Floored: Insulation

resistance meter tests for


electrostatic discharge Application Note

Manufacturers of electronic Static dissipative flooring


systems and devices go to great
lengths to protect their equip- When Computerstate Systems
Testing ment and products from electro- of Calgary, a manufacturer of
embedded systems for the oil and
Functions static discharge (ESD) damage.
gas, global positioning and com-
The cost of ESD-damagerepair
Case and rework, shipping, labour, munications industries, moved
facilities last year, the company
Study overhead, and loss of production
hired Diamond Hard Surfaces
timeranges from a few cents for
a simple component to several Inc, a local concrete coatings
hundred dollars for complex de- and specialty concrete flooring
vices. Most technical personnel in company, to apply an ESD floor
the electronics industry have ESD coating system.
protection processes in place for After a client interview,
both the factory and field. Diamond Hard President Walt
Curilla, P.Eng. had a clear idea of
Electrostatic dangers the appropriate polymer coatings
for the jobthe only question
When a statically-charged person was how to accurately measure
or object touches an ESD sensi- the resistance the coating would
tive device, the electrostatic provide, so that he could sub-
charge can be drained through stantiate the reduction of static
sensitive circuitry in the device. discharge to an acceptable dis-
If the electrostatic discharge sipative level. Curilla found the
possesses sufficient energy, answer in the Fluke 1520 insula-
localized overheating can tion resistance tester.
damage the device. Typically, an insulation
Two kinds of damage may resistance meter is used for
Measuring tools: Fluke 1520 result: testing motor wiring or electri-
1. Catastrophic damage, where cal distribution systems for fault
Insulation Resistance Tester* the electronic device is ren- conditions. Since all insulation
dered inoperable immediately degrades over time, insulation
after the ESD event resistance meters are helpful for
Operator: Diamond Hard 2. Latent damage, where the monitoring wiring conditions
Surfaces Inc., Calgary electronic device appears to and scheduling maintenance in
be working fine but has been advance of failure.
damaged nonetheless and When it comes to static
Inspections: Resistance (Ohms) could fail to operate properly dissipative flooring however,
at some time in the future. Curilla discovered that insulation
To protect against ESD, manufac- resistance meters are also adept
turers advocate wearing smocks at measuring resistance between
on the production floor and us- two points. For example, the
ing ESD protective wrist straps, average distance between the
antistatic work shoes, and static feet of a worker walking across
dissipative flooring. the production floor.

*Note: The Fluke 1520 has been replaced by


the Fluke 1507/1508 Insulation Testers.
Systematic testing Follow up
The Fluke Family of
To gather measurements, Curilla Being able to confirm levels of Insulation Resistance
placed 5 lb weights three feet ESD protection should bring
apart, an industry specification additional assurance to contract Testers
for measuring resistance on the electronics manufacturers and
floor. His team wrapped tin foil OEMs. Without testing the re- Fluke Insulation Resistance Testers
around the weights and applied sistance, we wouldnt be doing a measure resistance, primarily to
shaving cream and water as service to the client, Curilla says. determine the integrity of windings
conductors under the weights. Wed be taking many, many or cables in motors, transformers,
There is a bit of black art to it, chances. switchgear, and electrical installa-
Curilla says. Then, the meter For example, whether were tions.
applied 500 volts to measure installing dissipative / conduc- The newest models are the Fluke
resistance. tive coating or tile systems, how 1507 and 1503. Theyre smaller than
We needed to sample ten would the client know that their previous units, and offer multiple
test points after each layer was protective floor system works test voltages for troubleshooting,
applied: Carbon black epoxy and after it has been installed, if the commissioning, and preventative
polyurethane protective layers, installer did not test the floor be- maintenance applications. They
Curilla explained. That way, the fore, during or after installation? also include a remote probe, for
flooring installers could repair More importantly, how does the rapid multi-point testing.
any local anomalies, if neces- client know if their janitorial staff The Fluke 1587 and 1577 Insula-
sary, for each coating layer until are properly maintaining the tion Multimeters combine a 1 kV
the work-in-progress system clients floor six months, twelve digital insulation tester with a full-
achieved the expected resistance months or five years later? One featured True-RMS digital multimeter
values. (Acceptable readings in bad wax job can spoil your floors in a single, handheld device.
ohms are defined by an electro- performance. The Fluke 1550B is a more power-
static safety standard: conductive An ESD flooring system is like ful tester capable of testing up to
is under one megohm; dissipative a fire extinguisher or any other 5 KV. The Fluke 1520 MegOhmMeter
is one megohm to one gigohm). life safety device: Without regular 1 KV insulation resistance tester also
For instance, the testers proper testing, you will not know measures voltage and checks connec-
measurements showed the if your protective system will tions with its Lo-Ohms function.
installers which areas needed function per the original dissipa-
light sanding to lessen resistance. tive / conductive design intent
Grinding off any undesirable unless you test it regularly.
insulative barrier increases the
floors conductivity, dissipating
the static electricity that a person
walking across the floor could
otherwise build to unacceptable
levels with each step.
This type of floor testing
cannot be done with a standard
multi-meter. A megohmeter that
can apply a specified voltage
across the measured surface was
needed. Without the insulation
resistance meter, there would Fluke. Keeping your world
have been no way to do the test- up and running.
ing, said Curilla.
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
2006, 2007 Fluke Corporation. All rights reserved.
Specifications subject to change without notice.
Printed in U.S.A. 4/2007 2674023 A-EN-N Rev B

 Fluke Corporation Floored: Insulation resistance meter tests for electrostatic

You might also like