generators, autotrans- ential function must be guaranteed even
formers, etc. The terminal shall be appli- for the case when only two feeders are
cable for the protection of medium connected to the zone of protection and
voltage (MV), high voltage (HV) and extra then one of the two CTs is accidentally
high voltage (EHV) installations at a open circuited under full through-load
power system frequency of 50Hz or condition. It shall be possible to reset the
60Hz. The terminal shall be able to detect CT open circuit condition locally or
all types of internal phase-to-phase and remotely via the communication. Reset of
phase-to-ground faults in solidly the CT open circuit condition shall only
grounded or low impedance grounded be possible if there is no differential cur-
power systems, as well as all internal rent detected in the protected zone.
phase-to-phase faults in isolated or high-
impedance grounded power systems. Future station extensions must not
require any software or hardware modifi-
For all applications, it shall be possible to cations within the protection terminal if
include 1A and 5A primary CTs, with up the finally required number of CT inputs
to 10:1 ratio difference within the same are allowed for in the terminal at the
differential protection zone. There shall ordering stage. It must be possible to add
be no requirements for any auxiliary CTs. future bays on a one-by-one basis.
Compensation of different main CT ratios
shall be achieved numerically by a Comprehensive and continuous self-
parameter setting. monitoring of the protection terminal shall
ensure no incorrect operations of the dif-
The differential protection function shall ferential function in case of internal relay
have completely phase-segregated mea- failure. The terminal shall be provided
surements. The minimal operating time in with a front mounted menu driven
case of internal fault shall be around 10 human-machine-interface. Display of the
milliseconds, with guaranteed stability of service values for differential current and
the differential function for external faults total through-load current for each phase
even with very high short-circuit currents and zone of protection shall be provided.
and heavy CT saturation. The facility to An event list with the last 16 events shall
selectively block differential functions be available. Communication to the sta-
with an external binary signal shall be tion control system shall be included.
provided.
The summation bus differential principle
The terminal shall include the ability to shall be available as a cost effective solu-
detect CT open circuit condition. No tion for less demanding applications.
incorrect operation of the protection ter-
ABB Automation Products *HQHUDOGLIIHUHQWLDOSURWHFWLRQ 5('
1MRK 505 031-BEN
Page 20
Compact current relay RXHL 411 (3Ph BF initiation) 1MRK 509 049-BEN
Breaker failure relay RAHB 411 (1Ph/3Ph initiation) 1MRK 509 070-BEN