You are on page 1of 36

Low voltage electrical distribution

Micrologic
Control units
2.0 A, 5.0 A, 6.0 A, 7.0 A

User manual
09/2009
Micrologic control units Contents
2.0 A, 5.0 A, 6.0 A and 7.0 A

Discovering your control unit 2


Identifying your control unit 2
Overview of functions 4
Setting your control unit 10
Selecting the type of neutral protection 10
Setting procedure 11
Setting the Micrologic 2.0 A control unit 12
Setting the Micrologic 5.0 A control unit 13
Setting the Micrologic 6.0 A control unit 14
Setting the Micrologic 7.0 A control unit 15
Fault and status indications 16
Resetting the fault indications and checking battery status 16
Testing the ground-fault and earth-leakage functions 17
Menus 18
Accessing the menus 18
Measuring phase currents 19
Displaying the maximum current values 20
Resetting the maximum current values 21
Viewing the settings 22
Setting up the Modbus communications option 23
Technical appendix 24
Tripping curves 24
Changing the long-time rating plug 26
Zone selective interlocking (ZSI) 27
Digital display 28
Thermal memory 29

04443724AA - 09/2009 
Discovering your Identifying your control unit
control unit Designations

All Compact NS800-3200 and Masterpact NT and NW Micrologic 2.0 A: basic protection and ammeter
circuit breakers are equipped with a Micrologic control
t

DB119423
E51384A
unit that can be changed on site.
Micrologic 2.0 A

Control units are designed to protect power circuits and


connected loads.

100 %

40 %

menu

0 Ir Isd I
long time
Ir tr alarm
.8 (s) 4
8
.7 .9 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

Long time + Instantaneous


instantaneous
Isd
3 4 5
2.5 6
2 8
1.5 10
x Ir
setting

Micrologic 2.0 A
E51450A

Micrologic 5.0 A: selective protection and ammeter


t
E51385A

DB119424
Micrologic 5.0 A

X
Y
100 %

40 %

Z Ir

.6
.5
.7

.4
menu

long time
.8

x In
short time
.9

1
.95
tr
(s) 4 8 12

.98 1
2

.5
16
20
24
at 6 Ir

Ii
alarm

instantaneous
0 Ir Isd Ii I
Long time + Short time + Instantaneous
tsd
Isd 4
3 5 (s) .4 .4 .3 6
8 10
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15

X: type of protection
1.5 10 .1 2 0 2 off
x Ir on I t x In
setting delay

b 2 for basic protection


b 5 for selective protection
b 6 for selective + ground-fault protection
b 7 for selective + earth-leakage protection Micrologic 6.0 A: selective + ground-fault protection
Y: version number and ammeter
identification of the control-unit generation.
t
E51387A

t
Micrologic 6.0 A
DB119425
DB119424

"0" signifies the first generation.

Z: type of measurement 2
I t on
b A for "ammeter"
b P for "power meter" 100 %

2
I t off
b H for "harmonic meter" 40 %

b no indication: no measurements
menu

long time

0 Ig I
Ir .8 tr 8
alarm

0 Ir Isd Ii I
.7 .9 (s) 4 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

short time instantaneous

Long time + Short time Ground-fault protection


Isd tsd Ii
3
4 5 (s) .4 .4 .3 6
8 10
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off
on I t x In
x Ir

+ Instantaneous
setting delay
test
tg
Ig
D E F (s) .4 .4 .3
C G .3 .2
B H .2 .1
A I .1 2 0
on I t off
ground fault

Micrologic 7.0 A: selective + earth-leakage


protection and ammeter
t t
E51388B

DB119424

DB119426

Micrologic 7.0 A

100 %

40 %

menu

0 In I
long time

0 Ir Isd Ii I
Ir .8 tr 8
alarm
.7 .9 (s) 4 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

Long time + Short time Earth-leakage protection


short time instantaneous
Isd tsd Ii
3
4 5 (s) .4 .4 .3 6
8
10
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15

+ Instantaneous
1.5 10 .1 2 0 2 off
on I t off x In
x Ir
setting delay
test

In 5 7 I 230 350
3
2 10
140
1 20 800
.5 30 60
earth leakage

 04443724AA - 09/2009
Discovering your Identifying your control unit
control unit Presentation

1 top fastener

E51389B

E51390A
1
2 bottom fastener
3 protective cover 10
4 cover opening point logic
7. 0A
Micro
5 lead-seal fixture for protective cover
6 long-time rating plug 31
7 screw for long-time rating plug 12
8 connection with circuit breaker 11
9 infrared link with communications interfaces
13 9
10 terminal block for external connections 100 %

11 housing for battery 30 40 %


12 digital display
13 three-phase bargraph and ammeter 29
alarm

menu long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 Ir
.5 at 6

Adjustment dials
1
.4 x In

5 7
14 long-time current setting Ir
3 6
15 long-time tripping delay tr
16 short-time pickup Isd 8
4
17 short-time tripping delay tsd 2
18 instantaneous pick-up Isd
19 instantaneous pick-up Ii Micrologic 7.0 A Micrologic 2.0 A
20 ground-fault pick-up Ig
21 ground-fault tripping delay tg
E51391B

E51394A
24 25 26 27
22 earth-leakage pick-up In
23 earth-leakage tripping delay t 28
7
long time
Ir tr alarm
.8 (s) 4
8
.7 .9 12
Micrologic 7.0 A
Indications 14 .6 .95 2 16
.5 .98 1 20

31
.4 1 .5 24
x In at 6 Ir

15 Isd
instantaneous

24 LED indicating long-time tripping 3 4 5


6
18
2.5
2 8
25 LED indicating short-time tripping 1.5 10

12
x Ir

26 LED indicating ground-fault


setting

or earth-leakage tripping
33
27 LED indicating auto-protection tripping
28 LED indicating an overload 13
100 %
Navigation
Micrologic 5.0 A
40 %
29 navigation button to change menus
E51393A

28
30 navigation button to view menu contents
31 button for fault-trip reset and battery test 7
long time
Ir tr alarm

14
.8 (s) 4
8
.7 .9 12
29 menu 30 .6
.5
.95 2
.98 1
16
20
.4 1 .5 24

15
x In at 6 Ir

short time instantaneous

14
Ir
long time
.8 tr 8
alarm 28 Isd
3 4 5
tsd
(s) .4 .4 .3
Ii
6 8 10
Test .6
.7 .9 (s) 4
.95 2
12
16 16 2.5
2
6
8
.3
.2
.2
.1
4
3
12
15

7
.5 .98 1 20 1.5 10 .1 0 2 off

15 24 2
.4 1 .5 x Ir on I t x In
x In at 6 Ir

32 test button for ground-fault and earth-leakage Isd


short time
tsd
instantaneous 17 setting delay

3 4 5 (s) .4 .4 .3 Ii
6
8
10
.3 .2
protection 16
2.5
2
6
8 .2
.1 2 0
.1
4
3
12
15 19 19 33
33 test connector
1.5 10 on I t off 2 off
x Ir x In
17 In
setting
I
(ms) 230
delay
test
32
(A) 5 350
3 7
2 10

22 1
.5 30
20
140

60
800 33
earth leakage
Micrologic 6.0 A
23
E51392A

15 Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm 28
14 .6 .95 2 16
.5
.4
x In
1
.98 1
.5
20
24
at 6 Ir
7
17 Isd
short time
tsd Ii
instantaneous

3
4
5 (s) .4 .4 .3 6
8
10
.3 .2
16 2.5
2
6
8 .2 .1
4
3
12
15 19
1.5 10 .1 2 0 2 off
x Ir on I t off x In
21 Ig
setting
tg
delay
test
32
D
E
F (s) .4 .4 .3
.3 .2
20
C G
B
A I
H .2
.1 2 0
.1
33
on I t off
ground fault

04443724AA - 09/2009 
Discovering your Overview of functions
control unit Current protection

Protection settings
Depending on the type of installation, it is possible to set the tripping curve of your
control unit using the parameters presented below.

Micrologic 2.0 A
t

DB119427
1

0 Ir Isd I
1. current setting Ir (long time)
2. tripping delay tr (long time) for 6 x Ir
3. pick-up Isd (instantaneous)

Micrologic 5.0 A, 6.0 A, Micrologic 6.0 A Micrologic 7.0 A


7.0 A
t t t
1
DB119428

DB119429

DB119430
2
I t on 2
I t on
2
2
I t off 2
1 I t off 1
3
4 2 2
5

0 Ir Isd Ii I 0 Ig I 0 In I
1. current setting Ir 1. pick-up Ig (ground 1. pick-up In
(long time) fault) (earth leakage)
2. tripping delay tr 2. tripping delay tg 2. tripping delay t
(long time) for 6 x Ir (ground fault) (earth leakage)
3. pick-up Isd (short time)
4. tripping delay tsd
(short time)
5. pick-up Ii
(instantaneous)

Long-time protection
The long-time protection function protects cables (phases and neutral) against
overloads. This function is based on true rms measurements.

Thermal memory
The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of an
overload or not). The thermal memory optimises the long-time protection function of
the circuit breaker by taking into account the temperature rise in the cables. The
thermal memory assumes a cable cooling time of approximately 15 minutes.

Long-time current setting Ir and standard tripping delay tr

Micrologic control unit Accuracy 2.0 A, 5.0 A, 6.0 A and 7.0 A


Current setting Ir = In (*) x 0,4 0,5 0,6 0,7 0,8 0,9 0,95 0,98 1
tripping between other ranges or disable by changing rating plug
1.05 and 1.20 x Ir
Time delay (s) tr at 1.5 x Ir 0 to - 30 % 12,5 25 50 100 200 300 400 500 600
tr at 6 x Ir 0 to - 20 % 0,5 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0 to - 20 % 0,34 0,69 1,38 2,7 5,5 8,3 11 13,8 16,6

* In: circuit breaker rating

Setting accuracy of the Ir setting may be enhanced by using a different long-time


rating plug.
See the technical appendix "Changing the long-time rating plug".

 04443724AA - 09/2009
Discovering your Overview of functions
control unit Current protection

For the characteristics and external wiring of the zone Short-time protection
selective interlocking function, see the technical b The short-time protection function protects the distribution system against
appendix on "Zone selective interlocking". impedant short-circuits
b The short-time tripping delay can be used to ensure discrimination with a
The portable test kit can be used to test the wiring downstream circuit breaker
between circuit breakers for the zone selective b This function carries out true rms measurements.
interlocking function.
b The I2t ON and I2t OFF options enhance discrimination with downstream
protection devices
b Use of I2t curves with short-time protection:
v I2t OFF selected: the protection function implements a constant time curve;
v I2t ON selected: the protection function implements an I2t inverse-time
curve up to 10 Ir. Above 10 Ir, the time curve is constant.

b Zone selective interlocking (ZSI)


The short-time and ground-fault protection functions enable time discrimination
by delaying the upstream devices to provide the downstream devices the time
required to clear the fault. Zone selective interlocking can be used to obtain total
discrimination between circuit breakers using external wiring.

Short-time pick-up Isd and tripping delay tsd

Micrologic control unit 2.0 A, 5.0 A, 6.0 A and 7.0 A


Pick-up Isd = Ir x accuracy 10 % 1,5 2 2,5 3 4 5 6 8 10
Time delay (ms) settings I2t OFF 0 0,1 0,2 0,3 0,4
at 10 Ir I2t ON 0,1 0,2 0,3 0,4
I2t ON or tsd (max resettable time) 20 80 140 230 350
I2t OFF tsd (max break time) 80 140 200 320 500

Instantaneous protection
b The instantaneous-protection function protects the distribution system against
solid short-circuits. Contrary to the short-time protection function, the tripping delay
for instantaneous protection is not adjustable.
The tripping order is sent to the circuit breaker as soon as current exceeds the set
value, with a fixed time delay of 20 milliseconds.
b This function carries out true rms measurements.

Instantaneous pick-up Isd

Micrologic control unit 2.0 A


Pick-up Isd = Ir x accuracy 10 % 1,5 2 2,5 3 4 5 6 8 10

Instantaneous pick-up Ii

Micrologic control unit 5.0 A, 6.0 A et 7.0 A


Pick-up li = In (*) x accuracy 10 % 2 3 4 6 8 10 12 15 OFF

* In: circuit-breaker rating

04443724AA - 09/2009 
Discovering your Overview of functions
control unit Current protection

Protection of the fourth pole on four-pole


circuit breakers
Protection of the neutral conductor depends on the distribution system.
There are three possibilities.

Type of neutral Description


Neutral unprotected The distribution system does not require protection
of the neutral conductor.
Neutral protection The cross-sectional area of the neutral conductor is half that of
at 0.5 In the phase conductors.
b The long-time current setting Ir for the neutral is equal
to half the setting value
b The short-time pick-up Isd for the neutral is equal
to half the setting value
b The instantaneous pick-up Isd (Micrologic 2.0 A) for
the neutral is equal to half the setting value
b The instantaneous pick-up Ii (Micrologic 5.0 A / 6.0 A / 7.0 A)
for the neutral is equal to the setting value.
Neutral protection The cross-sectional area of the neutral conductor is equal to that
at In of the phase conductors.
b The long-time current setting Ir for the neutral is equal
to the setting value
b The short-time pick-up Isd for the neutral is equal
to the setting value
b The instantaneous pick-ups Isd and Ii for the neutral
are equal to the setting value.

Neutral protection for three-pole devices


Neutral protection is not available on three-pole devices.

Ground-fault protection on Micrologic 6.0 A


b An ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors.
The purpose of the ground-fault protection function is to eliminate this type of fault.
b There are two types of ground-fault protection.

Type Description
Residual b The function determines the zero-phase sequence current, i.e.
the vectorial sum of the phase and neutral currents
Source Ground Return b Using a special external sensor, this function directly measures
the fault current returning to the transformer via the earth cable
b It detects faults both upstream and downstream of
the circuit breaker
b The maximum distance between the sensor and
the circuit breaker is ten metres.

b Ground-fault and neutral protection are independent and can therefore be


combined.

Ground-fault pick-up Ig and tripping delay tg


The pick-up and tripping-delay values can be set independently and are identical for
both the residual and "source ground return" ground-fault protection functions.

Micrologic control unit 6.0 A


Pick-up Ig = In (*) x accuracy 10 % A B C D E F G H I
In y 400 A 0,3 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
400 A < In y 1200 A 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
In > 1200 A 500 A 640 A 720 A 800 A 880 A 960 A 1040 A 1120 A 1200 A
Time delay (ms) settings I2t OFF 0 0,1 0,2 0,3 0,4
at 10 In (*) I2t ON 0,1 0,2 0,3 0,4
I2t ON or tg (max resettable time) 20 80 140 230 350
I2t OFF tg (max break time) 80 140 200 320 500

* In: circuit-breaker rating

 04443724AA - 09/2009
Discovering your Overview of functions
control unit Current protection and alarms

Earth-leakage protection on Micrologic 7.0 A


b The earth-leakage protection function primarily protects people against indirect
contact because an earth-leakage current can provoke an increase in the potential of
the exposed conductive parts. The earth-leakage pick-up value In is displayed
directly in amperes and the tripping delay follows a constant-time curve
b An external rectangular sensor is required for this function
b This function is inoperative if the long-time rating plug is not installed
b q protected against nuisance tripping.
b kDC-component withstand class A up to 10 A.

Pick-up value In and tripping delay t

Micrologic control unit 7.0 A


Pick-up In accuracy 0 to - 20 % 0,5 1 2 3 5 7 10 20 30
Time delay (ms) settings
t (max resettable time) 60 140 230 350 800
t (max break time) 140 200 320 500 1000

Overload LED
E51398B

long time
Ir .8 tr 8
alarm
.7 .9 (s) 4 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir

short time instantaneous


Isd
4
tsd
(s) .4 .4 .3
Ii
6 8 10
100 %
3 5
2.5 6 .3 .2 4 12
2 8 .2 .1 3 15
1.5 10 .1 2 0 2 off
x Ir on I t x In
setting delay
test
In t
(A)
3
5
7
(ms) 230 350 40 %
2 10
140
1 20
800
.5 30 60
earth leakage

This LED signals that the long-time current setting Ir has been overrun.

The auto-protection function (excessive temperature or


short-circuit higher than circuit-breaker capacity) opens
Fault indications
the circuit breaker and turns on the Ap LED. Signals tripping due to an Signals tripping due
overrun of the long-time to an overrun of the short-
Caution. current setting Ir. time pick-up Isd
or the instantaneous pick-
If the circuit breaker remains closed and the Ap LED
up Isd / Ii.
remains on, contact the Schneider after-sales support
department.
E51399A

E51400A

Micrologic 7.0 A Micrologic 7.0 A

Caution.
The battery maintains the fault indications. If there are
no indications, check the battery.

Signals tripping due to an Signals tripping due to the


overrun of the ground- auto-protection function
fault pick-up Ig or the of the control unit.
earth-leakage pick-up
In.
E51402A
E51401A

Micrologic 7.0 A Micrologic 7.0 A

04443724AA - 09/2009 
Discovering your Overview of functions
control unit Ammeter measurements

If no information is displayed on the screen, see the b All Micrologic control units measure the true rms value of currents
technical appendix "Digital display". b The most heavily loaded phase is continuously displayed on the digital screen
b Using the navigation buttons, it is possible to display successively the I1, I2, I3,
neutral IN, Ig, IN and stored-current (maximeter) values
b The percent load on each phase is displayed. A bargraph displays the currents
measured on phases 1, 2 and 3 as a percentage of the long-time current setting Ir.

E60371A
1.125 x Ir
100 % 1 x Ir
0.8 x Ir
0.6 x Ir
40 % 0.4 x Ir

b Accuracy of the current measurements


Accuracy depends on both the value displayed (or transmitted) and the circuit-
breaker rating, where:

Accuracy = 0.5% In + 1.5% reading

Example
For a circuit breaker with a 4000 A rating and a current displayed on Micrologic of 49
A, the accuracy is:
0.5% x 4000 + 1.5% x 49 = 21 A

 04443724AA - 09/2009
04443724AA - 09/2009 
Setting your control unit Selecting the type
of neutral protection

On four-pole circuit breakers, it is possible to select the type of neutral protection for
the fourth pole:
b neutral unprotected (4P 3D);
b neutral protection at 0.5 In (3D + N/2);
b neutral protection at In (4P 4D).

E51383A
/2
3D+N
4P 4D
4P 3D

10 04443724AA - 09/2009
Setting your control unit Setting procedure

Setting procedure
1. Open the protective cover.

DB119432
DB119431
2. Select the desired
setting.
The set value is
automatically displayed
on the digital screen in
absolute value with the
relevant units.
b Current in amperes
(A and kA);
b Tripping delays in
seconds.

3. If no information is displayed, see the technical


DB119433

appendix "Digital display". If no further action is taken,


Microlo
gic 7.0
A
after a few seconds, the display returns to the main
menu for current measurements.

4. Close the protective cover and, if necessary, install a


lead seal to protect the settings.
100 %

40 %

menu

See the user manual for the portable test kit Using the portable test kit
To test the control unit, connect the portable test kit via the test connector.
DB119431

DB119435

7.0 A
logic
Micro

100 %

40 %

menu

04443724AA - 09/2009 11
Setting your control unit Setting the Micrologic 2.0 A
control unit

The rating of the circuit breaker in this example is 2000 A. Set the threshold values

DB119478
long time
alarm
In = 2000 A
Ir
DB119436

.8
.7 .9
.6 .95 Ir = 0.7 x In = 1400 A
.5 .98
.4 1 Isd = 3 x Ir = 4200 A
x In
instantaneous
Isd
3 4 5
2.5 6
2 8
1.5 10
x Ir
1 setting

In 2000 A
A
2000
In =

See pages 4 and 5 for information on the available


settings t
DB119438

Ir

Isd

0 I

Set the tripping delay


DB119479

long time tr = 1 s
tr alarm
(s)
8
4 12
2 16
1 20
.5 24
at 6 Ir

t
DB119440

tr

0 I

12 04443724AA - 09/2009
Setting your control unit Setting the Micrologic 5.0 A
control unit

The rating of the circuit breaker in this example is 2000 A. Set the threshold values

E60367A
long time In = 2000 A
Ir alarm
E51366B

.8 .9
.6
.7
.95
Ir = 0.7 x In = 1400 A
.5 .98
.4 1
Isd = 2 x Ir = 2800 A
x In
short time instantaneous Ii = 3 x In = 6000 A
Isd 4 5 Ii
3 6 8 10
2.5 6 4 12
2 8 3 15
1.5 10 2 off
x Ir x In
1 setting

In 2000 A
A
2000
In =

See pages 4 and 5 for information on the available


settings
Set the tripping delay
E60368B

long time tr = 1 s
tr alarm
Thresholds (s) 8 12
4
2 16
I2t ON curve I2t OFF curve 1 20
t t .5 24 tsd = 0.2 s
E51373A

E51372A

at 6 Ir
Ir Ir
short time
tsd
(s) .4 .4 .3
.3 .2 I2t on I2t off
Isd Isd .2 .1
.1 2 0
on I t
Ii Ii delay

0 I 0 I

Tripping delays
I2t ON curve I2t OFF curve
t t
E51376A

E51375A

tr tr

tsd tsd

0 I 0 I

04443724AA - 09/2009 13
Setting your control unit Setting the Micrologic 6.0 A
control unit

The rating of the circuit breaker in this example is 2000 A. Set the threshold values

DB119448
long time
Ir alarm
In = 2000 A
DB119436

.8
.7 .9
.6 .95
.5 .98
.4
x In
1 Ir = 0.7 x In = 1400 A
short time instantaneous
Isd Ii
3 4 5 6 8 10 Isd = 2 x Ir = 2800 A
2.5 6 4 12
2 8 3 15
1.5 10 2 x In off
x Ir Ii = 3 x In = 6000 A
1 setting
test
Ig
D E F
C G
B Ig = 640 A
In 2000 A B H
A
A I
2000
In =

ground fault

See pages 4 to 6 for information on the available


settings.
Set the tripping delay
DB119482

long time
Thresholds tr 8
alarm
(s) 4
I t ON curve
2
I t OFF curve
2
2
12
16
tr = 1 s
1 20
t t
DB119443

DB119444

Ir Ir .5 24
at 6 Ir

short time
tsd
(s) .4 .4 .3 tsd = 0.2 s
.3 .2
Isd Isd .2 .1
.1 2 0 I2t on I2t off
on I t off
Ii Ii delay
test
tg
0 I 0 I (s)
.4 .4 .3
.3 .2
t
DB119450

DB119451

t .1
.2 tg = 0.2 s
.1 2 0
on I t off
ground fault

Ig Ig

0 I 0 I

Tripping delays
I2t ON curve I2t OFF curve
t t
DB119445

DB119446

tr tr

tsd tsd

0 I 0 I

t t
DB119453
DB119452

tg tg

0 I 0 I

14 04443724AA - 09/2009
Setting your control unit Setting the Micrologic 7.0 A
control unit

The rating of the circuit breaker in this example is 2000 A. Set the threshold values

E51420A
long time
Ir alarm
.8 .9
E51366B

.7
.95
In = 2000 A
.6
.5 .98
.4 1
Ir = 0.7 x In = 1400 A
x In
short time instantaneous Isd = 2 x Ir = 2800 A
Isd Ii
3 4 5 6 8 10 Ii = 3 x In = 6000 A
2.5 6 4 12
2 8
1.5 10
3
2
15
off
In = 1 A
x Ir x In
1 setting
test
In
(A) 3 5 7
2 10
1 20
In 2000 A .5 30
A
2000
In =

earth leakage

See pages 4 to 7 for information on the available Set the tripping delay
settings.
E51422B

long time
Thresholds tr alarm tr = 1 s
(s) 4 8 12
I2t ON curve I2t OFF curve 2 16
1 20
t t .5 24
E51373A

E51372A

Ir Ir at 6 Ir

short time
tsd tsd = 0.2 s
.4 . 4 . 3
(s)

.3 .2
Isd Isd .2 .1
.1 2 0
on I t off
I2t on I2t off
Ii Ii delay
test
t
(ms) 230
0 I 0 I 350

t 140
E51421A

800
60 t = 140 ms
earth leakage

In

0 I

Tripping delays
I2t ON curve I2t OFF curve
t t
E51375A
E51376A

tr tr

tsd tsd

0 I 0 I

t
E51423A

0 I

04443724AA - 09/2009 15
Fault and status indications Resetting the fault indications
and checking battery status

The procedure for closing the circuit breaker following Resetting the fault indications
a fault trip is presented in the circuit-breaker user b Determine why the circuit breaker tripped.
manual. The fault indication is maintained until it is reset on the control unit.
b Press the fault-trip reset button.

E51439A
Micrologic 7.0 A

b Check the parameter settings of the control unit.

Checking the battery


DB119486

Press the battery-test button (same as the fault-trip reset button) to display
the battery status.

Battery fully charged


E51441A

Battery half charged


Change the battery

If no information is displayed, either:


b no battery is installed in the control unit, or;
b an auxiliary power supply is required.
See the technical appendix "Digital display".

If the battery needs to be changed, order a new battery Changing the control-unit battery
with the Schneider Electric catalogue number 33593. 1. Remove the battery 2. Remove the battery.
b Lithium battery cover.
b 1.2 AA, 3.6 V, 800 mA/h
DB119459
DB119458

b Ambient temperature: 130C.

100 %

40 %

3. Insert a new battery. 4. Put the cover back in


Check the polarity. place. Press the battery-
test button to check the
new battery.
DB119460

DB119461

100 %

40 %

16 04443724AA - 09/2009
Fault and status indications Testing the ground-fault and
earth-leakage functions

Charge and close the circuit breaker.


Using a screwdriver, press the test button for ground-fault and earth-leakage
protection. The circuit breaker should open.

DB119462
7.0 A
logic
Micro

100 %

40 %

menu

If the circuit breaker does not open, contact


the Schneider Electric after-sales support department.

Si votre disjoncteur ne dclenche pas :


contactez votre Service Aprs-Vente Schneider.

04443724AA - 09/2009 17
Menus Accessing the menus

Symbols used: Three menus may be accessed on Micrologic control units, providing the following
information:
b phase current measurements I1, I2, I3, neutral IN, ground-fault current Ig on the
E51404A

Micrologic 6.0 A control unit and earth-leakage current In on the Micrologic 7.0 A
control unit;
b maximeter current values for phases I1, I2, I3, neutral IN, the maximum ground-
Briefly press a key. fault current Ig on the Micrologic 6.0 A control unit and the maximum earth-leakage
current In on the Micrologic 7.0 A control unit;
b protection settings and tripping delays.
DB119463

1. Measurements 2. Maximeter 3. Settings

E51406A

E51407A

E51408A
Press and hold a key. Max
Ir=
A A A
It is possible at any time to stop consulting a current
measurement, a maximum current value recorded by
the maximeter or the setting values. After a few
seconds, the Micrologic control unit automatically
returns to the main menu displaying the current value
of the most heavily loaded phase. 100 % 100 % 100 %

The protection settings can be displayed directly on the


digital display. 40 % 40 % 40 %
menu menu menu

Press the "menu" button Press the "menu" button Press the "menu" button
to access the maximum to access the protection to return to the current
current values measured settings and tripping measurements.
by the maximeter. delays.

4. The system returns


to the main
"Measurements" menu.
E51409B

100 %

40 %

18 04443724AA - 09/2009
Menus Measuring phase currents

Current values may be read in the "Measurements" Display of current I1. Display of current I2. Display of current I3.
menu, which is also the main menu.

E51427A
E51425A

E51426A
If no particular action is taken, the system displays the
current value of the most heavily loaded phase. A A A

"Measurements" menu
100 % 100 % 100 %
Phase 1 is the most heavily loaded.
E51409B

40 % 40 % 40 %

Press the "arrow" button Press the "arrow" button Press the "arrow" button
to go on to current I2. to go on to current I3. to go on to current IN if
100 % the neutral is protected.

Display of current IN. Display of current Ig The system returns to


40 % (Micrologic 6.0 A) or the display of current I1.
current In
(Micrologic 7.0 A).

E51409B
E51428A
E51429A

A A A

100 % 100 % 100 %

40 % 40 % 40 %

Press the "arrow" button Press the "arrow" button


to go on to the ground- to return to current I1.
fault current Ig or the
earth-leakage current
In.

04443724AA - 09/2009 19
Menus Displaying the maximum
current values

Maximum current values may be read in the Display of the maximum Display of the maximum Display of the maximum
"Maximeter" menu. I1 current. I2 current. I3 current.

E51430A

E51431A

E51432A
If no particular action is taken, the system returns to the MAX MAX MAX
main menu. A A A

"Maximeter" menu.
E51407A

Max 100 % 100 % 100 %

40 % 40 % 40 %

100 % Press the "arrow" button Press the "arrow" button Press the "arrow" button
to go on to the maximum to go on to the maximum I3 to go on to the maximum
I2 current. current. current IN if the neutral is
40 % protected.
menu

Display of the maximum Display of the maximum The system returns to


IN current. Ig current or the the display of the
maximum In current. maximum I1 current.
E51434A

E51433A

E51435A
MAX MAX MAX

A A A

100 % 100 % 100 %

40 % 40 % 40 %

Press the "arrow" button to Press the "arrow" button


go on to the maximum to return to the maximum
ground-fault current Ig I1 current.
(Micrologic 6.0 A) or the
maximum earth-leakage
current In
(Micrologic 7.0 A)

20 04443724AA - 09/2009
Menus Resetting the maximum current
values

Maximum current values can be reset using the Select the maximum Reset. Select another value
"Maximeter" menu. current value to be to reset or return to
reset (e.g. I2 max.). the main menu.
If no particular action is taken, the system returns to the
main menu.

E51436A

DB119464

E51438A
MAX MAX MAX

A A A

"Maximeter" menu.
E51407A

Max

A
100 % 100 % 100 %

40 % 40 % 40 %

100 %

40 % Press the "arrow" button Press and hold the Press the "arrow" button
menu as many times as "arrow" button down for as many times as
required to select I2 max. three to four seconds. required to select another
The current value flashes maximum value to reset
during the reset, then or return to the main
changes to the present menu.
value (the new
maximum).

04443724AA - 09/2009 21
Menus Viewing the settings

Micrologic control unit


2.0 A 5.0 A 6.0 A 7.0 A
DB119483

Long-time current setting Ir Select the "Settings"


menu.
The Ir value is the first

Long-time tripping delay tr Press the "arrow" button


to go on to the tr value.

Short-time pick-up Isd Press the "arrow" button


to go on to the
short-time Isd value.

Short-time tripping delay tsd Press the "arrow" button


to go on to the tsd value.

Instantaneous pick-up Isd Press the "arrow" button


to go on to the
instantaneous Isd value.

Or

Instantaneous pick-up Ii the instantaneous Ii


value.

Ground-fault pick-up Ig Press the "arrow" button


to go on to the Ig value.

Earth-leakage pick-up In the In value.

Ground-fault tripping delay tg Press the "arrow" button


to go on to the tg value.

Earth-leakage tripping delay t the t value.

Press the "arrow" button


to return to the
beginning of the menu.

22 04443724AA - 09/2009
Menus Setting up the Modbus
communications option

When a communications option is used, the 1. Metering menu 2. Modbus address


communications parameters must be set.

E71903A

E71904A

DB119465
Note that the COM module should be set up only when
installed. Modification of a parameter on a system
A
already in operation may lead to communications
faults.

The "Parameter" menu for the communications option


displays the:
b address of the communications module;
100 % 100 % 100 %
b baud rate;
b parity;
b language.
40 % 40 % 40 %

Briefly press the button to scroll through the menu

parameter values.
Press the button somewhat longer to go on to the
next parameter.
After selecting the language, press and hold the
button to return to the "Metering" menu. You are in the "Metering" Set the Modbus address, then go on to the next
menu. Simultaneously parameter.
press the two buttons to
access the parameter
settings for the
communications option.

3. Baud rate 4. Parity


E71906A

DB119466

E71908A

100 % 100 % 100 %

40 % 40 % 40 %

Set the baud rate, then go on to the next Set the parity.
parameter.

5. Language
DB119467

E71910A

DB119468

100 % 100 % 100 %

40 % 40 % 40 %

then go on to the next Set the language, then return to the


parameter. "Metering" menu.

04443724AA - 09/2009 23
Technical appendix Tripping curves

Long-time and instantaneous protection


(Micrologic 2.0 A)

DB119484

Long-time, short-time and instantaneous protection


(Micrologic 5.0 A, 6.0 A and 7.0 A)
DB119485

24 04443724AA - 09/2009
Technical appendix Tripping curves

Ground-fault protection (Micrologic 6.0 A)

DB119471

04443724AA - 09/2009 25
Technical appendix Changing the long-time
rating plug

Select the long-time rating plug


A number of setting ranges for the long-time current setting are available on
Micrologic A control units by changing the long-time rating plug.
The available rating plugs are listed below.

Part number Setting range for the Ir value


33542 standard 0.4 to 1 x Ir
33543 low setting 0.4 to 0.8 x Ir
33544 high setting 0.8 to 1 x Ir
33545 without long-time protection
Ir = In for the Isd setting

Caution. Change the long-time rating plug


Following any modifications to the long-time rating Proceed in the following manner.
plug, all control-unit protection parameters must be
checked.
1. Open the circuit breaker.
2. Open the protective 3. Completely remove
cover of the control unit. the long-time rating plug screw.
DB119472

DB119473

Caution. 4. Snap out the rating 5. Clip in the new rating plug.
If no long-time rating plug is installed, the control unit plug.
continues to operate under the following downgraded 6. Refit the screw for the
DB119474

conditions: long-time rating plug.


b the long-time current setting Ir is 0.4;
b the long-time tripping delay tr corresponds to the 7. Check and/or modify the
value indicated by the adjustment dial; control-unit settings.
b the earth-leakage protection function is disabled.
DB119475

26 04443724AA - 09/2009
Technical appendix Zone selective interlocking (ZSI)

Operating principle
E51397B

b A fault occurs at point A.


Downstream device no. 2 clears the fault and sends a signal to upstream device
no. 1, which maintains the short-time tripping delay tsd or the ground-fault tripping
delay tg to which it is set.
b A fault occurs at point B.
Upstream device no. 1 detects the fault. In the absence of a signal from a
downstream device, the set time delay is not taken into account and the device trips
1 B
according to the zero setting. If it is connected to a device further upstream, it sends
a signal to that device, which delays tripping according to its tsd or tg setting.

Note:
On device no. 1, the tsd and tg tripping delays must not be set to zero because this would make
discrimination impossible.
2
A

Connections between control units


A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
upstream and downstream circuit breakers.
b Micrologic 5.0 A, 6.0 A, 7.0 A.
b Micrologic 5.0 P, 6.0 P, 7.0 P.
b Micrologic 5.0 H, 6.0 H, 7.0 H.
An interface is available for connection to previous generations of trip units.

Caution.
Wiring
b Maximum impedance: 2.7 / 300 metres
If the protection function is not used on circuit breakers b Capacity of connectors: 0.4 to 2.5 mm2
equipped for ZSI protection, a jumper must be installed b Wires: single or multicore
to short terminals Z3, Z4 and Z5. b Maximum length: 3000 metres
If the jumper is not installed, the short-time and ground- b Limits to device interconnection:
fault tripping delays are set to zero, whatever the v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected to a
position of the adjustment dial. maximum of 10 inputs;
v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and to
an input ZSI - IN CR (Z4) or GF (Z5).

Terminals Z1 to Z5 correspond to the identical


DB119703

indications on the circuit-breaker terminal blocks. upstream 1 Z1


circuit-breaker Z2 tsd = 0.3
Z3
Z4
Z5

point B

2 Z1
Z2
Z3 tsd = 0.2
Z4
Z5

point A

Z1 downstream Z1
Z2 circuit-breaker Z2
Z3 Z3
Z4 Z4
Z5 Z5

Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.

04443724AA - 09/2009 27
Technical appendix Digital display

For information on connecting an external power b Display of measurements operates without an external power supply.
supply, see the electrical diagrams in the The digital display goes off if the current drops below 0.2 x In (In = rated current).
circuit-breaker user manual. An optional 24 V external power supply may be used to maintain the display of
currents.

b Display back-lighting is disabled in the following situations:


v current less than 1 x In on one phase;
v current less than 0.4 x In on two phases;
v current less than 0.2 x In on three phases.

b The maximeter does not operate for currents under 0.2 x In.

The display back-lighting and the maximeter may be maintained, whatever the
current, by adding a 24 V external power supply. Even if an external power supply is
installed, the long-time, short-time, instantaneous and earth protection functions will
not use it.

28 04443724AA - 09/2009
Technical appendix Thermal memory

Thermal memory
The thermal memory is the means to take into account temperature rise and cooling
caused by changes in the flow of current in the conductors.

These changes may be caused by:


b repetitive motor starting
b loads fluctuating near the long-time protection settings
b repeated circuit-breaker closing on a fault.

Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.

Micrologic control units and thermal memory


All Micrologic control units are equipped as standard with a thermal memory.

b For all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend on the tr tripping delay:
v if the tripping delay is short, the time constant is low
v if the tripping delay is long, the time constant is high.

b For long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping curves.

Short-time protection and intermittent faults


For the short-time protection function, intermittent currents that do no provoke
tripping are stored in the Micrologic memory.
This information is equivalent to the long-time thermal memory and reduces the
tripping delay for the short-time protection.
Following a trip, the short-time tsd tripping delay is reduced to the value of the
minimum setting for 20 seconds.

Ground-fault protection and intermittent faults


The ground-fault protection implements the same function as the short-time
protection.

04443724AA - 09/2009 29
Notes

30 04443724AA - 09/2009
04443724AA - 09/2009 31
Notes

32 04443724AA - 09/2009
2009 - Schneider Electric - Tous droits rservs

Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS 30323
F - 92506 Rueil Malmaison Cedex This document has been printed on ecological paper

RCS Nanterre 954 503 439


Design: Schneider Electric
Capital social 896 313 776
Photos: Schneider Electric
www.schneider-electric.com
Printed:

04443724AA-04 09-2009

You might also like