Combustion Control for Boilers

1 September 23, 2004


Contents
1. Introduction
2. Basic type of boilers.
3. Why need boiler controls?
4. Combustion control for boilers.
5. Fujis oxygen gas analyzer.

2 September 23, 2004


1. Introduction
How does a boiler works?

A boiler is a water containing vessel which transfers heat from a fuel


source (oil, gas or coal) into steam which is piped to a point where
it can be used to run production equipment, to sterilize, to provide
heat, to steam-clean, etc.

The energy given up by the steam is sufficient to convert it back


into the form of water. When 100% of the steam produced is
returned to be reused, the system is called a closed system.

Since some processes can contaminate the steam, so it is not


always desirable to feed the condensate back into the boiler. A
system that does not return the condensate is called an open
system.

3 September 23, 2004


1. Introduction
Closed system

4 September 23, 2004


1. Introduction
Open system

5 September 23, 2004


2. Basic type of boilers.
The two main types of boilers are:
1. Firetube
2. Watertube

6 September 23, 2004


2. Basic type of boilers.
1. Firetube
Fire or hot gases are directed through the inside of tubes
within the boiler shell which are surrounded by water. The
tubes are arranged in banks so that the gases can be passed
through the boiler up to 4 times before passing out the stack.
This system exposes the maximum heat transfer surface to the
water. Firetube boilers are also known as shell boilers and can
produce up to approximately 750 hp or 25,000 lbs of steam per
hour. 80% of boilers in use are of this configuration.

7 September 23, 2004


2. Basic type of boilers.
1. Firetube

8 September 23, 2004


2. Basic type of boilers.
1. Firetube

9 September 23, 2004


2. Basic type of boilers.
2. Watertube
Fire or hot gases are directed to and around the outside of
tubes containing water, arranged in a vertical position.
Watertube boilers are usually rectangular in shape and have
two or more drums. The separation of steam and water takes
place in the top drum, while the bottom drum serves as a
collection point for sludge. This system is usually used when
more than 750 hp or several hundred thousand lbs of steam
per hour, are needed.

There are other designs with special configurations, adapting


them to particular applications

10 September 23, 2004


2. Basic type of boilers.
2. Watertube

11 September 23, 2004


2. Basic type of boilers.
2. Watertube

12 September 23, 2004


3. Why need boiler controls?
Boiler efficiency relates the boilers energy output to
the boilers energy input and can be expressed as:-

Boiler efficiency (%) = Heat exported by fluid/Heat provided by fuel

An accurate control of the amount of air is essential to the boiler


efficiency. Too much air will cool the furnace and carried away
useful heat. And too little air and the combustion will be
incomplete. Unburned fuel will be carried over and smoke may be
produced.

13 September 23, 2004


3. Why need boiler controls?
1. Increase uptime and availability
2. Reduce flue gas emissions
3. Maintain boiler safety
4. Control operating costs

14 September 23, 2004


3. Why need boiler controls?
1. Increase uptime and availability
The primary objective of most boilers operation is
maintaining the uptime and availability. It is essential to
maintain and upgrade the boiler control systems to assure
steam availability.
Modern controls are more reliable and can be readily
adjusts to load swings caused by varying plant operations.

15 September 23, 2004


3. Why need boiler controls?
2. Reduce flue gas emissions
Failure to comply with the current emissions regulations can
be as costly as loss of utilities. Government mandates are
enforced by fines, threat of closure, or imprisonment will
provide sufficient incentives for plants to comply with the
regulations; thus, modernize controls are necessary.
Improved in combustion efficiency means reduction in
waste disposal problems. And by accurately controlling the
oxygen, fuel flow and stack temperature, you will see
reductions in plant emissions.

16 September 23, 2004


3. Why need boiler controls?
3. Maintain boiler safety
Modernize control system will have tight integration with
flame safety or burner management system to improve
safety.
Accessing field data, diagnostics functions and alarms can
be achieved by coupling modern electronic controls.
Password security of the configuration software also assures
no unintended changes can be done which can endanger
your personnel and equipment.

17 September 23, 2004


3. Why need boiler controls?
4. Control operating costs
a) Reduction in fuel consumption
b) Reduction in engineering, installation and startup costs
c) Reduction maintenance costs associated with older
equipment
a) Reduction manpower with automatic responds
b) Provide a flexible control strategy to reduce process upsets
c) Readily data available for remote monitoring to determine
process optimization, boiler efficiency and load allocations

18 September 23, 2004


4. Combustion control for boilers.
Burner combustion control generally includes one or a
combination of the following methods:-
Excess air regulation
Oxygen trim
Burner modulation
Air/Fuel cross-limiting

Total heat control

19 September 23, 2004


4. Combustion control for boilers.
1. Excess air regulation
In actual practice, gas , oil, coal burning and other systems
do not do a a perfect job of mixing the fuel and air even
under the best achievable conditions. Additionally,
complete mixing may be a lengthy process. To ensure
complete combustion and reduce heat loss, excess air has
to be kept within suitable range.
The regulation of excess air provides:-
A better boilers hear transfer rate
An advance warming of flue gas problems
Excess air coming out of the zone of maximum efficiently
Substantial savings on fuel

20 September 23, 2004


4. Combustion control for boilers.
1. Excess air regulation

21 September 23, 2004


4. Combustion control for boilers.
2. Oxygen trim
When a measurement of oxygen in the flue gas is available, the
combustion control mechanism can be vastly improved (since the
percentage of oxygen in flue is closely related to the amount of
excess air) by adding an oxygen trim control module, allowing
Tighter control of excess air to oxygen setpoint for better
efficiency
Faster return to setpoint following disturbances
Tighter control over flue emissions
Compliance with emission standards
Easy incorporation of carbon monoxide or capacity override

22 September 23, 2004


4. Combustion control for boilers.
2. Oxygen trim

23 September 23, 2004


4. Combustion control for boilers.
3. Burner modulation
Modulating control is a basic improvement in controlling
combustion. A continuous control signal is generated by a
controller monitoring the steam or hot water line. Reductions in
steam pressure or hot water temperature lead to an increase in
firing rate. The advantages of introducing burner modulation in
combustion control include.
Fuel and air requirements are continuously matched to the
combustion demand
Steam pressure or hot water temperature is maintained within
closer tolerances
Greater boiler efficiency
Weighted average flue gas temperature is lower

24 September 23, 2004


4. Combustion control for boilers.
4. Air/Fuel cross-limiting
A cross limiting combustion control strategy ensures that there can
never be a dangerous ration of air and fuel within a combustion
process. This is implemented by always raising the air flow before
allowing the fuel flow to increase or by lowering the fuel flow
before allowing the air flow to drop.
Cross-limiting combustion control is highly effective and can easily
provide the followings
Optimization of fuel consumption
Safer operating condition by reducing risk of explosion
Fast adaptation to variation in fuel and air supplies
Satisfaction of the plant demand fore steam

25 September 23, 2004


4. Combustion control for boilers.
4. Air/Fuel cross-limiting

26 September 23, 2004


4. Combustion control for boilers.
5. Total heat control
A cross limiting combustion control strategy ensures that there can
never be a dangerous ration of air and fuel within a combustion
process. This is implemented by always raising the air flow before
allowing the fuel flow to increase or by lowering the fuel flow
before allowing the air flow to drop.

27 September 23, 2004


4. Combustion control for boilers.
5. Total heat control

28 September 23, 2004


4. Fujis oxygen gas analyzer.
Top class performance zirconia oxygen analyzer

29 September 23, 2004


4. Fujis oxygen gas analyzer.
Accurate O2 Measurement is Essential for Energy Saving!

The oxygen analyzer consists of a compact zirconia detector that


can be inserted directly in wall of the flowing sample gas. The
detector measures the oxygen content in the flowing sample gas
and transmits the signal to the converter. The converter will then
trigger the ON-OFF alarm based on the preset oxygen
concentration and give control signal to other devices.

Fuji Electrics oxygen analyzer has a unique construction that


eliminates the necessity of aspirating sampling gas or injecting air.
And make it extremely suitable for monitoring and controlling
combustion system like, heater boiler, kiln, melting furnace, low
oxygen warehouse and food packing machine.

30 September 23, 2004


4. Fujis oxygen gas analyzer.
Excess air coefficient and energy loss ratio
Excess Air Exhaust Oxygen, Energy Loss Ratio,
Coefficient O2 (%) Exhaust Gas (%)
1.1 1.9 9.4

1.2 3.5 10.3

1.3 4.8 11.1

1.4 6.0 12.0

1.6 7.9 13.7

(In the case of heavy oil combustion at exhaust gas temperature of 250 C and atmospheric temperature of 20 C)

31 September 23, 2004


4. Fujis oxygen gas analyzer.
Calculation of cost saving with improved combustion efficiency
(The data may varies based on the construction and performance of the boilers)

Item Case 1 Case 2

Evaporation rate from boiler 5ton/hr 1ton/hr

Annual operating hours 2,000hrs

Evaporation multiplier factor for boiler 12

Improved value of excessive air coefficient 1.6 -> 1.2


(O2 gas from 7.9% -> 3.5%)

Kerosene price USD 1.05/kg (USD 0.82/, SG 0.78)

Kerosene consumption rate 5,000kg/hr 12 = 420kg/hr 2,000kg/hr 12 = 85kg/hr

Annual saving through the improved 420kg/hr x USD 1.05/kg x 85kg/hr x USD 1.05/kg x
combustion efficiency (13.7 10.3) % x 2,000hrs (13.7 10.3) % x 2,000hrs
= USD 29,988.00 = USD 6,069.00
Note: The data shown in the above table are calculated on an assumption of improvement of energy loss = full reduction ratio,
therefore the combustion efficiency of the boiler must be taken into account for calculating fuel reduction rate accurately. Fuel
reduction ratio will therefore be least several percent higher in actuality.

32 September 23, 2004


4. Fujis oxygen gas analyzer.
Advantages:
1. No sampling device is required
The instrument requires no gas aspirating pump or ejector for normal measurements; therefore it
can be operated easily. It can be used very conveniently like traditional thermocouple.

2. Compact and light weight design


The detector and converter weigh about 1.6kg and 3.5kg respectively.

3. Instrument equipped with indicator and transmitting function


The converter is equipped with an indicator that permits direct readout of the oxygen concentration
transmitting output function or RS485 communication.

4. Alarm and control functions available


Though compact it is compact and lightweight in design, the converter consists of an oxygen
concentration setting mechanism as well as alarm setting and control circuits that can transmit
control signals.

5. Lost cost
Comparing Zircomat-P with other conventional oxygen analyzers it is much more economical in cost.

6. Easy maintenance
Zircomat-P assures easier maintenance comparing to other conventional oxygen analyzers and can
be used under severe site conditions for a long time.

33 September 23, 2004


4. Fujis oxygen gas analyzer.
System Outline

34 September 23, 2004


4. Fujis oxygen gas analyzer.
Technical Specifications
Measuring range 0 to 2 ~ 50%
Repeatability Within 0.5% maximum output signal
Linearity 2% full scale
Response time With 7 seconds
Power Supply 100, 115, 220 or 230 Vac, 50/60Hz
Power consumption 15 + 50VA
Warm up time 15minutes
Type Direct insertion type zirconia detector
Detector
Applicable gas temperature -20~+600 C or -20~+1,590 C
Sample gas pressure -3~+3kPa (-306~+306mmH2O)
Ambient temperature -20~+60 C or -5~100 C
Output signal 4~20mA or 0~1Vdc
Converter
Indication oxygen concentration 3-digits LED

Indication operation/settings 16-digits LCD

Mode display 03 x LED

Mounting Panel or Pipe Mounting

Optional function RS-485

35 September 23, 2004


4. Fujis oxygen gas analyzer.
Standard air ratio by Energy Economy Law in Japan for conservation of energy

Based on Article 4, Clause 1 of the law regarding rational use of energy (Law No. 49 published in 1979), judging
standard for enterprisers at factories (Notification No. 467 of the Ministry of Commerce and Industry, dated October
1979) has been amended on October 26, 1979 (Notification No. 559 of the Ministry of Commerce and Industry) to
specify standard air ratio.

1. Boilers
Classification Load Standard air ratio
Ratio
(%) Solid Liquid Gaseous Blast furnace
Fuel fuel fuel gas
For electrical enterprise 75~100 1.2~1.3 1.05~1. 1.05~1.1 1.2
1
Evaporation rate exceeding 75~100 1.2~1.3 1.1~1.2 1.1~1.2 1.3
Others

30ton/hr
Evaporation rate from 75~100 - 1.2~1.3 1.2~1.3 -
10~30ton/hr
Evaporation rate not 75~100 - 1.3 1.3 -
exceeding 10ton/hr

36 September 23, 2004


4. Fujis oxygen gas analyzer.
2. Industrial Furnaces
Classification Standard air Ratio
Metal melting furnace 1.3
Continuous steel heating furnace 1.25
Metal heating furnace not continuous steel heating type 1.3
Continuous thermal treatment furnace 1.3
Gas producer and gas heating furnace 1.4
Oil heating furnace 1.4
Pyrolytic furnace and modification furnace 1.3
Cement kiln 1.3
Alumina kiln and lime kiln 1.4
Continuous glass melting kiln 1.3

37 September 23, 2004


The End