You are on page 1of 12

Construction and Building Materials 145 (2017) 135146

Contents lists available at ScienceDirect

Construction and Building Materials


journal homepage: www.elsevier.com/locate/conbuildmat

Effect of freeze-thaw cycles on concrete reinforced with basalt-fiber


reinforced polymers (BFRP) bars
Mohamed-Akram Khanfour, Ahmed El Refai
Department of Civil and Water Engineering, Laval University, Quebec City, Quebec G1V 0A6, Canada

a r t i c l e i n f o a b s t r a c t

Article history: This paper examines the performance of concrete beams internally reinforced with basalt fiber-
Received 30 November 2016 reinforced polymers (BFRP) bars after being subjected to freeze-thaw (FT) cycles. Prior to beam testing,
Received in revised form 23 March 2017 pullout specimens were tested after being exposed to 100 and 200 FT cycles and to a freezing tempera-
Accepted 30 March 2017
ture of 20 C. The pullout test results showed that FT cycles had a slight effect on the bond strength of
the BFRP bars. Both unconditioned and conditioned specimens showed similar bond stress-slip relation-
ships and comparable bond strengths. Exposing the pullout specimens to low temperature resulted in a
Keywords:
decrease of 10% in their bond strength. In the beam tests, half of the beams were subjected to 200 FT
Basalt fiber-reinforced polymers
Concrete beams
cycles prior to testing whereas the remaining beams were tested at room temperature. The test param-
Bond eters included the reinforcement ratio, the shear span-to-depth ratios, a/d, and the environmental
Cold regions conditioning. It was observed that conditioning changed the mode of failure of some of the tested beams
Concrete as compared to that of their unconditioned counterparts. The effect of conditioning on the failure
Conditioning mode was less pronounced in the over-reinforced beams with a/d > 2.5. Conditioning under- and
Durability over-reinforced beams with a/d = 2.5 resulted in reductions of 7.4 and 13.4%, respectively, in their load
Flexure carrying capacities. FT conditioning had a slight effect on the ductility of the tested beams regardless
Freeze-thaw
of their a/d ratio or their internal reinforcement.
Pullout
2017 Elsevier Ltd. All rights reserved.
Tensile

1. Introduction and background strength depending on the absorption characteristics of the com-
posite whereas the exposure to elevated temperatures insignifi-
Concrete structures reinforced with fiber-reinforced polymer cantly affected the bond strength of the bars. In another study,
(FRP) bars may suffer severe degradation when exposed to harsh Altalmas et al. [2] reported on the bond strength of BFRP bars
environments. Concerns about the durability of FRP-reinforced exposed to acid, saline, and alkaline environments for 30, 60, and
structures are legitimate with the development of new types of 90 days. It was reported that the pullout specimens immersed in
resins and composites that have not been tested in the field. saline and alkaline solutions for 90 days exhibited 25% reduction
Recently, basalt fibers have emerged as alternatives to the conven- in their bond strength compared to 14% for specimens immersed
tional, wide-spread, glass fibers to form a new type of bars, the in acid solution. The inter-laminar shear between the FRP layers
basalt FRP (BFRP) bars. Following this evolution, several studies governed the failure of both unconditioned and conditioned spec-
have reported on the feasibility of use and the durability of the imens rather than the shear stress between the bar and concrete.
BFRP bars [10,11,14,12,16,18,20]. El Refai et al. [10] reported on On the other hand, the effect of freeze-thaw (FT) environment
the bond durability of different types of BFRP bars after being con- on the durability of FRP-reinforced structures have received little
ditioned with tap water, seawater, elevated temperature, and a attention in the literature. When subjected to FT cycles, concrete
combination of these environments. It was reported that the bond is saturated with water during the thawing phase. When water
stress-slip response was governed by the surface treatment of the freezes, it expands and develops high pressure in the concrete
bar and its manufacturing quality. The authors concluded that pores. The induced stresses may exceed the tensile strength of con-
moister environments had a detrimental effect on the bond crete leading to the formation of surface and internal cracks. War-
deh et al. [21] reported on the effect of FT cycles on concrete.
Concrete cylinders (160  320 mm) were exposed to FT cycles
Corresponding author.
between 20 C and 10 C. It was reported that the number of
E-mail addresses: mohamed-akram.khanfour.1@ulaval.ca (M.-A. Khanfour),
ahmed.elrefai@gci.ulaval.ca (A. El Refai).
cracks recorded on the concrete surface significantly increased

http://dx.doi.org/10.1016/j.conbuildmat.2017.03.237
0950-0618/ 2017 Elsevier Ltd. All rights reserved.
136 M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146

with the increasing number of cycles. The cracks became visible caused by low temperature could initiate bond failure in structures
after 60 cycles. Concrete cylinders lost 20% and 60% of their com- subjected to long periods of low temperature.
pressive strength after 30 cycles and 240 cycles, respectively. This paper reports on the bond durability of BFRP bars after
FT cycles may have detrimental effects on the mechanical prop- being exposed to cold environments (FT cycles and low tempera-
erties of the FRP bars. When the bars are subjected to moisture ture). It also reports on the performance of BFRP-reinforced con-
during FT cycles, water diffuses through the FRP matrix. Depending crete beams exposed to FT cycles and monotonically tested up to
on the resin type, the manufacturing quality, and the surrounding failure. In the first fold, pullout tests were carried out on uncondi-
temperature, deterioration in the resin may occur [19,13]. Bank tioned and conditioned concrete cylinders reinforced with BFRP
et al. [4] observed that the absorbed water molecules expanded bars. Failure mechanism and bond-slip relationships are presented.
during the freezing phase. The increase in volume resulted in radial In the second fold, the failure modes, the ultimate capacities, and
and circumferential cracks and consequently, additional water was the ductility of the tested beams are presented.
absorbed inside the matrix. With the subsequent cycles of FT,
cracks increased in number and width and the expansion process
continued, which resulted in a failure phenomenon whereby the 2. Bond test program
core of unidirectional fibers was debonded from the outer surface
of the bars causing part of the bar to be pulled out of concrete The matrix of the bond test program is shown in Table 1. Thirty-
under low applied forces [4]. six pullout specimens were prepared according to ACI 440.3R-04
Moreover, FRP bars have a higher coefficient of thermal expan- provisions [1]. The specimens consisted of standard concrete cylin-
sion (CTE) than that of concrete. When subjected to FT cycles, the ders of 150  300 mm concentrically reinforced with BFRP bars of
FRP bar is exposed to an elongated period of freezing temperature 8, 10, and 12 mm diameters. All of the test specimens had a bond
that causes higher contraction in the bar than in concrete. The length, Ld, equal to 7 times the bar diameter, db, to ensure bond fail-
developed gaps between the bar and concrete resulted in loss of ure between the BFRP bar and the surrounding concrete. Plastic
bond between the two materials [15,5]. tubes were placed at the top of the embedded portion of the bar
In an attempt to evaluate the bond durability of FRP bars, to act as bond breakers.
Alvarez [3] exposed 50 cylinders (150  300 mm) to 100 and 200 The test matrix comprised four groups of specimens that were
FT cycles (2 cycles/day between 20 C and 20 C at 70% relative categorized based on the exposure environment prior to testing.
humidity). The author reported that FT cycles had no effect on Group A consisted of nine unconditioned specimens that served
the bond strength values except for the glass FRP (GFRP) bar of as controls. Groups B and C included eighteen specimens (nine
19.1 mm diameter that showed a reduction in bond strength of specimens each) that were subjected to 100 and 200 FT cycles,
15% after 200 FT cycles. Davalos et al. [9] exposed 12 cylinders respectively, at a rate of 2 cycles per day as shown in Fig. 1a. Each
(100  200 mm) to 30 FT cycles (1 cycle/day between 20 and FT cycle consisted of a freezing phase at 25 C and a thawing
60 C) reinforced with GFRP and Carbon FRP (CFRP) bars. The phase at 15 C. The freezing temperature was attained in 2 h
authors concluded that the free-end slip of the pullout test speci- approximately and lasted for 5 h while the thawing temperature
mens increased and the bond strength reduced by about 18% after was attained in 2 h and remained constant for 3 h. The humidity
exposure. In another study, Saiedi et al. [17] tested five CFRP- of the environmental chamber was maintained at 50% during the
prestressed concrete beams (300  500  4400 mm) under fatigue FT period. Group D included nine conditioned specimens that were
loading at 28 C. All specimens were monotonically loaded to exposed to a constant freezing temperature of 20 C for 240 h.
failure after being cycled. The results showed that low temperature The specimens were tested under uniaxial pullout force as
caused an initial slip between the bars and concrete, which shown in Fig. 2. All specimens were instrumented with three linear
occurred at loads ranging between 70% and 90% of the ultimate variable displacement transducers (LVDT) during testing. Two
capacity of the beams. The authors concluded that the initial slip LVDTs were used to record the bar slip relative to the concrete

Table 1
Bond test matrix and results.

Specimena No. of specimens db, ld, smax smax,fe smax,le sa, le


mm mm (MPa) (mm) (mm) MPa
Group A Unconditioned pullout specimens
B8 3b 8 56 16.6 0.1 0.6 0.6
B10 3 10 70 16.6 0.2 0.7 0.4
B12 3 12 84 14.7 0.1 0.8 0.1
Group B Pullout specimens conditioned under 100 FT cycles
B8-FT100 3 8 56 17.2 0.2 0.8 0.3
B10-FT100 3 10 70 18.2 0.1 0.8 0.3
B12-FT100 3c 12 84 19.7 0.2 1.0 0.1
Group C Pullout specimens conditioned under 200 FT cycles
B8-FT200 3 8 56 18.7 0.1 0.9 0.4
B10-FT200 3 10 70 16.8 0.1 0.6 0.3
B12-FT200 3 12 84 15.3 0.1 0.7 0.2
Group D Pullout specimens conditioned under low temperature
B8-LT 3 8 56 15.6 0.2 1.0 0.1
B10-LT 3 10 70 15 0.4 0.9 0.1
B12-LT 3 12 84 16 0.2 1.3 0.1

smax = maximum bond stress, smax,N = normalized maximum bond stress, smax,le and smax,fe = slip corresponding at maximum stress at loaded and unloaded ends, respectively.
a
FT = freeze-thaw; 100 and 200 = number of FT cycles; LT = low temperature.
b
One specimen failed by concrete splitting.
c
Two specimens failed by concrete splitting.
M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146 137

Table 2
Concrete mix constituents.

Constituent Quantity (kg/m3)


Portland cement 474
Water 211
Coarse aggregate (14 mm) 381.5
Coarse aggregate (10 mm) 230.5
Fine aggregates 912
Air entraining agent 85.5
Super-plasticizer 94.7

Table 3
Nominal and actual diameters of BFRP bars.

Nominal diameter (mm)a Bar diameter


8.00 10.00 12.00
Measured diameter (mm)b 8.63 10.20 12.42
a
Reported by the manufacturer.
b
Measured using the Archimedes method.

Table 4
Mechanical properties of BFRP bars as reported by the manufacturers.

Average tensile strength (MPa) Ultimate strain (%) Elastic modulus (GPa)
1150 2.39 48

2.1. Materials

The concrete mix used to cast the pullout specimens is given in


Table 2. The mix had a maximum aggregate size of 14 mm and a
water-cement ratio of 0.45. Commercial admixture was used to
increase the workability and to minimize the water-cement ratio
Fig. 1. (a) Freeze-thaw cycles adopted in this study and (b) thermocouple readings in the mix. The measured slump during casting was 110 mm. After
during one day of freeze-thaw conditioning (2 cycles). de-moulding, the cylinder specimens were stored into a curing
room at a temperature of 20 C 2 C and a humidity of about
95% for 28 days. Concrete compressive strength of 49 MPa was
surface at the unloaded (free) end while the other LVDT recorded achieved after 28 days of curing.
the slip at the loaded ends. A data acquisition system was used Table 3 shows the nominal and actual diameters of the BFRP
to record the applied load and the corresponding slip at a rate of bars used. The mechanical properties of the bars as reported by
5 readings per second. the manufacturers are given in Table 4. The BFRP bars used were

Test setup Free end


BFRP bar
Lower
Loaded end LVDTs

Loaded end

Top
Free end LVDT

Fig. 2. Pullout test setup.


138 M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146

Delamination of the
outer layer

8 mm

Traces of resin
10 mm

12 mm

Fig. 3. BFRP bars used in this study. Fig. 4. Typical mode of failure of unconditioned and conditioned specimens
(specimen B10-FT100).

sand-coated on their surfaces and had shallow spiral indentations


spaced at 2.75 mm along their length as shown in Fig. 3. No apparent damage to concrete surrounding the bar was
Concrete cylinders were subjected to the same environmental observed. These findings suggest that bond failure took place along
conditioning as the pullout specimens to assess the effect of FT the interfacial shear surface between the grained layer and the
cycles and the freezing temperature on the compressive strength subsequent core layers of the bar. Failure was therefore governed
0
of concrete, f c. Some cylinders were internally instrumented with by the shear strength along the fibres interface rather than the
thermocouples to measure the variation in concrete temperature shear strength between the bar and concrete. This finding indicates
during the FT cycles. Readings of the thermocouples during a rep- the negligible effect of conditioning on the bond mechanism and
resentative day (2 cycles/day) can be depicted in Fig. 1b. An the mode of failure of the tested specimens.
increase of 7.5 and 11.5% in fc was observed after exposure to
100 and 200 FT cycles, respectively. This increase in strength was 3.2. Bond stress-slip response
attributed to the further curing during conditioning. Concrete
cylinders subjected to constant freezing temperature showed no The plots in Figs. 5 and 6 show the bond stress-slip curves of
variation in their compressive strengths. Table 5 shows the unconditioned and conditioned sample specimens at their
0
recorded values of fc before and after conditioning. unloaded and loaded ends, respectively. It is important to note that
these plots do not show the average results listed in Table 1 and
3. Bond test results therefore are not intended to be used in comparing the bond
parameters of the tested specimens.
The bond test results are listed in Table 1. Each listed value rep- Similar patterns of bond-slip curves are noticed for both uncon-
resent the average result of three tested specimens in each set. The ditioned and conditioned specimens indicating that conditioning
following subsections report on the main bond characteristics had a slight effect on the bond-slip response of the specimens.
observed during the tests. These findings confirmed those of Chen et al. [8] who reported sim-
ilar results for GFRP and CFRP-reinforced pullout specimens sub-
3.1. Failure modes jected to FT cycles. Regardless of the bar diameter, the unloaded
ends of both unconditioned and conditioned specimens showed
All unconditioned and conditioned bars failed in pullout mode almost zero slip until the maximum bond stress was attained
except three specimens of the sets B8-FT100 (1 specimen) and (Fig. 5). A load drop was then observed and the bar slipped until
B12-FT100 (2 specimens) that failed due to splitting of the concrete a fraction of the peak load was attained before slippage continued
cylinder. These specimens were disregarded from subsequent bond with little or no change in the load applied. All unconditioned and
calculations. conditioned specimens showed similar responses at their loaded
At the end of each test, specimens were split to visually assess ends (Fig. 6). No variation in the stiffness of the bars were observed
the condition of the bar and the surrounding concrete. In all of the after conditioning. This was indicated by the similar slopes of the
tested specimens that failed in pullout mode, it was observed that bond stress-slip curves obtained.
the BFRP bar surface was significantly damaged and the outer layer
of the bar was partially peeled off (delaminated) from the 3.3. Bond strength
subsequent bar layers. Fig. 4 shows this mode of failure for
specimen B10-FT100. White powder was detected along the whole Table 1 lists the bond strengths of the tested specimens. The
embedded length of the bar indicating traces of crushed resin. BFRP bars of 8 mm diameter showed a slight increase in their bond

Table 5
Variation in the concrete compressive strength after conditioning.
0 0 0 0
Cylinder f c , MPa (before conditioning) f c , MPa (100 FT cycles) f c , MPa (200 FT cycles) f c , MPa (Low temperature)

1 49.6 52.9 54.8 50.2


2 49.0 53.0 55.3 49.7
3 49.4 53.1 54.9 49.6
Average 49.3 53.0 55.0 49.8
M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146 139

Fig. 5. Bond stress-slip curves of representative samples at unloaded ends. (Note: values of bond stress and slippage are not the average values listed in Table 1).

strengths after conditioning to 100 and 200 FT cycles. BFRP bars of 0.9 mm slip compared to 0.6 mm for the unconditioned ones. BFRP
10 and 12 mm also showed an increase in their bond strengths bars of 10 mm and 12 mm diameter showed that specimens sub-
after 100 FT cycles. After 200 cycles, however, their bond strengths jected to 100 cycles of FT encountered an increase in slip of about
reduced. On the other hand, BFRP bars of 8 and 10 mm diameters 14% while those exposed to 200 FT cycles showed 20% decrease in
conditioned in low temperature showed a slight decrease in their slip occurred. These findings were consistent with the slight
bond strengths whereas those of 12 mm diameter showed a slight increase/decrease in the bond strengths of the conditioned speci-
increase. mens as compared to the bond strengths of their unconditioned
Normalized bond strengths were calculated to offset the varia- counterparts. They also indicated the insignificant effect of the FT
tion in the concrete compressive strength after conditioning. The cycles on the slip of the bars.
normalized strengths were calculated by dividing the obtained On the other hand, BFRP bars of group D having 8, 10, and
strengths by the square root of the corresponding compressive 12 mm diameters showed 67, 29, and 63% increase in average slip-
0
strength, fc. Fig. 7 shows the normalized strengths of all of the page at their loaded ends, respectively, compared to their uncondi-
tested specimens. tioned counterparts. This increase in slippage in the conditioned
It can be noticed that slight variations occurred in the bond specimens was associated with a decrease in the corresponding
strengths after conditioning. Discrepancies in the test results was bond strengths.
indicated by the non-uniform pattern of the data obtained. A max-
imum loss of bond strength of 10% was observed in specimens B10- 3.5. Bar adhesion
LT of group D.
Adhesion of the BFRP bar to concrete is defined as the bond
3.4. Bar slippage stress at onset of slip at the loaded end, that is the stress threshold
at which the adhesion breaks between the bar and concrete. Table 1
Table 1 gives the slip of the unconditioned and conditioned bars summarizes the average adhesion stresses obtained for the uncon-
at peak stresses. Insignificant slip values were encountered at the ditioned and conditioned specimens.
unloaded ends of all of the tested specimens. At the loaded ends, It can be observed that unconditioned BFRP bars of small diam-
the 8 mm diameter bar exposed to 200 FT cycles exhibited eters developed greater adhesion to concrete than those with large
140 M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146

Fig. 6. Bond stress-slip curves of representative samples at loaded ends. (Note: values of bond stress and slippage are not the average values listed in Table 1).

stresses. On the other hand, the 8 and 10 mm bars subjected to


low temperature showed decrease in their adhesion stresses of
83 and 75% of those of their unconditioned counterparts.

4. Beam test program

The beam test program consisted of 12 beams of 1800 mm long


each and a cross section of 152  254 mm as shown in Fig. 8. The
beams were categorized in two groups according to their reinforce-
ment ratios. Group 1 consisted of six beams that were reinforced in
tension with two BFRP bars of 8 mm diameter representing a rein-
forcement ratio of 0.28% (under-reinforced beams) whereas those
of group 2 were reinforced with two BFRP bars of 10 mm diameter
representing a reinforcement ratio of 0.45% (over-reinforced
beams). Half of the beams in each group were exposed to 200
Fig. 7. Effect of conditioning on the normalized bond strengths of the tested cycles of FT whereas the other half acted as controls. Table 6 shows
specimens. the beams test matrix.
All beams were simply supported and tested in a four-point
loading configuration. Three shear span-to-depth ratios, a/d, of
diameters. The 8, 10, and 12 mm diameter BFRP bars showed adhe- 3.1, 2.8, and 2.5 were investigated. The mid-span deflections were
sion stresses of 0.6, 0.4, and 0.1 MPa, respectively (Table 1). Condi- measured by means of a LVDT that was placed at the soffit of the
tioning with FT cycles resulted in a decrease in the adhesion stress beam during testing. All of the tested beams were instrumented
in all of the tested specimens. The 8 mm bar showed a 50% by strain gauges at midspan of the BFRP bars and concrete. A data
decrease in the adhesion stress after 100 FT cycles while the 10 acquisition was used to record the strain and LVDT readings at a
and 12 mm bars showed insignificant changes in their adhesion rate of 5 readings per second.
M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146 141

Fig. 8. Details of the beam specimens.

Table 6
Beam test matrix and results.

Beama a (m) a/d FT cycles Pexp (kN) 0 q Mtheo (kN m) Ptheo (kN) Pexp Failure mode
f c (MPa) qbal Ptheo

Group 1: Under-reinforced beams


U8-3.1 0.68 3.1 77 49.3 0.88 24.3 71.3 1.07 Bar rupture
U8-2.8 0.61 2.8 83 49.3 0.88 24.3 79.5 1.04 Bar rupture /concrete crushing
U8-2.5 0.55 2.5 95 49.3 0.88 24.3 88.2 1.07 Bar rupture
C8-3.1 0.68 3.1 200 76 55 0.8 24.4 71.7 1.05 Concrete crushing
C8-2.8 0.61 2.8 200 86 55 0.8 24.4 80 1.07 Concrete crushing
C8-2.5 0.55 2.5 200 87 55 0.8 24.4 88.6 0.98 Concrete crushing
Group 2: Over-reinforced beams
U10-3.1 0.68 3.1 100 49.3 1.38 31.7 93.2 1.07 Shear-flexure
U10-2.8 0.61 2.8 103 49.3 1.38 31.7 104 0.99 Shear-flexure
U10-2.5 0.55 2.5 136 49.3 1.38 31.7 115 1.17 Concrete crushing
C10-3.1 0.68 3.1 200 100 55 1.25 33.5 98.6 1.01 Concrete crushing
C10-2.8 0.61 2.8 200 107 55 1.25 33.5 110 0.97 Concrete crushing
C10-2.5 0.55 2.5 200 118 55 1.25 33.5 122 0.96 Shear-flexure
a
U = Unconditioned; C = Conditioned; 8 and 10 = diameters of the BFRP bars; 3.1, 2.8, and 2.5 = span-to-depth ratio, a/d, of the tested beams.

5. Beam test results in a balanced failure where concrete in compression crushed


simultaneously with the rupture of the bars. This different mode
The beam test results are listed in Table 6. The following sub- of failure was attributed to the discrepancy in the properties of
sections report on the beam results observed during the tests. the concrete mix and/or of the BFRP bars.
On the other hand, different modes of failure were observed in
the over-reinforced unconditioned beams (group 2). Beams with
5.1. Failure modes and load-carrying capacities a/d > 2.5 (i.e., U10-3.1 and U10-2.8) failed in a compression
shear-flexure failure mode in which concrete in compression
The modes of failure of the tested beams are summarized in crushed under the point load (Fig. 10). As the applied load
Table 6 and are shown in Figs. 9 and 10 for the under- and over- increased, flexural cracks were formed in the constant moment
reinforced beams, respectively. The unconditioned beams rein- zone. Close to ultimate, a large crack was formed in the shear span
forced with 28 mm BFRP bars failed in an explosive mode due and propagated towards the point load. The depth of concrete in
to the rupture of the BFRP bars except the beam U8-2.8 that failed the compression zone gradually decreased at the cracks tip until
142 M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146

a) Beam U8-3.1 b) Beam C8-3.1

Concrete
crushing
Bar rupture

c) Beam U8-2.8 d) Beam C8-2.8

Concrete
crushing

Concrete
Bar rupture crushing

e) Beam U8-2.5 f) Beam C8-2.5

Concrete Concrete
Bar rupture crushing crushing

Fig. 9. Modes of failure of the unconditioned and conditioned under-reinforced beams.

compression failure occurred. At failure, the inclined crack extended from the bottom fibers of the beam leading to the reduc-
made an angle of 55. Beam U10-2.5, having span-to-depth ratio tion in the compression depth until failure occurred.
a/d = 2.5, failed by concrete crushing between the two point loads. On the other hand, all of the conditioned beams of group 2
This mode of failure was attributed to the arch action developed, failed by concrete crushing between or below one of the point
which increased the shear resistance of the beam due to its small loads. Unlike their unconditioned counterparts, failure due to con-
a/d ratio. Close to ultimate, diagonal cracks forming a compression crete crushing in beams C10-3.1 and C10-2.8 was more ductile and
strut were clearly distinguished indicating the typical mode of the beams showed a progressive collapse of concrete layers in their
failure of a short-span beam. compression zone. Beam C10-2.5 failed in a compression shear-
Prior to testing, all of the conditioned beams showed multiple flexure mode outside the constant moment where concrete crush-
fine cracks that were developed in the tension zone. This was ing was observed below the loading point.
attributed to the volume expansion of water during the freezing Insignificant change occurred in the load-carrying capacities of
phase, which resulted in tensile stresses that caused concrete the tested beams having a/d > 2.5 after conditioning. This can be
cracking. During the test, these fine cracks expanded rapidly with depicted from the capacities listed in Table 6 for both uncondi-
the increase of the applied load. In fact, these cracks played the role tioned and conditioned beams. However, strength reduction was
of crack initiators as the load increased. observed in beams having a/d = 2.5 after exposure to FT cycles. This
The mode of failure observed for the conditioned beams of reduction was more pronounced in the over-reinforced beam C10-
group 1 (under-reinforced specimens) differed from that of the 2.5 of group 2 due to the brittle mode of failure observed. Beams
unconditioned ones. While the unconditioned beams in this group C8-2.5 and C10-2.5 showed reductions of 7.4 and 13.4%, respec-
failed by the bar rupture as previously noted, all of their condi- tively, in their load carrying capacities compared to their uncondi-
tioned counterparts failed by concrete crushing between the two tioned counterparts.
point loads regardless of their a/d ratio. No rupture in the BFRP bars
was observed in these specimens. Beam C8-3.1 exhibited concrete 5.2. Load-deflection relationships
crushing to a height equal to 40% of the beams depth (approxi-
mately 100 mm) measured from the lower fiber of the beam. Beam Load-deflection (P-D) relationships of the tested beams are
C8-2.5 failed after the propagation of two major cracks that shown in Fig. 11. Similar patterns of the P-D curves were observed
M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146 143

a) Beam U10-3.1 b) Beam C10-3.1

Shear-flexure Concrete
failure crushing

c) Beam U10-2.8 d) Beam C10-2.8

Concrete
Shear-flexure crushing
failure

e) Beam U10-2.5 f) Beam C10-2.5

Concrete Shear-flexure
crushing failure
Fig. 10. Modes of failure of the unconditioned and conditioned over-reinforced beams.

at mid-span for both unconditioned and conditioned specimens. ultimate loads of 83 and 86 kN. On the other hand, the uncondi-
For all of the tested beams, the P-D curves consisted of three seg- tioned and conditioned beams U8-2.5 and C8-2.5 showed almost
ments namely, (a) linear uncracked stage, which extended from similar post-cracking stiffness with a slight variation in their
the onset of loading until the first crack appeared, (b) service stage, midspan deflections.
in which the slope of the P-D curve decreased sharply indicating On the other hand, the variation in the P-D relationship after
the loss of stiffness of the beam and significant increases in deflec- conditioning was less pronounced in the over-reinforced beams.
tion occurred. This was associated with the expansion of the exist- Beams C10-3.1 showed higher stiffness and less deflections than
ing cracks and the development of new cracks along the beams, its counterpart U10-3.1 with no variation in its load-carrying
and finally (c) the ultimate stage, which was characterized by fur- capacity after conditioning. Beams C10-2.8 and C10-2.5 showed
ther reduction in the beam stiffness and the formation of diagonal minor changes in their stiffness after conditioning and negligible
shear cracks. The beam deflections excessively increased at this changes in their midspan deflections were observed. These find-
stage until failure occurred. ings can be depicted from the load-deflection curves of both beams
Conditioning did not change the pattern of the P-D curves of the in Fig. 11.
beam. However, under-reinforced beams with a/d > 2.5 showed
various levels of increase in their post-cracking stiffness after con- 5.3. Strain measurements
ditioning. This increase in stiffness can be depicted from the slopes
of the P-D curves of the unconditioned beams U8-3.1 and U8-2.8 Fig. 12 shows the load-strain curves of the under- and over-
and those of their conditioned counterparts C8-3.1 and C8-2.8. This reinforced beams. As can be noticed, the load-strain curves con-
increase was attributed to the increase in the compressive strength sisted of three segments with two turning points that indicated
of concrete after conditioning due to the long curing exposure. The the concrete cracking and the ultimate stage. Prior to cracking,
increase in stiffness was also accompanied by a decrease in the all specimens showed an increase in strains in both concrete and
measured deflections at midspan of the conditioned beams. For BFRP reinforcement as the applied load increased. The post-
instance, the midspan deflections of beams U8-3.1 and C8-3.1 were cracking stage was characterized by a noticeable increase in con-
51 and 36 mm, respectively, corresponding to ultimate loads of 77 crete strains, which occurred at different rates depending on the
and 76 kN. Similarly, beams U8-2.8 and C8-2.8 showed midspan reinforcement ratio and the a/d ratio of the tested specimen. Short
deflections of 53 and 42 mm, respectively, corresponding to beams having a/d = 2.5 showed the highest rate of increase in their
144 M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146

Fig. 11. Load-deflection relationships for (a) under-reinforced and (b) over-reinforced beams.

concrete strains. This could be noticed from the steep load-strain cracking and the large deflections recorded at this stage of loading.
curves of beams U8-2.5 and U10-2.5. On the other hand, beams Exposing the beams to FT cycles slightly decreased the strains in
with a/d > 2.5 (beams U8-2.8, U8-3.1, U10-2.8, and U10-3.1) the BFRP bars at all stages of loading. This decrease was more pro-
showed an increase in the concrete strains but at a lower rate. nounced in under-reinforced beams with a/d > 2.5, which was con-
It can be noticed that exposing the beams to FT cycles slightly sisted with the observed stiffness and the measured mid span
affected the measured strains in concrete, as shown in Fig. 12 for deflections.
both under- and over-reinforced beams. The effect of FT cycles
on the concrete strains was more pronounced in the under- 6. Theoretical investigation
reinforced beams. The conditioned specimens in this group
recorded less strains at all stages of loading than their uncondi- 6.1. Load-carrying capacities
tioned counterparts. This finding was consistent with the load-
deflection pattern of such beams in which an increase in stiffness The provisions of the Canadian codes CSA-806-12 [7] and the
was observed. CSA-S6-10 [6] were used to predict the ultimate moment and the
On the other hand, the post-cracking stage of all of the tested load-carrying capacities of the unconditioned and conditioned
beams was characterized by a significant increase in the reinforce- beams. Predicted and experimental values are listed in Table 6.
ment strains indicated by the horizontal plateaus shown in Fig. 12. The variation in concrete compressive strength after conditioning
These plateaus reflected the abrupt drop in the beam stiffness after was taken into account during the analysis of the conditioned
M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146 145

Fig. 12. Load-strain relationships for (a) under-reinforced and (b) over-reinforced beams.

beams. It is worth noting that the increase in the concrete com- where Mu and Ms are the ultimate and service moments, respec-
pressive strength after conditioning has led to a slight decrease tively, and wu and ws are the corresponding curvatures of the
in the ratio q=qbal , where q is the reinforcement ratio of the tested beam. The CSA-S6-10 code [6] recommends that Ms and ws be
beam and qbal is the balanced reinforcement ratio [7]. A good cor- taken as the moment and curvature corresponding to a maxi-
relation between the predicted and experimental capacities was mum compressive concrete strain, ecs , of 0.001. It also recom-
observed. mends that DF should not be less than 4 for FRP-reinforced
beams.
6.2. Effect of conditioning on ductility The theoretical ultimate and service moments were used to
calculate the deformation factor of both unconditioned and
The CSA-S6-10 [6] recommends the use of the deformability conditioned beams. These moments, in addition to the depths of
factor, DF, to determine the ductility of the FRP-reinforced beams the theoretical neutral axis at both ultimate and service stages
as given by Eq. (1): (cu and cs, respectively) are given in Table 7. It can be noticed that
conditioning slightly increased the ductility of the beams, which
Mu wu
DF 1 was attributed to the increase in the concrete compressive
Ms ws strength after conditioning.
146 M.-A. Khanfour, A. El Refai / Construction and Building Materials 145 (2017) 135146

Table 7
Ductility factors for unconditioned and conditioned beams.

Beam At ultimate At service DF


0
fc (MPa) Mu (kN m) ecu cu, (mm) wu  10 5
(1/mm) Ms (kN m) ecs cs, (mm) ws  10 5
(1/mm)

Under-reinforced beams
Unconditioned 49 24.3 0.003 21.4 14 10.1 0.001 20 5 6.73
Conditioned 55 24.4 0.003 19.6 15.4 10.5 0.001 19.4 5.2 6.85
Over-reinforced beams
Unconditioned 49 31.8 0.003 28.4 10.5 12.5 0.001 24.8 4 6.68
Conditioned 55 33.5 0.003 27.2 11.1 13 0.001 24.1 4.2 6.78

7. Conclusions extended to the Structures Laboratory technicians at Laval Univer-


sity for their assistance during the tests.
An experimental program was carried out to investigate the
effect of FT cycles and low temperature on the performance of References
the BFRP-reinforced concrete. Unconditioned and conditioned pull-
[1] ACI (American Concrete Institute), Guide test methods for fiber- reinforced
out and beam specimens were tested. The following conclusions
polymers (FRPs) for reinforcing or strengthening concrete structures, ACI
can be drawn: 440.3R-04, Farmington Hills, MI, 2004.
[2] A. Altalmas, A. El Refai, F. Abed, Bond degradation of basalt fiber-reinforced
1- Failure of pullout specimens was governed by the shear polymer (BFRP) bars exposed to accelerated aging conditions, Constr. Build.
Mater. 81 (2015) 162171.
strength along the bar-concrete interface. Exposure to FT [3] V.A. Alvarez, Temperature effect on bond properties of fiber-reinforced
cycles and low temperature did not change the mode of fail- polymer (FRP) bars embedded in concrete M.Sc. thesis, Sherbrooke
ure of the conditioned specimens. University, 2004.
[4] L.C. Bank, M. Puterman, A. Katz, The effect of material degradation on bond
2- Exposure to low temperature resulted in a decrease in the properties of fiber reinforced plastic reinforcing bars in concrete, ACI Mater. J.
bond strength of 10% of the BFRP-reinforced pullout speci- 95 (3) (1998) 232243.
mens. FT cycles had negligible effect on the bond strength [5] A. Belarbi, H. Wang, Bond durability of FRP bars embedded in fiber-reinforced
concrete, J. Compos. Constr. 16 (4) (2012) 371380.
of the BFRP bars to concrete. [6] Canadian Standards Association CSA, Canadian highway bridge design code,
3- BFRP bars of 8, 10, and 12 mm exhibited 67, 29, and 63% CSA-S6-10, Mississauga, ON, Canada, 2010.
increase in average slippage at their loaded ends, respec- [7] Canadian Standards Association CSA, Design and construction of building
components with fiber-reinforced polymers, CSA-S806-12, Mississauga, ON,
tively, compared to their unconditioned counterparts after Canada, 2012.
being exposed to low temperature. FT cycles had negligible [8] Y. Chen, J.F. Davalos, I. Ray, H.Y. Kim, Accelerated aging tests for evaluations of
effect on the bar slippage. durability performance of FRP reinforcing bars for concrete structures,
Compos. Struct. 78 (2007) 101111.
4- Perfect bond was observed between the BFRP reinforcement
[9] J.F. Davalos, Y. Chen, I. Ray, Effect of FRP bar degradation on interface bond
and the surrounding concrete during the beam tests. This with high strength concrete, Cem. Concr. Compos. 30 (2008) 722730.
finding agrees well with the results of the pullout tests in [10] A. El Refai, F. Abed, A. Altalmas, Bond durability of basalt fiberreinforced
which bond strengths were slightly affected by FT cycles. polymer bars embedded in concrete under direct pullout conditions, J.
Compos. Constr. (2014), http://dx.doi.org/10.1061/(ASCE)CC.1943-
5- FT conditioning resulted in a more ductile failure in under- 5614.0000544.
reinforced beams that failed due to concrete crushing rather [11] A. El Refai, M.A. Ammar, R. Masmoudi, Bond performance of basalt fiber-
than the bar rupture. This mode of failure was attributed to reinforced polymer bars to concrete, J. Compos. Constr. (2014), http://dx.doi.
org/10.1061/(ASCE) CC.1943-5614.0000487.
the increase in the compressive strength of concrete after [12] F. Elgabbas, E. Ahmed, B. Benmokrane, Flexural behaviour of concrete beams
conditioning. reinforced with ribbed basalt-FRP bars under static loads, J. Compos. Constr.
6- The effect of FT cycles on the failure mode of the tested (2016), http://dx.doi.org/10.1061/(ASCE)CC.1943-5614.0000752.
[13] V.M. Karbhari, Response of fiber reinforced polymer confined concrete
beams was less pronounced in the over-reinforced speci- exposed to freeze and freeze-thaw regimes, J. Compos. Constr. 6 (1) (2002)
mens with a/d > 2.5. However, under- and over-reinforced 3540.
beams with a/d = 2.5 resulted in reductions of 7.4 and [14] M. Mahroug, A. Ashour, D. Lam, Experimental response and code modelling of
continuous concrete slabs reinforced with BFRP bars, Compos. Struct. 107
13.4%, respectively, in their load carrying capacities com- (2014) 664674.
pared to their unconditioned counterparts. [15] R. Masmoudi, A. Zaidi, P. Grard, Transverse thermal expansion of FRP bars
7- FT conditioning had a slight effect on the ductility of the embedded in concrete, J. Compos. Constr. 9 (5) (2005) 377387.
[16] T. Ovitigala, M. Ibrahim, M. Issa, Serviceability and ultimate load behavior of
tested beams regardless of their a/d ratio or their internal
concrete beams reinforced with basalt fiber-reinforced polymer bars, ACI
reinforcement. Struct. J. 113 (04) (2016), http://dx.doi.org/10.14359/51688752.
[17] R. Saiedi, A. Fam, M.F. Green, Behavior of CFRP-prestressed concrete beams
It is important to note that, due to the complex action of FT con- under high-cycle fatigue at low temperature, J. Compos. Constr. 15 (4) (2011)
482489.
ditioning, more specimens should be tested to verify the effect of [18] A. Serbescu, M. Guadagnini, K. Pilakoutas, Mechanical characterization of
FT cycles on the performance of BFRP-reinforced beams. Caution basalt FRP rebars and long-term strength predictive model, J. Compos. Constr.
should be paid when extending these conclusions to other types (2014), http://dx.doi.org/10.1061/(ASCE)CC.1943-5614.0000497.
[19] E.A. Tannous, H. Saadatmanesh, Durability of AR glass fiber reinforced plastic
of BFRP bars or when different concrete strengths are used. It is bars, J. Compos. Constr. 3 (1) (1999) 1219.
also recommended to carry out further studies to investigate the [20] D. Tomlinson, A. Fam, Performance of concrete beams reinforced with basalt
effect of other environmental conditions on the performance of FRP for flexure and shear, J. Compos. Constr. (2014), http://dx.doi.org/10.1061/
(ASCE)CC.1943-5614.0000491.
the BFRP-reinforced structures. [21] G. Wardeh, A.S. Mohamed, E. Ghorbel, Analysis of concrete internal
deterioration due to frost action, J. Building Phys. 35 (1) (2011) 5482.
Acknowledgments

The authors would like to acknowledge Magmatech personnel


for providing the BFRP bars used in this study. Special thanks are

You might also like