Modular Gen-set Controller
Multiple Internal Software Configuration - MINT
User guide
!! Warnings !!
Remote control
InteliGen controller can be remotely controlled. In the event that maintenance needs to be done to the gen-
set, check the following to ensure that the engine cannot be started.
To be sure:
Disconnect remote control via RS232 line
Disconnect input REMOTE START/STOP
or
Disconnect output STARTER and output GCB CLOSE/OPEN
The InteliGen contains a large number of configurable setpoints, because of this it is impossible to describe
all applications. InteliGens functions are subject to change from SW version to SW version. This manual only
describes the product and is not guaranteed to be set for your application on arrival.
Text
PAGE (Capital letters in the frame) buttons on the front panel
Break Return (Italic) set points
Generator protections (Bold) Set point group
REMOTE START/STOP (Capital letters) binary inputs and outputs
Conformity declaration
Following described machine complies with the appropriate basic safety and health
requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
Switch InteliGen to MAN mode and disconnect the Binary outputs Starter and Fuel to
avoid unexpected automatic start of genset and GCB closing.
The following instructions are for qualified personnel only. To avoid personal injury do
not perform any action not specified in this User guide !!!
BI1
BI6
BI7
BI8
BI9
BI4
BI5
BI2
BI3
L1k
L2k
L3k
L1
L2
L3
L1
L2
L3
L1l
L2l
L3l
LB 5
iG-CU
EXTENSION MODULES
iG-PCM / iG-PCLSM
EXTENSION MODULES
iG-COM / iG-IOM
RS 232
BOOT JUMPER
(FUEL)
8 - 36 V DC
BO1
BO2
AI2 (TEMP)
AI3 (FUEL)
RPM GND
AI1 (OIL)
RPM IN
COM
+ -
BO3
BO4
BO5
BO6
BO7
BO8
BO9
IG-PCLSM Terminals
LSM+
AVRi+
Shield
GND
LSM-
AVRi-
LB 4
VoutR
Vout
BO12
BO13
BO11
+ -
BI10
BI12
BI13
BI11
Warning !!!
Switch IG-CU off before connecting IG-PCLSM !
IG-COM Terminals
There is different wiring of IG-COM CAN connectors from hardware version 4.0.
LB 4
CAN 2 EXTENSION MODULE CAN 1
CAN R 120
IG-MU Terminals
RS 422 LB 6
COM
COM
H
H
L
COM
RxB
RxA
TxB
TxA
CAN CAN
RS 232
RS 485
iG-MU
RS 485 / RS 422
RS 232
POWER
8-36V DC
Indication LED:
TxCAN, RxCAN Indicates data transfer on the CAN2 line.
TxD, RxD Indicates data transfer on the RS232 line.
RUN Lights when at least one other unit is active on the CAN2 bus.
Blinks when no unit is communicated on the CAN2 bus.
PWR Lights All time when power supply is switched on.
P4
P3
P1 P2
IGS-PTM is modification of standard IG-IOM module with four analog inputs, which can be configured for
range:
0 250 (suitable for Pt100, Ni100),
0 100 mV (suitable for thermocouples),
0 20 mA.
IGS-PTM can be connected to IG-CU or IS-CU. Detail description see in IGS-PTM manual.
AI4
C OM
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
iG-IOM
IG -C U
RS232
8-36V DC
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
Hint:
IG-IOM, IGS-PTM power supply indication LED :
lights when power supply is in the range
blinks when there is no communication between IG-CU and IG-IOM, IGS-PTM
1
113 (4,4")
2
130 (5,1")
123 (4,8")
~ 130 (5,1")
170 (8,87")
2
1
(0,9")
~ 110 (4,3")
iG-PCLSM iG-COM
24
80 (3,1")
42,5 (1,7")
45 (1,8")
iG-CU
185 (7,3")
AC1
OCOM
OUT2
AC2
0 - 230/277 - 400/480
36 (1,4)
LB 5 iG-AVRi
TRANS/LV
AVRi +
AVRi -
0 - 18
43 (1,7) 43 (1,7)
Secondary terminals
96 mm (3,8)
95 mm 43 mm
(3,7) (1,7)
IG-IOM
AI4
COM
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
iG-IOM
IG-CU
RS232
8-36V DC
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
95 mm 43 mm
(3,7) (1,7)
AO+
GND
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
AI4
AO-
0-20 mA
BINARY INPUTS ANALOG INPUTS ANALOG OUT
COMPENSATION
96 mm (3,8)
Rx
iGS-PTM
H COM L
CAN
CAN
Tx
LB 4
8-36V DC
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
95 mm 43 mm
(3,7) (1,7)
configuration - Binary outputs - (left bottom) button. Detail descriptions see in iGL-RA15.pdf user
guide.
54 (2,1)
44 (1,7)
106 (4,2)
120 (4,7)
125 (4,9)
~ 25 (1,0)
165 (6,5)
~ 75 (3,0)
~ 35 (1,4)
38 (1,5)
40 (1,6)
180 (7,1)
185 (7,3)
IG-MTU, IG-MTU-C
IG-MTU Separation transformers unit for InteliGen controller. It is used for three wire system, system with
separated Neutral or when galvanic separation between generator or mains voltage and
controller is required.
IG-MTU-C Separation transformers unit with additional filter for controller. It is used like IG-MTU in special
cases of extreme distortion of generator voltage by higher harmonics due to inverters etc..
LB 3
95 (3,74")
iG-MTU
N L1 L2 L3
155(6,10") 60 (2,36")
Hint:
IG-MTU-C phase shift is 6. Use two IG-MTU-C units for both generator and bus voltage measuring or set
Sync/Load ctrl: GtoB angle Req setpoint (-6 when IG-MTU-C is connected to Vg terminals).
IG-MTU and IG-MTU-C units are the same dimension and DIN 35 mm rail mounted.
ETHERNET LB 5
RJ 45
1 2
96 mm (3,8)
MODEM / IB CONFIG
iG-IB
IG-CU / DONGLE
3 4 5 6
95 mm 43 mm
(3,7) (1,7)
95 mm 43 mm
(3,7) (1,7)
BATTERY
STARTER
FUEL SOLENOID
FUEL LEVEL
WATER TEMP
OIL PRESSURE
DIESEL/GAS ENGINE
RPM
H L
COM COM
L H CAN
CAN EXTENSION MODULE CAN
G
G
Serial No.
GENERATOR
iG-COM
Inl L1k
Ink L1l
EXTENSION MODULES L2k
COM
0-5A
AI1 OIL
GENERATOR
L3k
AI2 TEMP L3l
AI3 FUEL
ANALOG INPUTS
N
RPM GND
Serial No.
L1
RPM
RPM IN
3 x 230 V
VOLTAGE
L2
GENERATOR
L3
BO1
L1
STARTER
START
L2
iG-CU
FUEL SOLENOID BO2
Generator C.B.
FUEL L3
GEN C.B. BO3
EXTENSION MODULES
LOAD RES. OK BO4 iG-PCM / iG-PCLSM
FIX
UNLOAD BI1
BO5 GEN C.B. FEED-BACK
HORN BO6 BI2 LOAD RESERVE
PRESTART BO7 BI3 SYST START / STOP
BINARY OUTPUTS
SYNCHRONISE BO8 BI4 EMERG STOP
BINARY OUTPUTS
SYST READY BO9 BI5
N
L3
L2
L1
CONFIGURABLE
BI6 ACCESS LOCK
BINARY INPUTS
SD OIL PRESS
+24V
BI7
BI8 SD WATER TEMP
RS 232
POWER
BI9 SD FUEL LEVEL
+ -
8 - 36 V DC
SIGNALS
CONTROL
RS-232C
Interface
PE
Modem or PC
SYSTEMSTART / STOP
MGCB
LOAD
Recommended wirings
IG-PCLSM
REGULATOR
AUTOMATIC
GOVERNOR
FROM GENERATOR
VOLTAGE
230/400 V
SPEED
iG-AVRi
TRANS
230/400 V
18 V
18 V AC
LOAD SHARING PARALLEL LINE
LB 5
+
-
LSM+
AVRi+
GND
Shield
VoutR
LSM-
Vout
AVRi-
LB 5
BO12
BO13
BO11
-
BI10
BI12
BI13
BI11
0 V DC
0 V DC
CONFIGURABLE
0- 2 0 m A
AI4
COM
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
ANALOG OUT
iG-IOM
IG-CU
RS232
BINARY OUTPUTS
POWER
8-36V DC
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
0 V DC
8 - 36 V D C
Hint:
Analog inputs COM terminal has to be connected to minus power supply.
IG-MU Wiring
RS485 / RS 422 connection
TxB B
TxA A RS485
IG-MU RxB
RxA
TxB
TxA RS422
IG-MU RxB
RxA
LOAD
GCB1
3x 3x
G1
CAN
3xUG
3xUB
3xIG
AVR
iG-AVRi
iG-PCLSM
OUT
iG-CU AVRi
iG-COM
AVRi
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
PRIORITY 0 LOAD SHARING LINE
PRIORITY
GCB2
SELECTOR 3x
G2
CAN
3xU B
3xUG
3xIG
AVR
iG-AVRi
iG-PCLSM
OUT
iG-CU AVRi
iG-COM
AVRi
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
PRIORITY 0
START/STOP
LOAD
3x MGCB GCB1
3x 3x
G1
CAN
3xU B
RES.OK.(1)
3xUG
RES.OK.(2)
3xIG
AVR
MGCB
MGCB iG-AVRi
iG-PCLSM
AVRi
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
PRIORITY 0 LOAD SHARING LINE
LOAD RESERVE 2
MGCB
PRIORITY
GCB2
SELECTOR 3x 3x
G2
CAN
3xUG
3xUB
3xIG
AVR
iG-AVRi
iG-PCLSM
OUT
iG-CU AVRi
iG-COM
AVRi
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
PRIORITY 0
START/STOP LOAD RESERVE 2
Specification
MGCB support
Gen-sets unload in island parallel
Power management (if IG-COMs are installed)
Hardware requirements
nx IG-CU
nx IG-COM (Optional)
nx IG-PCLSM
nx IG-AVRi, IG-AVRi-TRANS (Optional)
Hint:
Set SysAMFstrt del and SysAMFstp del setpoints at 1s for fast response
Input MCB FEEDBACK should not be configured
LOAD
U,f
T 3x
3x MCB GCB1
3x 3x 3x
G1
3x CAN
3xUG
U,f
3xUB
3xIG
AVR
(3.PH.RELAY) iG-AVRi
iG-PCLSM
KA AVRi
iG-CU AVRi
iG-COM
OUT
KA
MCB
Vout SPEED
MGC LSM
GOVERNOR
SYS START/STOP
PRIORITY 0 LOAD SHARING LINE
PRIORITY
GCB2
SELECTOR 3x
G2
CAN
3xUG
3xUB
3xIG
AVR
iG-AVRi
iG-PCLSM
AVRi
iG-CU AVRi
iG-COM
OUT
Vout SPEED
LSM GOVERNOR
SYS START/STOP
U,f PRIORITY 0
LOAD
U,f
T 3x
3x
MCB MGCB GCB1
3x 3x 3x 3x
G1
CAN
3xU G
3xU B
U,f
RES.OK.(1)
RES.OK.(2)
3xIG
AVR
MGCB
MGCB
iG-AVRi
iG-PCLSM
AVRi
iG-CU AVRi
iG-COM
OUT
MGCB
MCB
MCB
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
PRIORITY 0 LOAD SHARING LINE
LOAD RESERVE 2
MGCB
PRIORITY
GCB2
SELECTOR 3x 3x
G2
CAN
3xUG
3xUB
3xIG
AVR
iG-AVRi
iG-PCLSM
AVRi AVRi
iG-CU
iG-COM
OUT
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
U,f PRIORITY 0
LOAD RESERVE 2
Specification
Automatic start-up when the mains fails
Reclosing MCB after mains returns
MGCB support
Gen-sets unload in island parallel
Power management (if IG-COMs are installed)
Hardware requirements
1x Uf relay (Mains decoupling relay) unit + MCB control
nx IG-CU
nx IG-COM (Optional)
nx IG-PCLSM
nx IG-AVRi, IG-AVRi-TRANS (Optional)
Hint:
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Setpoint SysAMFstp del is used for GCB opening after the mains returns. It is similar to setpoint Mains Ret
del in Single Stand-by.
Input MCB FEEDBACK should not be configured
U,f
T 3x
3x MCB GCB1
3x 3x
G1
3x CAN
3xUB
3xUG
U,f
3xIG
AVR
(3.PH.RELAY) iG-AVRi
iG-PCLSM
KA AVRi
iG-CU AVRi
iG-COM
OUT
KA
MCB
MCB
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
PRIORITY 0 LOAD SHARING LINE
MCB FEEDBACK
PRIORITY
GCB2
SELECTOR 3x
G2
CAN
3xUG
3xUB
3xIG
AVR
iG-AVRi
iG-PCLSM
AVRi
iG-CU AVRi
iG-COM
OUT
PARALL.
TO MAINS
REQUIRED
Vout SPEED
MCB LSM
GOVERNOR
SYS START/STOP
U,f PRIORITY 0
MCB FEEDBACK
MCB
Specification
Synchronize gen-sets to mains
Import-Export or Base load power control
Automatic start-up when mains fails
After mains returns GCBs opening, reclosing MCB and synchronizing gen-sets to mains
Gen-sets unload
Power management (if IG-COMs are installed)
Hardware requirements
1x Uf relay unit (Mains decoupling relay) + MCB control
1x External Mains Load sharing module for Import-Export power control or Base load power control on
local Load sharing modules
nx IG-CU
Description
1) The system is started by the Uf relay or by the switch Parallel to mains required.
2) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Power
management by closing of SYS START/STOP input, if the gen-sets had not run in parallel to mains
before.
3) When mains returns, Uf relay opens SYS START/STOP, and GCBs are opened.
4) Bus 3 phase voltage relay detects no voltage and with its time delay closes MCB
5) If the switch Parallel to mains required is closed, gen-sets are again synchronized to the bus.
6) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
7) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
8) PRIORITY SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hint:
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by. If the input MCB FEEDBACK is active, the delay is 1s.
Setpoint SysAMFstp del is used for GCB opening after the mains returns. It is similar to setpoint Mains Ret
del in Single Stand-by. If the input MCB FEEDBACK is active, the delay for unloading is 1s.
LOAD
U,f
T 3x
MCB
3x
3x 3x
GCB1 3x
G1
3x
CAN
3xUG
U,f
3xUB
3xIG
AVR
iG-AVRi
KA
iG-PCLSM
AVRi
iG-CU AVRi
iG-COM
(3.PH.RELAY) OUT
KA
MCB
MCB Vout SPEED
LSM
GOVERNOR
EXT.SYN Kt SYS START/STOP
PRIORITY 0 LOAD SHARING LINE
MCB FEEDBACK
PRIORITY
GCB2 3x
SELECTOR G2
KA Kt
EXT.
SYN MCB CAN
3xUB
3xUG
3xIG
SYN.ENABLED AVR
iG-AVRi
iG-PCLSM
AVRi
iG-CU AVRi
iG-COM
OUT
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
MCB PRIORITY 0
MCB FEEDBACK
MCB
U,f
T 3x
MCB MGCB
3x
3x
3x
GCB1 3x
G1
3x
(3.PH.RELAY)
U,f CAN
3xU G
3xU B
KA
3xIG
AVR
iG-AVRi
G CB1
G CB2
KC
iG-PCLSM
AVRi
iG-CU AVRi O UT
iG-COM
KA
RES.O K(1)
RES.O K(2)
M G CB
MCB KC
Vout SPEED
M CB LSM
GOVERNOR
SYS START/STO P
EX T.SYN Kt MGCB MASTER SELECT LO AD SHARING LINE
LOAD RESERVE 2
MG CB MCB FEEDBACK
M ASTER SELECTO R 3x
GCB2 3x
KA Kt
G2
EX T.
SYN M CB CAN
3xU G
3xU B
3xIG
AVR
SYN.ENABLED
iG-AVRi
iG-PCLSM
AVRi
iG-CU AVRi O UT
iG-COM
Vout SPEED
LSM
GOVERNOR
SYS START/STO P
M CB M ASTER SELECT
LOAD RESERVE 2
M CB FEEDBACK
MCB
Specification
Automatic start-up when mains fails
After mains returns MCB synchronizing
One interrupt only stand-by
MGCB support
Gen-sets unload
Power management (if IG-COMs are installed)
Hardware requirements
1x Uf relay unit (Mains decoupling relay) + MCB control
1x External MCB Synchronizer
nx IG-CU
Hint:
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Time relay Kt is used for beginning of MCB synchronization after the mains returns. It is similar to setpoint
Mains Ret del in Single Parallel to Mains (SPtM) application.
Setpoint SysAMFstp del is not used in this case.
U,f
T 3x
3x MCB GCB1
3x 3x
G1
3x
CAN
3xUB
3xUG
U,f
3xIG
AVR
(3.PH.RELAY) iG-AVRi
iG-PCLSM
KA AVR
iG-CU AVRi i
iG-COM
OUT
KA
MCB
Vout SPEED
MCB LSM
GOVERNOR
SYS START/STOP
EXT.SYN Kt
PRIORITY 0 LOAD SHARING LINE
MCB FEEDBACK
GCB2
PRIORITY 3x
SELECTOR G2
KA Kt
EXT.
MCB CAN
3xUG
3xUB
SYN
3xIG
AVR
SYN.ENABLED iG-AVRi
iG-PCLSM
AVR
iG-CU AVRi i
iG-COM
OUT
PARALL.
TO MAINS
REQUIRED
Vout SPEED
LSM
GOVERNOR
SYS START/STOP
MCB PRIORITY 0
MCB FEEDBACK
MCB
Specification
Synchronize gen-sets to mains
Import-Export or Base load power control
Uninterruptible stand-by
After mains returns MCB synchronizing
Automatic stand-by with Short time parallel to mains
Gen-sets unload
Power management (if IG-COMs are installed)
Description
1) The system is started by the Uf relay or by the switch Parallel to mains required.
2) The Uf relay opens MCB after the mains fails. At the same time the Uf relay starts Power
management by closing of SYS START/STOP input, if the gen-sets had not run before.
3) When mains returns, external synchronizer synchronizes gen-sets to the mains.
4) To stop the gen-sets while running in parallel to mains open the switch Parallel to mains required.
5) While stopping in parallel to mains, active MCB FEEDBACK ensures gen-sets soft unload
6) PRIORITY SELECT selects the gen-set priority regardless of the Priority setpoint, if needed.
Hint:
Setpoint SysAMFstrt del is used for engines start delay after the mains fails. It is similar to setpoint
EmergStart del in Single Stand-by.
Time relay Kt is used for beginning of MCB synchronization after the mains returns. It is similar to setpoint
Mains Ret del in Single Parallel to Mains (SPtM) application.
After MCB closing, the delay for gen-sets unloading is 1s (MCB FEEDBACK is closed).
Setpoint SysAMFstp del is not used in this case.
Power supply
To ensure proper function:
Use min. power supply cable of 1.5mm2
Power supply of IG-PCLSM module should be directly connected to IG-CU.
Maximum continuous DC power supply voltage is 36VDC. Maximum allowable power supply voltage is
39VCD. The InteliGen power supply terminal is protected against large pulse power disturbances. When
there is a potential risk of the controller being subjected to conditions outside its capabilities, an outside
protection devise should be used.
Hint:
The InteliGen controller should be grounded properly in order to protect against lighting strikes!!
The maximum allowable current through the controllers negative terminal is 4A (this is dependent on binary
output load).
Sometimes can occur starting problems due to low capacity (low temperature) 12VDC starting battery even if
the controller power supply voltage range is from 8 VDC.
In this case connect external capacitor + separating diode or I-LBA - Low Battery Adaptor module to allow
the controller to continue operation during engine cranking.
Relays Relays
controller controller
T2A D T2A
+ + + +
I-LBA
+
- - - -
C
- + - +
12VDC Battery 12VDC Battery
The 5 000 micro Farad capacitor ensures the 50ms The I-LBA module ensures the 100ms voltage dip
voltage dip under following conditions: under following conditions:
Voltage before dip is 12V and after 50ms the voltage Voltage before dip is 12V and after 100ms the
recovers to min. controller allowed voltage, i.e. 8V. voltage recovers to min. allowed voltage 5V,
The capacitor size depends on required time, i.e. for IG-PCLSM and IG-COM modules are connected to
100ms dip 10 000 micro Farad is needed for the IG (modules disconnecting increases voltage dip up
same conditions. to 200ms).
The I-LBA enables controller operation from 5VDC
(for 10 to 30 sec).
The wiring resistance from battery should be up to
0.1 Ohm for I-LBA proper function.
+
- iG-CU
T1A
-
+ iG-PC(LS)M
-
+ - HUGE
LOADS
Battery STARTER
Fuse
Fuse
K1 K2
K1 K2
IG controller
T1A
+
-
DC relays
- +
24VDC Battery
Grounding
To ensure proper function:
The shortest possible piece of wire should be used when grounding the controller.
Use cable min. 2,5mm2 .
The - terminal of the battery has to be properly grounded.
As short
as possible
Magnetic pick-up
To ensure proper function:
Use a shielded cable
MAGNETIC
PICK-UP
Signal
RPM-IN
iG-CU GND
iS-CU D C
Signal
GAC
Speed Control Unit
ESD 5500
+ -
Power
Supply
- Power
+
Supply
+ -
Battery
Be aware of interference signal from Speed governor when one speed pick-up is used.
If engine will not start:
- check ground connection from pick-up to controllers, eventually disconnect ground connection to one
of them
- galvanically separate InteliGen RPM input using ComAp separation transformer RPM-ISO (1:1)
- use separate pick-up for Speed governor and InteliGen
Controller indicates "Sd Underspeed" + "Pickup fault" after engine start when the pickup signal is good for
start and low speed but too big for higher speed (lost of signal due to RPM input saturation).
Increase gap between pickup and engine flywheel or change type of pickup.
Hint:
LOAD
N N
L3
L1
L2
L1
L2
L3
N
MAINS G ENERATO R
VOLTAG E VOLTAGE
IG-CU SSB, SPtM
Current measurement
To ensure proper function:
Use cables of 2,5mm2
Use transformers to 5A
Connect CT according to following drawings
K L
L1
k l K L
Standard three CT conenction
G L2
k l K L L3 Single stand-by
k l Short time parallel
N
I1 k I1 l I2 k I2 l I3 k I3 l
K L
L1
k l K L
G L2 Two CT connection.
k l
L3
Typical wiring for middle-high voltage application
spare of one transformer.
In k In l I1 k I1 l I2 k I2 l I3 k I3 l
L1
k l
G L2
This arrangement covers earth faults in the load network
k l L3 only.
k l
N
k l
In k In l
K L
L1
k l This arrangement is necessary for restricted earth fault
G L2
k l L3 protection. The location of the neutral earthing point in
k l relation to the protection current transformers in the neutral
N conductor determines whether four or five current
k l transformers are employed.
K
k
L
l
In k In l
L1
k l This arrangement is necessary for restricted earth fault
G L2
protection. The location of the neutral earthing point in
k l L3 relation to the protection current transformers in the neutral
k l conductor determines whether four or five current
N
k l transformers are employed.
In k In l
Connect separate current transformer to gen-set neutral. Adjust EarthFltCurrCT in Basic settings and
EarthFaultCurr and EthFltCurr del limits in Generator protection group.
Voltage measurement
L1
L2
G
L3
N L1 L2 L3 L1 L2 L 3
G ENERATO R MAINS
Drawing text translation
Generator
Mains
IG MTU
Connect one or two IG-MTU or MTU-C units to separe generator and mains voltage from controller. IG-MTU-
C is usually connected to Vg terminals to protect against higher voltage harmonics.
Four wire mains and four-pole circuit breaker or Three wire mains and three wire genset or electric
three wire mains separation
400V
400V
400 V
400 V
400 V
400V
0V
0V
0V
0V
0V
0V
400V
400V
0V
0V
0V
T1 T2 T3 T1 T2 T3
T1 T2 T3
400V
0V
400V
400V
0V
400 V
400 V
400 V
0V
0V
0V
400V
400V
400V
0V
0V
0V
0V
IG-MTU IG -M T U IG -M T U
L2
L1
L3
N
L2
L1
L3
N
L1
L2
L3
L1
L2
L3
MAINS / BUS
GENERATOR L1
L2
L3
0V
0V
L3
N
VOLTAGE TERMINALS
Recommended wirings
Generator (bus) single-phase voltage has to be connected to all three-voltage terminals L1, L2, L3.
Generator current has to be connected to L1k, L1l terminals only.
L1 L1 N L1
L2
L3
L1
L2
L3
N
GENERATOR
BUS VOLTAGE VOLTAGE
BI1
BI6
BI7
BI8
BI9
BI4
BI5
BI2
BI3
L1k
L2k
L3k
L1
L2
L3
L1
L2
L3
L1l
L2l
L3l
N
GENERATOR CURRENT GENERATOR VOLTAGE BINARY INPUTS
0-5A 3 x 230 / 400 V
LB 5
iG-CU
EXTENSION MODULES
iG-PCM / iG-PCLSM
EXTENSION MODULES
iG-COM / iG-IOM
RS 232
BOOT JUMPER
(FUEL)
8 - 36 V DC
BO1
BO2
AI2 (TEMP)
AI3 (FUEL)
RPM GND
AI1 (OIL)
RPM IN
COM
BO3
BO4
BO5
BO6
BO7
BO8
BO9
+ -
Jumpers setting
RPM Grounding Terminal
Resistance
3 measurement
jumper on
2
pins 1-2.
1 Default
3 settings.
2
1 3 Current
measurement
AI1
AI2
AI3
2
jumper on
1 pins 2-3.
3 Voltage
measurement
2
no jumper
1 connected.
4-20mA/600 4-20mA/1000
No. Primary Converted No. Primary Converted
1 400 0 1 400 0
2 2000 600 2 2000 1000
Default characteristics
Following table describes how to use default characteristics.
IG-CU IGS-PTM
WinEdit cfg: WinEdit cfg:
Sensor Jumper on Meas type= Jumper on Meas type =
PT100/C Not possible on IG-CU 1-2, Resistance Resistance
NI 100/C
PT1000/C Resistance Resistance
NI 1000/C Pins 1-2
VDO Temp Resistance Resistance
VDO Press Pins 1-2 Not possible on IGS-PTM
VDO Level
0-20mA/100 Current (linear) Resistance
4-20mA/100 Pins 2-3
0-20mA/100-PTM Pins 2-3, Resistance
4-20mA/100-PTM Not possible on IG-CU Current
100mV/100-PTM No jumper, Resistance
Voltage
Hint:
External resistors 120 ohm for 20mA current measuring are not needed for IG hardware version 5 and above
when analog input jumper is set to 2-3.
- POWER
IG-CU Possible connection of three resistive sensors to
analog inputs AI1, AI2, AI3.
COM
AI3
AI1
AI2
Example of connection of one wire (grounded to
engine frame) sensors.
Engine frame
3x RESISTIVE
SENSOR
-
Battery
- POWER
AI3
AI1
AI2
Engine frame
3x RESISTIVE
SENSOR
-
Battery
IG-CU
analog inputs AI1, AI2, AI3.
COM
- 3x RESISTIVE
Battery
SENSOR
COM
position for this type of measurement.
AI3
AI1
AI2
WinEdit configuration = Current (linear).
IG-CU
- POWER
+24V
AI1 CURRENT SENSOR
AI2 RESISTIVE SENSOR
AI3 BINARY INPUT
IG-CU
- PO W ER
Analog inputs are designed for resistive sensors with resistance in range of 0 to 2,4k.
To ensure a proper function use shielded cables, especially for length over >3m.
Binary input
Open, close state are detected, threshold level is 750 .
Dim: Physical dimension of measured value (C, %, Bar, ..) . Maximum length is three characters.
Set to: Bar
Alarm active
Set to: Engine running only Alarm detection is active only when engine is running, Engine
protections: Protection del [s] after the BO starter is off, (RPM reached Start RPM).
When Analog input configuration is finished set the setpoints Anl Inp level1, Anl Inp level2, Anl Inp del in
Engine protection group.
Each Analog input has separate triplet of setpoints: Anl Inp level1, Anl Inp level2, Anl Inp del. Names of
these setpoints are fixed and do not depend on the name of measured value which can be changed.
Number of decimal points of Anl Inp level1 and Anl Inp level2 is the same as the configured number of
decimal points of measured value.
4k7
iG-CU
+ -
Power
Supply
T1A + -
24VDC Battery
Binary outputs
LOAD
iG-CU
+ -
Power
Supply
T1A + -
24VDC Battery
120
There is different wiring of CAN connectors
from IG-COM hardware version 4.0
H L
COM COM Green CAN connectors are separated:
L H
CAN 2 EXTENSION MODULE CAN 1
CAN1 = for extension modules
- IG-IOM, IGS-PTM, IGL-RA15,
- connection to Extension module 9 pin
connector:
CAN H = pin 5
H L CAN L = pin 9
COM COM
L H CAN2 = inter-controller CAN,
CAN 2 EXTENSION MODULE CAN 1 - galvanically separated
- internal resistor 120 ohm via jumper
iG-MU
1 2
IG-IB.
MODEM / IB CONFIG
IG-CU / DONGLE
iG-IB
3 4 5 6
120
Hint:
For CAN cables details see chapter Technical data Communication interface.
CAN bus must be connected in series, from one unit to the next, (no star, no branches) both ends must by
the 120-ohm resistor terminated.
For longer distances it is recommended to connect COM terminals between IG-COM units
RxB
RxA
COM
COM
H
H
L
TxB
TxA
CAN
CAN
COM
H
H
L
RS 232
EXTENSION MODULE
EXTENSION MODULE
RS 422
RS 232
iG-MU
Se rial No.
POWER
8-36V DC
Serial No.
Serial No.
--
COM
COM
H
H
L
L
CAN
CAN
5 CAN H CAN H
CAN L CAN L
120ohm
IG-CU 9
CANH
CANH
CANL
CANL
COM
COM
CONNECTOR 9 5
120 ohm
IG-IOM (optional)
Drawing text translation
Extension modules
Connector
Optional
Connection rules
CAN bus line must be connected in series, from one unit to the next (no star, no cable stubs, no branches)
both ends must by the 120-ohm (internal or external) resistor terminated.
Maximal CAN bus length is up to 200 meters when Basic settings: CAN bus mode = 32C or up to 900
meters when Basic settings: CAN bus mode = 8C.
InteliGen MINT, SW version 6.2, ComAp August 2005 44
IG-MINT-MINT+IOM-6.2.PDF
For CAN data cables details see chapter Technical data Communication interface. CAN cable shielding
connect to IG-CU case.
IG-CU contains internal fix 120-ohm resistor. Use D SUB9 male connector: CAN H = 5, CAN L = 9,
COMMON = 3 and 8. IG-CU must be on the CAN bus end.
New IG-IOM and IGS-PTM units contain internal jumper removable 120-ohm resistor (in older IOM types are
fix resistors). To be sure check resistor presence by ohmmeter. Unit with internal resistor connect to the end
of CAN line.
Following connections are supported (IOM, PTM, RA15 order is not important).
IG-CU IG-IOM
IG-CU IGS-PTM
IG-CU IGL-RA15
IG-CU IG-IOM IGL-RA15
IG-CU IGS-PTM IGL-RA15
It is possible to connect only one IG-IOM or IGS-PTM and one IGL-RA15 to IG-CU.
Note that Binary inputs and outputs configured on IG-CU (and IG-PC(LS)M ) have much faster response
against IG-IOM, IGS-PTM. It is recommended to configure function inputs like Emergency stop, GCB
feedback, MCB feedback and others exclusively to IG-CU.
Binary inputs IGCU + IG-PCLSM default
Hint:
When remove IG-PCLSM module from IG-CU configured binary IG-PCLSM alarms are not active.
There is no indication of disconnected IG-PCLSM module.
Hint:
Before connection of IG-IOM or IGS-PTM use +IOM aig archive. Use WinEdit to configure these binary
inputs. Any binary input can be configured as a warning, unload, slow stop, shutdown see chapter Alarm
Management.
WARNING: When the data cable between the IG-CU and the IG-IOM, IGS-PTM is disconnected, a SD alarm
is activated. IG-IOM, IGS-PTM power supply LED blinks when the data bus is dead between the IG-IOM,
IGS-PTM and IG-CU.
Not used
Binary input has no function. Use this configuration when Binary input is not connected.
GCB feedback
Use this input to detect, whether the generator circuit breaker is open or closed.
If the feedback is not used, connect this input to the output GCB CLOSE/OPEN
MCB feedback
Use this input for indication, whether the mains circuit breaker is open or closed.
This input indicate, whether the gen-sets group operates in parallel to mains (MCB FEEDBACK is closed) or
parallel isolated (MCB FEEDBACK is open) .
Hint:
MCB feedback must be connected to all controllers operating in Power management group when operating
in parallel to the mains.
Emergency stop
Input immediately activates the engine shut down. Emergency stop is not blocked by Sprinkler function
see below. Emergency stop is indicated in Alarm list and is recorded in History. When Emergency stop is
activated the Binary outputs:
- Fuel solenoid, Ignition and GCB close/open opens,
- Binary output Stop solenoid closes.
Hint:
From safety reasons (broken wire) is recommended to configure Emergency stop as Open to activate.
The Emergency stop input should not stop the engine in the case of controller fail. In such case can the
second Emergency stop button contact e.g. disconnect the Fuel solenoid or Speed governor supply (or
activate Stop solenoid, etc..).
Sprinkler
If the input is closed all alarms are disabled except the binary input EMERGENCY STOP and
"engine overspeed protection".
Sys start/stop
If the input closes InteliGen starts the Pwr management (in AUT mode only).
If the input opens, InteliGen inactivates Pwr management process and stops the gen-set.
Remote OFF
If closed, iG is in OFF mode (there are three modes OFF-MAN-AUT). When opened, controller is switched
back to previous mode.
Hint:
Remote OFF will switch controller to OFF mode even if the Access code is active or Controller mode is
password protected.
Binary input can be connected to timer switch, to avoid start of engine.
Load reserve 2
If the input LOAD RESERVE 2 is closed the setpoints LoadRes strt 2, LoadRes stp 2 will be selected.
Load reserve 3
If the input LOAD RESERVE 3 is closed the setpoint LoadRes strt 3, LoadRes stp 3 will be selected.
Load reserve 4
If the input LOAD RESERVE 4 is closed the setpoint LoadRes strt 4, LoadRes stp 4 will be selected.
Hint:
When more than one Load reserve binary inputs are closed, the higher number has higher priority.
All controllers operating in Power management group have to selected the same Load reserves.
Priority 0
If the input is closed, the gen-set has the highest priority (Priority =0) in Power management regardless of
the value of the setpoint Priority.
Start button
Binary input has the same function as Start button on the InteliGen front panel. It is active in MAN mode
only.
Stop button
Binary input has the same function as Stop button on the InteliGen front panel. It is active in MAN mode
only.
FaultResButton
Binary input has the same function as Fault reset button on the InteliGen front panel.
HornResButton
Binary input has the same function as Horn reset button on the InteliGen front panel.
Gen CB button
Binary input has the same function as GCB button on the InteliGen front panel. It is active in MAN mode
only.
Remote MAN
When closed Controller is switched to MAN Mode. When opened controller is switched to previous mode.
RemControl lock
Locks command writing and setpoint changing from all remote terminals.
GCB disable
Active input blocks in AUT (not in MAN) mode closing GCB.
ForwSyncDisab
Active input blocks forward GCB synchronizing.
Oil press
Behavior for Inverted = Open to activate configuration:
Binary input must be closed when engine is not running and opened when is running. "Sd Oil press B" is
activated when input is opened on not running engine or when stays closed Engine params: Protection del
after engine start.
"Sd Oil press B" protection is not active when input is not configured.
Detection of "running" engine and subsequent alarm message "Sd Stop fail" is blocked.
The controller shows "Emerg Man" state and the engine can not be started.
Generator current and power (energy) measurement is active in this mode, regardless of actual state of the
engine.
After the binary input "Emerg. manual" is open again, the controller recovers to previous mode
and behaves according to the actual situation (e.g. should the engine run, it tries to stop it).
Function is active in any controller mode and activation of this input is written to history.
Hint:
Maximal inductive load of contact relay outputs BO1 and BO2 is 4 Amps. Use external relays for higher load.
Hint:
Before connection of IG-IOM or IGS-PTM use +IOM aig archive. Use WinEdit to configure these binary
outputs.
WARNING: When the data cable between the IG-CU and the IG-IOM, IGS-PTM is disconnected, IG-IOM,
IGS-PTM alarms are not active, only common IOM alarm appears.
Fuel solenoid
The setpoint Engine params: Fuel solenoid selects the output function: DIESEL, GAS.Fuel solenoid
(DIESEL / GAS)
Ignition
The closed output switches on the ignition.
The output closes if: RPM > 30.
The output opens if: RPM < 3.
Pre-start
The output closes prior to the engine start (Prestart) and opens when START RPM speed is reached. During
repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Cooling pump
The output closes when gen-set starts and opens AfterCoolTime delayed after stop the engine.
Idle/Nominal
The output closes during engine start, after Idle time elapses. The output opens after engine has stopped.
Hint:
Connect Binary output IDLE / NOMINAL to speed governor to switch the speed: opened = IDLE,
closed=RATED.
GCB close/open
The output controls the generator circuit breaker.
Hint:
Supposed time to close (reaction time) of GCB is 0,1 sec.
GCB ON coil
Pulse output for GCB closing.
GCB UV coil
GCB undervoltage coil.
GCB ON coil
GCB UV coil
2s 2s
Hint:
GCB UV coil automatically opens when GCB is closed spontaneously not from controller except
Synchronization state.
Syst ready
The output closes if the system load reserve could be achieved.
Hint:
Gen-sets have to be included in Power management by closing of input SYS START/STOP
Is ready to take the load when is in AUT mode and no shut down alarm is active and accepted, Setpoint
Power management = ENABLED or EXTERNAL, BI Remote start/stop is closed.
Use this output as an alarm indication.
Syst res OK
The output closes when selected system load reserve is achieved.
PBNom > PAkt + Reserve
PBNom Sum of the nominal power of all gen-sets on the bus
PAkt System load
Reserve selected setpoint LoadRes strt 1 or LoadRes strt 2
The output can be used for closing of MGCB (Master generator circuit breaker)
Hint:
Gen-set has to be included in Power management by closing of input SYS START/STOP
Gen-set has to be in AUT mode
Setpoint Power management has to be ENABLED or EXTERNAL..
Syst res1 OK
The output closes when LoadResStrt 1 limit is achieved. It is not important which reserve is selected by
Binary inputs Load reserve x.
InteliGen MINT, SW version 6.2, ComAp August 2005 52
IG-MINT-MINT+IOM-6.2.PDF
Syst res2 OK
The output closes when LoadResStrt 2 limit is achieved. It is not important which reserve is selected by
Binary inputs Load reserve x.
Syst res3 OK
The output closes when LoadResStrt 3 limit is achieved. It is not important which reserve is selected by
Binary inputs Load reserve x.
Syst res4 OK
The output closes when LoadResStrt 4 limit is achieved. It is not important which reserve is selected by
Binary inputs Load reserve x.
Hint:
Binary outputs Syst resx OK change is based on corresponding LoadResStrt x setpoint only without
hysteresis and delay.
GenParamsOK
The output is copy of generator status LED on IG front panel. The output is closed if genset is running and all
genset electric values are in limits and no no Sd or Unload alarm is active.
Hint:
Use this output for switching of auxiliary device (e.g. cooling pump) driven from generator independently on
the GCB.
Alarm
The output closes if :
any alarm comes up or
the gen-set malfunctions
The output opens if
FAULT RESET is pressed
The output closes again if a new fault comes up.
Horn
The output closes if:
any alarm comes up or
the gen-set malfunctions
The output opens if:
FAULT RESET is pressed or
HORN RESET is pressed or
Max time of HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Full load
The output closes if the gen-set is fully loaded and there is no reserve in engine power. The output can be
used for load shedding. The output closes when the load >= 0.9 * Nomin power for more than 3sec. The
output opens when the load < 0.9 * Nomin power.
Ready to load
The output is closed if genset is running and all electric values are in limits no alarm is active. The GCB is
already closed or is able to be closed. The output opens during cooling state.
Unload
The output is closed during unloading of genset.
Synchro
The output is closed during genset forward and reverse synchronizing and opens when GCB or MCB is
closed.
Vg fail
The output closes if the generator over/under voltage alarm or voltage asymmetry alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
fg fail
Output closes if the generator over/under frequency alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Overload
Output closes if the generator overload alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Reverse power
Output closes if the generator reverse power alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Overspeed
Output closes if the gen-set overspeed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Underspeed
Output closes if the gen-set under speed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Start fail
Output closes after the gen-set start-up fails.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Overcurrent
Output closes if the generator
IDMT over current or
current unbalance or
short current alarm activates.
InteliGen MINT, SW version 6.2, ComAp August 2005 54
IG-MINT-MINT+IOM-6.2.PDF
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Earth fault
Output closes when Earth fault protection is active.
Output opens when protection is not active and FAULT RESET is pressed.
Batt volts
Output closes when battery over/under voltage warning appears.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Common Wrn
Output closes when any warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Common Stp
Output closes when any slow stop alarm appears.
The output opens, if
No slow stop alarm is active and
FAULT RESET is pressed
Common Sd
Output closes when any shut-down alarm appears.
The output opens, if
No sd alarm is active and
FAULT RESET is pressed
Common Unl
Output closes when any unload alarm appears.
The output opens, if
No unload alarm is active and
FAULT RESET is pressed
Common Fls
Output closes when any sensor fail alarm appears.
The output opens, if no Sensor fail is active and Fault reset button is pressed.
AVR up
AVR down
Binary outputs for Volt / PF control by motorized potentiometer. Outputs should be used when IG-AVRi
module is not connected.
Hint:
The Alarm Wrn VoltRegLim is blocked when binary output AVR up and AVR down are configured.
SPEED up
SPEED down
Binary outputs for Sync / Load control by motorized potentiometer. Minimal pulse duration is 0,15 sec.
Maximal pulse duration is 10,0 sec.
Hint:
InteliGen MINT, SW version 6.2, ComAp August 2005 55
IG-MINT-MINT+IOM-6.2.PDF
The Alarm Wrn SpdRegLim is blocked when binary output AVR up and AVT down are configured.
The response of SPEED UP and SPEED DOWN binary outputs is very fast and frequent to make control
process more precise. It is supposed direct connection to electronic speed governor without mechanical
elements like relays, motorized potentiometer or servo. Min pulse duration 0,15 sec, max pulse duration 10
sec.
OFF mode
The output is closed, if OFF mode is selected.
MAN mode
The output is closed, if MAN mode is selected.
AUT mode
The output is closed, if AUT mode is selected.
AIM 1
AIM 2
AIM 3
AIM 4
Output closes when IG-IOM, IGS-PTM Analog input 1, 2, 3, 4 Level1 or Level2 (e.g. warning or shutdown)
alarm appears.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Stop solenoid
Output closes when is active stop command.
Output activates as well when engine moves spontaneously, not from starter sequence.
Output is closed for minimal Engine params: Stop time (default 60 s) in any case and 5 sec after RPM=0.
Service time
Output closes when gen-set Service count down timer Service time reaches zero.
Cooling
Output closes when gen-set is in Cooling state.
CommonSdStpUnl
Output closes when any Shut-down or Stop or Unload alarm appears.
The output opens, if
No from above alarms are active and
IOM BI5 stat, .. IOM BI8 stat (IG-IOM or PTM Binary input status)
When corresponding binary input (BIM5 to BIM8) is configured as Alarm and this Alarm is active (or inactive
but not accepted by Fault reset button) then output is closed.
When corresponding binary input (BIM5 to BIM8) is configured as function (e.g. GCB feedback) then output
follows input state.
When password is set from the controller front panel only the affected setpoints are not accessible from
WinEdit (direct or Modem) until password is set in WinEdit (direct or Modem). Setpoints opened from front
panel are automatically closed 15 minutes after the last key has been depressed or when wrong value of
password is set.
It is possible to protect remote Start, Stop, GCB and MCB commands from WinEdit, MultiEdit as well. This
three level command protection can be configured from WinEdit.
EnterPassword
Password is a four-digit number. Only setpoints associated with the entered password level can be modified.
Use or to select the desired password and then hit enter.
ChangePassword 1
ChangePassword 2
ChangePassword 3
Hint:
Any password can be changed once that level password or higher has been entered.
Access code
Can be changed from WinEdit software only.
Has to be set before remote modem or SMS connection is opened.
Can be up to 16 ASCII characters due to Internet
At first the Password3 has to be entered before the new Access code can be changed.
Commands protection
Commands password protection protects following commands from WinEdit / MultiEdit direct, modem or
GSM modem connection:
Start, Stop, Horn reset, Fault reset, GCB close/open, MCB close/open.
Selected Command password level 0, 1, 2, 3 is valid for all commands. Selected level is in RED color.
Process control
Hint:
The first character of replicated setpoints name is #.
#SystBaseLoad [kW]
Total required power of gen-sets group operating in parallel to mains (MCB feedback closed).
Step: 1
Range: 0 +30000 kW
#SystPwrFactor [-]
The required power factor of gen-sets group operating in parallel to mains.
Step: 0,01
Range: 0,60 1,00
Basic settings
Gen-set name
User defined name, used for InteliGen identification at remote phone or mobile connection.
Gen-set name is max 14 characters long and have to be entered manually using WinEdit software.
Hint:
Gen-set name is not changed when new archive is loaded.
Check Gen-set name after firmware upgrade.
CT Ratio [/5A]
Generator current transformer ratio.
Step: 1 A/5A
Range: 1 10000 A/5A
Hint:
When /1A CT is used (e.g. 100A/1A) then set CT Ratio five times higher (500/5A).
/1A CT is not recommended because only 20% of measuring range is used.
PT ratio [/1]
Gen-set potential transformers ratio.
Step: 0,1 V / V
Range: 0,1 500,0 V / V
Vb PT Ratio [/1]
Bus potential transformers ratio.
Step: 0,1 V / V
Range: 0,1 500,0 V / V
AnOut-kW/20mA [kW/20mA]
Conversion coefficient from gen-set power to IG-IOM, IGS-PTM analog output in kW to full output scale 20
mA.
Step: 1 kW / 20mA
Range: 1 - 32000 kW / 20mA
Hint:
Available only for IG-IOM, IGS-PTM configuration.
EarthFltCurrCT [/5A]
Earth fault protection CT ratio.
Step: 1 A/5A
Range: 1 5000 A/5A
Generator poles 50 Hz 60 Hz
2 3000 3600
4 1500 1800
6 1000 1200
Engine params
Prestart time [s]
This is the time the binary output PRE-START is active for prior to engine start.
Set to zero if you want to leave the output PRE-START open. RPM must be zero during Prestart time.
InteliGen MINT, SW version 6.2, ComAp August 2005 61
IG-MINT-MINT+IOM-6.2.PDF
Step: 1s
Range: 0 600 s
BO Starter
BO IDLE/NOMINAL
Idle time Min stab time
Electric protections
active
Start Fail
Drawing text translation
Start RPM
Start Fail
BO Starter
BO IDLE/NOMINAL
Hint:
Pressing START button in MAN mode skips the Idle time and switch to running state.
If the engine is unsuccessful in starting the Fuel Solenoid output will stay energized 25% longer in order to
vent the remaining gas.
M axCrank time
BO Fuel
solenoid=Diesel closed opened closed opened
+1sec
BO Fuel +1sec
closed opened closed opened
solenoid=G as
BO Ignition on off on
Engine protect
NextServTime [h]
This is the amount of time that will elapse till service on the gen-set is required. When the countdown is
complete:
Service alarm is detected
Alarm list is recorded
Step: 1h
Range: 0 65535 h
Overspeed [%]
Threshold for over speed protection
Step: 1% of nominal RPM
Range: 50 150%
Hint:
Engine params: Start RPM value is checked as underspeed level.
Following AIM set points are available only when IG-IOM, IGS-PTM is configured.
AnlInIOM1 lev1 []
The level for IOM ANALOG INPUT 1 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM1 lev2 []
The level for IOM ANALOG INPUT 1 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM2 lev1 []
The level for IOM ANALOG INPUT 2 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM2 lev2 []
The level for IOM ANALOG INPUT 2 alarm detection.
AnlInIOM3 lev1 []
The level for IOM ANALOG INPUT 3 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM3 lev2 []
The level for IOM ANALOG INPUT 3 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM4 lev1 []
The level for IOM ANALOG INPUT 4 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM4 lev2 []
The level for IOM ANALOG INPUT 4 alarm detection.
Step: 1
Range: -100 - +10000
Hint:
The analog input del is still enabled even if these inputs are configured as binary inputs contrary to standard
Binary inputs B1 to BI9 which have fix 1 sec delay for activation.
Gener protect
Hint:
All Alarm limits are the last acceptable values. Alarm detection starts when measured value is over the alarm
limit.
Overload [%]
Threshold for generator overload (in % of Nominal power) triggers when exceeded.
Step: 1% of Nominal power
Range: Overload wrn 300%
Protection: Unload (GCB open), Cooling, Stop.
Ishort [%]
Ishort is a percentage over nominal current, that when reached the GCB Close/Open, GCB UV coil, and the
GCB Off coil are immediately opened, the event is recorded in the alarm and history list, and the engine will
cool down and stop if the Fault reset button is not depressed.
Step: 1 % of Nominal current
Range: 100 - 500 %
Protection: Unload (GCB open), Cooling, Stop.
IDMT is inversely proportional to the generators overcurrent. The higher the overcurrent gets the less time
will elapse before the alarm is activated.
When the IDMT protection is activated the GCB is opened, the event is recorded in the alarm and history list,
and the engine will cool down and stop if the fault reset button is not depressed.
Where Reaction time is the amount of time from IDMT detection to the opening of the GCB.
2Inom del
Igen
Nominal current Ishort
It is typical to allow genset to operate for 110% for one hour in 24 hours. In this case the setpoint Nominal
current should be set to 110% of the genset nominal current.
Where Igen is the maximum current of the three phases of generator current.
EXAMPLE of Reaction time for different over current levels. Values in column 200% are equal 2Inom del.
Overcurrent
200 % = 100 % 101 % 110 %
2Inom del
0,2 s No action 20 s 2s
Reaction time 2s No action 200 s 20 s
20 s No action No action 200 s
(time > 900 s)
EarthFaultCurr [%]
Threshold for generator Earth fault protection.
Step: 1 % of Nominal current
Range: 1 300 %
Protection: Unload (GCB open), Cooling, Stop.
Pwr management
Hint
All parameters in the Power management group except Power management, Priority have to be equal
throughout all the controllers and are automatically replicated from one controller into the other connected
controllers.
The first character of all replicated setpoint names is #. It is visible on InteliGen screen and in WinEdit.
See below examples for five gensets 100 kW each. Compare genset-starting sequence for setting
Pwr mgmt mode = ABS (kW) or REL (%) during Actual power increasing.
200 kW
400 kW
300 kW
500 kW
100 kW
0 kW
160 kW
260 kW
360 kW
60 kW
Actual power
1. Genset running
2. Genset running
3. Genset running
4. Genset running
5. Genset running
40 % of 200 kW
400 kW
500 kW
100 kW
200 kW
300 kW
0 kW
260 kW
360 kW
Actual power
40 80 120 160
kW kW kW kW
1. Genset running
2. Genset running
3. Genset running
4. Genset running
5. Genset running
#SysAMFstrtDel [s]
(System AutoMainsFail starting delay, Power management activation delay).
Delay between mains failure and the emergency start of the gen-sets when Binary input SYS START/STOP
is closed e.g. controlled by mains decoupling relay. Island operation, MCB FEEDBACK is opened.
#SysAMFstpDel [s]
(System AutoMainsFail stopping delay)
Delay between Binary input SYS START/STOP opening and GCB opening in island mode when Binary input
MCB FEEDBACK is opened.
Delay between mains return to start of genset unloading when binary input SYS START/STOP is controlled
from mains decoupling relay.
If the MCB FEEDBACK is closed, the delay between Binary input SYS START/STOP opening and start of
genset unloading in parallel to the mains is fixed to 1s.
Step: 1s
Range: 0 600 s
PBNom Sum of the nominal power of all gen-sets on the bus apart of the one, which is going to be
stoped.
PAkt System load
Reserve LoadRes Stp 1 or LoadRes Stp 2
Step: 1 kW%
Range: 0 32000 kW%
Hint:
The engine will be stopped only when #MinRun power level stays running.
2nd gen-set
400
Load Res Stp 60 kW
1st gen-set
200
250
150 170 170
150 100
100
1st gen-set Y Y Y Y Y Y Y
2nd gen-set N N Y Y Y Y N
Load in %
LoadResStrt
70%
LoadResStp
50%
40% 60%
45% 45%
1st gen-set Y Y Y Y Y Y Y
2nd gen-set N N N Y Y Y N
Sync/Ld ctrl
Hint:
Adjusting procedure of Sync/load and Volt/PFcontrol loops see in chapter IM - IG MINT setpoints
adjustment.
SpeedRegChar [POSITIVE / NEGATIVE ]
Switch between isochronous speed governor characteristic.
POSITIVE: When controller Speed governor output voltage increases engine speed increases.
NEGATIVE: When controller Speed governor output voltage decreases engine speed increases.
Hint:
All corresponding set points Slip freq gain, Angle gain and Load gain are positive.
When set to NEGATIVE Binary outputs SPEED UP and SPEED DOWN works in opposite way.
Phase window []
Maximum phase angle difference between generator and bus.
Step: 1
Range: 0 90
GtoB AngleReq []
Phase difference between generator and mains voltage. Use this setpoint for phase correction of potential
transformers for forward synchronizing.
Step: 1
Range: -30 to +30
T2 T1
GCB
G
3 3x10 kV 3x230/400VAC 4 L1, L2, L3, N
Vb GCB Vg Ig
iG -CU
LS gain [%]
Gain of load sharing power control loop.
Step: 0.1%
Range: 0 to +200.0 %
LS der [%]
Relative stability factor of load sharing power control loop.
Step: 1%
Range: 0 100 %
Hint:
There is a background control loop to keep generator frequency at Nominal frequency value. This
background loop operates very slowly only when GCB is closed.
When LS int (or LS gain) is set to zero, background loop is switched off as well.
Hint:
LS gain, LS int and LS der setpoints are active when gensets group operates in
Island parallel: GCBs are closed and MCB is opened. Process control: SysLdCtrlPtM = LdSharing.
Parallel to mains: GCBs and MCB are closed. Process control: SysLdCtrlPtM = LdSharing.
Load control operates via IG-PCLSM load sharing line, where 7,5 VDC value means requirement of Nominal
genset power.
Volt/PF ctrl
AVRRegChar [POSITIVE / NEGATIVE ]
Switch between AVR characteristic.
POSITIVE: When controller and AVRi output voltage increases generator voltage increases.
NEGATIVE: When controller and AVRi output voltage decreases generator voltage increases.
Hint:
All corresponding set points Voltage gain and PF gain are positive.
When set to NEGATIVE Binary outputs AVR UP and AVR DOWN works in opposite way.
PF int [%]
Relative integration factor of power factor control loop. Increasing of integration value causes quicker
response.
Step: 1%
Range: 0 100 %
PF der [%]
Relative stability factor of power factor control loop.
Step: 1%
Range: 0 100 %
Hint:
PF gain, PF int and PF der setpoints are active only when is gen-set parallel to mains.
VS gain [%]
Gain of VAR (power factor) sharing control loop.
Step: 0.1 %
Range: 0 to +200.0 %
VS int [%]
Relative integration factor of of VAR (power factor) sharing control loop.
Step: 1%
Range: 0 100 %
Hint:
VS (PF) int in fact hides two setpoints:
- VS int to keep the the reactive power precisely shared
- maintain system voltage at nominal. This is very slow additional voltage control loop (only integrative
control). Its power is about 10times weaker than real VS int. Primary voltage control should be done by AVR
governor.
VS der [%]
Relative stability factor of of VAR (power factor) sharing control loop.
Step: 1%
Range: 0 100 %
Hint:
VS gain, VS int and VS der setpoints adjusts AVR only when
GCB closed and MCB open or
GCB closed and MCB closed and the Setpoint SysLdcrtlPtM is set to Loadsharing)
to adjust PF (VAR sharing) and maintain system voltage at nominal.
AcallCH1..3-Type
Up to three separate channels are available for any one of the following types of messages:
DISABLED: Channel is disabled.
DATA: Standard analog, GSM or ISDN modem connection to WinEdit.
SMS: Channel sends SMS message. Only when is GSM modem connected.
E-MAIL: Channel sends E-mail. Only when is IG-IB connected.
EML-SMS: Channel sends E-mail with short SMS. Only when is IG-IB connected.
Email contains
- header with serial number and application info.
- Alarm list
- 20 History records (reason, date, time)
Example of EML-SMS:
AL=(Sd Water Temp,Wrn Water Temp,!Emerg Stop,ActCallCH1Fail)
AcallCH1..3Addr
Address for channel 1...3 active call. Each above message type has either a number or an e-mail address
associated to it.
For more details see WinEdit-MultiEdit guide chapter IG-IB Internet communication.
Hint:
To receive active call run WinEdit Type of connection = Active call. WinEdit Active call window contains list
of received AIG or AIS files. Each list item contains Gen-set name, Date, Time, IS serial number.
NumberRings AA [-]
Number of rings prior to open modem connection from PC to controller.
Step: 1
Range: 1 30
Hint:
NumberRings AA change is not accepted immedatelly but after controller is switched on or when modem is
connected to controller.
A.c.multiplier [-]
When active call is activated, controller tries A.c.multiplier times to open the connection.
Step: 1
Range: 1 to 250
Hint:
Timeout for connection is 90 sec and after 120 sec controller starts the next attempt. Incoming calls are
blocked when controller tries to send an active call.
All LOAD SHED outputs are activated (closed) to trip unessential load before genset goes to island (MCB
opens) from parallel to mains:
a) After Mains fail before genset starts to island in AUT mode.
b) Before MCB is opened in MAN mode by button.
#Time [HHMMSS]
Real time clock adjustment.
Sensor spec
Calibr AI1 (AI2, AI3) []
Calibr AIM1 (AIM2, AIM3, AIM4) []
Calibrating constant to adjust the measured value of IG-CU and IG-IOM, IGS-PTM (when configured) analog
inputs. The units of the calibration constant are the same as the associated analog input, e.g. If entering 5 for
Calibr AI1, and AI1 is oil pressure in psis then it would be 5 psis.
Step: 1
Range: -1000 +1000
Hint:
Calibr AI1, Calibr AI1, Calibr AI3 have to be adjusted when measured value is near the alarm level.
Customer adjustable characteristics Curve A, Curve B, Curve C adjust in WinEdit.
LOAD
MAINS GEN
Q Q Q
Cos < 0 L Cos > 0 L Cos > 0 L Cos < 0 L Cos > 0 L
Export P Import P Consumption P Consumption P Generation P
Import Q Import Q Inductive LOAD Generation Q Generation Q
Mains
Exported active power is supplied to the mains. It is displayed in negative numbers e.g. 20kW.
Imported active power is consumed from the mains. It is displayed in positive numbers e.g. +20kW.
When reactive power is imported (>0) InteliMains displays L (inductive) character of the load. Process
control: SysImportLdChr = L-Im kVAr.
When reactive power is exported (<0) InteliMains displays C (capacitive) character of the load.
Process control: SysImportLdChr = C-Ex kVAr.
Load
Active power consumed by Load is displayed in positive numbers e.g. 20kW.
When reactive power is positive (>0) InteliMains displays L (inductive) character of the load.
When reactive power is negative (<0) InteliMains displays C (capacitive) character of the load.
Genset
Generated active power is displayed in positive numbers e.g. 20kW.
When reactive power is positive (>0) InteliGen displays L (inductive) character of the load.
When reactive power is negative (<0) InteliGen displays C (capacitive) character of the load.
IMPORTATNT
Speed governor has to be adjusted for optimum performance before controller Sync / load control
adjusting.
Check generator phase sequence before the first GCB connection.
- 5 % of nominal - 5 % of nominal
SpeedRegChar = POSITIVE SpeedRegChar = NEGATIVE
To decrease Speed governor out sensitivity use IG-PCLSM VoutR output and connect external
resistor R2 in parallel to output.
VoutR output voltage is in this case R2 / (R1+R2) = 1 / 11 = 0.09 times off Vout voltage.
R2=1k
R1=10k
VoutR AUX input
Vout range:
-10.0 V to +10.0 V
Each genset in the group should have the same speed governor out sensitivity. Speed governor
characteristics difference unbalances Load sharing during synchronizing of loaded gensets group to
the mains.
IG-AVRi-TRANS (AC power supply for AVRi) have to be supplied from gen-set voltage.
AVRi outputs can be connected: OUT1-OUT2 or unsymmetrical OUT1-GND or OUT2-GND.
To check AVR DCout bias range set Voltage gain = 0.
0V 0V
0% AVR DCout bias 100.0 % 0% AVR DCout bias 100.0 %
AVRi Out1 or Out 2 to GND output voltage depends on AVRi trim setting
um
im
ax
m
= m
AVRi output voltage
ot imu
ip min Out1 - GND Out2 - GND Out1 Out2
VR i pot =
A AVR Bias \ Pot Min Max Min Max Min Max
0V AVR DCout bias
50 %
0% 0 0 2 10 - 2 V -10 V
0% 100.0 %
50 % 1 5 1 5 0V 0V
100 % 2 10 0 0 + 2 V 10 V
-10 V
Adjust AVR and AVRi to keep Nominal genset voltage at AVR DCout bias = 50%.
To decrease AVRi output voltage sensitivity turn AVRi trim ccw.
When the AVR characteristic is negative (increasing AVRi output decreases generator voltage) set
AVRChar = NEGATIVE (All AVR gain setpoints are positive).
Each genset should have the same AVRi out sensitivity. AVR characteristics difference unbalances PF
sharing during synchronizing of loaded gensets group to the mains.
3. Voltage control
Conditions: running single gen-set, analog Volt/PF control using IG-AVRi module.
Hint:
Simulate voltage steps by changing of Nominal voltage setpoint and check stable Voltage control.
Voltage matching
Vbus
InteliGen - MINT
AVRi
analog output
Voltage gain +
Voltage int
Voltage der +
Vgen
AVR DCout bias
4. Forward synchronizing
Conditions: two running gen-sets, one is connected in MAN mode to dead bus, on the second genset
press in MAN mode GCB close/open button to start synchronising to the bus.
Adjust Sync control set points of each gen-set separately. Check InteliGen-MINT synchroscope
screen.
IG - Sync/Load control: Voltage window, Phase window, Dwell time,
Speed gov bias, Slip freq gain, Slip freq int, Slip freq der and Angle gain, Angle der.
Hint:
At first set Phase window = 0 to avoid GCB closing.
Simulate speed steps by changing of Speed gov bias setpoint or press repeatedly GCB close/open button to
start stop synchronizing and check stability of synchronizing.
5. Load sharing
Conditions: two gensets are running in isolated parallel (MCB is opened). In the first step no load, then
apply full load.
When all gensets are running idle voltage of Load sharing line is zero V.
When all gensets are running at Nominal power voltage of Load sharing is 7,5V.
In parallel isolated mode (MCB is opened) adjust following Load sharing set points.
When genset is loaded, unloaded, loading, unloading check the Load sharing. Check if Speed governor
analog output does not reach limits below 10V or over 10V of the range.
IG - Sync/Load control: Load ramp, LS gain, LS int, LS der,
GCB open level, GCB open del
Hint:
Load sharing
SPEED G OVERNO R
1.InteliGen - MINT isolated parallel 2.InteliGen - MINT SPEED G OVERNOR
analog output
analog output
+-10 V LS gain LS gain
LS line: 0 to +7,5 V + +-10 V
LS int LS int
+ LS der LS der
+ +
6. VAR sharing
Conditions: are the same as in step 5 Load sharing.
In isolated parallel mode (MCB is opened) adjust following VAR sharing set points. When loaded,
unloaded, loading, unloading check the PF sharing. Check if AVR analog output does not reach
limits below 0% or over 100% of the range.
IG - Volt/VAR control: VS gain, VS int, VS der
Hint:
When one genset is running loaded in MAN mode press GCB close/open button of the second genset to
synchronize and load. Then press STOP button to unload genset and open GCB. Pressing of the
START button returns IG controller back from Cooling to Idle state.
Hint:
Check output values of Sync/Load and Volt/PF control loops at InteliGen MINT Synchro screen.
Load and VAR sharing can be unbalanced during synchronizing when different sizes of gensets (or
different adjusting of speed governors) are running in parallel.
Adjust following InteliMains synchronizing set points, check InteliMains synchroscope screen.
IM - Sync/Load control: Voltage window, Phase window, Dwell time,
Slip freq gain, Slip freq int, Slip freq der and Angle gain, Angle der.
Hint:
Press repeatedly MCB close/open button on InteliMains controller (in MAN mode) to start /stop
synchronizing and check IM synchroscope screen. At first set Phase window = 0 to avoid MCB closing.
Back synchronizing
InteliMains InteliGen - MINT
fbus SPEED G OVERNO R
Slip freq gain analog output
Slip freq int LS line: +- 10 V LS gain + +-10 V
Slip freg der LS int
Angle gain LS der
Angle der +
fmains
Speed gov bias
Load and PF sharing can be unbalanced during synchronizing when different sizes of gensets (or
different adjusting of speed governors) are running in parallel.
During synchronizing (Volt matching is active) adjust following Voltage control set points:
InteliGen MINT, SW version 6.2, ComAp August 2005 90
IG-MINT-MINT+IOM-6.2.PDF
IM - Volt/PF control: Volt gain, Volt int, Volt der.
Hint:
At first set Phase window = 0 to avoid MCB closing.
Press repeatedly MCB close/open button on InteliMains controller (in MAN mode) to start /stop
synchronizing and check IM synchroscope screen.
For test, adjust Nominal voltage of gensets group to different value from the mains voltage (e.g.210V).
Vbus
Voltage matching
InteliMains InteliGen - MINT
AVRi
Voltage gain VS gain analog output
CAN bus +
Voltage int VS int
Voltage der VS der +
Vm ains
AVR DCout bias
Adjust following InteliGen MINT Load and PF control set points and check forward synchronizing,
stable load/unload and PF control.
IG - Sync/Load control: Load gain, Load int, Load der, Load ramp.
IG - Volt/PF control: PF gain, PF int, PF der.
Hint:
When mains is connected to the bus in MAN mode press the GCB close/open button of IG-MINT controller
to start synchronizing to the mains, loading at the #SysBaseLoad value. Then press the STOP button to
unload genset and open GCB. Pressing of the START button returns controller back from Cooling to
Running state.
#SysBasePF
InteliGen - MINT
AVRi
PF gain analog output
+
PF int
PF der
+
Genset PF
AVR DCout bias
Adjust following InteliMains Load and PF control set points and check forward synchronizing, stable
load/unload and IM/EX Load and PF control.
IM - Sync/Load control: Load gain, Load int, Load der, Load ramp.
IM - Volt/PF control: PF gain, PF int, PF der.
Hint:
Forward synchronizing test
When mains is connected to the bus in MAN mode press the GCB close/open button of IG-MINT controller
to start forward synchronizing and voltage matching of single genset to the mains.
InteliMains via LS line and CAN bus controls SysImport load and SysImport PF value which is shared
between gensets in the group.
When the STOP button of IG-MINT controller is pressed, genset unloads, opens GCB and steps to Cooling
state. Pressing of the START button returns controller back from Cooling to Running state.
Actual
m ains Load control
InteliMains InteliGen - MINT
power SPEED GOVERNOR
analog output
Load gain LS line: +7,5 V LS gain + +-10 V
Load int LS int
Load der LS der
+
SysImport load
Speed gov bias
Actual
Mains
PF control
InteliMains InteliGen - MINT
PF AVRi
PF gain VS gain analog output
CAN bus +
PF int VS int
PF der VS der +
SysImport
PF
AVR DCout bias
Hint:
Output values of Sync/Load and Volt/PF control loops check at InteliMains synchroscope screen.
LSO indicates IM-PCLSM load sharing output in the range from 10.0V to +10.0V.
VVO indicates IM Volt/PF output to CAN bus in the range from -1000 to +1000.
Curve A VDO pressure Curve B VDO temperature Curve C VDO Fuel level
3900 -20 10 0 10 0
1525 0 50 20 180 100
700 20 85 40
440 30 119 60
170 0 0 0 0 38 0
200 13 8 38 20 57 12
230 25 15 57 30 77 25
280 38 23 77 40 96 37
330 50 30 96 50 116 50
390 63 38 116 60 135 62
460 75 45 135 70 155 75
560 88 53 155 80 174 87
690 100 60 174 90 194 100
194 100
100mV/100-PTM
Primary Converted
mV0100R mV0100Out
0 0
10 4
40 16
70 28
110 45
140 57
170 68
210 84
230 92
250 100
3 2 1 4
5
15
9
10
16
11
12 14 13 7 18 8 17
Pushbuttons:
1. MODE Cycle forward through gen-set operation modes OFF -> MAN -> AUT.
2. MODE Cycle backward through gen-set operation modes OFF -> MAN -> AUT.
3. HORN RESET Deactivates the HORN.
4. FAULT RESET Acknowledges faults and alarms.
5. START Starts the gen-set in MAN mode.
6. STOP Stops the gen-set in MAN mode.
7. MCB ON/OFF Has no affect in MINT application.
8. GCB ON/OFF When in MAN mode opens and closes (synchronizes) the Generator
circuit breaker.
9. PAGE Cycles through the display screens MEASUREMENT->ADJUSTEMENT->HISTORY.
10. Select the setpoint, select the screen or increase setpoint value.
11. Select the setpoint, select the screen or decrease setpoint value.
12. ENTER Confirm setpoint value.
Synchronizing
When voltage is detected on the bus (within Voltage window) InteliGen starts synchronizing and waits for
closing of GCB.
Display menus
There are 3 display menus available: MEASUREMENT, ADJUSTMENT and HISTORY
Each menu consists of several screens. Pressing the PAGE button repeatedly will scroll the user through the
menu screens.
1 2
3
OFF MAN AUT TEST
Ready 4
Mains Oper
cos 0.00 7
RPM 0
Tim er 0
5
8
6
Generator screen
Load surge maximal value
Load surge actual value
Gen freq
Gen V1-2, V2-3, V3-1 ph-ph
Gen V1, V2, V3 ph-N (triple barograph)
Gen I1, I2, I3 (triple barograph)
Bus screen
EarthFaultCurr
Bus freq
Bus Vb1-2, Vb2-3, Vb3-1 ph-ph
Bus Vb1, Vb2, Vb3 ph-N (tripple bargraph)
Hint:
IG-IOM, IGS-PTM binary inputs are visible only when is IG-IOM, IGS-PTM is configured.
Statistic
Kilowatt-hours kWh Active energy total
Reactive power hours kVArh Reactive energy total
Run hours
Number of starts
NextServTime
Synchroscope
Angle between V1g and V1m (synchroscope)
V1g Generator first phase voltage
V1m Mains first phase voltage
Power management
Engine priority
Total available power (sum of Nominal power)
Total run power (sum of Nominal power - running)
Active reserve (single barograph)
CAN16 bus status address 1 to 16 (binary)
CAN23 bus status address 17 to 32 (binary)
Alarm list
101
Page
PAGE
History Screens
Measure Screens Par. Edit Screens History Screens
12345h
GEN PROTECT
Screen
MAINS FAIL
586 kW 14:23:15
IG-MINT-MINT+IOM-6.2.PDF
PAGE ENTER
GEAR TEETH OF
150 150 -
NOM RPM
Next 1500 1500 RPM
START RPM LE Y
30 30%
Flow Chart of pushbutton Operation
ENTER
PAGE
..... TO MEASURE SCREEN
Next Screen
Engine Basic
Engine Prot
Gen Basic
Gen Protect
Mains Fail
Gear Teeth
Nom RPM
Start RPM
Crank Time
Parameter setting
Set cursor by - buttons
Press - to editing mode
Adjust parameter by - buttons
Press - to write parameter into memory
Press - to cancel of editing mode
Table of history
To measure screen
OFF mode
Outputs STARTER, GCB CLOSE/OPEN and FUEL SOLENOID are not energized. Genset cannot be
started. If START,STOP,GCB ON/OFF buttons is pressed the iG will not respond.
MAN mode
1) To start the gen-set press START.
2) When the generator voltage is within limits (adjusted in the setpoints group Generator protections)
generator GCB green LED on the front panel lights.
3) Press GCB ON/OFF to close the GCB. If the generator voltage is out of the limits, InteliGen does not to
respond to the GCB ON/OFF .
a) If InteliGen detects dead bus, immediately closes GCB OPEN/CLOSE output.
b) If InteliGen detects voltage (Voltage window) on the bus, starts synchronizing.
4) To stop the engine press STOP
a) InteliGen unloads the gen-set. When the gen-set load reaches GCB Open level, (but max. GCB
open del), iG opens GCB CLOSE/OPEN. Unloading is active only when binary input MCB feedback
is closed or other gen-set is connected to bus. In other case GCB CLOSE/OPEN opens immediately.
b) Gen-set is cooled and stopped.
Hint:
InteliGen does not respond to the binary input SYS START/STOP. The genset is permitted to run for an
unlimited amount of time.
InteliGen is disconnected from Power management
Load and power factor sharing in parallel isolated group are active only when Load sharing line and CAN bus
between all gen-sets are connected.
AUT mode
1) All gen-sets necessary to cover selected LoadRes strt are started
a) immediately when SYS START/STOP binary input is closed
b) delayed SysAMFstrt del when MCB FEEDBACK binary input is opened mains failure comes
2) The first gen-set closes GCB to the dead bus, the rest are synchronized to the bus.
a) If InteliGen detects dead bus, immediately closes GCB OPEN/CLOSE output.
b) If InteliGen detects voltage (Voltage window) on the bus, starts synchronizing.
2) When all necessary gen-sets are connected to the bus and LoadRes strt is achieved, SYST RES OK
output is closed. Output could be used to close the MGCB.
3) Gen-sets get loaded and total active and reactive load are shared between parallel operating gen-sets.
4) Close input LOAD RESERVE 2 (or 3 or 4) and use setpoint LoadRes strt, if necessary.
5) If load increases and selected LoadRes strt is not achieved, after a Next start del next gen-set with the
highest priority is started and synchronized to the bus.
6) If load decreases and selected LoadRes stp is exceeded, after a Next stop del the running gen-set with
the lowest priority is unloaded, got off line, cooled and stopped.
7) Gen-sets group stops when binary input SYS START/STOP opens. If the input MCB FEEDBACK is
closed (gen-sets are in parallel to mains) InteliGen unloads the gen-sets. When gen-set is unloaded
(see GCB open level or GCB open del) opens SYST RES OK and opens GCB CLOSE/OPEN.
Hint:
InteliGen does not respond to GCB ON/OFF
InteliGen does not respond to START and STOP
Load shedding
G en-set power
Ld shed level
closed
BO Load shed 1
closed
BO Load shed 2
closed
BO Load shed 3
Ld recon level
Hint:
The alarm can be configured for any IG-CU, IG-PCLSM and IG-IOM, IGS-PTM binary input.
When warning comes up it is displayed on the Alarm list screen and the selected entries are written to the
History record.
Detection of each binary input alarm is fix 1 sec time delayed.
Analog input Alarms have usually two levels - e.g. wrn and sd.
Use WinEdit to modify binary or analog inputs protections.
Sensor fail does not activate binary output common Alarm.
Warning
When warning comes up, only alarm outputs are closed.
Possible warnings:
Binary inputs configured as Warning (alarms are displayed and stored under configured name)
Analog inputs configured as Warning (alarms are displayed and stored under configured name)
Battery voltage alarm level
Shut down
When a shutdown occurs, InteliGen opens outputs GCB CLOSE/OPEN, FUEL SOLENOID, STARTER.
Slow stop
When the slow stop alarm comes up InteliGen unloads gen-set, opens output GCB CLOSE/OPEN, waits for
Cooling time and opens FUEL SOLENOID output.
ElProt
When the Electric generator protection (Unload) comes up, InteliGen opens the output GCB CLOSE/OPEN
In MAN and AUT mode engine is cooled and stopped.
HistoryRecord
History record protection activates history record only.
Underspeed
Protection
delay Engine running only, SD, Slow stop, Wrn
All the time & Overspeed protections & Ig IDMT, Ig unbal, IG short
Mains>V, Mains<V, Mains>f, Mains<f, MVolt unbal
Ready
RPM=0 Cranking Starting Running Loaded Loaded
GCB opened
Max stab time
GCB closed
Synchronizing
Starter OFF
Unloading
Cooling
Start
Idle
Stop
or
When the BO GCB close/open (MCB close/open) in steady state and GCB feedback (MCB feedback) is
changed the GCB fail (MCB fail) is detected immediately (no delay).
closed
BO G CB close/open opened BO G CB close/open
closed
BI G CB feedback BI G CB feedback opened
active active
Alarm: G CB fail Alarm: G CB fail
Alarm detection: Alarm detection:
immediatelly immediatelly
When BO GCB close/open (MCB close/open) opens there is 2 sec delay for the breaker to respond before a
GCB fail (MCB fail) will be detected.
InteliGen MINT, SW version 6.2, ComAp August 2005
109
IG-MINT-MINT+IOM-6.2.PDF
BO G CB close/open opened
BI G CB feedback opened
T ime delay
5 sec active
Alarm: G CB fail
When BO GCB close/open (MCB close/open) closes, there is following delay for the breaker to respond
before a GCB fail (MCB fail) will be detected:
2 sec when synchronizing SPtM, MINT, MEXT (parallel modes)
5 sec in stand-by SSB (island modes)
closed
BO G CB close/open
active
Alarm: G CB fail
R1
R2
R3
R4
R5
When Speed governor output stays on +9,8V or -9,8V for more than 2 sec the warning SpdRegLim is
detected on the Alarm list.
When AVRi output stays on <2% or >98% for more than 2 sec the warning VoltRegLim is detected on the
Alarm list.
This warning indicates only (no other action) wrong connection or adjusting of control loop. Control loops
should operate within range.
Hint:
Corresponding warning is blocked when Binary outputs SPEED up,SPEED down or AVR up, AVR down are
configured.
Hint:
When group of InteliGens are not interconnected by CAN digital line, each gen-set operate separately.
In this case is recommended to adjust the equal setpoints in all InteliGens manually.
Setpoints consistency
Any changes of following setpoints in the ProcessControl group and in Power management group
(except Priority) done in one InteliGen are automatically replicated in all other connecting InteliGens.
ProcessControl Pwr management Date and Time
#SystLoadCtrl #Syst start del #Time
#SystPFControl #Syst stop del #Date
#SystBaseLoad #LoadRes Strt 1
#SystPwrFactor #LoadRes Strt 2
#LoadRes Strt 3
#LoadRes Strt 4
#LoadRes Stp 1
#LoadRes Stp 2
#LoadRes Stp 3
#LoadRes Stp 4
#Next start del
#Ovrld NextDel
#Next stop del
#Slow stop del
Any new powered InteliGen receive automatically all replicated parameters from InteliGen with the lowest
Controller adr
Start-stop sequence
MODE = MAN
Hint:
Gen-set stops immediately when button STOP is pressed during Cooling procedure.
Unsuccessful start
Crank attempts=3
State Closed outputs Condition of next transition
Ready Start request
Prestart PRESTART Prestart time
Cranking PRESTART,STARTER,FUEL SOLENOID MaxCrank time
Crank PRESTART CrankFail paus
pause
Cranking PRESTART,STARTER,FUEL SOLENOID MaxCrank time
Crank PRESTART CrankFail paus
pause
Cranking PRESTART,STARTER,FUEL SOLENOID MaxCrank time
Not ready HORN, GENERAL FAULT FAULT RESET
Ready >>>>
2 - RxD 2 - RxD
RS232
RS 232
RS232
3 - TxD 3 - TxD
230 VAC 5 - GND 5 - GND
0 VDC
- +
Battery
PC software - WinEdit
On the PC (for direct or modem connection) has to be installed the ComAps software package WinEdit.
(based on Windows 95 or newer platform)
WinEdit enables:
read the quantities,
adjust all set points,
read the history
control the engine
configure the controller
select software configuration
modify alarm inputs and outputs
modify password, commands protections,
direct or modem communication
receive active calls
History file
InteliGen stores a record of each important event into the history file. The history file seats 117 records.
When the history file is full, the oldest records are removed.
Hint:
To force history download in WinEdit (direct or modem) open History window and select History | Read
history command.
Record structure
Abbreviation Historical Value
No. Number of historical event
Reason Event specification
Date Date of historical event in format DD/MM/YY
Time Time of historical event in format HH:MM:SS
Pwr Generator active power
PF Generator PF
LChr Character of the load
Spd Engine speed
InteliGen MINT, SW version 6.2, ComAp August 2005
115
IG-MINT-MINT+IOM-6.2.PDF
Gfrq Generator frequency
Vg1 Generator voltage L1
Vg2 Generator voltage L2
Vg3 Generator voltage L3
Ig1 Generator current L1
Ig2 Generator current L2
Ig3 Generator current L3
Im3 Mains current L3
Bfrq Bus frequency
Vb1 Bus voltage L1
Vb2 Bus voltage L2
Vb3 Bus voltage L3
Batt Battery voltage
OilP IG-CU Analog input 1 value (default Oil pressure)
Wtmp IG-CU Analog input 2 value (default Water temperature)
Flev IG-CU Analog input 3 value (default Fuel level)
AIM1 IG-IOM, IGS-PTM Analog input 1 value (when configured
IG-IOM, IGS-PTM)
AIM2 IG-IOM, IGS-PTM Analog input 2 value (when configured
IG-IOM, IGS-PTM)
BInp Binary inputs IG-CU
BIPC Binary inputs IG-PCLSM
BIM IG-IOM, IGS-PTM Binary inputs (when configured IG-IOM,
IGS-PTM)
Bout Binary outputs IG-CU
BOPC Binary outputs IG-PCLSM
BOM IG-IOM, IGS-PTM Binary outputs (when configured IG-
IOM, IGS-PTM)
Mode Mode IG - OFF, MAN AUT
Generator voltage unbalance Unl Vgen Unbal Unl Vgen Unbal unl
Generator overload warning Wrn Overload Wrn Overload 0
Generator overload UnlGen Overload UnlGen Overload unl
Load surge protection LoadSurge LoadSurge Unl
Reverse power Unl Rev Pwr Unl Rev Pwr unl
Synchronization timeout Stp SyncTO Stp SyncTO Stp
Reverse sync timeout Wrn RevSyncTO Wrn RevSyncTO Wrn
Earth fault protection Unl EarthFltC Unl EarthFltC Unl
Failure of generator circuit breaker GCB fail GCB fail unl
Generator short current protection Unl Short Igen Unl Short Igen unl
Generator IDMT protection Unl IDMT Unl IDMT unl
Generator current unbalance Unl Igen Unbal Unl Igen Unbal unl
Hint:
Binary and analog inputs alarm events are recorded and displayed under a user name.
Modem Bridge (MB) is IG-MU connected to modem.
Local Bridge (LB) is IG-MU connected to PC.
Note SD stop fail is detected when Engine params: Stop time after engine stop (when BO Fuel
solenoid is opened or Stop solenoid is closed) the RPM is still > 30.
The complete description of Modbus communication protocol can be found in Modbus Protocol Reference
Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are available from web
site at http://www.modicon.com/openmbus/ .
Hint:
InteliGen MINT, SW version 6.2, ComAp August 2005
119
IG-MINT-MINT+IOM-6.2.PDF
Any Modem goes to init procedure in following cases
- after controller reset (when modem is already connected)
- whenever is modem connected to controller
- each 20 minutes when is no connection
- when connection is closed
- when data transmit error occurs
SMS commands
Are not available from IG sw version 6.0.
Active SMS message is invoked by controller request. Active SMS message is sending to GSM phone
number specified in setpoints group Act. Calls/SMS on InteliGen/InteliSys. Specified phone number must
be in international format +cccyyyxxxxxx where ccc is country code, yyy is operator prefix and xxxxxx is local
phone number. Active message contains items of actual Alarm list (most eight items).
INTERNET
ETHERNET
LED 1 2
IB CONFIG
DONGLE
iG-CU
MODEM
RS232
IG-CU
iG-IB
(iS-CU)
LED 3 4 5 6 LED
CAN POWER
IG-IB interface
Modem / IB config RS232 interface for IG-IB configuration or Modem connection
IG-CU / Dongle RS232 interface for one controller connection or for Dongle for multiple
controllers communication.
CAN bus interface to group of controllers
Ethernet to LAN interface to company net
See IG-IB Internet bridge
Connection types
Internet or Modem (wired line) remote connection from WinEdit or MultiEdit software.
Active calls: E-mail or SMS via Internet.
IG-IB configuration
Connect IG-IB Modem interface to PC and run IB-cfg software.
Adjust items in IB configuration window IP address etc.
Values
Name Sw configuration Date Sw conf. ver. Ser. num. Filename
InteliGen MINT 13.5.2004 6,1 4100096
Setpoints
Name Sw configuration Date Sw conf. ver. Ser. num. Filename
InteliGen MINT 13.5.2004 6,1 4100096
Group Name Value Dimension Password Com. obj. Low limit High limit Data type
Operating conditions
Operating temperature IG-CU -20..+70oC
Operating temperature IG-CU-LT -30..+70oC
Storage temperature -30..+80oC
Flash memory data retention time 10 years
Protection front panel IP65
Humidity 95% without condensation
(From IG serial number xxxx0900)
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94 (EN 61000-6-3)
EN 50081-2:96 (EN 61000-6-4)
EN 50082-1:99 (EN 61000-6-1)
EN 50082-2:97 (EN 61000-6-2)
Vibration 5 - 25 Hz, 1,6mm
25 - 100 Hz, a = 4 g
Shocks a = 200 m/s2
Current inputs
Nominal input current (from CT) 5A
Load (CT output impedance) < 0,1
CT input burden < 0,2 VA per phase (In=5A)
Max. measured current from CT 11 A
Current measurement tolerance 2% from the Nominal current
Max. peak current from CT 150 A / 1s
Max. continuous current 12 A
IG-MTU
Primary voltage Ph-Ph 3x400 VAC / 50Hz (3x480 VAC / 60 Hz)
Secondary voltage Ph-N 3x 230 V AC ( 3x277 VAC / 60 Hz) , 5 VA
Mechanical dimensions: 155 x 95 x 60 mm , DIN rail (35 mm) mounted
Primary/secondary Phase shift < 1
Operating temperature -30..+70oC
IG-MTU-C
Primary voltage Ph-Ph 3x400 VAC / 50Hz (3x480 VAC / 60 Hz)
Secondary voltage Ph-N 3x 230 V AC ( 3x277 VAC / 60 Hz) , 5 VA
Mechanical dimensions: 155 x 95 x 60 mm , DIN rail (35 mm) mounted
Primary/secondary Phase shift 6
Operating temperature -30..+70oC
Analog inputs
Not electrically separated
Resolution 10 bits
InteliGen MINT, SW version 6.2, ComAp August 2005
130
IG-MINT-MINT+IOM-6.2.PDF
Sensor resistance range 0 -2,4 k
Resistance measurement tolerance 4 % 2 out of measured value
RS232 interface
Maximal distance 10m
Speed 19.2kBd
Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length and
32 IG-COM units connected:
Nominal Velocity of Propagation min. 75% (max. 4,4 ns/m)
Wire crosscut min.0,25 mm2
Maximal attenuation (at 1 MHz) 2 dB / 100m
Hint:
IG-PCLSM
Power supply: 8 36 V DC
Consumption: 100 mA
Binary inputs
Number of inputs 4
Input resistance 4,7 k
Input range 0-36 VDC
Switching voltage level for close contact indication 0-2 V
Max voltage level for open contact indication 8-36 V
IG-AVRi
Power supply: 18V AC from IG-AVRi Trans/LV or IG-AVRi Trans/100
Absolutely maximum power supply range: 15 - 25 VAC or 20 - 35VDC
Operating temperature -30..+70oC
IG-AVRi Trans/LV
Primary voltage 1: 230-277 VAC
Absolute low limit: 230 VAC 20%
Absolute high limit: 277 VAC + 20%
Frequency: 50 - 60 Hz
Secondary voltage: 18 V AC, 5 VA
Operating temperature -30..+70oC
IG-AVRi Trans/100
Primary voltage: 100 120 VAC
Absolute low limit: 100 VAC 20%
Absolute high limit: 120 VAC + 20%
Frequency: 50 - 60 Hz
Secondary voltage: 18 V AC
Operating temperature -30..+70oC
Analog inputs
Not electrically separated
Number of inputs 4
Resolution 10 bits
Sensor resistance range 0 -2,4 k
Resistance measurement tolerance 4 % 2 out of measured value
Analog output
Not electrically separated
Number of outputs 1
Resolution 10 bits
Output range 0 to 20 mA 0,33 mA
IG-MU
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Operating temperature -30..+70oC
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Interface to modem or PC RS232, RS422, RS485
Interface to controller CAN
IG-IB
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Operating temperature -30..+70oC
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Interface to controller RS232 or CAN
Interface to modem RS232
Interface to Ethernet RJ45
IGS-PTM
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Operating temperature -30..+70oC
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Interface to controller CAN
InteliGen MINT, SW version 6.2, ComAp August 2005
133
IG-MINT-MINT+IOM-6.2.PDF
Binary inputs and outputs see IG-IOM
Analog output see IG-IOM
Analog inputs
Not electrically separated
Number of inputs 4
Resolution 10 bits
Maximal resistance range 0 250
Maximal voltage range 0 100 mV
Maximal current range 0 20 mA
Resistance measurement tolerance 1 % 2 out of measured value
Voltage measurement tolerance 1,5 % 1mV out of measured value
Current measurement tolerance 2,5 % 0,5mA out of measured value
IGL-RA15
Power supply
Voltage supply 8-36V DC
Consumption 0,35-0,1A (+1A max horn output)
Depend on supply voltage
Operating conditions
Operating temperature -20..+70oC
Storage temperature -30..+80oC
Protection front panel IP65
Horn output
Maximum current 1A
Maximum switching voltage 36 VDC
Internal preheating foil is mounted in InteliGen LT to extend display operational temperature range.
Preheating starts at temperature below 5 oC and preheating power depends on temperature and power
supply voltage.
Technical data
IG-CU Standard IG-LT
Operating temperature -20 oC..+70oC -30 oC..+70oC
Storage temperature -30 oC..+80oC -30 oC..+80oC
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all.
Order codes
There are two types of preheating foil to cover full temperature and controller power supply range.