Professional Documents
Culture Documents
1
Table of Content
S.No. Name of Experiment Page No.
2
Experiment no :- 1
Apparatus :
Tachometer 1no
Specifications of Appraratus :-
Motor Generator
Learning Objective:-Student will learn how to measure armature resistance & Field
Resistance & open circuit Characteristics of a dc Shunt Generator
Circuit Diagram :
3
Procedure:
4. Now start the motor and bring the speed ot rated value
6. Now decrease the field rheostat and record If and Eg up to rated voltage of generator .
10. To fing the value of armature & field resistance connect the circuit as shown in
the diagram
11. Note the values of voltage and current and find the value of resistance
(R=V/I) Scope of Result Expected: Students can know when Saturation is reached
Observation Table :
4
Speed.. r.p.m
5
Experiment no :- 2
Apparatus :
Tachometer 1no
Load as required
Specifications :-
Motor Generator
Learning Objective:
Circuit Diagrams :
8
Procedure:
1) Make the connections as shown in the circuit diagram . Start the motor with the help
of the starter
2) Adjust the field regulator of the motor so that the generator runs at its rated speed .
3) Adjust the field regulator so that rate voltage is obtained at its terminal.
4) Gradually apply the load in steps and note down the readings if the load as given on
name plate generator . Keep the speed constant at its rated value by adjusting motor field
regulator .
6) Determine the external load armature resistance experimentally using the circuit diagram
Observation Table :
Speed .. r.p.m
Precautions :
9
Experiment No :3
Aim : To perform Swinburnes test (no load test) to determine the losses of dc shunt motor
Apparatus :
1 Ammeter 0-2A 1
2 Ammeter 0-5A 1
3 Ammeter 0-25A 1
4 Voltmeter 0-300V 1
5 Voltmeter 0-30V 1
6 Rheostat 290.1.4A 1
Learning Objective: Students will know how to measure losses and efficiency of Dc machine
Circuit Diagram :
11
Procedure :
3. Switch on the dc supply to the motor and start it with the help of starter . In case the
starter is not provided with the motor , then a rheostat of 45,5 A can be included in the
armature circuit , which should be fully inserted in the armature circuit at the instant of
starting the motor and should be cut out after the motor has picked up the speed .
Ensure that the voltage applied to the motor is of the rated value .
4. Adjust the speed of motor to rated value by varying the resistance in the field circuit
3. Switch on some bulbs in the lamp bank load , so that the current flowing in the armature
circuit is the rated full load current of the dc motor , wait for 30min with the full load
current flowing in the armature winding , so that the temperature of the armature
winding approximately becomes equivalent to that obtained under working conditions
Observations :
12
Learning Outcome to be written by student in 50-70 words
Experiment no. 4
Aim : To connect and find the constant of a single phase energy meter .
Apparatus :
Lamp load .
Frequency =50Hz
Energy meter constant K = No. of rev. made by the disc/Elect. Energy consumed in Kwh (in
a given time )
Procedure :
Connect energy meter to the supply and load the energy meter .
Put load on the energy meter by switching - ON various number of lamps through DPST
switch and switches S1,S2,S3(about 1Kw).
Record the readings of energy meter . Also record the number of revolutions made by
the disc .
Observation :
Result :
15
Experiment no 5:-
Specifications :
Motor Generator
Learning Objective: students will know how to put load on Dc motor & how to measure
torque, how speed varies with torque
THEORY:
In a series motor the load current , armature current and field current are same terminal
voltage.
V= EgIa (Ra+Rse)
Where ,
V = terminal voltage
Ra = Armature resistance ()
This voltage drop for different values load current may be represented by a straight Line .
16
External Characteristic : It is the characteristic drawn between terminal voltage V and load
current I1.
The ohmic drop line OA is added to these external characteristic , in order to get the internal
characteristic.
Graph I : O.C.C
17
Procedure :
b) Keep the motor field rheostat in minimum resistance position and do not connect any
load on the generator
c) Switch ON the power supply and start the motor with the help of starter
e) Now, switch On the load and for different values of load ,note the ammeter and
voltmeter readings
f) After loading the generator up to the rated value gradually reduce the load in steps
and switch off the supply
TABULAR COLUMN:
18
MODEL GRAPHS:
y3 y2 y1
m)
(N
T(rp
N m)
Efficiency %
N
y
Torq
Spee
ue
d
Speed N (rpm)
Output Power (Watts) x
Torque T (Nm)
PRECAUTIONS:
Thus load test on DC compound motor is conducted and its efficiency as well as torque is
determined.
Experiment : To study the speed control of a dc shunt motor . To draw the speed variation with
respect to change of
Objective : After performance the experiment the students understand that speed of shunt motor
can be varied by inserting and changing a resistance in the field circuit or armature circuit .
Apparatus:
250 V dc supply
One tachometer
DPST switch
Connecting leads
Circuit Diagram :
22
Procedure :
Make the connections as per the circuit diagram and get it checked by the teacher
Field control :
Take the reding of the ammeter A1 and measure speed with tachometer.
Change the value of the rheostat R f in steps and take the reading of ammeter A1
and measure the speed of motor and record them .
Armature control:
Take the reading of ammeter A2 and measure the speed of the motor at each step
and record them.
Bring the rheostat Ras back to zero position. Switch OFF supply
Field control:
Armature control:
23
Precautions
Result:
1. In field control method by adding a resistance in the field winding the speed of
motor increases N 1/ 1/If
2. In the armature control method by adding a resistance in armature circuit the speed
of motor decreases. Speed { N Eb V-Ia(Ra+Ras) }
24
Experiment no.7
Apparatus :
1 Ammeter MI 0-15A 2
2 Ammeter MI 0-30A 1
3 Voltmeter MI 0-300/600V 1
Circuit Diagram
Figure 1
25
Procedure :
2. Switch on the supply to the primary circuit where the primaries of both the transformer
are connected In parallel
3. The voltmeter connected in the secondary circuit of transformer will read either zero or
twice the secondary terminal voltage of each transformer
4. If the voltmeter reads zero connect a1 to a1 and a2 to a2 for the secondary windings to
be In parallel
In case the voltmeter reads twice the secondary terminal voltage then
connect a1 to a2 and a2 to a1 for parallel operation of the two transformers
Step 2:
step 1
26
3. Close the switch S1 to energize both the primaries. Ensure that the switch S2 is kept
open. In case then voltage ratio of the two transformer are unequal , there will be a
circulating current .
4. Close the switch S2 adjust a particular load on secondary and record the readings of
all the instruments connected in circuit .
5. Repeat the step 3 for various values of load current upto rated capacity of the transformer
operating in parallel .
6. Switch off the load slowly.Open the switch S2 and then switch off the supply to
the primaries of the transformers.
OBSERVATIONS:-
Sr no. VL IL I1 I2
Precautions:
2) The position of the starter must be check before giving supply SCOPE
RESULT EXPECTED: Load sharing between two Transformers
27
Experiment no.8
Aim : To study the polarity & ratio test of single phase transformer
Apparatus :
1 Ammeter MI 0-15A 2
2 Ammeter MI 0-30A 1
3 Voltmeter MI 0-300/600V 1
Learning Objective:- How to check the polarity of single phase transformers in parallel
Procedure :-
Polarity check
29
5. Connect the circuit as shown in figure
6. Switch on the supply to the primary circuit where the primaries of both the
transformer are connected In parallel
7. The voltmeter connected in the secondary circuit of transformer will read either
zero or twice the secondary terminal voltage of each transformer
OBSERVATIONS:-
Sr no. VL IL WL I1 I2
Experiment :- To perform open circuit and short circuit test on a single phase transformer
and find equivalent circuit , voltage regulation & efficiency .
Apparatus:-
One Wattmeter (0-20W) for OCT & One Wattmeter (0-200W) for
SCT Two voltmeter 0-300V
Learning Objectives: How to find out Iron & Copper Losses of a single
phase Transformer
Circuit diagram:-
32
b) Short Circuit Test:
Procedure
Make the connection as per th circuit to perform open circuit test (OCT)
To perform open circuit test switch on th ac supply through DPST switch at rated voltage
. take the readings of wattmeter Wi(iron losses) voltmeter readings V1 and V2 (for
transformer ratio)
To perform short circuit test switch on supply through DPST to variac increase the
voltage fed to be primary of the transformer insteps so that ammeter carries current Isc =
0.25IFL =0.51I FL=0.75I FL=1I FL .For each take the reading of wattmeter Wc
Observation
33
Transformation ratio K = V2/V1
V I P V I P (V2-V1)/V2*100
34
where output = Voltmeter Reading V1 (at OCT) X Ammeter reading A
(at SCT)X p.f.
Precautions :-
36
Experiment no:- 10
Aim : to find the efficiency and voltage regulation of single phase transformer under
different loading conditions .
Apparatus :
Wattmeter 0-200W
Ammeter 0-10Amp.
Connecting leads
Learning Objectives: How to find out Iron & Copper Losses of a single phase transformer
Circuit diagram :
Procedure :-
Put on Supply
37
Switch on Load so that suitable load current flows
Increase Load on transformer & take five to seven sets of reading at different loads .
SCOPE OF RESULT EXPECTED:-Students will learn how to find Efficiency & Regulation
of Single Phase Transformer at different Loads
Precautions :-
39
Experiment no: 11
Objective : In industry load usually 3 phase . By performing this experiment the students
will be in position to convert3-phase powerto 2-phase power
Apparatus :
3 phase AC supply .
3 phase balance load (like induction motor or 3 resistors connected in star connection ).
TPIC switch .
Circuit Diagram
Procedure
Increase Load on transformer & take five to seven sets of reading at different loads .
41
Experiment no: 12
Aim : To measure the power and power factor of 3 phase balanced circuit by two watt
meter method
Objective : In industry load usually 3 phase . By performing this experiment the students
will be in position to measure power and power factor of 3 phase load .
Apparatus :
3 phase AC supply .
3 phase balance load (like induction motor or 3 resistors connected in star connection ).
TPIC switch .
Connecting leads
Procedure :
Switch on the load ( i.e start the motor through starter if the load is induction motor )
Note : Observe the reading of two watt meters , if any of them gives down scale reading (if
happens when load power factor is below 0.5) switch off the supply and reverse the
connection of current coil of the watt meter and while doing the calculation consider the
reading as negative ).
Change the load (in case of inducting motor put the mechanical load by tightening the belt
on the pulley .
Take the readings of two watt meters and record in the observation table
Circuit diagram
42
Observation Table :
43
Learning Outcome to be written by student in 50-70 words
44