2015-09-24

EdgeConneX Inc.

Gensler
Aldgate House
33 Aldgate High Street
London EC3N 1AH

EdgeConnex - Amsterdam, Netherlands UK


Tel (0)20 7073 9600
Fax (0)20 7539 1917

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


09/12/2016

INITIAL PERMIT SET


ISSUED FOR CONTRACT (PACK 1) Aldgate House
33 Aldgate High Street
London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917

CLIENT

EdgeConneX Inc.
2201 Cooperative Way, Suite 200

Revision Date 09/12/2016


Herndon, VA 20171
Tel +01 866.304.3217

CLIENT'S CONSULTANT

WOOLVERSTONE HOUSE
61 BERNERS STREET
LONDON
W1T 3NJ

Tel: 0207 0433410

EdgeConnex - Amsterdam, Netherlands


PROJECT NUMBER: 08.7142.000

08.7142.000
C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:

APPLICABLE CODES AND STANDARDS ABBREVIATIONS GRAPHIC SYMBOLS GRAPHIC SYMBOLS GRAPHIC SYMBOLS GRAPHIC SYMBOLS Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works
CODES ARE BASED ON BOUWBESLUIT 2012 & THE 2009 INTERNATIONAL BUILDING CODE (113C)

BUILDING CODE: BOUWBESLUIT 2012


PLUMBING CODE: SEE RED ENGINEERS DWGS
MECHANICAL CODE: SEE RED ENGINEERS DWGS
A L CONSTRUCTION PLAN SYMBOLS REFLECTED CEILING PLAN SYMBOLS BUILDING REGULATION SYMBOLS BUILDING REGULATION SYMBOLS cont.
A/C AIR CONDITIONING L ANGLE
ELECTRICAL CODE: SEE RED ENGINEERS DWGS ACOUS. ACOUSTICAL LAM. LAMINATE PARTITION
LIFE SAFETY CODE: BOUWBESLUIT 2012 ACOUS.T ACOUSTICAL TILE L.H. LEFT HAND
(or AC.T) 0 XXX 0
ADD'N(L) ADDITIONAL REFERENCE TO PARTITION TYPE C-05 CEILING TYPE AS AUTOMATIC SOUNDER SGU SINGLE GLAZED UNITS
ACCESSIBILITY CODE: BOUWBESLUIT 2012 ADJ. ADJUSTABLE M
ALUM. ALUMINIUM SP
NFPA 13: FIRE SPRINKLER STANDARD ALT. ALTERNATE MAINT. MAINTENANCE +13.500 0 AASV AUTOMATICALLY ACTUATED SMOKE VENT AREA PROTECTED BY SPRINKLERS
NFPA 72: FIRE ALARM STANDARD ANOD. ANODIZED MAX. MAXIMUM FINISHED FLOOR LEVEL
APP. APPROVED MECH. MECHANICAL CHANGE IN FINISHED CEILING LEVEL
NFPA 10: FIRE EXTINGUISHER STANDARD APPROX. APPROXIMATE MTL. METAL AKC AUTOMATIC FIRE DOOR St Op NEW STRUCTURAL OPENING
2008 NATIONAL ELECTRICAL CODE ARCH. ARCHITECT or MEZZ. MEZZANINE Name 0
ARCHITECTURAL MFG. MANUFACTURING LEVEL MARK B FIRE BLANKET SV NATURAL SMOKE VENT
1994 AMERICANS WITH DISABILITIES ACT AUTO. AUTOMATIC MFR. MANUFACTURER
ICC A117.1-2003 MGR. MANAGER Elevation
AVG. AVERAGE +00000 HEIGHT OF CEILING ABOVE FINISHED FLOOR LEVEL
A.F.F. ABOVE FINISHED FLR MIN. MINIMUM BG BREAK GLASS FEC FIRE EXTINGUISHER CUPBOARD
MISC. MISCELLANEOUS
NOTE: APPLICABLE CODES MAY VARY DEPENDING ON SITE LOCATION. ALL CODES MUST BE MTD. MOUNTED XXX EQUIPMENT REFERENCE CO2 AREA PROTECTED BY CARBON DIOXIDE TD TRAP DOOR
CONFIRMED WITH THE LOCAL AHJ FOR EACH CONSTRUCTION PROJECT. B MUL.
MW.
MULLION
MICROWAVE P PRESENCE DETECTOR
M.J. MASTIC JOINT
BD. BOARD CO2E CARBON DIOXIDE FIRE EXTINGUISHER VL VERTICAL ESCAPE LADDER
BLDG. BUILDING XXX JOINERY REFERENCE RECESSED DIRECTIONAL DOWNLIGHT
BLK. BLOCKWORK N CO2E-5 CARBON DIOXIDE FIRE EXTINGUISHER - 5KG VP DOOR WITH VISION PANEL
HMIS BRKT.
BRZ.
BSMT.
BRACKET
BRONZE
BASEMENT (N)
NEG.
NORTH
NEGATIVE
01 NOTE REFERENCE NUMBER
RECESSED DOWNLIGHT
CP BREAK GLASS CALL POINT WR WET RISER
HAZARDOUS MATERIAL INVENTORY STATEMENT N.I.C. NOT IN CONTRACT R REMOTE INDICATOR
No. NUMBER ELEVATION REFERENCE
IFC 2701.1 SCOPE, EXCEPTION 6
C N.T.S. NOT TO SCALE
1
Ref
ROW ON ELEVATION SHEET WHERE SHOWN SECURITY CAMERA
CR CARD READER W9 WATER FIRE EXTINGUISHER
CAB. CABINET
QUANTITY OF ACIDS WITHIN STATIONARY BATTERY SYSTEMS CONTAINED
C.C.
CER.
CENTRE TO CENTRE
CERAMIC
O A101 SHEET WHERE SHOWN
SD SMOKE DETECTOR
C0 CLASS "0" SURFACE
WITHIN UPS SKIDS AND PACS ARE NOT INCLUDED WITHIN THE HMIS PER
SFPC 2701.1, EXCEPTION 6.
C/L
CLG.
(or CEIL.)
CENTRE LINE
CEILING
O.A.
OFF.
OPNG.
OVERALL
OFFICE
OPENING A SPEAKER ALARM
C1 CLASS "1" SURFACE ELEVATION INDICATIONS
CLNRs. CLEANERS Ref DESCRIPTION OF SIMILAR OR OPPOSITE C3
OPP. OPPOSITE 1 CLASS "3" SURFACE
IFC 2701.5.2 HAZARDOUS MATERIALS INVENTORY STATEMENT CLR. CLEAR ORIG ORIGINAL DETAIL NUMBER
CLR.OPG. CLEAR OPENING
OUTDOOR CONTROL AREA COL. COLUMN A101 SHEET WHERE SHOWN DA DISABLED ACCESS ROUTE STONE
CONC.
CONN
CONCRETE
CONNECT or
P
GENERATORS: SEE CHEMICAL CONNECTION AREA TO BE DETAILED DGU DOUBLE GLAZED UNITS
SITE PLAN FOR NAME CAS USE CONST.
CONT.
CONSTRUCTION
CONTINUOUS
PART. BD.
P.LAM.
PLAS.
PARTICLE BOARD
PLASTIC LAMINATE
PLASTER
POWER AND TELEPHONE SYMBOLS BRICK / CONCRETE BLOCK
LOCATIONS DIESEL 68476-30-2 STORAGE COR. CORNER DGU-E DOUBLE GLAZED UNITS WITH LOW 'E' COATING
PLY PLYWOOD
CORR. CORRIDOR PNL. PANEL
CRS. CENTRES PR. PAIR SIM SECTION REFERENCE DRI DRY RISER INLET
CTR. CENTRE PREFAB. PREFABRICATED 1 RAISED FLOOR GROMMET FINISHED WOOD
CUPBD. CUPBOARD DETAIL NUMBER
PROJ. PROJECT
C.W. COLD WATER PTN. PARTITION A0.100 DRO DRY RISER OUTLET
C.T. CAVITY TRAY SHEET WHERE SHOWN
PTD. PAINTED
CLOSED CIRCUIT TV CAMERA GLASS
ENERGY CODE D
P.C. PRE CAST
DWC DISABLED PERSONS WC

D.A. DOUBLE ACTING


Q XXXX SPECIFICATION REFERENCE
CR CARD READER E "PUSH TO EXIT" BUTTON
BUILDING ENVELOPE REQUIREMENTS - OPAQUE ASSEMBLIES
IECC ENERGY CODE TABLE 301.1 - CLIMATE ZONE 4
DBL.
DEPT.
DET.
DOUBLE
DEPARTMENT
DETAIL
QUAL.
QUAN.
QUALITY
QUANTITY ROOM NAME XXXX ROOM NAME DR DOOR RELEASE
EL AREA PROTECTED BY ESCAPE LIGHTING SECTION INDICATIONS
D.F. DRINKING FOUNTAIN XXXX
ASSEMBLY REQUIRED
DIA.
DIM.
DIAMETER
DIMENSION
R L0q12 ROOM NUMBER E
EMH ELECTROMAGNETIC DOOR HOLD OPEN
DIV. DIVISION LVL: Level 1 EMERGENCY BREAK GLASS SAND OR GROUT
ROOF INSULATION R-20 R. REMOVE 1500
DN. DOWN R / A. RETURN AIR EMSV ELECTRO MECHANICAL SMOKE VENT
WALLS ABOVE GRADE - DATA CENTER R-13 DR. DOOR RAD. RADIUS
WALLS ABOVE GRADE - OFFICE R-13 DIS. DISABLED R.C. REINFORCED CONCRETE FIRE BELL
DWG. DRAWING. RECEP. RECEPTICLE
FD 120 SPECIFIC PERIOD (mins) FIRE RESISTANT DOOR
SLAB-ON-GRADE (UNHEATED) - DATA CENTER NR DRW. DRAWER. XXX EARTH OR NATURAL GROUND
DISH WASHER REF. REFERENCE DOOR NUMBER (WITH SCHEDULE) SPECIFIC PERIOD (mins) FIRE RESISTANT DOOR
SLAB-ON-GRADE (UNHEATED) - OFFICE NR DW. REFL. REFLECTED
DPC. DAMPROOF COURCE FLOOR BOX FD 20S
SWING DOORS U-0.70 REINF. REINFORCED WITH SMOKE SEAL
DPM. DAMP PROOF MEMBRANE REL. RELOCATE
ROLL UP DOORS U-1.45 RESIL. RESILIENT XXX WINDOW NUMBER FEI-DS FIRE SIGN, DOUBLE SIDED, SUSPENDED POROUS FILL (GRAVEL)
SCENE SETTING SWITCH
CURTAIN WALL / STOREFRONT U-FACTOR 0.50 E REQD.
R.H.
REQUIRED
RIGHT HAND
ENTRANCE DOOR U-FACTOR (SHGC<0.25) 0.85 Rm. ROOM ALIGN FEI-SS FIRE SIGN, SINGLE SIDED, SUSPENDED
(E) EAST RND. ROUND LIGHT SWITCH GANGED STONE
SOLAR HEAT GAIN COEFFICIENT (<0.25) 0.40 E.D. EXTERNAL DIAMETER REV. REVISION ALIGN WITH ESTABLISHED WALL SURFACE
ELEC. ELECTRIC RWP RAIN WATER PIPE
FESD SUSPENDED FIRE EXIT SIGN
ELECT. ELECTRICAL
EL. ELEVATION LIGHT SWITCH WITH NEON
ENGR.
EQ.
ENGINEER
EQUAL / EQUIVALENT
S ELEVATION DATUM POINT
EXIT EXISTING FIRE EXIT SIGN CONCRETE
EQUIP. EQUIPMENT (S) SOUTH FFF DOOR WITH NO LOCK FASTENINGS
LIGHT SWITCH WITH POWER CORD
GENERAL NOTES: EXH.
EXIST.
EXP JT.
EXHAUST
EXISTING
EXPANSION JOINT
S.C.
SCHED.
SECT.
SOLID CORE
SCHEDULE
SECTION 1 REVISION REFERENCE FI FOAM INLET
BRICK
1. DO NOT SCALE DRAWINGS; ALWAYS REFER TO PROVIDED DIMENSIONS. PROJECT EXPOS. EXPOSED SHT. SHEET LIGHT SWITCH TIMED
EXT. EXTERIOR SIM. SIMILAR
MEASUREMENTS NOT TAKEN DIRECTLY FROM PROVIDED DIMENSIONS SUBJECT CONTRACTOR S.O. STRUCTURAL OPENING FR FIRE RESISTANT WALL
TO LIABILITY FOR ANY RESULTANT ERRORS. F
S.O.P
SPL.
SETTING OUT POINT
SPLASH XX COLUMN GRID LINES MARKER 2 LIGHT SWITCH TWO WAY
FRC FIRE RESISTANT CEILING
CONCRETE MASONRY UNIT
2. IT IS THE INTENT OF THE ARCHITECTURAL DRAWINGS TO INCLUDE INFORMATION NECESSARY FOR SQ. SQUARE
THE COMPLETION OF THE PROJECT. IT IS THE RESPONSIBLITY OF THE GENERAL CONTRACTOR F.A FIRE ALARM. sq ft SQUARE FEET
FAP. FIRE ALARM PANEL sq m SQUARE METER LIGHT SWITCH FRG FIRE RESISTANT GLAZING METAL
TO INQUIRE AS TO THE INTENT OF THE DRAWINGS IN AREAS IN QUESTION OF MEANING AND
INTENT.
FABR.
F.E.
F.E.C.
FABRICATE
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
S.S.
ST.
STA.
STAINLESS STEEL
STAIN
STATION
FINISHES LEGEND FRT
3. GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS OF CONSTRUCTION AND M MICROPHONE DOORS FREE ROTATE ON ACTUATION OF ALARM
F.F. FINISH FLOOR STD. STANDARD READ IN CONJUNCTION WITH FINISHES SCHEDULE
SHALL CONSTRUCT WORK IN COMPLIANCE WITH ALL APPLICABLE BUILDING CODES AND F-F FACE TO FACE STL. STEEL NON-FERROUS ALUMINIUM
ORDINANCES. F.F.L. FINISHED FLOOR LEVEL STRUCT. STRUCTURAL C FR 30 FIRE RATED WALL TO SPECIFIC PERIOD (mins)
F.H.C. FIRE HOSE CABINET SUSP. SUSPENDED CLEANERS SOCKET
4. REFER TO ___ SERIES DRAWINGS FOR LOCATION OF FIRE RESISTIVE ASSEMBLIES. FIN. FINISH(ED) SYMM SYMMETRY
FLR. FLOOR SYS. SYSTEM ? WALL FINISH FSG FIRE SUPPRESSANT GAS PLYWOOD
5. REFER TO ___ SERIES DRAWINGS FOR ACCESSIBLE ENTRANCE/EGRESS LOCATIONS. FLUOR. FLUORESCENT SPEC. SPECIFIED
LL
6. REFER TO ___ SERIES DRAWINGS FOR LOCATIONS AND TYPES OF FIRE EXTINGUISHERS. F.MALE / F. FEMALE SSL. STRUCTURAL SLAB LEVEL POWER SOCKET OUTLET LOW LEVEL
F9 FOAM FIRE EXTINGUISHER
7. PROVIDE UL LISTED FIRESTOP ASSEMBLIES FOR ALL THROUGH AND MEMBRANE PENETRATION F.O.C. FACE OF CONCRETE
F.O.F. FACE OF FINISH
THROUGH FIRE RESISTIVE ASSEMBLIES IN ACCORDANCE WITH SPECIFICATION SECTION 07_84_00 WOOD (FINISH)
AND DETAILS SHOWN IN THE J/K SERIES DRAWINGS. THE CONTRACTOR SHALL PROVIDE
F.O.G.
F.O.S.
FACE OF GYP. BD.
FACE OF STUD T ? WALL FINISH POWER SOCKET OUTLET HA AREA PROTECTED BY HALON GAS
F.O.W. FACE OF WALL ? SKIRTING FINISH
FIRESTOPPING SUBMITTAL(S) FOR ALL PENETRATION CONDITIONS FOR A/E REVIEW PRIOR TO FR. FRAME T&B. TOP & BOTTOM HD HEAT DETECTORS
BEGINNING WORK. LABEL ALL FIRESTOP ASSEMBLIES IN ACCORDANCE WITH THE SPECIFICATION. F.S. FULL SIZE TECH. TECHNICAL POWER SOCKET OUTLET WITH NEON WOOD (CONTINUOUS)
FURR. FURRING TEL. TELEPHONE
8. REFER TO DRAWING ___ FOR TYPICAL MOUNTING HEIGHTS, DOOR STRIPING, GYPSUM BOARD TEMPD. TEMPERED WALL FINISH HR15 15m HOSE REEL
?
DETAILS, ETC. TEMP'Y. TEMPORARY POWER SOCKET OUTLET GANGED
9. REFER TO DRAWING ___ FOR WALL TYPES, WALL HEAD DETAILS AND BLOCKING REQUIREMENTS. G TEMP.GL. TEMPERED GLASS ? DADO FINISH
HR30 30m HOSE REEL
WOOD (BLOCKING)
THK. THICK (NESS) ? SKIRTING FINISH INTERRUPTED MEMBER
10. REFER TO DRAWING ___ FOR THE DOOR AND FRAME DETAILS. G.A. GENERAL ARRANGEMENT TOS. TOP OF SLAB
11. REFER TO DRAWING ___ FOR THE DOOR SCHEDULE. GAU. GAUGE TYP. TYPICAL PUSH BUTTON
IP FIRE ALARM INDICATOR PANEL
G.D. GARBAGE DISPOSAL
12. ALL PLYWOOD USED ON THE INTERIOR OF THIS PROJECT SHALL BE FIRE RESISTANT TREATED. GEN. GENERAL INSULATION (LOOSE OR BATT)
13. FIRE EXTINGUISHER CABINETS (FEC) LOCATED IN NON-RATED PARTITIONS SHALL BE SEMI- GL.
GYP.
GLASS or GLAZED
GYPSUM U XXXX CEILING FINISH ISOLATOR SRUR KL FIRE DOOR KEEP LOCKED
RECESSED. GYP. BD. GYPSUM BOARD
14. FIRE EXTINGUISHER CABINETS (FEC) LOCATED IN RATED PARTITIONS SHALL BE SURFACE U.L. UNDERWRIGHTERS KS FIRE DOOR KEEP SHUT
LABORATORY SHAVER SOCKET INSULATION (RIGID)
MOUNTED.
15. THE FACILITY IS PRIVATELY OWNED AND NOT OPEN TO THE PUBLIC. THE FACILITY IS
H U/S.
UTIL.
UNDER SIDE
UTILITY
SPECIAL FINISH
LP DISABLED PERSON LIFTING PLATFORM
U.O.N. UNLESS OTHERWISE NOTED
OPERATIONAL 24 HOURS / 7 DAYS PER WEEK. MICROSOFT SECURITY MONITORS THE FACILITY 24 HDWR. HARDWARE SPECIAL SOCKET OUTLET GLASS (LARGE SCALE)
HWD. HARDWOOD LV
HOURS / 7 DAYS PER WEEK AND AN EMERGENCY RESPONSE TEAM IS AVAILABLE DURING THESE HGT. HEIGHT 1t FLOOR FINISH LOBBY VENTILATION
TIME PERIODS. H.M. HOLLOW METAL V T THERMOSTAT
4
3
09/12/2016
23/11/2016
ISSUED FOR CONTRACT (PACK 1)
DRAWING PACKAGE 1
HORIZ. HORIZONTAL NC NON-COMBUSTABLE MATERIAL
16. UPS SKIDS WITHIN UPS ROOMS CONTAIN STATIONARY SEALED VRLA BATTERY SYSTEMS HAVING HVAC. HEATING VERT. VERTICAL GYPSUM BOARD 2 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
A GEL CAPACITY OF MORE THAN 50 GALLONS USED FOR FACILITY STANDBY POWER, EMERGENCY VENTILATING & VEST. VESTIBULE (DRAWING PACKAGE 2)
AIR CONDITIONING VOL. VOLUME TELEPHONE AND DATA OUTLET OB OPTICAL BEAM SMOKE DETECTOR
POWER AND UNINTERRUPTED POWER SUPPLY. A 1-HOUR FIRE BARRIER HAVE BEEN PROVIDED TO H.W. HOT WATER VER. VERIFY CHANGE IN FLOOR FINISH 1 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
SEPARATE THE INCIDENTAL USER ER IBC TABLE 508.2.5.
P DRY POWDER FIRE EXTINGUISHER ACOUSTICAL TILE rev date revision note
17. EXTERIOR EQUIPMENT SHOWN WITHIN THE SIDEYARDS ARE NOT CONSIDERED BUILDINGS.
18. ROOF TOP AIR HANDLER EQUIPMENT IS NOT CONSIDERED OCCUPIABLE SPACE OR HABITABLE I W TELEPHONE OUTLET

SPACE. (W) WEST PB PANIC BOLT TO DOOR


I.M. ICE MAKER W/ WITH FABRIC WRAPPED PANEL
19. EXIT DISTANCES INDICATED REPRESENT THE GREATEST TRAVEL DISTANCE WHERE SHOWN. I.D. INTERNAL DIAMETER W.C. WATER CLOSET R
INFO. INFORMATION WD. WOOD
RAMPED AREA
INCL. INCLUDE or INCLUSIVE Aldgate House
INCAN. INCANDESCENT
WDW.
W.H.
W/ O.
WINDOW
WATER HEATER
WITHOUT
WHITE GOODS / APPLIANCES LEGEND RF RAISED FLOOR 33 Aldgate High Street
London EC3N 1AH
WT. WEIGHT UK
RSS ROLLER SHUTTER Tel (0)20 7073 9600
DW DISHWASHER Fax (0)20 7539 1917
SB SAND BUCKET

SC SELF CLOSING DOOR


GENERATOR NOTES: RF REFRIGERATOR
SD SMOKE DETECTOR
GENERATORS HAVE THE FOLLOWING FEATURES:
1. UL2085 LISTED FUEL TANK. MW MICROWAVE
SES POWERED SMOKE EXTRACT SYSTEM CLIENT
2. IN ADDITION TO VISUAL INSPECTION OF THE TANKS, AN AUTOMATIC LEAK DETECTION SYSTEM
IS REQUIRED. THE DETECTION SYSTEM US TO IDENTIFY THE GENERATOR NUMBER AND IS TO SF DOOR WITH SIMPLE FASTENINGS
REPORT BACK TO THE FACILITY OPERATION CENTER ALARM PANEL. CM COFFEE MACHINE
3. AUTOMATIC SPRINKLERS ARE NOT REQUIRED FOR THE GENERATORS SGC STRUCTURAL GLASS CLADDING
4. AN EPO FOR EACH GENERATOR IS REQUIRED TO BE LOCATED IN THE FACILITY OPERATION
CENTER. THE REPORTING PANEL IN THE FACILITY OPERATION CENTER IS TO IDENTIFY THE
GENERATOR NUMBER AND WEATHER IF IS RUNNING.
5. AT EXISTING SITES, THE GENERATOR NUMBERING SYSTEM FROM ADJACENT SITES IS TO
EdgeConneX Inc.
CONTINUED (FOR EXAMPLE: BN1, BN2, BN3 & BN4 CONTINUES TO BN6). 2201 Cooperative Way, Suite 200
LIFE SAFETY LEGEND Herndon, VA 20171
Tel +01 866.304.3217

EXISTING WALL TO REMAIN


NEW PARTITION CLIENT'S CONSULTANT

1 HR. RATED PARTITION

A PATH OF TRAVEL (DISTANCE IN


ACCESSIBILITY NOTES SCHEDULE ON SHEET)
STAIR/EXIT DESIGNATION
1. THE BUILDINGS AND FACILITIES ON THE MICROSOFT SITE ARE PRIVATELY OWNED AND NOT OPEN TO 2
CAPACITY USED WOOLVERSTONE HOUSE
THE GENERAL PUBLIC. THE PRIMARY FUNCTION WITH THE BUILDINGS AND FACILITIES CONSISTS OF 200 138 ACTUAL USE
ELECTRONIC DATA PROCESSING.
61 BERNERS STREET
STAIR/EXIT CAPACITY LONDON
2. ACCESSIBLE ROUTES INDICATED ON THE DRAWINGS ARE A MINIMUM OF 850mm IN WIDTH WITH W1T 3NJ
ALLOWED ENCROACHMENTS IN ACCORDANCE WITH BOUWBESLUIT 2012. EXIT LIGHT

3. TACTILE SIGNS STATING "EXIT" AND COMPLYING WITH ICC ANSI A117.1-09 SHALL BE PROVIDED EXIT LIGHT WITH DIRECTIONAL ARROW Tel: 0207 0433410
ADJACENT TO EACH DOOR TO AN EGRESS STAIRWAY, EXIT PASSAGEWAY AND AT THE EXIT
DISCHARGE. F FIRE ALARM PULL STATION

4. DOORS THAT PROVIDE EXIT ACCESS ALONG AN ACCESSIBLE ROUTE ARE A MINIMUM OF 900mm F FIRE ALARM ANNUNCIATOR
key plan
CLEAR WIDTH.
FAC FIRE APPARATUS CABINET, FIRE HOSE
5. DOOR HARDWARE: HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERABLE PARTS ON AND EXTINGUISHER
ACCESSIBLE DOORS ALONG ACCESSIBLE ROUTES ARE TO COMPLY WITH ICC ANSI A117.1-09, SECTION DATA HALL 3
404.2.7 AND BOUWBESLUIT 2012. FHC FIRE HOSE CABINET
FEC FIRE EXTINGUISHER CABINET
6. DOOR OPENING FORCE IS TO COMPLY WITH THE FOLLOWING REQUIREMENTS IN ACCORDANCE WITH
ICC ANSI A117.1-09. FE DATA HALL 1
FIRE EXTINGUISHER
True North
-INTERIOR SWING DOORS WITHOUT CLOSERS: 5-POUND MAXIMUM FORCE. SP FIRE STANDPIPE
OFFICE
-PANIC AND FIRE EXIT HARDWARE: 15 POUNDS MAXIMUM FORCE. S SMOKE DETECTOR N
-OTHER SWING DOORS: 15 POUNDS MAXIMUM FORCE.
SMOKE TIGHT project status
7. DOOR THRESHOLDS ALONG ACCESSIBLE ROUTES ARE TO BE A MAXIMUM OF 1/2 INCH IN HEIGHT ISSUED FOR CONTRACT (PACK 1)
ABOVE THE FINISH FLOOR LEVEL WITH BEVELED EDGES.

8. WHEELCHAIR TURNING SPACE, CLEAR FLOOR AND GROUND SPACE AND REACH RANGES THAT project
SERVE AN ACCESSIBLE ROUTE ARE TO COMPLY WITH ICC ANSI A117.1-09, CHAPTER 3 AND EdgeConnex - Amsterdam, Netherlands
BOUWBESLUIT 2012.

9. MANEUVERING CLEARANCES AT DOORS THAT SERVE AN ACCESSIBLE ROUTE ARE TO COMPLY WITH Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL
ICC ANSI A117.1-09, SECTION 404 AND BOUWBESLUIT 2012. project no
08.7142.000
10. CONTROLS, OPERATING MECHANISMS AND HARDWARE INTENDED FOR OPERATION BY THE scale date drawn checked
OCCUPANTS IN ACCESSIBLE SPACES, ALONG AN ACCESSIBLE ROUTES OR AS PART OF ACCESSIBLE As indicated @ A0 04/11/16 TS WR
ELEMENTS ARE TO BE ACCESSIBLE IN ACCORDANCE WITH ICC ANSI A117.1-09 AND BOUWBESLUIT
2012. sheet number

A0.00
title

PROJECT INFORMATION &


SHEET INDEX

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works
DOOR SCHEDULE

DR VISION FIRE RATING FRAME FRAME IRONMONGERY Door


GENERAL NOTES (DOOR DETAILS)
DOOR NO. ROOM NO. ROOM NAME DR TYPE LEAF WIDTH LEAF HEIGHT MATERIAL DR FINISH PANEL / HR MATERIAL FINISH HEAD JAMB GROUP NOTES Hardware
A ALL DOOR FRAMES SHALL RECEIVE SEALANT
AND BACKER RODS, FULL PERIMETER OF
LEVEL 0 FRAME BOTH SIDES.
D0s12 D0s12 MECH F 1000 2700 HM PT05 No 0 HM PT05 4A0.20 3A0.20 SET 01 (none)
DATA HALL 0
D0w30 D0w30 MECH F/F 2000 2700 HM PT05 No 1 HM PT05 4A0.20 3/A0.20 SET 02 (none)
PT05 INTERIOR PAINTING

SPECIFICATION SECTION: 09 91 23
MANUFACTURER: BENJAMIN MOORE
COLOR NUMBER: 1616
COLOR NAME: STORMY SKY
GLOSS: SEMI-GLOSS
CONTACT: www.benjaminmoore.eu
LOCATION: REF PLANS, DOOR AND FRAMES

GROUP NO. 01 GROUP NO. 02 **NOTE: MOUNT ALL CLOSERS ON NON-PUBLIC SIDE OF DOORS
ELECTRIC CYLINDRICAL CLASSROOM LOCKSET (ACTIVE LEAF) ELECTRIC CYLINDRICAL LOCKSET
ELECTRIC HINGE (ACTIVE LEAF) ELECTRIC HINGE
HINGES HINGES COORDINATE LOCATIONS WITH SECURITY CONTRACTOR UNDER CONTRACT TO TENANT
AUTO FLUSH BOLT SET DOOR CLOSER W/ STOP ARM
DUSTPROOF STRIKE SEAL SET J-BOX 152 x 152 x 101D, EC TO PROVIDE DOUBLE BOX ONE WITHIN PARTITION TO RECEIVE
DOOR CLOSERS W/ STOP ARMS 8" KICKPLATE CONDUIT. THE OTHER SURFACE MOUNTED TO ALLOW CONDUIT OR OPEN CABLE CONVEYANCE.
COORDINATOR 8" MOP PLATE
OPEN CABLE TO MICRO & POWER SUPPLY
CLOSER MOUNTING BRACKET SET LATCH GUARD (OUTSWING)
SEAL SET (JAMBS & ASTRAGAL)
CABLE TRAY ON OPPOSITE SIDE OF WALL (OPTIONAL)
8" KICKPLATES 3500MM
8" MOP PLATES
WALL STOPS 3350MM
OVERLAP ASTRAGAL (INACTIVE LEAF; SIM TO NG 550)
PROVIDED BY DOOR SUPPLIER OR GC. 3200MM EXIT
SECURITY CAMERAS MOUNTED @ 3050MM
3050MM

152 152
6" 6"
2750MM
DOOR CONTACTS FOR DOOR PROP AND DOOR POSITION - BY SECURITY CONTRACTOR, EC
TO PROVIDE CONDUIT FROM FRAME TO J-BOX LOCATED ON SECURE SIDE. REFER TO
SECURITY CONTRACTOR PLAN FOR CONTACT LOCATIONS

HARDWARE GROUP DESCRIPTIONS 6


EGRESS MOTION DETECTOR BY SECURITY CONTRACTOR, EC TO PROVIDE HORIZONTAL
TRIM RING OVER J-BOX WITHIN PARTITION LOCATED ON SECURE SIDE AS REQUIRED.
SCALE: 1 : 1 610
STROBE / HORN
2' - 0"
2400MM H
INTERCOM DEVICE BY SECURITY CONTRACTOR, EC TO PROVIDE J-BOX W/ TRIM RING. CAN
SHARE CONDUIT WITH EMERGENCY DOOR RELEASE. (OPTIONAL)

ELECTRIC HINGE EMERGENCY DOOR RELEASE BUTTON ON OPPOSITE SIDE OF WALL (IF REQUIRED) TO BE
BY GC PROVIDED BY SECURITY CONTRACTOR, EC TO PROVIDE VERTICAL TRIM RING OVER SINGLE
GANG BOX WITHIN PARTITION AND CONDUIT TO CARD READER J-BOX WITH STRING
LOCATED ON SECURE SIDE.
203
8" LIGHT SWITCH - ZONE
ELECTRICAL
LOCKSET BY GC
WIDTH AS 1500MM
WIDTH AS NOTED NOTED
1200MM
MAX
LOCK ALARM BOX/UNIT

HEIGHT AS NOTED

HEIGHT AS NOTED
EPO SWITCH LOCATED ON SECURE SIDE (AS REQUIRED)
DOOR TO BE MORTISED BY
GC, PANIC HARDWARE BY CARD READER (ON OPPOSITE SIDE OF WALL) BY SECURITY CONTRACTOR, EC TO
GC WHERE REQUIRED PROVIDE VERTICAL TRIM RING OVER SINGLE GANG BOX WITHIN PARTITION 5 09/12/2016 ISSUED FOR CONTRACT (PACK 1)
4 23/11/2016 DRAWING PACKAGE 1
ELEC. STRIKE WITH CONDUIT TO SPLICE BOX ON SOME DOORS, 3 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
(DRAWING PACKAGE 2)
REFER TO DOOR SCHEDULE
2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
NOTE:
rev date revision note
SECURITY CONTRACTOR TO PROVIDE & INSTALL ALL HARDWARE & DEVICES. GC TO
F/F F COORDINATE BOTH EC & TENANT-PROVIDED SECURITY CONTRACTOR.
SECURE SIDE OF DOOR
NOTES:
DOUBLE FLUSH FLUSH PANEL
1. ALL CONDUIT 20MM MINIMUM PROVIDED BY GC PROVIDE TWO STRINGS AT EACH TERMINATION POINT UNLESS OTHERWISE APPROVED BY PROJECT MGR.
PANEL Aldgate House
2. ALL PLENUM BOXES TO BE USED ABOVE CEILING AS REQUIRED.
33 Aldgate High Street
3. CABLING AND LOW VOLTAGE WIRING BY SECURITY CONTRACTOR.
London EC3N 1AH
UK
DOOR TYPES LEGEND Tel (0)20 7073 9600
Fax (0)20 7539 1917

DOOR AND FRAME TYPE LEGEND SINGLE DOOR TYP. CONDUIT REQUIREMENTS 2
SCALE: 1 : 1 5 SCALE: 1 : 20
CLIENT

EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
Tel +01 866.304.3217
VARIES - SEE PARTITION TYPES

BOXED DOUBLE STUD REFER TO WALL TYPES FOR COORDINATE LOCATIONS WITH SECURITY CONTRACTOR UNDER CONTRACT TO TENANT
FRAMING WALL ASSEMBLY AND CLIENT'S CONSULTANT
THICKNESS J-BOX 152 x 152 x 101D, EC TO PROVIDE DOUBLE BOX ONE WITHIN PARTITION TO
RECEIVE CONDUIT. THE OTHER SURFACE MOUNTED TO ALLOW CONDUIT OR OPEN
FILL VOIDS IN STUDS CABLE CONVEYANCE.
WITH INSULATION WHERE
15 NOTED PER WALL TYPE OPEN CABLE TO MICRO & POWER SUPPLY
SEALANT, TYP BOTH 1"
SIDES CABLE TRAY ON OPPOSITE SIDE OF WALL (OPTIONAL)
3500MM
GASKET WHERE WOOLVERSTONE HOUSE
50
2"

SCHEDULED 3350MM 61 BERNERS STREET


SCHEDULED DOOR LONDON
3200MM EXIT
SECURITY CAMERAS MOUNTED @ 3050MM W1T 3NJ
SCHEDULED DOOR FRAME
3050MM

152 152
6"
Tel: 0207 0433410

6"
2750
DOOR CONTACTS FOR DOOR PROP AND DOOR POSITION BY SECURITY

TYPICAL INTERIOR DOOR HEAD 4


CONTRACTOR, EC TO PROVIDE CONDUIT FROM FRAME TO J-BOX LOCATED ON
SECURE SIDE. REFER TO SECURITY CONTRACTOR PLAN FOR CONTACT LOCATIONS
key plan

SCALE: 1 : 5 EGRESS MOTION DETECTOR BY SECURITY CONTRACTOR, EC TO PROVIDE


HORIZONTAL TRIM RING OVER J-BOX WITHIN PARTITION LOCATED ON SECURE SIDE DATA HALL 3
610
STROBE / HORN
2' - 0"
2400MM H
INTERCOM DEVICE BY SECURITY CONTRACTOR, PROVIDE J-BOX W/ TRIM RING DATA HALL 1
ASTRAGAL CAN SHARE CONDUIT WITH EMERGENCY DOOR RELEASE. (AS REQUIRED) True North

OFFICE
ELECTRIC HINGE
EMERGENCY DOOR RELEASE BUTTON ON OPPOSITE SIDE OF WALL N
(IF REQUIRED) TO BE PROVIDED BY SECURITY CONTRACTOR, EC TO PROVIDE VERTICAL
BY GC TRIM RING OVER SINGLE GANG BOX WITHIN PARTITION AND CONDUIT
project status
TO CARD READER J-BOX WITH STRING LOCATED ON SECURE SIDE.
SEALANT, TYP BOTH SIDES ELECTRICAL
LIGHT SWITCH - ZONE
ISSUED FOR CONTRACT (PACK 1)
LOCKSET BY GC
1500MM
REFER TO WALL TYPES FOR
WALL ASSEMBLY AND THICKNESS project
1200MM EdgeConnex - Amsterdam, Netherlands
SCHEDULED DOOR MAX
50 FRAME
DOUBLE METAL STUD FRAMING 2" EPO SWITCH LOCATED ON SECURE SIDE (OPTIONAL) Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL
VARIES - SEE PARTITION TYPES

DOOR TO BE MORTISED project no


15
1"

BY GC, PANIC 203 CARD READER (ON OPPOSITE SIDE OF WALL)


8" BY SECURITY CONTRACTOR, EC TO PROVIDE VERTICAL
08.7142.000
GASKETS WHERE HARDWARE BY GC
SPECIFIED TRIM RING OVER SINGLE GANG BOX WITHIN PARTITION scale date drawn checked
WHERE REQUIRED
As indicated @ A0 04/11/16 TS WR
sheet number
ELECTRIC STRIKE WITH CONDUIT TO SPLICE BOX ON SOME DOORS
INACTIVE LEAF REFER TO DOOR SCHEDULE
A0.20
15
1"

NOTE:
SECURITY CONTRACTOR TO PROVIDE & INSTALL ALL HARDWARE & DEVICES. GC TO title
FILL VOIDS IN STUDS WITH SCHEDULED DOOR COORDINATE BOTH EC & TENANT-PROVIDED SECURITY CONTRACTOR.
INSULATION WHERE SECURE SIDE OF DOOR
NOTES:
NOTED PER WALL TYPE FRAME ANCHOR
1. ALL CONDUIT 20MM MINIMUM PROVIDED BY EC PROVIDE TWO STRINGS AT EACH TERMINATION POINT UNLESS OTHERWISE NOTED. DOOR TYPE ELEVATIONS &
2. ALL PLENUM BOXES TO BE USED ABOVE CEILING AS REQUIRED.
3. CABLING AND LOW VOLTAGE WIRING BY SECURITY CONTRACTOR, UNO. SCHEDULE

TYPICAL INTERIOR DOOR JAMB 3 DOUBLE DOOR TYP. CONDUIT REQUIREMENTS


SCALE: 1 : 5 SCALE: 1 : 20 1
C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
PT01 INTERIOR PAINTING AF01 ACCESS FLOORING Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.

SPECIFICATION SECTION: 09 91 23 SPECIFICATION SECTION: 09 69 00


FINISH LEGEND All dimensions to be verified by contractor on site prior to any works

MANUFACTURER: BENJAMIN MOORE MANUFACTURER: LINDNER GROUP


COLOR NUMBER: OC-65 PRODUCT NAME: NORTEC power AF## ACCESS FLOORING
COLOR NAME: CHANTILLY LACE PRODUCT NUMBER: YP 44 ST X SW120 +CM system CL## ACOUSTICAL PANEL CELINGS
GLOSS: EGGSHELL FINISH: STATIC-DISSIPATIVE HPL CL## ACOUSTICAL TILE CEILINGS
CONTACT: www.benjaminmoore.eu SIZE: 60cm MODULE CL## ACOUSTICAL METAL PANEL CEILINGS
LOCATION: REF DRAWINGS PANEL EDGE: INTEGRAL TRIM CL## LINEAR METAL CEILINGS
TOTAL WEIGHT: 67 kg/m2 (1589.93 LB/FT2) CL## LINEAR WOOD CEILINGS
CL## STRETCHED-FABRIC CEILING SYSTEMS
COLOR NUMBER: 70103
CO## HIGH-PERFORMANCE COATINGS
COLOR NAME: AS SELECTED BY ARCHITECT
PT02 INTERIOR PAINTING CONTACT: +44 (0)20/8246-6200
CO## SPECIAL COATINGS
CP## TILE CARPETING - MODULAR
LOCATION: REF PLANS CP## SHEET CARPETING - BROADLOOM
SPECIFICATION SECTION: 09 91 23 NOTES: REF CO01 FOR SPECIAL COATINGS BELOW DF## DECORATIVE FINISHING
MANUFACTURER: BENJAMIN MOORE
DF## MULTICOLOR INTERIOR FINISH
COLOR NUMBER: OC-65
COLOR NAME: CHANTILLY LACE CL01 ACOUSTICAL TILE CEILINGS FA## FLUID APPLIED RESINOUS FLOORING
FW## FABRIC-WRAPPED PANELS
GLOSS: SEMI-GLOSS GF## DECORATIVE FILMS
CONTACT: www.benjaminmoore.eu SPECIFICATION SECTION: 09 51 23 GL## GLAZING
LOCATION: REF DRAWINGS MANUFACTURER: ARMSTRONG WORLD INDUSTRIES GL## DECORATIVE GLASS GLAZING
INC. IS## INFORMATION SPECIALITIES
PRODUCT NAME: FINE FISSURED MT## DECORATIVE METAL
PRODUCT NUMBER: 1728 PF## PLASTIC FABRICATIONS
PT03 INTERIOR PAINTING COLOR: PLATINUM PL## PLASTIC LAMINATE
SIZE: 600mm BY 600mm PR## WALL AND DOOR PROTECTION
SPECIFICATION SECTION: 09 91 23 THICKNESS: 15mm PT## PAINTING
MANUFACTURER: BENJAMIN MOORE TILE EDGE: BOARD (SQUARE) PT## EXTERIOR PAINTING
COLOR NUMBER: 1548 INSTALLATION: SUSPENSION SYSTEM PT## INTERIOR PAINTING
COLOR NAME: CLASSIC GRAY GRID SYSTEM: PRELUDE XL MAX RB## RESILIENT WALL BASE AND
GLOSS: SEMI-GLOSS EDGE TRIM: SHADOWLINE ACCESSORIES
CONTACT: www.benjaminmoore.eu CONTACT: DANIELLE JORDAN, djordan@armstrong.com RS## RESILIENT SHEET FLOORING
LOCATION: REF DRAWINGS LOCATION: REF REFLECTED CEILING PLAN RS## LINOLEUM FLOORING
NOTES: <INSERT> RT## RESILIENT TILE FLOORING
RT## PLASTIC-MATRIX TERRAZZO FLOOR
TILE
PT04 INTERIOR PAINTING CL02 EXPOSED CEILING RT## STATIC-CONTROL RESILIENT FLOORING
SC## STONE COUNTERTOPS
SPECIFICATION SECTION: 09 91 23 SPECIFICATION SECTION: 09 51 33 SC## SIMULATED STONE COUNTERTOPS
MANUFACTURER: BENJAMIN MOORE FINISH: PAINTED SF## STRETCHED-FABRIC WALL SYSTEMS
COLOR NUMBER: 2063-30 LOCATION: REF REFLECTED CEILING PLAN SO## SOLID SURFACING
COLOR NAME: BLUEBERRY NOTES: OPEN TO ABOVE ST## STONE TILING
GLOSS: EGGSHELL ST## STONE FLOORING
CONTACT: www.benjaminmoore.eu ST## STONE FACING
LOCATION: REF DRAWINGS CO01 SPECIAL COATINGS TL## TILING
TR## PORTLAND CEMENT TERRAZZO
SPECIFICATION SECTION: 09 97 00 FLOORING
MANUFACTURER: EUCLID CHEMICAL TR## TERRAZZO FLOOR TILE
PT05 INTERIOR PAINTING PRODUCT NAME: EVERCLEAR TR## RESINOUS MATRIX TERRAZZO
FLOORING
PRODUCT NUMBER: <INSERT>
SPECIFICATION SECTION: 09 91 23 COLOR: <INSERT> UM## UNIT MASONRY
MANUFACTURER: BENJAMIN MOORE UP## UPHOLSTERY
FINISH: SATIN
COLOR NUMBER: 1616 WB## WOOD BASE
CONTACT: <INSERT>
COLOR NAME: STORMY SKY WC## WALL COVERINGS
LOCATION: REF PLANS WD## WOOD
GLOSS: SEMI-GLOSS NOTES: NON-YELLOWING, SEALING COMPOUND WITH
CONTACT: www.benjaminmoore.eu WF## BAMBOO FLOORING
VOC CONTENT OF 250 G/L OR LESS WHEN WF## WOOD FLOORING - PRE-ENGINEERED
LOCATION: REF PLANS, DOOR AND FRAMES CALCULATED ACCORDING TO 40 CFE 59, SUBPART WF## WOOD FLOORING - SOLID WOOD
(EPA METHOD 24) WF## WOOD ATHLETIC FLOORING
WT## HORIZONTAL LOUVER BLINDS
RESILIENT WALL BASE AND
RB01 ACCESSORIES
WT## VERTICAL LOUVER BLINDS
WT## CURTAINS AND DRAPES
WT## ROLLER WINDOW SHADES
SPECIFICATION SECTION: 09 65 13
WT## ROMAN WINDOW SHADES
MANUFACTURER: ARMSTRONG WORLD INDUSTRIES
INC.
PRODUCT NAME: AS SELECTED BY ARCHITECT NOTES:
PRODUCT NUMBER: AS SELECTED BY ARCHITECT 1. ALL ITEMS LISTED ABOVE MAY NOT BE
COLOR: AS SELECTED BY ARCHITECT USED.
SIZE: 64mm (2 1/2 INCHES) 2. LOCATIONS NOTED IN SCHEDULE DO NOT
CONTACT: DANIELLE JORDAN, djordan@armstrong.com INDICATE ALL LOCATIONS. SEE DRAWINGS
LOCATION: REF PLANS, ALL GYPSUM PARTITIONS FOR EXTENT OF WORK.

MT01 EXPANDED METAL MESH

MANUFACTURER: ALABAMA METAL INDUSTRIES


CORPORATION (AMICO)
PRODUCT NAME: ARCHITECTURAL SERIES EXPANDED
MESH
PRODUCT NUMBER: APEX STYLE 03 ALUMINUM
MATERIAL: ALUMINUM GRADE 5005 TO ASTM B209
FINISH: CLEAR SATIN ANODIZE
THICKNESS: 0.125"
INSTALLATION: REFER TO AMICO, PHIL SHEVCHENKO
TELEPHONE DIRECT LINE 289/313-2211 FOR
APPLICATION SPECIFIC INSTALLATION
RECOMMENDATIONS.
TOTAL WEIGHT: 1.350 lbs/ft
OPENNESS FACTOR: 24%
CONTACT: PHIL SHEVCHENKO; TELE 800/663-4474,
EMAIL PSHEVCHENKO@GIBRALTAR1.COM
LOCATION: REF PLANS 3 09/12/2016 ISSUED FOR CONTRACT (PACK 1)
NOTES: BASIS OF DESIGN: EXPANDED MESHES AND 2 23/11/2016 DRAWING PACKAGE 1
ATTACHMENT BRACKETS ARE PRODUCED AND 1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
DISTRIBUTED BY ALABAMA METAL INDUSTRIES rev date revision note
CORPORATION, AMICO; 1080 CORPORATE DR.,
BURLINGTON, ONTARIO L7L 5R6

MT02 CLOSE MESH BAR GRATING Aldgate House


33 Aldgate High Street
London EC3N 1AH
PRODUCT NAME: CLOSE MESH METAL GRATING UK
Tel (0)20 7073 9600
FINISH: GALVANISED Fax (0)20 7539 1917
LOCATION: REF PLANS
NOTES: REF. MEP FOR LOAD REQUIRMENTS.

MT03 WELDED BAR GRATING


CLIENT
PRODUCT NAME: WELDED BAR METAL GRATING
FINISH: GALVANISED
LOCATION: REF PLANS
NOTES: REF. STRUCTURAL

EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
Tel +01 866.304.3217

CLIENT'S CONSULTANT

WOOLVERSTONE HOUSE
61 BERNERS STREET
LONDON
W1T 3NJ

Tel: 0207 0433410

key plan

DATA HALL 3

DATA HALL 1
True North

OFFICE
N
project status

ISSUED FOR CONTRACT (PACK 1)


project
EdgeConnex - Amsterdam, Netherlands

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


D:\RevitUserModels\08.7142.000-EDCAMS01-ARCH_Heni Warwick.rvt

project no
08.7142.000
scale date drawn checked
@ A0 10/26/2016 HW WR
sheet number

A0.30
title

FINISHES SCHEDULE
09/12/2016 16:55:50

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works

NOTE: IN THE EVENT OF A CONFLICT BETWEEN


THESE DETAILS AND THEIR ASSOCIATED
DISCIPLINE'S DRAWINGS, THE ASSOCIATED BIOMETRIC READER; TOP @ 1220mm
DOOR CLEARANCE FLOOR STRIPING APPLIES AT THE FOLLOWING LOCATIONS: DISCIPLINE'S DRAWINGS SHALL GOVERN.
ALL DOORS SWINGING IN TO LOADING DOCK AND/OR RECEIVING AREAS. CARD READER
ALL AZ ELECTRICAL ROOM DOORS SWINGING IN TO THE COLO CLEAR AISLES STROBE/SPEAKER ELECTRICAL OUTLET / PHONE

ALIGN

ALIGN
DESIGNATED WITH STRIPING. JACK ABOVE DESK
ALL DOOR SWINGS IN TO AZ MECHANICAL GALLERIES. HOUSE PHONE
FIRE EXTINGUISHER FIRE ALARM CONTROL
INTERIOR CNR ELECTRICAL ROOM DOORS. AUTOMATIC DOOR SIGN
WAINSCOT PANEL

ALIGN
60mm PAINTED STRIPING AZ WIRE MESH ENCLOSURE DOORS THERMOSTAT ACTUATOR
WHERE LIGHT SWITCH DRINKING
OCCURS EMERGENCY DOOR FOUNTAINS
LIGHT SWITCH WALL MOUNTED FIRE
455 RELEASE BUTTON (EDR) EXTINGUISHER
305 455 305 305 150 150

7' - 11"
1' - 6" 305

2400
150

1' - 0"
6"

1' - 6" 1' - 0" 1' - 0" 6" 6" T/ DEVICE


1' - 0"

5' - 11"
TOP TOP

1800
TOP TOP
150

150

150

4' - 11"

4' - 11"
6"

6"
6"

1220 MAX
1200 MAX
1500

1500
3' - 11"

3' - 11"
4' - 0"

4' - 0"
1220

1200

965 MIN
950 MIN

950mm
950mm

3' - 2"
3' - 1"
FIRE EXTINGUISHER

2' - 9"
850
1' - 6"
450
CABINET

ELECTRICAL OUTLET /
SINGLE LEAF - 90 SINGLE LEAF - 180 DOUBLE LEAF - 90 DOUBLE LEAF - 180 PHONE JACK

DOOR CLEARANCES - FLOOR STRIPING 1 TYPICAL INTERIOR DEVICE MOUNTING HEIGHTS 2


SCALE: 1 : 50 SCALE: 1 : 50

5 09/12/2016 ISSUED FOR CONTRACT (PACK 1)


4 23/11/2016 DRAWING PACKAGE 1
3 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
GRID GRID (DRAWING PACKAGE 2)
CONTROL JOINTS, ONE CONTROL JOINT, ONE 2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
10 metres MAX 10 metres MAX
SIDE MINIMUM SIDE MINIMUM 1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%

SCHEDULED AT GYP BD WALLS AT GYP BD WALLS rev date revision note


DOOR AND STEEL CONTROL JOINT CONTROL JOINT; FIRE CONTROL
FRAME WINDOW RATED JOINT AT FIRE- JOINT
WAINSCOT FRAME BARRIER
WAINSCOT Aldgate House
WHERE WHERE 33 Aldgate High Street
OCCURS OCCURS London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917
CONTROL JOINT CONTROL JOINT BEHIND
WALL BASE BEHIND WAINSCOT WAINSCOT WHERE
WHERE NOTED OCCURS WALL BASE
WHERE NOTED

CLIENT

EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
TYPICAL INTERIOR GYPSUM BOARD CONTROL JOINT 3 Tel +01 866.304.3217
SCALE: 1 : 50

CLIENT'S CONSULTANT

WOOLVERSTONE HOUSE
61 BERNERS STREET
LONDON
W1T 3NJ

Tel: 0207 0433410

key plan

DATA HALL 3

DATA HALL 1
True North

OFFICE
N
project status

ISSUED FOR CONTRACT (PACK 1)


project
EdgeConnex - Amsterdam, Netherlands

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


project no
08.7142.000
scale date drawn checked
1 : 50 @ A0 04/11/16 TS WR
sheet number

A0.41
title

MOUNTING HEIGHTS AND


CLEARANCES

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works

EXISTING BUILDING

5 PARKING SPACES
EXISTING BUILDING

REFER TO ELECTRICAL
CONSULTANT DRAWINGS FOR
EXISING AND NEW ROOF UNITS

CANAL
EXISTING BUILDING
1 09/12/2016 ISSUED FOR CONTRACT (PACK 1)
rev date revision note

Aldgate House
33 Aldgate High Street
London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917

CLIENT

FIRE LANE
EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
Tel +01 866.304.3217

CLIENT'S CONSULTANT

WOOLVERSTONE HOUSE
61 BERNERS STREET
LONDON
W1T 3NJ

Tel: 0207 0433410

key plan

DATA HALL 3

DATA HALL 1
True North

OFFICE
N
project status

ISSUED FOR CONTRACT (PACK 1)


KOOLHOVE
NLAAN project
EdgeConnex - Amsterdam, Netherlands

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


D:\RevitUserModels\08.7142.000-EDCAMS01-ARCH_Heni Warwick.rvt

project no
08.7142.000
scale date drawn checked
1 : 200 @ A0 12/09/16 Author Checker
sheet number

A0.50
title

SITE PLAN
09/12/2016 16:55:52

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works

FE FE
EXIT ROUTE A
POP 1
MECH TFX - 3 TFX - 4
L0a3
D0s12 L0c7 L0c5
FE
UP

EXIT ROUTE B
EXIT ROUTE
DATA HALL
N.I.C.

C
D0m18
UPS ROOM
L0e1

TE C EXIT ROUT
EXIT ROU E B

EXIT ROUTE B UP

EXIT ROUTE D
MECH MECH FE
D0w30 D0j15

TFX - 2 TFX - 1 INKOOPRUIMTE


FE L0a2
L0l8 L0k5

EXIT ROUTE E

EXIT ROUTE E
MMR - 1
D0m14

EXIT ROUTE F
EXIT ROUTE C

ASSEMBLY/

EXIT ROUTE D
STORAGE

N.I.C. L0r12

DATA HALL IT
D0m17 D0q14 1 09/12/2016 ISSUED FOR CONTRACT (PACK 1)
rev date revision note

Aldgate House
33 Aldgate High Street
London EC3N 1AH
UK
Tel (0)20 7073 9600
STAIR TO BE Fax (0)20 7539 1917

UP LOADING DOCK REVIEWED


L0t11 EXIT SCHEDULE
UP
EXIT ROUTE TRAVEL DISTANCE TO EXIT
CLIENT
EXIT ROUTE A 49 m
EXIT ROUTE B 36 m
FE EXIT ROUTE C 59 m
FE EXIT ROUTE D 35 m
MECH ANTEROOM EXIT ROUTE E 32 m
FIRE PUMP EdgeConneX Inc.
D0w19 L0a6 EXIT ROUTE F 12 m
L0w16 FIRE PUMP
EXIT ROUTE D 2201 Cooperative Way, Suite 200
L0w16 Herndon, VA 20171
Tel +01 866.304.3217
UP

RR
N.I.C. LIFE SAFETY LEGEND CLIENT'S CONSULTANT

RR BUSINESS

SECURITY
OFFICE

EXISTING WALL TO REMAIN


NEW PARTITION WOOLVERSTONE HOUSE
CORRIDOR 61 BERNERS STREET
1 HR. RATED PARTITION
BUSINESS LONDON
W1T 3NJ
A PATH OF TRAVEL (DISTANCE IN
SCHEDULE ON SHEET) Tel: 0207 0433410
STAIR/EXIT DESIGNATION
2
CAPACITY USED

200 138 ACTUAL USE


key plan
STAIR/EXIT CAPACITY

EXIT LIGHT
DATA HALL 3
EXIT LIGHT WITH DIRECTIONAL ARROW

F FIRE ALARM PULL STATION


FIRE EXTINGUISHER CODE NEN4001 -TABLE 12 FIRE CLASSIFICATIONS HAZARD CLASSIFICATIONS F FIRE ALARM ANNUNCIATOR
DATA HALL 1
Tag Note Text DEFINITIONS (NFPA 10, SECTION 3.3.4 EXCERPT): DEFINITIONS (NEN 4011 DOCUMENT INTEGRAL FIRE SAFETY, SECTION 6.2 CONTAINMENT AND FLOW RATE CAPACITY OF ESCAPE ROUTES -EXCERPT): True North
A FLAMMABLE LIQUIDS WILL NOT BE PRESENT WITHIN THE DATA CENTER. HOWEVER, CLASS A FIRES: ORDINARY COMBUSTIBLE MATERIALS, SUCH AS WOOD, CLOTH, PAPER, 6.2 Opvang- en doorstroomcapaciteit van vluchtroutes
FLAMMABLE LIQUIDS (DIESEL FUEL) WILL BE STORED WITH THE EXTERIOR GENERATOR PACS RUBBER AND MANY PLASTICS FAC FIRE APPARATUS CABINET, FIRE HOSE OFFICE
Portable extinguishers - Draagbare blusmiddelen - SIZE AND PLACEMENT (NEN4001 - TABLE 12)
B FIRE EXTINGUISHERS ARE SIZED AND LOCATED ON THE BASIS OF THE ANTICIPATED HAZARD CLASS B FIRES: FLAMMABLE LIQUIDS, COMBUSTIBLE LIQUIDS, PETROLEUM GREASES, TARS, OILS, De eisen aan de opvang- en doorstroomcapaciteit binnen een gebouw zijn verwoord in de Regeling Bouwbesluit 2012. Het doel van de eisen, zoals omschreven in deze
regeling, is om te waarborgen dat voldoende snel (door de beperkingen aan de loopafstand) een veilig gebied kan worden bereikt en dat dit veilige gebied ook voldoende
AND EXTINGUISHER N
OIL-BASED PAINTS, SOLVENTS LACQUERS, ALCOHOLS, AND FLAMMABLE GASES.
PER NEN4001, TABLE 12. Hoeveelheid blusstof CLASS C FIRES: FIRES THAT INVOLVE ENERGIZED ELECTRICAL EQUIPMENT.
capaciteit bezit om vluchtende personen op te vangen. Daarbij geldt dat vervolgens voldoende snel het aansluitende terrein moet kunnen worden bereikt. FHC FIRE HOSE CABINET
Brandklasse (Fire class) Blusmiddel (Agent) Aantal (number) In de Regeling Bouwbesluit 2012 is een rekenmethode opgenomen waarmee de opvang- en doorstroomcapaciteit van een vluchtroute wordt bepaald. Daarnaast moeten de project status
C REFER TO FLOOR PLANS FOR EXACT LOCATIONS OF FIRE EXTINGUISHER TYPES IDENTIFED Ruimte / gebied (Room/Area) (Volume agent) vluchtroutes van een gebouw over voldoende doorstroomcapaciteit beschikken zodat het gebouw binnen de daartoe gestelde tijd (in dit geval 15 minuten) kan worden FEC FIRE EXTINGUISHER CABINET
ON THE FIRE EXTINGUISHER PLANS.
Schakelruimte E (Electrical room) E1 CO2 6 kg n per 150m2
ontruimd.
De vereiste doorstroomcapaciteit wordt bepaald door per verdieping het aantal personen dat op dat gedeelte van een trappenhuis is aangewezen, te delen door het verschil
ISSUED FOR CONTRACT (PACK 1)
D EDGE IS TO PROVIDE APPROPRIATE HOUSEKEEPING THROUGHOUT THE FACILITY, IN van de aanwezige ontruimingstijd en het aantal bouwlagen dat nog moet worden afgelegd tot de toegang van het gebouw. FE FIRE EXTINGUISHER
ACCORDANCE WITH THE NEN4001 FIRE CODE. Generator (binnen 10m) A--B--C1 Schuim (Foam)/ CO2 6 liter / 6 kg n per 150m2 Voor de bepaling van de aanwezige opvang- en doorstroomcapaciteit zijn de volgende uitgangspunten gehanteerd:
de opvangcapaciteit van een vloer bedraagt 4 personen per m2 vrije vloeroppervlakte; SP project
E COVERAGE AREAS SHOWN ARE INTENDED TO SHOW GENERAL EXTENT OF COVERAGE ONLY FIRE STANDPIPE
Technische ruimte (Technical room) A--B--C1 Schuim (Foam)/ CO2 6 liter / 6 kg n per 150m2 de opvangcapaciteit van de trede van een trap, uitgedrukt in personen, is gelijk aan 0.9 x de breedte van de trap uitgedrukt in meters; EdgeConnex - Amsterdam, Netherlands
AND ARE NOT INTENDED TO SHOW SPECIFIC/EXACT BOUNDARIES. THE NUMBER OF FIRE de doorstroomcapaciteit van een gang/deur bedraagt 90 personen/m breedte per minuut;
S
Overige ruimten (Other rooms) de doorstroomcapaciteit van een trap bedraagt 45 personen/m trapbreedte per minuut. SMOKE DETECTOR
EXTINGUISHERS SHOWN EXCEEDS THE NUMBER REQUIRED TO ACCOMMODATE THE AREA A--B--C1 Schuim (Foam)/ CO2 6 liter / 6 kg n per 150m2
In het ontwerp van het Datacenter AMS06.1 zijn de volgende uitgangspunten van toepassing; Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL
SQUARE FOOTAGE(S) TO ENSURE TRAVEL DISTANCES REMAIN AT OR BELOW THE MAXIMUM
D:\RevitUserModels\08.7142.000-EDCAMS01-ARCH_Heni Warwick.rvt

alle uitgangen hebben een vrije doorgangsbreedte van minimaal 0,85 m;


SMOKE TIGHT project no
PERMITTED BY CODE. INSTALLATION HEIGHT
alle trappen hebben een minimale breedte van 1,1 m. [N.B. dit project heeft geen binnentrappen].
Binnen de Datacenters is, gezien de gebruiksfunctie, het aantal aanwezige personen zeer gering. Voor de bezetting van de industrie functie (datacenters) mogen er niet meer 08.7142.000
F THE TRAVEL DISTANCES GIVEN IN THE FIRE EXTINGUISHER PLANS ARE PROVIDED TO SHOW GROSS WEIGHT NOT EXCEEDING 18.1KG: <= 1200mm dan 1 persoon per 30m2 aanwezig zijn, de bezetting dient te worden afgestemd op het oppervlakte.
GROSS WEIGHT EXCEEDING 18.1KG: <= 1065mm Gezien de hoeveelheid aanwezige vluchtwegen van in totaal 6 deuren per data room welke direct leiden naar het aansluitende terrein en een vluchtdeur naar het scale date drawn checked
OVERLAP AND WORST CASE (MAXIMUM) TRAVEL ROUTES.
CLEARANCE FROM BOTTOM OF FIRE EXTINGUISHER AND FLOOR: >=100mm naastgelegen brandcompartiment, zal dit niet leiden tot problemen met de doorstroom- en opvangcapaciteit. As indicated @ A0 09/12/16 HW WR
INSTALLATION HEIGHT OF FIRE EXTINGUISHERS ALONG AN ACCESSIBLE ROUTE SHALL COMPLY WITH THE 6L FOAM OR 6kg CO2 sheet number
6.2 Containment and flow rate capacity of escape routes
NEN-5252 STANDARD HEIGHTS, WITH THE FIRE EXTINGUISHER HANDLE AT 1000MM ABOVE THE FFL. (FOR AREAS EXCLUDING
The requirements for the containment and flow rate within a building are expressed in the Building Regulations (Bouwbesluit ) 2012. The purpose of these requirements is to
ensure that sufficiently quickly (by the restricting the allowed walking distance) a secure area can be reached and that this safe area also has the capacity to accommodate
the number of escaping people. It also ensures that people are able to leave the premises reasonably quick.
ELECTRICAL)

6kg CO2
A0.80
The Building Regulations 2012 provides a calculation method for the containment and flow rate capacity of an escape route. In addition, the escape routes of the building
must have sufficient flow capacity so that the building within the prescribed time (in this case 15 minutes) can be cleared.
(ELECTRICAL AREAS) title
The required flow rate is determined by the number of persons per floor assigned to that percentage of a staircase by dividing the difference of the actual clearance time and
the number of floors that still must be passed to the exit of the building.
For determining the actual accommodation and flow rate the following criteria have been used:
the capacity of a floor is determined at a rate of 4 persons per m2 of floor area;
DRY RISER LIFE SAFETY PLAN
the capacity of the step of a staircase, expressed in number of people, is equal to 0.9 x the width of the staircase in meters;
the flow capacity of a corridor / door is 90 persons / m width per minute;
the flow capacity of a staircase is 45 persons / m stair width per minute.
In the design of the Datacenter AMS06.1 the following basic principles apply;
PRIMARY ACCESS TO BUILDING FOR FIREFIGHTERS
09/12/2016 16:55:53

All exits have a clear passage width of at least 0.85 m;


All staircases have a minimum width of 1.1 m. [N.B. This project has no interior stairs]
Within data centers, seen their function, the number of people present is very low. For the occupancy rate of the industrial function (data centers) the Building regulations
stipulate that there should be no more than 1 person per 30m2 present. The occupancy rate must be according to the area. SECONDARY / ADDITIONAL ACCESS POINTS
Given the amount of existing routes totaling 6 per data room with doors which lead directly to the exterior and an escape door to an adjacent fire compartment, this will be TO BUILDING FOR FIREFIGHTERS
compliant with the containment and flow rate requirements.

NOTE: C GENSLER 2015


ALL FIRE EXTINGUISHERS TO All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
CONFORM TO NEN 4001 FIRE SAFETY -
PROJECTING OF PORTABLE AND
MOVABLE FIRE EXTINGUISHERS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.

SHEET NOTES All dimensions to be verified by contractor on site prior to any works

1 PROVIDE NEW OPENING IN WALL.


PREPARE OPENING TO ACCEPT DOOR AS
SCHEDULED.
A A

DEMOLITION NOTES
Tag Note Text
UP A RE: A00 DRAWING SERIES FOR
SCHEDULES, LEGENDS, SYMBOLS AND
ABBREVIATIONS.
B FOR CONSTRUCTION PLAN AND OTHER
B B PLAN REFERENCES, RE: A2 DRAWING
SERIES.
C COORDINATE WITH PROPERTY
MANAGER FOR RETURN OF SALVAGE
ITEMS TO BUILDING OWNER FOR
FUTURE REUSE. COORDINATE WITH
PROPERTY MANAGER FOR ITEMS
REQUIRED.
D REMOVE EXISTING INTERIOR
PARTITIONS, DOORS, FRAMES,
HARDWARE, FLOOR AND WALL
FINISHES, LIGHTS AND CEILING
C C SYSTEMS NOT SHOWN TO REMAIN OR
AS REQUIRED FOR NEW WORK.
E REMOVE EXISTING TELEPHONE AND

N.I.C. DATA CABLING NOT SHOWN TO REMAIN


ON CONSULTANT'S PLANS OR AS
REQUIRED FOR NEW WORK.
F REMOVE EXISTING MECHANICAL,
ELECTRICAL, AND PLUMBING SYSTEMS
NOT SHOWN TO REMAIN ON
CONSULTANT'S PLANS OR AS
REQUIRED FOR NEW WORK.
G PATCH, REPAIR, AND PREPARE ALL
D D AFFECTED AREAS IN PREPARATION
FOR NEW WORK.
H ERECT AND MAINTAIN DUSTPROOF
PARTITIONS AS REQUIRED TO PREVENT
200 SPREAD OF DUST, FUMES, AND SMOKE,
7 3/4" 2046 ETC. TO OTHER PARTS OF THE
6'-8 1/2" BUILDING. UPON COMPLETION,
REMOVE PARTITIONS AND REPAIR
1 DAMAGED SURFACES TO MATCH
ADJACENT SURFACES.
UP
J IF DEMOLITION IS PERFORMED IN
EXCESS OF THAT REQUIRED, RESTORE
E E AFFECTED AREAS AT NO COST TO THE
OWNER.
K REMOVE FROM SITE DAILY AND
LEGALLY DISPOSE OF REFUSE, DEBRIS,
RUBBISH, AND OTHER MATERIALS
RESULTING FROM DEMOLITION
OPERATIONS.
L REMOVE EXISTING FLOOR FINISHES
AND PREPARE SUBFLOOR AS
REQUIRED FOR NEW FLOOR FINISHES.
E' E' M COMPLY WITH APPLICABLE LOCAL,
DN STATE AND FEDERAL CODES AND
F F REGULATIONS PERTAINING TO SAFETY
OF PERSONS, PROPERTY AND
ENVIRONMENTAL PROTECTION.
12 13 14 15 16 N PROVIDE AND MAINTAIN BARRICADES,
LIGHTING, AND GUARDRAILS AS
REQUIRED BY APPLICABLE CODES AND
REGULATIONS TO PROTECT
OCCUPANTS OF BUILDING AND OTHER
WORKERS.

G G

N.I.C. 6
5
4
09/12/2016
23/11/2016
18/11/2016
ISSUED FOR CONTRACT (PACK 1)
DRAWING PACKAGE 1
ISSUE FOR PRICING & CONSTRUCTION
(DRAWING PACKAGE 2)
3 07/11/2016 HATCH UPDATED AROUND MECH CORRIDOR
2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
rev date revision note

H H
Aldgate House
33 Aldgate High Street
London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917

UP
UP
J J CLIENT

EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
K Tel +01 866.304.3217
K
UP M L
CLIENT'S CONSULTANT
L
N.I.C. UP
M
N
1 2 3 4 5 6 7 8
L' L' WOOLVERSTONE HOUSE
61 BERNERS STREET
LONDON
W1T 3NJ
N
Tel: 0207 0433410

key plan

DATA HALL 3

DATA HALL 1
True North

OFFICE
N
project status

9 10' 10 11' 11 12' 13' 14' 15' ISSUED FOR CONTRACT (PACK 1)
project
EdgeConnex - Amsterdam, Netherlands

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


project no
08.7142.000
scale date drawn checked
1 : 100 @ A0 04/11/16 TS WR
sheet number

A1.00
title

DEMOLITION PLAN - LEVEL 0

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
SHEET NOTES All dimensions to be verified by contractor on site prior to any works

1 THE PARTITIONS AROUND THE DATA HALLS WILL BE


PROTECTED WITH A ONE HOUR FIRE RATED ASSEMBLY.
2 ASSEMBLY AROUND STEEL COLUMNS TO BE REPAIRED IF
4740 4800 4800 4800 4800 4800 4800 4800 4800 4800 4800 4800 4800 4800 4740
DAMAGED AND RE-PAINTED WHERE NECESSARY.
3 PAINT COLUMN TO MATCH ADJACENT WALL.
7 PROVIDE STAINLESS STEEL CORNER GUARDS: 100mm
UP
A.F.F. TO 2700mm A.F.F.; SCREW ON TO FASTEN AND APPLY
A A CEMENT PRIOR TO FASTENING TO CORNER.

MECH
750 POP 1 FLOOR / CEILING GRILLES TO M&E
D0s12
SPECIFICATION & LOCATIONS
TFX - 3 TFX - 4 L0a3
5220

B L0c7 L0c5
C D A REFER TO ELECTRICAL PACKAGE FOR
1 LIGHTING
A2.05
UP
PACKAGE 1 PACKAGE 1
108 RACKS
1000KW
138 RACKS
1000KW 0 B4A
UP
WALL PARTITION LEGEND
B B
1
EXISTING WALL TO REMAIN
NEW PARTITION
A
1 HR. RATED PARTITION
5280

2 DATA HALL
A2.05 D0m18
1
N.I.C. CONSTRUCTION PLANS
C MECH C
D0s12
Tag Note Text
2
A RE: A00 DRAWING SERIES FOR SCHEDULES, LEGENDS, SYMBOLS,
0 B4A ABBREVIATIONS AND CODE ANALYSIS RELATED TO PROJECT
5280

B DOOR NUMBERS ARE THE SAME AS THE ROOM INTO WHICH THEY
SWING. MULTIPLE DOORS INTO A SINGLE ROOM HAVE AN
ALPHABETICAL DESIGNATION. RE: A0.20 FOR DOOR SCHEDULE AND
TYPES.
C COORDINATE AND PROVIDE BLOCKING FOR MILLWORK AND ITEMS
D
ATTACHED OR MOUNTED TO PARTITIONS OR CEILINGS.
D PARTITIONS ARE DIMENSIONED FROM FINISH FACE TO FINISH FACE,
D D UNO. MAINTAIN DIMENSIONS MARKED "CLEAR". ALLOW FOR
THICKNESSES AND MOUNTING OF FINISHES.
E CIVIL ITEMS ARE SHOWN HALFTONE AS AN UNDERLAY FOR CONTEXT
DATA HALL 3
(PAVEMENTS, CURBS, PARKING, ROADS, ETC). REFER TO CIVIL
(246 600 X 1200MM RACKS) 1
DRAWINGS FOR SPECIFIC LOCATION(S) OF THESE ITEMS, SPECIFIC
2,250KW CRITICAL LOAD
BULDING LOCATION INFORMATION, ETC.
5280

UP
D0s12 9KW/RACK

D0w30 S.O.P
B A No architecture work required in
C MECH
this area, units to be installed in UP
existing mechanical corridor. D0j15
Refer to mechanical drawings.
E E

LIFT TFX - 2 TFX - 1


4210

L0l8 L0k5 1 B9.10

MECH
D0w30
E' E'
1070

DN
F F
12 13 14 15 16
5280

MMR - 1
D0m14

G G 6
5
09/12/2016
23/11/2016
ISSUED FOR CONTRACT (PACK 1)
DRAWING PACKAGE 1
4 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
ASSEMBLY/ (DRAWING PACKAGE 2)

N.I.C. STORAGE
L0r12
3
2
1
07/11/2016
04/11/2016
26/10/2016
HATCH UPDATED AROUND MECH CORRIDOR
AMS01 PHASE 2 (DRAWING PACKAGE 1)
ISSUE FOR OWNERS REVIEW 95%
5280

rev date revision note

DATA HALL IT
D0q14 Aldgate House
D0m17 33 Aldgate High Street
H H London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917

STAIR
5280

L0r15 MAN TRAP


CLIENT
L0s13
LOADING DOCK
UP
L0t11
UP
J
ANTEROOM J EdgeConneX Inc.
L0a6
2201 Cooperative Way, Suite 200
Herndon, VA 20171
5220

Tel +01 866.304.3217


MECH FIBER
FIRE PUMP
D0w19 L0w17
L0w16
K CLIENT'S CONSULTANT

560
6 5 4 3 2 1
UP UP UP M L
L GAS
RR
N.I.C UP

4350
RR
BUSINESS M WOOLVERSTONE HOUSE
SECURITY 61 BERNERS STREET
N OFFICE LONDON
1 2 3 4 5 6 7 8 W1T 3NJ
L' L' Tel: 0207 0433410
CORRIDOR
BUSINESS
N
key plan

DATA HALL 3

DATA HALL 1
True North
1500 3300 2500 2300 3800 6100 6100 6100
OFFICE
N
project status

ISSUED FOR CONTRACT (PACK 1)


project
EdgeConnex - Amsterdam, Netherlands
9 10' 10 11' 11 12' 13' 14' 15' Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL
project no
08.7142.000
scale date drawn checked
As indicated @ A0 04/11/16 TS WR
sheet number

A2.00
title

FLOOR PLAN - LEVEL 0

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works

1 2 3 4 5 6 7 8 9 10

2 1/4"
55
5 6
NEW RAISED ACCESS FLOOR TO MECH CORRIDOR MECH AF01 PT03
RB01

11'-0 1/2"
D0s12

3368
7
B C 3
D A

150
6"
0 B4A PACKAGE 1 PACKAGE 1 0 B4A
55 2 2 2 2 2 108 RACKS 2 2 2 2 2 2 138 RACKS 2 2 2 2 2
2 1/4" 1000KW 1000KW

B
1'-1"
330

A
150
6"

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS

FLOOR GRILLES TO M&E SPECIFICATION & LOCATIONS


150
3276 6" 40185
10' - 9" 131' - 10"
CLEAR

2
A2.05
1773
5'-9 3/4"
1
0 B4A

C DATA HALL
1 D0m18
PT04

49'-2 1/2"
CLEAR
15000
MECH RB01

D0s12

PT02
RB01

AF01

D
5

5 09/12/2016 ISSUED FOR CONTRACT (PACK 1)

2870
4 23/11/2016 DRAWING PACKAGE 1
DATA HALL 3 3 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
(246 600 X 1200MM RACKS AF01 (DRAWING PACKAGE 2)
2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
2,250KW CRITICAL LOAD
1 1 1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
9KW/RACK
D0s12 rev date revision note
200
8"

S.O.P
D0w30 Aldgate House
150
6"

5 6 33 Aldgate High Street


7
C B A 9
London EC3N 1AH
UK
MECH Tel (0)20 7073 9600
Fax (0)20 7539 1917
MECH D0j15
D0w30

E CLIENT
5
MAN TRAP
L0s13

1 2 3 4 5 6 7 8 9 10 EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
Tel +01 866.304.3217

CLIENT'S CONSULTANT

1 ENLARGED FLOOR PLAN - LEVEL 0 / DATA HALL 0


SCALE: 1 : 50

WOOLVERSTONE HOUSE
61 BERNERS STREET
2 LONDON
SHEET NOTES CONSTRUCTION PLANS W1T 3NJ

Tel: 0207 0433410


Tag Note Text
DATA HALL 1 SLAB 1 EXISTING COLUMNS TO BE PAINTED (PT03) A RE: A00 DRAWING SERIES FOR SCHEDULES, LEGENDS, SYMBOLS,
5520 2 PAINT (PT03) ALIGN WITH SERVER ROWS ON FLOOR GRID. COORDINATE ABBREVIATIONS AND CODE ANALYSIS RELATED TO PROJECT
WITH MEP. SEE ELEVATION 1/A11.13 key plan
B DOOR NUMBERS ARE THE SAME AS THE ROOM INTO WHICH THEY
4 3 PAINT COLUMN TO MATCH ADJACENT WALL. SWING. MULTIPLE DOORS INTO A SINGLE ROOM HAVE AN
4 SEALED CONCRETE ALPHABETICAL DESIGNATION. RE: A0.20 FOR DOOR SCHEDULE AND
TYPES. DATA HALL 3
2 5 SEAL ALL CONCRETE BELOW RAISED ACCESS FLOOR (CO01) REFER TO
INDICATIVE LINE OF C COORDINATE AND PROVIDE BLOCKING FOR MILLWORK AND ITEMS
FINISH SCHEDULE SHEET A0.30
MECH EQUIPMENT
6 ALL EXPOSED WALL & STRUCTURE ABOVE 12'-0" A.F.F. TO BE PAINTED PT05 ATTACHED OR MOUNTED TO PARTITIONS OR CEILINGS.
3 7 PROVIDE STAINLESS STEEL CORNER GUARDS: 100mm A.F.F. TO 2700mm D PARTITIONS ARE DIMENSIONED FROM FINISH FACE TO FINISH FACE, DATA HALL 1
A.F.F.; SCREW ON TO FASTEN AND APPLY CEMENT PRIOR TO FASTENING TO UNO. MAINTAIN DIMENSIONS MARKED "CLEAR". ALLOW FOR
True North
CORNER. THICKNESSES AND MOUNTING OF FINISHES.
E CIVIL ITEMS ARE SHOWN HALFTONE AS AN UNDERLAY FOR CONTEXT OFFICE
(PAVEMENTS, CURBS, PARKING, ROADS, ETC). REFER TO CIVIL N
DRAWINGS FOR SPECIFIC LOCATION(S) OF THESE ITEMS, SPECIFIC
10'-11 3/4"

MECH DATA HALL


BULDING LOCATION INFORMATION, ETC.
3345

project status
D0s12 D0m18
ISSUED FOR CONTRACT (PACK 1)
project
0 B4A EdgeConnex - Amsterdam, Netherlands

DATA HALL 0 Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


project no
750
SECTION NOTES
2'-5 3/4"

08.7142.000
755

scale date drawn checked


1
As indicated @ A0 04/11/16 TS WR
sheet number
1 CONCRETE SLAB (SEE STRUCTURAL)
2 ZONE FOR ELECTRICAL EQUIPMENT &
FITTINGS A2.05
3 SCHEDULED CEILING (REFER TO RCP)
title
4 STEEL STRUCTURE (SEE STRUCTURAL)

ENLARGED FLOOR PLAN -


TYPICAL SECTION 2 LEVEL 0
SCALE: 1 : 50
WALL PARTITION LEGEND

EXISTING WALL TO REMAIN


NEW PARTITION C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
1 HR. RATED PARTITION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
SHEET NOTES All dimensions to be verified by contractor on site prior to any works

FLOOR / CEILING GRILLES TO M&E


SPECIFICATION & LOCATIONS
A A
REFER TO ELECTRICAL PACKAGE FOR
LIGHTING

MECH CL02
D0s12

REFLECTED CEILING PLAN NOTES


A RE: A00 DRAWING SERIES FOR SCHEDULES, LEGENDS,
B B SYMBOLS AND ABBREVIATIONS.
B RE: A0.41 FOR TYPICAL DEVICE MOUNTING LOCATIONS.
C CENTER ALL EXIT SIGNS, SMOKE DETECTORS, ETC. IN THE
CENTERLINE OF CORRIDORS AND CENTERLINE OF LIGHT
FIXTURES, UNO., OR VIOLATION OF APPLICABLE CODES
WOULD OCCUR.
D INSTALL REGISTERS AND LIGHT FIXTURES WITHIN GRID
MECH
LINES. INSTALL SPEAKERS, LIGHT FIXTURES, AND OTHER
CL01
CEILING ELEMENTS IN THE GEOMETRIC CENTER OF
D0s12
C DATA HALL C ACOUSTICAL UNITS OR CELING PANELS, UNO.
CL02 +3350 E IN ACOUSTICAL CEILINGS, LOCATE ALL SPRINKLER HEADS IN
D0m18
THE GEOMETRIC CENTER OF PANELS, UNO.

1
A4.05
N.I.C. F IF IT IS NOT POSSIBLE TO LOCATE SPRINKLER HEADS AS
REQUIRED ABOVE FOR ANY REASON, INCLUDING, WITHOUT
LIMITATION, CODE REQUIREMENTS, DO NOT PROCEED WITH
WORK UNTIL SUCH CONDITIONS HAVE BEEN REVIEWED
WITH ARCHITECT.
G PROVIDE SPRINKLER HEAD LOCATIONS FOR ARCHITECT'S
REVIEW FOR AESTHETIC PURPOSES PRIOR TO ANY
D D INSTALLATION, AND PRIOR TO SUBMITTING DRAWINGS FOR
PERMIT. CONTRACTOR WILL, OTHERWISE, BE REQUIRED TO
RELOCATE HEADS AT ITS SOLE EXPENSE.
H RE: MEP DRAWINGS FOR DESIGN OF MECHANICAL AND
ELECTRICAL SYSTEMS. ARCHITECTURAL PLANS GOVERN
FOR LOCATION OF ITEMS INSTALLED IN CEILINGS. NOTIFY
S.O.P
ARCHITECT IF CONFLICTS OCCUR.
J ARRANGE CONCEALED ITEMS TO PROVIDE ADEQUATE
CLEARANCES FOR CEILING AND ITS DEVICES.
K RE: ELECTRICAL DRAWINGS FOR FIXTURE SCHEDULE, EXIT
E MECH E LIGHTS AND OTHER LIFE SAFETY DEVICES.
D0j15 L VERIFY ACCESS PANEL LOCATIONS WITH ARCHITECT PRIOR
TO LAYOUT OF WORK REQUIRING ACCESS.
M PLUMB ALL STEM, AIRCRAFT CABLE, AND APPURTENANCES
USED TO SUPPORT SUSPENDED LIGHT FIXTURES, UNO.
N REMOVE ALL PAINT FROM EXPOSED DUCTWORK, CONDUIT
AND PIPING. REMOVE ALL TAGS AND LABELS NOT REQUIRED
BY CODE.
E' E' O FINISH HVAC DIFFUSERS, DRAPERY POCKETS, AND
SPEAKER GRILLES TO MATCH ADJACENT FINISH, UNO.
F F P PROVIDE CONCEALED SPRINKLER HEADS WITH CAPS WHICH
ARE FACTORY-PAINTED TO MATCH THE CEILING IN ALL
12 13 14 15 16 DRYWALL CEILINGS. LOCATE ALL HEADS TO ALIGN WITH
LIGHT FIXTURES, UNO.
Q PROVIDE CONCEALED SPRINKLER HEADS WITH CAPS WHICH
ARE FACTORY-PAINTED TO MATCH THE CEILING IN ALL
DRYWALL CEILINGS. LOCATE ALL HEADS TO ALIGN WITH
LIGHT FIXTURES, UNO.

G G

N.I.C. 6
5
4
09/12/2016
23/11/2016
18/11/2016
ISSUED FOR CONTRACT (PACK 1)
DRAWING PACKAGE 1
ISSUE FOR PRICING & CONSTRUCTION
(DRAWING PACKAGE 2)
3 07/11/2016 HATCH UPDATED AROUND MECH CORRIDOR
2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
rev date revision note

H H
Aldgate House
33 Aldgate High Street
London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917

J J CLIENT

EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
K
Tel +01 866.304.3217
K
M L
CLIENT'S CONSULTANT
L
2
A9.50
M
N
1 2 3 4 5 6 7 8
L' L' WOOLVERSTONE HOUSE
61 BERNERS STREET

N.I.C N
LONDON
W1T 3NJ

Tel: 0207 0433410

key plan

DATA HALL 3

DATA HALL 1
True North

OFFICE
N
project status

9 10' 10 11' 12' 13' 14' 15' ISSUED FOR CONTRACT (PACK 1)
project
EdgeConnex - Amsterdam, Netherlands

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


project no
08.7142.000
scale date drawn checked
As indicated @ A0 04/11/16 TS WR
sheet number

A4.00
title

REFLECTED CEILING PLAN -


LEVEL 0

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
2 3 4 5 6 7 8 9 10 SHEET NOTES All dimensions to be verified by contractor on site prior to any works

FLOOR / CEILING GRILLES TO M&E


A SPECIFICATION & LOCATIONS

REFER TO ELECTRICAL PACKAGE FOR


LIGHTING

REFLECTED CEILING PLAN NOTES


CL02 MECH
D0s12
A RE: A00 DRAWING SERIES FOR SCHEDULES, LEGENDS,
SYMBOLS AND ABBREVIATIONS.
2
A4.05
B RE: A0.41 FOR TYPICAL DEVICE MOUNTING LOCATIONS.
C CENTER ALL EXIT SIGNS, SMOKE DETECTORS, ETC. IN THE
CENTERLINE OF CORRIDORS AND CENTERLINE OF LIGHT
FIXTURES, UNO., OR VIOLATION OF APPLICABLE CODES
WOULD OCCUR.
D INSTALL REGISTERS AND LIGHT FIXTURES WITHIN GRID
LINES. INSTALL SPEAKERS, LIGHT FIXTURES, AND OTHER
CEILING ELEMENTS IN THE GEOMETRIC CENTER OF
B ACOUSTICAL UNITS OR CELING PANELS, UNO.
E IN ACOUSTICAL CEILINGS, LOCATE ALL SPRINKLER HEADS IN
THE GEOMETRIC CENTER OF PANELS, UNO.
F IF IT IS NOT POSSIBLE TO LOCATE SPRINKLER HEADS AS
REQUIRED ABOVE FOR ANY REASON, INCLUDING, WITHOUT
LIMITATION, CODE REQUIREMENTS, DO NOT PROCEED WITH
WORK UNTIL SUCH CONDITIONS HAVE BEEN REVIEWED
WITH ARCHITECT.
G PROVIDE SPRINKLER HEAD LOCATIONS FOR ARCHITECT'S
REVIEW FOR AESTHETIC PURPOSES PRIOR TO ANY
INSTALLATION, AND PRIOR TO SUBMITTING DRAWINGS FOR
2
PERMIT. CONTRACTOR WILL, OTHERWISE, BE REQUIRED TO
A4.05
RELOCATE HEADS AT ITS SOLE EXPENSE.
H RE: MEP DRAWINGS FOR DESIGN OF MECHANICAL AND
ELECTRICAL SYSTEMS. ARCHITECTURAL PLANS GOVERN
FOR LOCATION OF ITEMS INSTALLED IN CEILINGS. NOTIFY
ARCHITECT IF CONFLICTS OCCUR.
J ARRANGE CONCEALED ITEMS TO PROVIDE ADEQUATE
CLEARANCES FOR CEILING AND ITS DEVICES.
K RE: ELECTRICAL DRAWINGS FOR FIXTURE SCHEDULE, EXIT
C LIGHTS AND OTHER LIFE SAFETY DEVICES.
CL01 L VERIFY ACCESS PANEL LOCATIONS WITH ARCHITECT PRIOR
CL02 DATA HALL TO LAYOUT OF WORK REQUIRING ACCESS.
D0m18 +3350
M PLUMB ALL STEM, AIRCRAFT CABLE, AND APPURTENANCES
USED TO SUPPORT SUSPENDED LIGHT FIXTURES, UNO.
MECH N REMOVE ALL PAINT FROM EXPOSED DUCTWORK, CONDUIT
D0s12 AND PIPING. REMOVE ALL TAGS AND LABELS NOT REQUIRED
BY CODE.
O FINISH HVAC DIFFUSERS, DRAPERY POCKETS, AND
SPEAKER GRILLES TO MATCH ADJACENT FINISH, UNO.
P PROVIDE CONCEALED SPRINKLER HEADS WITH CAPS WHICH
ARE FACTORY-PAINTED TO MATCH THE CEILING IN ALL
DRYWALL CEILINGS. LOCATE ALL HEADS TO ALIGN WITH
LIGHT FIXTURES, UNO.
Q PROVIDE CONCEALED SPRINKLER HEADS WITH CAPS WHICH
ARE FACTORY-PAINTED TO MATCH THE CEILING IN ALL
DRYWALL CEILINGS. LOCATE ALL HEADS TO ALIGN WITH
LIGHT FIXTURES, UNO.

5 09/12/2016 ISSUED FOR CONTRACT (PACK 1)


4 23/11/2016 DRAWING PACKAGE 1
3 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
(DRAWING PACKAGE 2)
2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
rev date revision note

S.O.P S.O.P
Aldgate House
33 Aldgate High Street
London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917

1 2 3 4 5 6 7 8 9 10
CLIENT

1 ENLARGED REFLECTED CEILING PLAN


SCALE: 1 : 50

EdgeConneX Inc.
2201 Cooperative Way, Suite 200
Herndon, VA 20171
Tel +01 866.304.3217

CLIENT'S CONSULTANT

WOOLVERSTONE HOUSE
61 BERNERS STREET
LONDON
W1T 3NJ

Tel: 0207 0433410


SUSPENSION SYSTEM

key plan

DATA HALL 3

DATA HALL 1
True North

OFFICE
N
project status

ISSUED FOR CONTRACT (PACK 1)


SCHEDULED CEILING

project
PERIMIETER / EDGE TRIM EdgeConnex - Amsterdam, Netherlands

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


project no
SCHEDULED PARTITION 08.7142.000
scale date drawn checked
As indicated @ A0 04/11/16 TS WR
sheet number

A4.05
title

REFLECTED CEILING PLAN -


LEVEL 0
CEILING PERIMETER DETAIL 2
SCALE: 1 : 1

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works

METAL STUD CRIPPLE WALL

ROOF DECK (SEE STRUCTURAL

1185 MAX. BOTTOM OF STRUCTURE


3' - 11"

900mm TO 1200mm MAX - MTL. STUDS SEE SPECIFICATIONS 50mm X 50mm X 16 GA


DOUBLE JAMB STUDS. CLIP ANGLE FASTENED TO
1245mm - 2440mm - HEAVY BAR JOIST AND STUD
GAUGE DOUBLE JAMB STUDS BRACE
FOR OPENINGS 1200mm WIDE 100mm MIN METAL
MAX. USE SINGLE STUD HEADER BRACE STUDS AT
ANCHOR ANGLE AND RUNNER TRACKS. FOR 750mm CENTRES MAX
AT DOUBLE STUDS, TYP. OPENINGS 2400mm WIDE MAX.
DEEP LEG SLIP TRACK FIRE STOP STUD
USE DOUBLE STUD BOX HEADER
W/ 75mm LEGS AND PENETRATIONS
AND RUNNER TRACKS
25mm MIN GAP
TOP OF SLAB
BOTTOM RUNNER WALL ASSEMBLY,
ROOF TRUSS NOTE: REFER TO UL LISTING HW-D-0520 FOR TOP OF WALL REFER TO PLANS
FIRE STOPPING REQUIREMENTS FOR WALL TYPE

TYPICAL MTL STUD DOOR FRAMING 8 1-HR RATED WALL HEAD PAR. TO STRUCTURE 4
SCALE: 1 : 50 SCALE: 1 : 10

COPE STUD BRACE AND


ATTACH TO TRACK W/ 4-
#8 SHEET METAL 1
UNDERSIDE OF ROOF DECK COMPRESSIBLE FOAM BLOCK 12mm MIN
SCREWS.

25
1"
2 MAX

100mm STUD BRACE AT


1200mm CENTRES
ALTERNATE DIRECTION
BUILT-UP METAL STUD FRAMING;
ACOUSTIC SEALANT EVERY SECOND BRACE
MATCH DEPTH OF STRUCTURE

LAYER 15mm 3

100
4"
GYP BD EXISTING SLAB TO REMAIN 1 A2A PARTITION TAG
75mm LONG LEG DEFLECTION 7 PARTITION TYPE DESIGNATOR
SLIP TRACK; STOP STUDS SUSPENDED ACOUSTIC PRE-FORMED MINERAL WOOL WALL PLUG (SEE PARTITION SERIES TYPE SCHEDULES)
25mm BELOW TOP OF TRACK CEILING SYSTEM (WHERE 2

75
INDICATED ON PLAN) FRAMING MEMBER DEPTH

3"
SLIP-TYPE HEAD JOINT
#8 TEK SCREW AT EACH PLATE WALL PARTITION; SEE ACOUSTIC (SEE TABLE B OR TABLE C - BELOW
8
PLANS FOR TYPE INSULATION (WHERE
CONTINUOUS ACOUS SEALANT PARTITION SERIES
REFER TO PLANS FOR WALL TYPE INDICATED ON PLAN)
@ NON-RATED ASSEMBLY; FIRE-RATED (SEE TABLE A - BELOW)
SEALANT @ RATED ASSEMBLY
FIRE RATING (IF APPLICABLE)
4
SOUND ATTENUATION BLANKET TABLE A- PARTITION SERIES CONSTRUCTION ASSEMBLY
SERIES SHEATHING FRAMING MEMBERS SHEATHING
SCHEDULED CEILING, REFER A 1-LAYER METAL C-STUD 1-LAYER
TO REFLECTED CEILING PLAN
B 2-LAYERS METAL C-STUD 2-LAYERS
WALL DEFLECTION HEAD PERP. TO STRUCTURE 7 TYP PARTIAL HGT PARTITION BRACING DETAIL 3 5 C 1-LAYER METAL C-STUD 2-LAYERS
SCALE: 1 : 5 SCALE: 1 : 5 METAL STUD
D 1-LAYER METAL C-STUD NONE
6
GYPSUM BOARD E 2-LAYERS METAL C-STUD NONE
F 1-LAYER MTL HAT CHANNEL NONE
PERPENDICULAR TO DECK FLUTES G 1-LAYER NONE NONE
H 1-LAYER METAL C-H STUD LINER PNL
5 09/12/2016 ISSUED FOR CONTRACT (PACK 1)
J 2-LAYERS METAL C-H STUD LINER PNL 4 23/11/2016 DRAWING PACKAGE 1
K 1-LAYER (2) METAL C-STUDS 1-LAYER 3 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
(DRAWING PACKAGE 2)
#8 SHEET METAL SCREWS L 2-LAYERS (2) METAL C-STUDS 2-LAYERS 2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
AT 300mm CENTRES TYP 1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
M NONE CMU NONE
rev date revision note
CRIPPLE STUD N-U RESERVED FOR FUTURE EXPANSION
WALL STUD V-Z CUSTOM N/A N/A

Aldgate House
PROVIDE MIN. 1.5mm (16 GA) 33 Aldgate High Street
STUDS & BACKING PLATE TABLE B- FRAMING DEPTH SCHEDULE London EC3N 1AH
ANCHORAGES. DOUBLE STUDS AT HEADER 3 UK
END OF PARTITIONS EXISTING SLAB TO REMAIN TAG NUMBER MTL STUD MTL C-H STUD WOOD STUD Tel (0)20 7073 9600
DESIGNATION DEPTH DEPTH DEPTH Fax (0)20 7539 1917
150mm MIN HEADER 7
3 #8 PAN HEAD SHEET METAL - NO FRAMING
SCREWS MEMBERS PRE-FORMED MINERAL WOOL WALL PLUG
0 7/8" FURRING CHANNEL N/A
150mm X 1.5mm (16 GA)
1
CLIP ANGLE WITH 4-#8 FLAT STRAP & BACKING PLATE 1 40mm N/A N/A
UNPUNCHED STUD WITH FLANGES
SHEET METAL SCREWS CLIENT
COPED AT VERT. STUDS. ATTACH 8 2 65mm 65mm N/A
INTO STUD AND HEADER
TO TWO STUDS MIN. & EXTEND HEADER
150mm MIN. BEYOND MOUNTING
CONTINUOUS ACOUS SEALANT 3 90mm N/A N/A
TRACK @ NON-RATED ASSEMBLY; FIRE-RATED
POINT EACH DIRECTION 4 100mm 100mm 100mm
JOINING PLATE SEALANT @ RATED ASSEMBLY
NOTES: 6 148mm 148mm 148mm
2
8 200mm N/A N/A
1. DETAIL DEPICTS A TYPICAL BACKING PLATE ASSEMBLY FOR HANDRAILS, SLIP-TYPE HEAD JOINT EdgeConneX Inc.

VERIFY WITH DOOR FRAME


GRAB BARS, TOILET ACCESSORIES, WALL BUMPERS, JOINERY, BASE/UPPER 4 10 250mm N/A N/A
BASE TRACK 2201 Cooperative Way, Suite 200

MANUFACTURER
CABINETS, CHAIR RAILS, ETC.
SOUND ATTENUATION BLANKET
Herndon, VA 20171
2. COORDINATE BACKING PLATE LOCATION AND HEIGHTS WITH MFRS MOUNTING TABLE C- MASONRY WIDTH SCHEDULE
INSTRUCTIONS. SCHEDULED CEILING, REFER Tel +01 866.304.3217
TO REFLECTED CEILING PLAN TAG NUMBER CMU
3. FIRE TREATED SOLID 2X WOOD BLOCKING IS AN ACCEPTABLE ALTERNATE DESIGNATION WIDTH
METHOD FOR BLOCKING (CONTRACTOR OPTION). 5
CLIP ANGLE WITH 4-#8 SHEET
METAL SCREWS INTO STUD METAL STUD 4 3 5/8"
CLIENT'S CONSULTANT
AND 12mm DIA HILTI KWIKBOLT 6 6 5 5/8"
3 WITH 100mm MIN GYPSUM BOARD
EMBEDMENT INTO CONCRETE 8 7 5/8"
(NOT REQUIRED WHEN 10 9 5/8"
DOUBLE STUDS HAVE A PARALLEL TO DECK FLUTES
STRENGTHENING PLATE WITH 12 11 5/8"
ITS OWN CONCRETE ANCHOR

STEEL SHEET THICKNESS FOR STUDS AND RUNNERS WOOLVERSTONE HOUSE


TYPICAL STUD FRAMING BACKING PLATE 6 TYP INTERIOR HEADER DETAIL 2 GAGE* MIN. STEEL BASE METAL THICKNESS (UNCOATED) 61 BERNERS STREET
SCALE: 1 : 10 SCALE: 1 : 5 LONDON
A T01 INCH MILS MM W1T 3NJ
12 0.1017 97 X
14 0.0713 68 X Tel: 0207 0433410
16 0.0566 54 1.34
18 0.0451 43 1.09
20 0.0312 30 0.84 key plan

ACOUSTIC SEALANT COMPRESSIBLE 22 0.0270 27 0.68


FOAM BLOCK 25 0.0179 18 0.45
25
1"

DATA HALL 3
WIDTH OF DUCT + INSULATION + 50mm EACH SIDE *GAGE 16,18 USED FOR STRUCTURAL FRAMING; 20, 22,
BOTTOM OF STRUCTURE AND 25 USED FOR NON-STRUCTURAL FRAMING
1 LAYER 15mm THICK MOISTURE RESISTANT *USE OF DIMPLED STEEL STUDS ACCEPTABLE PROVIDED DATA HALL 1
DUCT GYPSUM BOARD BOTH SIDES CONTRACTOR SUPPLIES DOCUMENTATION PROVING THE
True North
SUSPENDED CEILING OPENING TOP CHANNEL EQUIVALENT MINIMUM BASE METAL THICKNESS IS
WHERE APPLICABLE METAL STUDS, 600mm CENTRES,
REFER TO PLANS FOR STUD SIZE ACHIEVED OFFICE
N
900mm TO 1200mm MAX - FOR OPENINGS 1200mm WIDE MAX. VAPOUR BARRIER (WHERE INDICATED) GENERAL NOTES
15mm GYP BD, TYP
DOUBLE JAMB STUDS. USE SINGLE STUD HEADER AND INSULATION (WHERE INDICATED ON PLAN) project status
1250mm TO 2400mm - HEAVY RUNNER TRACKS. FOR OPENINGS GN-01. PARTITION TYPES ARE NOT SEQUENTIAL.
GAUGE DOUBLE JAMB STUDS 1250mm x 2400mm WIDE MAX. USE GN-02. ALL PARTITION SHEATHING TO BE 5/8" GYPSUM ISSUED FOR CONTRACT (PACK 1)
DOUBLE STUD BOX HEADER AND BOARD UNLESS OTHERWISE NOTED.
25
1"

RUNNER TRACKS
project
75mm LONG LEG DEFLECTION GN-03. REFER TO A09.100 SERIES FOR ALL PARTITION
EdgeConnex - Amsterdam, Netherlands
75
3"

SLIP TRACK; STOP STUDS 25mm CONDITIONS LISTED IN PARTITION SCHEDULE.


100mm MIN METAL BELOW TOP OF TRACK TOP OF SLAB MTL. STUDS SEE
BRACE STUDS AT SPECIFICATIONS PARTITION FRAMING DETAILS Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL
750mm CENTRES MAX 2 (MIN) #8 TEK SCREW AT EACH GN-04. ALL PARTITIONS SHALL BE COORDINATED WITH
FIRE TYPE THK ATTEN TESTED STC SHEET project no
PLATE SCHEDULED FINISHES FOR PARTITION LAYOUT AND 08.7142.000
ANCHOR ANGLE BOTTOM CHANNEL RTG MARK (IN) DEPTH SPACING TOP BOT THK ASSEMBLY RTG NOTES
REFER TO PLANS FOR WALL TYPE REQUIRED CLEARANCES. scale date drawn checked
AT DOUBLE STUDS, TYP. 0 B4A A T01 A B01
1 B4A A T01 A B01 GN-05. PROVIDE BLOCKING IN PARTITIONS FOR As indicated @ A0 04/11/16 TS WR
ARTWORK HANGING AS INDICATED. SEE sheet number
CONSTRUCTION PLAN(S) AND/ OR INTERIOR
ELEVATIONS FOR LOCATIONS. A12.00
GN-06.FOR INTERIOR FRAMING LIMITING HEIGHTS REFER
TO SSMA TABLES FOR INTERIOR NON-STRUCTURAL NON- title
COMPOSITE PARTITIONS
GN-07. CONTRACTOR TO RE-CONFIRM STUD SIZING PARTITION TYPES
WALL DEFLECTION HEAD DETAIL 10 TYPICAL DUCT STUD FRAMING (THROUGH DRYWALL) 5 PARTITION TYPE A 1 A TYPE AND SUBMIT SELECTION CRITERIA FOR REVIEW
INCLUDING DELINEATION OF SLAB TO UNDERSIDE OF
SCALE: 1 : 5 SCALE: 1 : 50 SCALE: 1 : 5 SLAB INFORMATION

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works

GYPSUM BOARD FACE


OF PARTITION OR SOFFIT

WALL ANGLE BY CLG MFR

100 TYP
LAY-IN CLG

4"
C
L C
L

SEE RCP
CEILING METAL PROFILE

CEILING TILE, SEE CEILING SPEC.


CONT SEALANT BEAD @ JT B/N ANGLE & PTN.

SEE RCP
AT SOFFIT LOCATIONS, GYP BD FACE PROJECTS
25mm OUTBOARD OF CSWK UPPER CAB PLAM FACE
TYP UON TO ALIGN ADJACENT GYP BOARD FACE(S)
IN RCP.

TYPICAL WALL MOLDING/ ANGLE 5 CEILING PLAN JOIN 1


SCALE: 1 : 2 SCALE: 1 : 2

STRUT GRID OR CEILING


STRUCTURE ABOVE TILES ARE LAID IN WITHOUT CLIPS
(SEE SPECIFICATIONS FOR
LOCATIONS/SPACING REQUIREMENTS

ACOUSTIC CEILING TILE


SECURE COMPRESSION STRUT TO CEILING
SUSPENSION WIRES; SIZE & SPACING AS SECURE COMPRESSION STRUT TO CEILING
RECOMMENDED BY CEILING GRID MFR SUSPENSION WIRES; SIZE & SPACING AS
RECOMMENDED BY CEILING GRID MFR

DROP RODS; SIZE & SPACING AS


DROP RODS; SIZE & SPACING AS RECOMMENDED BY RECOMMENDED BY CEILING GRID MFR
CEILING GRID MFR (SEE STRUCTURAL DWGS)
CEILING SUSPENSION SYSTEM
CEILING SUSPENSION SYSTEM

SUSPENDED ACOUSTIC CEILING TILE

SEE RCP
SEE RCP
SUSPENDED ACOUSTIC CEILING TILE

TYP LAY-IN COMPRESSION STRUT DETAIL 6 CEILING - TYP HOLD DOWN CLIP DETAIL 2
SCALE: 1 : 5 SCALE: 1 : 5

2 09/12/2016 ISSUED FOR CONTRACT (PACK 1)


1 23/11/2016 DRAWING PACKAGE 1
rev date revision note

Aldgate House
33 Aldgate High Street
London EC3N 1AH
UK
Tel (0)20 7073 9600
Fax (0)20 7539 1917

10 MIN. DROP BAR, REFER TO STRUCTURAL DWGS


CLIENT
0"

FASTENER (SEE SPECIFICATION) SUSPENDED ACOUSTIC CEILING GRID

WHITE WALL (SEE SPECIFICATION) EdgeConneX Inc.


SEE RCP
2201 Cooperative Way, Suite 200
Herndon, VA 20171
CEILING TILE, SEE CEILING SPEC. Tel +01 866.304.3217
CEILING GRID EDGE ANGLE

SCHEDULED PARTITION (SEE FLOOR


CLIENT'S CONSULTANT
PLAN FOR TYPE)

WOOLVERSTONE HOUSE
CEILING - TYP EDGE DETAIL 3
61 BERNERS STREET
LONDON
SCALE: 1 : 5 W1T 3NJ

Tel: 0207 0433410

key plan

DATA HALL 3

DATA HALL 1
CEILING METAL PROFILE True North

OFFICE
N
project status
CEILING TILE, SEE CEILING SPEC.
ISSUED FOR CONTRACT (PACK 1)
project
EdgeConnex - Amsterdam, Netherlands

Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL


D:\RevitUserModels\08.7142.000-EDCAMS01-ARCH_Heni Warwick.rvt

project no
08.7142.000
scale date drawn checked
SEE RCP
As indicated @ A0 10/27/2015 Author Checker
sheet number

A12.10
title

DETAILS - CEILING
09/12/2016 16:56:07

CEILING PROFILE 4
SCALE: 1 : 1

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988
notes:
Do not scale from drawings. All discrepancies to be reported to Gensler architect immediately.
All dimensions to be verified by contractor on site prior to any works

SYSTEM NO. W-L-2241 SYSTEM NO. W-L-1049


F RATINGS - 1 AND 2 HR (SEE ITEM 1B)
F RATINGS - 1 AND 2 HR (SEE ITEM 1)
T RATING - 0 HR
T RATINGS - 0, 1/4, 1 AND 1-3/4 HR (SEE ITEM 2)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
A
3 2 3

A 1A 1B
2

2
1A 1B
3 2
3
A SECTION A-A

1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE-RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE


A SECTION A-A
(Cont'd on W-L-1049 B Card)
CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR
U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL 1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/ STUD WALL ASSEMBLY
INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND
WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED MAX 16 IN. (406 SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
SYSTEM NO. UL R4024, 96NK13566 B.
MM) OC. STEEL STUDS TO BE MIN 3-1/2 IN. (89 MM) WIDE AND SPACED MAX 24 IN. (610 MM) OC.
GYPSUM BOARD* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS SPECIFIED IN A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS.
THE INDIVIDUAL WALL AND PARTITION DESIGN.DIAM OF OPENING TO BE 1 IN. TO 1-1/8 IN. (25 TO WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM)
29 MM) LARGER THAN OUTSIDE DIAM OF PIPE. OC. STEEL STUDS TO BE MIN 3-1/2 IN. (89 MM) WIDE AND SPACED MAX 24 IN. (610 MM) OC.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WHEN STEEL STUDS ARE USED AND THE DIAM OF OPENING EXCEEDS THE WIDTH OF STUD
WALL ASSEMBLY IN WHICH IT IS INSTALLED. CAVITY, THE OPENING SHALL BE FRAMED ON ALL SIDES USING LENGTHS OF STEEL STUD
2. THROUGH PENETRANT - ONE NONMETALLIC PIPE, CONDUIT OR TUBE TO BE INSTALLED INSTALLED BETWEEN THE VERTICAL STUDS AND SCREW-ATTACHED TO THE STEEL STUDS
10mm MAX. GAP ECCENTRICALLY OR CONCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBE TO AT EACH END. THE FRAMED OPENING IN THE WALL SHALL BE 4 TO 6 IN. (102 TO 152 MM) WIDER
METAL CONTROL JOINT
BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. THE FOLLOWING TYPES AND AND 4 TO 6 IN. (102 TO 152 MM) HIGHER THAN THE DIAM OF THE PENETRATING ITEM SUCH
SIZES OF NONMETALLIC PIPES, CONDUITS AND TUBES MAY BE USED: THAT, WHEN THE PENETRATING ITEM IS INSTALLED IN THE OPENING, A 2 TO 3 IN. (51 TO 76 MM)
A. POLYVINYL CHLORIDE (PVC) PIPE - NOM 2 IN. (51 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID CLEARANCE IS PRESENT BETWEEN THE PENETRATING ITEM AND THE FRAMING ON ALL FOUR SIDES.
OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN,
15mm GAP 40mm TYPE S WASTE OR VENT) PIPING SYSTEMS. ANNULAR SPACE SHALL BE MIN 0 IN. ( 0 MM, POINT B. GYPSUM BOARD* - 5/8 IN. (16 MM) THICK, 4 FT (1.22 M) WIDE WITH SQUARE OR TAPERED
SCREWS, CONTACT) TO MAX 1 IN. (25 MM). EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND
600mm OC. B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 2 IN. (51 MM) DIAM (OR SMALLER) SDR SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES
STEEL STUD 13.5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS. ANNULAR DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 26 IN. (660 MM)
SPACE SHALL BE MIN 0 IN. ( 0 MM, POINT CONTACT) TO MAX 1 IN. (25 MM). FOR STEEL STUD WALLS. MAX DIAM OF OPENING IS 14-1/2 IN. (368 MM) FOR WOOD STUD WALLS.
C. RIGID NONMETALLIC CONDUIT+ - NOM 2 IN. (51 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF
TWO 15mm TYPE X GYPSUM
CONDUIT INSTALLED IN ACCORDANCE WITH ARTICLE 347 OF THE NATIONAL ELECTRICAL CODE THE WALL ASSEMBLY IN WHICH IT IS INSTALLED.
BOARD STRIPS
(NFPA 70). ANNULAR SPACE SHALL BE MIN 0 IN. ( 0 MM, POINT CONTACT) TO MAX 1 IN. (25 MM).
D. ELECTRICAL NONMETALLIC TUBING+ - NOM 2 IN. (51 MM) DIAM (OR SMALLER) PVC TUBING 2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER
INSTALLED IN ACCORDANCE WITH ARTICLE 331 OF THE NATIONAL ELECTRICAL CODE (NFPA 70). CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR
ANNULAR SPACE SHALL BE MIN 0 IN. ( 0 MM, POINT CONTACT) TO MAX 1 IN. (25 MM). TUBING MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEGREES FROM
1-HOUR NON COMBUSTIBLE E. CROSS LINKED POLYETHYLENE (PEX) TUBING - NOM 1 IN. (25 MM) DIAM (OR SMALLER) SDR9 PERPENDICULAR. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF
PEX TUBING FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS. ANNULAR SPACE OPENING SHALL BE MIN 0 IN. (0 MM, POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR
SHALL BE MIN 0 IN. ( 0 MM, POINT CONTACT) TO MAX 1 IN. (25 MM). TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING
F. ACRYLONITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 1-1/2 IN. (38 MM) DIAM (OR SMALLER) TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
SCHEDULE 40 SOLID-CORE OR CELLULAR CORE ABS PIPE FOR USE IN CLOSED (PROCESS OR
SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS. ANNULAR SPACE SHALL BE A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
MIN 1/4 IN. (6 MM) TO MAX 3/4 IN. (19 MM). B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
WHEN ITEM 2A OR 2B IS USED, THE T RATING IS 1/4 HR. WHEN ITEM 2C, 2D, OR 2E IS USED, C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING, NOM
THE T RATING IS 1 HR AND 1-3/4 HR FOR 1 HR AND 2 HR FIRE RATED WALLS, RESPECTIVELY. 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 1 IN. (25 MM) DIAM (OR SMALLER)
WHEN ITEM 2F IS USED, T RATING IS 0 HR. FLEXIBLE STEEL CONDUIT.
3. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN. (16 MM) THICKNESS OF FILL MATERIAL D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL ASSEMBLY. AT POINT CONTACT E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
LOCATION, MIN 1/4 IN. (6 MM) DIAM BEAD OF FILL MATERIAL APPLIED AT NONMETALLIC
PIPE/GYPSUM BOARD INTERFACE ON BOTH SURFACES OF WALL. 3. FILL, VOID OR CAVITY MATERIAL* - SEALANT MIN 5/8 IN. (16 MM) THICKNESS OF FILL MATERIAL
APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT
SPECIFIED TECHNOLOGIES INC - SPECSEAL LCI SEALANT LOCATION BETWEEN THROUGH PENETRANT AND GYPSUM BOARD, A MIN 3/8 IN. (10 MM) DIAM BEAD
OF FILL MATERIAL SHALL BE APPLIED AT THE GYPSUM BOARD/THROUGH PENETRANT INTERFACE
*BEARING THE UL CLASSIFICATION MARK ON BOTH SURFACES OF WALL.

SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, 101, 102 OR 105 SEALANT


*BEARING THE UL CLASSIFICATION MARK

FIRE RATED CONTROL JOINTS1 5 FIRESTOPPING @ NON-METALLIC PIPE PENETRATION1 3 FIRESTOPPING @ METALLIC PIPE PENETRATION1 2 5
4
09/12/2016
23/11/2016
ISSUED FOR CONTRACT (PACK 1)
DRAWING PACKAGE 1
SCALE: 1 : 5 SCALE: 1 : 5 SCALE: 1 : 10
3 18/11/2016 ISSUE FOR PRICING & CONSTRUCTION
(DRAWING PACKAGE 2)
2 04/11/2016 AMS01 PHASE 2 (DRAWING PACKAGE 1)
1 26/10/2016 ISSUE FOR OWNERS REVIEW 95%
rev date revision note

SYSTEM NO. W-L-3369 SYSTEM NO. W-L-3218


Aldgate House
33 Aldgate High Street
London EC3N 1AH
F RATINGS - 1 AND 2 HR (SEE ITEM 1) F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 1 AND 3) UK
Tel (0)20 7073 9600
T RATINGS - 1 AND 2 HR (SEE ITEM 1) T RATINGS - 3/4 AND 1 HR (SEE ITEM 3) Fax (0)20 7539 1917
L RATING AT AMBIENT - LESS THAN 1 CFM/DEVICE L RATING AT AMBIENT - 4 OR 7 CFM (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/DEVICE
A L RATING AT 400 F - 2 OR 3 CFM (SEE ITEM 3)
2
2
CLIENT
3

1A

1B
2
EdgeConneX Inc.
3 2201 Cooperative Way, Suite 200
Herndon, VA 20171
3
1A 1B
Tel +01 866.304.3217
A
SECTION A-A
CLIENT'S CONSULTANT
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL 3. CABLES - WITHIN THE LOADING AREA FOR EACH FIRESTOP DEVICE MODULE, THE CABLES MAY
BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED WITHIN THE INDIVIDUAL REPRESENT A 0 TO 100 PERCENT VISUAL FILL. CABLE FILL TO BE DISTRIBUTED AT A UNIFORM
1. WALL ASSEMBLY - THE 1 OR 2 HR FIRE RATED BYPSUM BOARD/STUD WALL ASSEMBLY U300, U400 OR V400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE HEIGHT ACROSS THE WIDTH OF THE FIRESTOP DEVICE MODULE. CABLES TO BE RIGIDLY
SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE DIRECTORY AND SHALL INCORPORATE THE FOLLOWING CONSTRUCTION FEATURES: SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. ANY COMBINATION OF THE FOLLOWING
INDIVIDUAL U300, U400 OR V400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE A. STUDS - WALL FRAMING SHALL CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. TYPES OF CABLES MAY BE USED:
RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED MAX 16 IN. (406
FEATURES: MM) OC. STEEL STUDS TO BE MIN 3-1/2 IN. (89 MM) WIDE AND SPACED MAX 24 IN. (610 MM) OC. A. MAX 400 PAIR NO. 24 AWG (OR SMALLER) COPPER CONDUCTOR TELECOMMUNICATION CABLE
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL B. GYPSUM BOARD* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS SPECIFIED IN WITH POLYVINYL CHLORIDE (PVC) JACKETING AND INSULATION.
STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED THE INDIVIDUAL WALL AND PARTITION DESIGN. OPENING IN GYPSUM BOARD TO BE MAX 1/4 IN. B. MAX 350 KCMIL SINGLE COPPER CONDUCTOR POWER CABLE WITH XLPE JACKET AND INSULATION WOOLVERSTONE HOUSE
16 IN. (406 MM) OC. STEEL STUDS TO BE MIN 3-1/2 IN. (89 MM) WIDE AND SPACED MAX (6 MM) LARGER THEN WIDTH AND HEIGHT DIMENSIONS OF FIRESTOP DEVICE(S). C. MAX 7/C NO. 12 AWG COPPER CONDUCTOR CONTROL CABLE WITH PVC OR XLPE JACKET AND INSULATION. 61 BERNERS STREET
24 IN. (610 MM) OC. D. MAX 3/C NO. 10 AWG METAL CLAD OR ARMORED CABLE WITH STEEL OR ALUMINUM JACKET. LONDON
B. GYPSUM BOARD* - 5/8 IN. (16 MM) THICK, 4 FT (1.2 M) WIDE WITH SQUARE OR TAPERED THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY RATING OF THE E. MAX 3/C NO. 8 AWG NM CABLE (ROMEX) WITH PVC INSULATION AND JACKET.
WALL IN WHICH IT IS INSTALLED. F. MAX FOUR PAIR NO. 22 AWG (OR SMALLER) COPPER CONDUCTOR DATA CABLE WITH PVC OR W1T 3NJ
EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER
TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300, U400 PLENUM RATED JACKETING AND INSULATION.
OR V400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. 2. FIRESTOP DEVICE* - ONE, TWO, THREE, FOUR OR SEVEN FIRESTOP DEVICE MODULES GANGED G. MAX RG/U COAXIAL CABLE WITH FLUORINATED ETHYLENE INSULATION AND JACKETING. Tel: 0207 0433410
THE HOURLY F AND T RATINGS OF THE FIRESTOP SYSTEM ARE EQUAL TO THE TOGETHER. EACH FIRESTOP DEVICE MODULE CONSISTS OF A 3 BY 3 BY 10-1/2 IN. (76 BY 76 BY 267 H. FIBER OPTIC CABLE WITH PVC OR POLYETHYLENE (PE) JACKET AND INSULATION HAVING A MAX
HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. MM) LONG GALV STEEL TUBE WITH AN INTUMESCENT MATERIAL LINING. FIRESTOP DEVICE DIAM OF 5/8 IN. (16 MM).
2. CABLE - MAX 4 PAIR NO. 22 AWG (OR SMALLER) COPPER CONDUCTOR DATA CABLE WITH MODULES TO BE INSTALLED IN ACCORDANCE WITH THE ACCOMPANYING INSTALLATION I. OPTICAL FIBER RACEWAY+ - MAX 1-1/2 IN. (38 MM) DIAM (OR SMALLER) OPTICAL FIBER
PVC INSULATION AND JACKET. ONE CABLE TO BE ROUTED INTO STUD CAVITY THROUGH INSTRUCTIONS. THE SPACE BETWEEN THE FIRESTOP DEVICE MODULE(S) AND THE PERIPHERY OF RACEWAY ("INNERDUCT") FORMED OF EITHER PVC OR POLYVINYLIDENE FLUORIDE (PVDF) WITH
9/16 IN. (14 MM) DIAM HOLE DRILLED THROUGH GYPSUM BOARD ON ONE SIDE OF WALL. THE OPENING SHALL BE MIN 0 IN. ( 0 MM, POINT CONTACT) TO MAX 1/8 IN. (3.2 MM). FIRESTOP OPTICAL FIBER CABLE FILL. RACEWAYS INSTALLED IN ACCORDANCE WITH ARTICLE 770 OF THE key plan
3. FIRESTOP DEVICE* - DEVICE CONSISTING OF PLASTIC GROMMET HALVES WITH FOAM DEVICE MODULE(S) SECURED IN PLACE BY MEANS OF STEEL WALL PLATES INSTALLED WITH NATIONAL ELECTRICAL CODE (NFPA 70).
INSERTS. PLASTIC GROMMET DEVICE SHALL BE INSTALLED AROUND CABLE AT IT'S GASKETING MATERIAL SUPPLIED WITH PRODUCT. STEEL WALL PLATES INSTALLED ON BOTH SIDES
EGRESS FROM THE GYPSUM BOARD WALL AND INSERTED IN WALL OPENING IN OF WALL AND SECURED TO EACH DEVICE BY MEANS OF STEEL SET SCREWS PROVIDED WITH WHEN THE HOURLY RATING OF THE WALL ASSEMBLY IS 1 HR, THE T RATING IS 3/4 HR. WHEN THE DATA HALL 3
ACCORDANCE WITH THE ACCOMPANYING INSTALLATION INSTRUCTIONS. DEVICE. EACH FOUR- AND SEVEN-GANG STEEL WALL PLATE SHALL BE FASTENED TO THE STUDS HOURLY FIRE RATING OF THE WALL ASSEMBLY IS GREATER THAN 1 HR, THE T RATING IS 3/4 HR WHEN
WITH STEEL SCREWS SIZED TO EXTEND THROUGH THE GYPSUM BOARD LAYERS AND PENETRATE ITEM 3A, 3B, 3C, 3D OR 3E IS USED. OTHERWISE THE T RATING IS 1 HR. WHEN ITEM 3A, 3B, 3C, 3D OR 3E
SPECIFIED TECHNOLOGIES INC - READY FIRESTOP GROMMET RFG1 1/2 IN. (13 MM) INTO THE FRAMING MEMBER. EACH FIRESTOP DEVICE MODULE IS TO BE INSTALLED IS USED, THE MAXIMUM F RATING IS 2 HR. WHEN MAX 200 PAIR NO. 24 AWG TELECOMMUNICATION
WITH ENDS PROJECTING AN EQUAL DISTANCE BEYOND EACH SURFACE OF THE WALL ASSEMBLY. CABLE IS USED OR WHEN ITEM 3F, 3G, 3H OR 3I IS USED, THE MAXIMUM F RATING IS 4 HR.
DATA HALL 1
*BEARING THE UL CLASSIFICATION MARK
AS AN ALTERNATE, THE FOUR- AND SEVEN-GANG STEEL WALL PLATES MAY BE INSTALLED DIRECTLY WHEN ITEM 3A IS USED, THE L RATING FOR EACH FIRESTOP DEVICE WITH 100 PERCENT VISUAL FILL IS True North
AGAINST THE STUDS FOR WALLS HAVING 16 AND 24 IN. (406 AND 610 MM) CENTER-TO-CENTER STUD 4 CFM AT AMBIENT AND 3 CFM AT 400F. WHEN ITEM 3F, 3G, OR 3H IS USED, THE L RATING FOR EACH
SPACING, RESPECTIVELY, PRIOR TO INSTALLATION OF THE GYPSUM BOARD LAYERS. THE STEEL WALL FIRESTOP DEVICE WITH 100 PERCENT VISUAL FILL IS 7 CFM AT AMBIENT AND 2 CFM AT 400F. OFFICE
PLATES SHALL BE SECURED TO THE STUD BY MEANS OF STEEL SCREWS. AFTER INSTALLATION OF THE N
STEEL WALL PLATES AND FIRESTOP DEVICE MODULES, THE GYPSUM BOARD SHALL BE INSTALLED AS 4. FILL, VOID OR CAVITY MATERIAL* - SEALANT OR PUTTY - (NOT SHOWN) - AS AN ALTERNATE TO
SPECIFIED IN THE INDIVIDUAL U300 OR U400 DESIGN WITH A MAXIMUM 1/8 IN. (3.2 MM) GAP BETWEEN GYPSUM JOINT COMPOUND, THE GAP BETWEEN THE FIRESTOP DEVICE MODULE AND THE CUTOUT project status
THE FIRESTOP DEVICE MODULE AND THE CUTOUT IN THE GYPSUM BOARD. GAP BETWEEN THE IN THE GYPSUM BOARD MAY BE SEALED WITH FILL MATERIAL ON EACH SIDE OF THE WALL
FIRESTOP DEVICE MODULE AND THE CUTOUT IN THE GYPSUM BOARD MAY BE FILLED WITH GYPSUM ASSEMBLY WHEN FOUR- AND SEVEN-GANG STEEL WALL PLATES ARE INSTALLED DIRECTLY ISSUED FOR CONTRACT (PACK 1)
JOINT COMPOUND OR FILL MATERIAL (ITEM 4). AGAINST THE WOOD OR STEEL STUDS.

SPECIFIED TECHNOLOGIES INC - EZ PATH SERIES 33 FIRE RATED PATHWAY SPECIFIED TECHNOLOGIES INC - SPECSEAL SERIES SSS SEALANT, SPECSEAL LCI SEALANT, SPEC SEAL PUTTY project
EdgeConnex - Amsterdam, Netherlands
2A. FIRESTOP DEVICE* - EXTENSION MODULE - (OPTIONAL, NOT SHOWN) - MODULE ATTACHED TO *BEARING THE UL CLASSIFICATION MARK
ENDS OF 3 BY 3 BY 10-1/2 IN. (76 BY 76 BY 267 MM) LONG FIRESTOP DEVICE (ITEM 3) TO INCREASE Koolhovenlaan 12, 1119 NE Schiphol-Rijk, NL
ITS LENGTH TO FACILITATE INSTALLATION IN THICKER WALLS. EACH MODULE CONSISTS OF A 3 BY
project no
3 BY 6 IN. (76 BY 76 BY 152 MM) LONG GALV STEEL TUBE WITH AN INTUMESCENT MATERIAL LINING.
EXTENSION MODULE TO BE INSTALLED IN ACCORDANCE WITH THE ACCOMPANYING INSTALLATION 08.7142.000
INSTRUCTIONS. WHEN MODULE IS USED, FIRESTOP DEVICE (ITEM 2) AND EXTENSION MODULE(S) scale date drawn checked
SECURED IN PLACE BY MEANS OF STEEL WALL PLATES INSTALLED WITH GASKETING MATERIAL As indicated @ A0 04/11/16 TS WR
SUPPLIED WITH PRODUCT. STEEL WALL PLATES INSTALLED ON BOTH SIDES OF WALL AND sheet number
SECURED TO EACH DEVICE OR EXTENSION MODULE(S) BY MEANS OF STEEL SET SCREWS
PROVIDED WITH WALL PLATES. FIRESTOP DEVICE AND EXTENSION MODULE(S) ASSEMBLY TO BE
INSTALLED WITH ENDS PROJECTING AN EQUAL DISTANCE BEYOND EACH SURFACE OF THE WALL
ASSEMBLY.
A12.31
title
SPECIFIED TECHNOLOGIES INC - EZ PATH EXTENSION

FIRE STOPPING DETAILS

FIRESTOPPING @ SINGLE CABLE PENETRATION1 4


SCALE: 1 : 5
FIRESTOPPING @ MULTI-CABLE PENETRATION1 1
SCALE: 1 : 5

C GENSLER 2015
All rights reserved, including but not limited to The Copyright, Design and Patents Act 1988