Fire Pump Controllers for

Business Critical Continuity

JockeyXG Pump Controllers


FTA550F Series
Firetrol FTA550F Series JockeyXG Pump Con- Main switch not in Auto alarm
trollers are intended for use with fire pump systems. Pressure recording
They are used for pressure maintenance in fire pump Event log (3000 events stored in controller
installations to prevent unnecessary operation of memory)
the main fire pump. Data log (including cycle counter)
Door mounted display/user interface featuring
Approvals Firetrol Jockey Pump Controllers a 128 x 64 pixel backlit LCD Graphical Display,
are listed by Underwriters Laboratories, Inc., in Membrane Type User Controller Push-buttons
accordance with UL508A, Standard for Industrial and LED indication for:
Controls, and CSA, Standard for Industrial Control Power ON
Equipment (cUL). They are built to meet or exceed Pump Running
the requirements of the approving authorities as Alarm
well as NEMA and the latest edition of NFPA 70, 2 lines of user selectable display information
National Electrical Code.
FTA550 Jockey Pump Controllers
Enclosures The standard enclosures, up to 20 The FTA550F Jockey Pump Controller utilizes
HP*, are red non-metallic material for installation in across the line, full voltage starting. Full voltage
areas protected from direct sunlight with an ambi- is applied to the motor as soon as the controller is
ent temperature above 41F (5 C). The standard actuated, and the motor supplies its rated torque.
enclosure rating is NEMA type 2/12 (IEC IP11/IP52). When the controller is actuated, either by a
drop in system pressure (in the Auto mode), or by
Standard FeaturesThe following are included placing the HAND-OFF-AUTO switch in the Hand
as standard with each controller: position, the pump will start. In the Auto mode,
NEMA Type 2/12 (IEC IP11/IP52) Polycarbonate the pump will continue to run until the pressure
enclosure (UL50E Construction) returns to a normal level and the minimum run
Horsepower rated motor circuit protector and timer has expired, whichever occurs last. In the
starting contactor Hand mode, the pump will continue to run until
Suitable for use as service equipment the HAND-OFF-AUTO selector switch is moved
HAND-OFF-AUTO selector switch from the Hand position.
Minimum run timer The stainless steel pressure transducer is
On-Delay timer mounted inside the enclosure and is piped to a fit-
Pump restart timer ting on the bottom of the enclosure.
Control circuit transformer with 24VAC
secondary Options and Modifications See publication
0-300 psi (0-20.7 bar) stainless steel solid state PD550F-01 for list of available options and modi-
pressure transducer fications.
Overpressure indication
Low Pressure indication *See publication SD550F-01 for available horse-
Failed to start indication power and voltage configurations.

CB550F-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2010 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550F Fire Pump Controllers for
Business-Critical Continuity
Jockey Pump Controllers
Specifications

Jockey Pump Controller 3R, 4, 4X, and 12 protection and shall be fully accessible
The auxiliary jockey pump controller, if required and without opening the controller door. The display and user
specified on the plans and specifications, shall be factory interface shall utilize multiple levels of password protec-
assembled, wired, and tested and specifically designed tion for system security. A minimum of 3 password levels
for this type of service. This controller shall be of the same shall be provided. The operator shall have the ability to
manufacturer as the main fire pump controller. choose up to 2 lines of data to be displayed on the main
(home) information screen.
Approvals
Firetrol Jockey Pump Controllers are listed by Under- Digital Status/Alarm Messages
writers Laboratories, Inc., in accordance with UL508A, The digital display shall indicate text messages for
Standard for Industrial Controls, and CSA, Standard for the status and alarm conditions of:
Industrial Control Equipment (cUL). They are built to meet Pump Running Sequential Start Time
or exceed the requirements of the approving authorities as Minimum Run Time Low System Pressure
well as NEMA and the latest edition of NFPA 70, National Pump Restart Timer Fail to Start
Electrical Code. Automatic Start System Overpressure
User Selectable #11 Main Switch Position
Construction User Selectable #21
The jockey pump controller shall be full voltage start- 1
User may choose from the following to be shown on main display
ing, rated for wye-connected power systems above 240V. (stop pressure setting, start pressure setting, cycles/period, cycles/
month, cycles/day, cycles/hour, total cycle count, pump total run time)
The controller components shall be housed in a NEMA
Type 2/12 (IEC IP11/IP52) polycarbonate, wall mounted
enclosure (UL50E Construction). The controller shall The Sequential Start Timer, Minimum Run Timer/Off
incorporate a horsepower rated manual circuit protector Delay Timer and Pump Restart Timer shall be displayed
and starting contactor, control circuit transformer with as numeric values reflecting the value of the remaining
24VAC secondary and 200-600V multi-tap primary, main time.
disconnect switch, HAND-OFF-AUTOMATIC selector
switch and a 0-300 psi (0-20.7 bar) stainless steel solid LED Visual Indicators
state pressure transducer. LED indicators, visible with the door closed, shall
indicate:
Short Circuit Current Ratings Power ON Alarm
The jockey shall have standard short circuit current Pump Running
ratings of:
30kA @ 480 Volts Max. Data Logging
18kA @ 600 Volts The digital display shall monitor the system and log
the following data:
Operator Interface Motor Calls/Starts Pump Total Run Time
The fire pump controller shall feature an operator in- Pump Last Run Time Total Controller Pwr On Time
terface with user keypad. The interface shall monitor and Last Pump Start Min/Max System Pressure
display motor operating conditions, including all alarms, Last Phase Fail/Reverse Cycle Counts
events, and pressure conditions. The display shall be
a 128x64 Backlit LCD capable of customized graphics.
The display and interface shall be NEMA rated for Type 2,
Event Recording shall be based upon successful tri-axial shake-table
Memory - The controller shall record all operational testing in accordance with ICC-ES AC-156. Certification
and alarm events to system memory. All events shall be without testing shall be unacceptable. Controller shall
time and date stamped and include an index number. be clearly labeled as rated for installation in seismic areas
The system memory shall have the capability of storing and a Certificate of Conformance shall be provided with
3000 events and allow the user access to the event log the controller.
via the user interface. The user shall have the ability to
scroll through the stored messages in groups of 1 or 10. Operation
A digitally set On Delay (Sequential Start) timer shall
Serial Communications be provided as standard. Upon a call to start, the user
The controller shall feature a RS485 serial communica- interface shall display a message indicating the remaining
tions port for use with 2 or 4 wire Modbus communica- time value of the On Delay timer.
tions. The controller shall include a Minimum Run Timer
to allow the motor to run for a set period of timer after
Solid State Pressure Transducer starting. The timer shall be programmable through the
The controller shall be supplied with a stainless steel user interface.
solid state pressure transducer with a range of 0-300 psi A pump restart delay timer shall be provided to al-
(0-20.7 bar) 1 psi. The solid state pressure transducer low the residual voltage of the motor to decay prior to
shall be used for both display of the system pressure and restarting the motor and to prevent severe short cycling
control of the jockey pump controller. Systems using ana- of the motor. The timer shall be programmable through
log pressure devices or mercury switches for operational the user interface.
control will not be accepted. A Lamp Test feature shall be included. The user
The START and STOP PRESSURE shall be adjustable interface shall also have the ability to display the status
through the user interface. The pressure transducer shall of the system inputs and outputs.
be mounted inside the controller to prevent accidental An Audible Test feature shall be included to test the
damage. The pressure transducer shall be directly pipe operation of the audible alarm device (if supplied).
mounted to a bulkhead pipe coupling without any other The disconnect switch shall be mechanically inter-
supporting members. Field connections shall be made locked so that the enclosure door cannot be opened with
externally at the controller coupling to prevent distortion the handle in the ON position except by a hidden tool
of the pressure switch element and mechanism. operated defeater mechanism. The disconnect switch
shall be capable of being padlocked in the OFF position
Seismic Certification for installation and maintenance safety.
The controller shall be certified to meet or exceed the The controller shall be a Firetrol brand.
requirements of the 2006 International Building Code
and the 2010 California Building Code with Importance
Factor 1.5 and Sds equal to 1.88 or less. Qualifications

SP550F-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2012 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550F Fire Pump Controllers for
Business-Critical Continuity
XG Jockey Pump Controllers
Product Description

Low Pressure indication


Failed to start indication
Main switch not in Auto alarm
Pressure recording
Event log (3000 events stored in controller
memory)
Data log (including cycle counter)
Door mounted display/user interface featuring
a 128 x 64 pixel backlit LCD Graphical Display,
Membrane Type User Controller Push-buttons
and LED indication for:
Power ON
Pump Running
Alarm
2 lines of user selectable display information
DescriptionFiretrol FTA550F XG Jockey Pump
Controllers are intended for use with fire pump
systems. They are used for pressure maintenance NOTE: FTA550F XG Jockey Pump Controllers are
in fire pump installations to prevent unnecessary only available in the voltage/horsepower
operation of the main fire pump. combinations shown below and with the op-
tions shown on the reverse side. For other
ApprovalsFiretrol jockey pump controllers are combinations and options, see documen-
listed by Underwriters Laboratories, Inc., in ac- tation for FTA550E series XG Jockey Pump
cordance with UL508A, Standard for Industrial Controllers.
Controls, and CSA, Standard for Industrial Control
Equipment. They are built to meet or exceed the VOLTAGE 3-PHASE MAX HP Short Circuit
requirements of the approving authorities as well (50/60 Hertz) (MCP) Current Rating
as NEMA and the latest edition NFPA 70, National
Electrical Code. -H 200-208 7.5 30kA
-A 220-240 10 30kA
Standard FeaturesThe following are included as -F 380-415V - WYE 15 30kA
standard with each controller: -B 440-480V - WYE 20 30kA
NEMA Type 2/12 (IEC IP11/IP52) Polycarbonate -C 550-600V - WYE 20 18kA
enclosure (UL50E Construction)
Horsepower rated motor circuit protector and VOLTAGE 1-PHASE MAX HP Short Circuit
starting contactor (50/60 Hertz) (MCP) Current Rating
Suitable for use as service equipment
HAND-OFF-AUTO selector switch -D 110-120 Volts 2 30kA
Minimum run timer -T 200-208 Volts 3 30kA
On-Delay timer -E 220-240 Volts 3 30kA
Pump Restart Timer
Control circuit transformer with 24VAC
secondary
0-300 psi (0-20.7 bar) stainless steel solid state NOTE: Firetrol Brand Jockey Pump controllers DO NOT
pressure transducer CONTAIN MERCURY filled pressure switches.
Overpressure indication
OPTIONS & MODIFICATIONS -BY Contacts for Remote Indication, Pump
Overload
SPECIAL ENCLOSURES -EF Contacts for Remote Indication, Switch Not
-T NEMA Type 3R (IEC IP14)* In Auto
-E NEMA Type 4 (IEC IP56)* -HV Audible Alarm (required if local audible
-F NEMA Type 4X (IEC IP56)* alarm indication is desired).
-KH Contacts for Remote Indication, Common
*Supplied with non-metallic enclosure Output for Any Alarm
-NZ Interlock Input Contacts to Prevent Jockey
ANTI-CONDENSATION SPACE HEATERS1 Pump from Starting During Main Controller
-J 120 Volt Space Heater With Operation
Thermostat -S Tropicalization
-K 120 Volt Space Heater With -SEI Seismic Certification (in accordance
with IBC)
Humidistat -ZPA Customized, annual service display message
-M 240 Volt Space Heater With (when factory programmed or programmed by
Thermostat Firetrol representative during start-up)
-N 240 Volt Space Heater With -ZPJ Communications, Serial Modbus over RS485, 2 or
Humidistat 4 wire

1
Power source supplied by others *Export Packaging available for additional cost

PRESSURE TRANSDUCERS
-C 0-300 pis (0-21.1 bar) Pressure Transducer NOTE: For requirements not listed here (higher
for Corrosive Service short circuit ratings, larger horsepowers,
-D 0-600 psi (0-42.25 bar) Pressure Transducer options not listed...etc) please refer to
for Corrosive Service documentation for FTA550E series Jockey
Pump Controllers.
MISCELLANEOUS
-AC Contacts for Remote Indication, Pump Run
-AM Contacts for Remote Indication, Failed to
Start
-AST Auto Start Contacts (for connection to user
supplied N.O. remote starting device)
-BW Contacts for Remote Indication, Phase
Failure/Reversal

PD550F-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2012 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550F Fire Pump Controllers for
Business-Critical Continuity
XG Jockey Pump Controllers
Model Number Selection Guide

FTA550F XG JOCKEY PUMP CONTROLLERS


FTA550F-A G __ __ __ __ - __ (Example: FTA550F-AG015B-T-BY)

FTA NUMBER OPTIONS & MODIFICATIONS


FTA550F (See other side)
TIMER OPTION
-A With Programmable VOLTAGE 3-PHASE MAX HP
Running Period Timer (50/60 Hertz)
MOTOR CURRENT PROTECTION -H 200-208 Volts 7.5
-G Manual Motor Protector -A 220-240 Volts 10
*Suitable for Use as Service Equipment* -F 380-415V - WYE 15
Short Circuit Current Rating -B 440-480V - WYE 20
200-480V - 30kA -C 550-600V - WYE 20
600V - 18kA
VOLTAGE 1-PHASE MAX HP
HORSEPOWER (KW) (50/60 Hertz)
014 - 1/4 HP (.18) 004 - 4 HP (3)
013 - 1/3 HP (.23) 005 - 5 HP (3.7) -D 110-120 Volts 2
012 - 1/2 HP (.37) 006 - 5 1/2 HP (4) -T 200-208 Volts 3
034 - 3/4 HP (.56) 007 - 7 1/2 HP (5.5) -E 220-240 Volts 3
001 - 1 HP (.75) 010 - 10 HP (7.5)
011 - 1 1/2 HP (1.1) 015 - 15 HP (11)
002 - 2 HP (1.5) 020 - 20 HP (15)
003 - 3 HP (2.2)

(See Voltage Selection for Maximum


HP/Voltage Combinations)

NOTE: For requirements not listed here (higher


short circuit ratings, larger horsepowers,
options not listed...etc) please refer to
documentation for FTA550E series Jockey
Pump Controllers.
-BY Contacts for Remote Indication, Pump
OPTIONS & MODIFICATIONS Overload
-EF Contacts for Remote Indication, Switch Not
SPECIAL ENCLOSURES In Auto
-T NEMA Type 3R (IEC IP14)* -HV Audible Alarm (required if local audible
-E NEMA Type 4 (IEC IP56)* alarm indication is desired).
-F NEMA Type 4X (IEC IP56)* -KH Contacts for Remote Indication, Common
Output for Any Alarm
*Supplied with non-metallic enclosure -NZ Interlock Input Contacts to Prevent Jockey
Pump from Starting During Main Controller
ANTI-CONDENSATION SPACE HEATERS1 Operation
-J 120 Volt Space Heater With -S Tropicalization
Thermostat -SEI Seismic Certification (in accordance
-K 120 Volt Space Heater With with IBC)
Humidistat -ZPA Customized, annual service display message
-M 240 Volt Space Heater With (when factory programmed or programmed by
Firetrol representative during start-up)
Thermostat -ZPJ Communications, Serial Modbus over RS485, 2 or
-N 240 Volt Space Heater With 4 wire
Humidistat
1
Power source supplied by others *Export Packaging available for additional cost
PRESSURE TRANSDUCERS
-C 0-300 psi (0-21.1 bar) Pressure Transducer NOTE: For requirements not listed here (higher
for Corrosive Service short circuit ratings, larger horsepowers,
-D 0-600 psi (0-42.25 bar) Pressure Transducer options not listed...etc) please refer to
for Corrosive Service documentation for FTA550E series Jockey
Pump Controllers.
MISCELLANEOUS
-AC Contacts for Remote Indication, Pump Run
-AM Contacts for Remote Indication, Failed to
Start
-AST Auto Start Contacts (for connection to user
supplied N.O. remote starting device)
-BW Contacts for Remote Indication, Phase
Failure/Reversal

SD550F-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2012 Emerson Electric Co.