You are on page 1of 27

IOQ Centre logo can be inserted here

INSTALLATION / OPERATIONAL
QUALIFICATION PROTOCOL

INSERT REFRIGERATOR NAME & I.D.


Centre Name
HFEA Centre Number
Centre Address

Document Reference: IOQ- Insert document reference and revision


Issue Date: Insert issue date

Document Author
Name Position Signature Date

Populate Populate

Approval
Name Position Signature Date

Populate Populate

Populate Populate
IOQ Centre logo can be inserted here

1. APPROVALS

1.1 Implementation approval


Implementation approval is given following review of the submitted protocol and must be completed prior to execution
of the protocol. This approval is detailed on the cover page.
1.2 Interim approval
Equipment use will be suspended if non-conformances categorised as high have not been resolved.
Interim approval may be granted to permit continued equipment use if non-conformances categorised as high have been
resolved.
Interim approval may also be granted if non-conformances categorised as low are outstanding.
Name Position Signature Date

Populate Populate

Comments

1.3 Final Approval


Final approval is given when all non-conformances have been resolved.
Name Position Signature Date

Populate Populate

Populate Populate

Comments

IOQ-insert doc reference and revision


Page 2 of insert total pages up to list of appendices page
IOQ Centre logo can be inserted here

TABLE OF CONTENTS
Section Page
1. APPROVALS..............................................................................................................................................................2
2. DOCUMENT CONTROL..........................................................................................................................................3
3. INTRODUCTION & SCOPE.....................................................................................................................................4
4. DATA COLLECTION................................................................................................................................................5
5. NON-CONFORMANCES..........................................................................................................................................6
6. PERSONS PERFORMING IOQ................................................................................................................................6
7. PRE-REQUISITES TO COMMENCE IQ SECTION................................................................................................7
8. INSTALLATION CHECK (IQ)..................................................................................................................................8
9. COMMISSIONING CHECK (IQ)...........................................................................................................................10
10. PRE-REQUISITES TO COMMENCE OQ SECTION............................................................................................12
11. FUNCTION & ALARM CHECKS (OQ).................................................................................................................13
12. TEMPERATURE MAPPING STUDY (OQ)...........................................................................................................15
13. INTERNAL SOP AND TRAINING REVIEW (OQ)...............................................................................................20
14. SUMMARY OF TESTS PERFORMED..................................................................................................................22
15. list of Appendices......................................................................................................................................................23

2. DOCUMENT CONTROL

2.1 Revision History


Date Issued Revision Reason for Issue

Populate A Draft issued for internal review

1 Issued for approval

IOQ-insert doc reference and revision


Page 3 of insert total pages up to list of appendices page
IOQ Centre logo can be inserted here

3. INTRODUCTION & SCOPE

3.1 Introduction
The purpose of this IOQ is to qualify the refrigerator (detailed below) to confirm that it has been installed according to
the design intent and operates in accordance with the manufacturers specifications, drawings and other relevant design
documents.
The IOQ will cover the following refrigerator:
Equipment Name Make & Model Identification No. Location

Refrigerator

This refrigerator is used for .


3.2 Scope
This protocol will include the following IQ verifications:
Confirm availability of supporting documentation
Confirm correct installation of refrigerator and suitable utility connections
Review of commissioning report
This protocol will include the following OQ verifications:
Confirm correct functioning of all components including temperature control
Confirm correct alarm functionality
Temperature mapping of the refrigerator chamber to determine temperature distribution under normal
operating and breach conditions
Standard Operating Procedures and training review
Note: Validation of the utilities supplying the refrigerator does not form part of this IOQ.

IOQ-insert doc reference and revision


Page 4 of insert total pages up to list of appendices page
IOQ Centre logo can be inserted here

4. DATA COLLECTION

All written data will be entered using a blue or black indelible pen in clear handwriting at the time of testing or
completion.
All dates will be entered in the International Standard format, i.e. 01 Jun 2008. American format (MMM DD YY) must
not be used.
Mistakes and errors will be crossed out using a single line and correction made in blue or black pen. Correction fluid
must not be used.
The person responsible for the correction must initial and date any corrections, with any appropriate explanation, at the
time of change.
Ticks, crosses and dittos must not be used. The checker should indicate the appropriate response by his/her
initials.
Deviations from approved test procedures or acceptance criteria will be made by crossing out and a suitable explanation
for the change given. The change will be signed and dated by the person instigating the change. If there is a significant
change this may require a higher level of approval.
All empty or incomplete boxes will be scored through. They should be annotated as non applicable with N/A, and
initialled and dated.
All attachments and appendices will be cross-referenced in the protocol and signed and dated.
All drawings/schedules/quotations etc. will be marked up in accordance with the relevant protocol test instructions to
indicate compliance, non-compliance and deviations from the expected result.
The following highlighter pens will be used for marking up documents and drawings: -
Yellow indicates compliance with the drawing/schedule etc.
Blue indicates non-compliance with the drawing/schedule etc.
Green indicates areas that were unable to be checked and should be accompanied by a simple explanation
Where the documentation is to be stored electronically, any raw data or supporting documents must be scanned in.
If the protocol is to be completed electronically, the document must have adequate security to avoid amendment and
alteration to the completed protocol.

IOQ-insert doc reference and revision


Page 5 of insert total pages up to list of appendices page
IOQ Centre logo can be inserted here

5. NON-CONFORMANCES

Where there are failures or deviations in meeting some or all of the agreed approved acceptance criteria during the
execution of protocols, the impact of the failure is assessed and categorised and formally documented on a non-
conformance form for control and close out.
The non-conformance solution must be approved by a responsible person before the protocol can reflect closure.
Comments on corrective action taken to resolve the non conformance are documented on the form and the form is held
with the appropriate protocol for traceability and reference
Non conformances are encountered when the equipment/system/process does not agree with or operate to the specified
design criteria.
A non-conformance also arises when the specification, test method or acceptance criteria has been incorrectly defined in
the protocol.
Categorising of non-conformance is as per the table below:
Category Description Required Action

Must be rectified immediately.


Non-conformances which could have a
High The process of qualification cannot continue
critical impact on gametes or embryos
until the non-conformance is resolved

Non-conformances which have either no The process of qualification may continue, only
Low impact or a negligible impact on gametes or following review of the non-conformance and
embryos with signed acceptance

6. PERSONS PERFORMING IOQ

All personnel entering information in this protocol must be identified in the table below by name, affiliation, full
signature and initials.
Personnel must be fully aware of all the procedures to follow, specifically procedures for data collection and recording
discrepancies.
Name Company Signature Initials Date

IOQ-insert doc reference and revision


Page 6 of insert total pages up to list of appendices page
IOQ Centre logo can be inserted here

7. PRE-REQUISITES TO COMMENCE IQ SECTION

Pre-Requisite Description Initials Comments

Installation is complete with refrigerator in final location

Refrigerator has been commissioned by the supplier and a


commissioning report is available for review

IOQ-insert doc reference and revision


Page 7 of insert total pages up to list of appendices page
IOQ Centre logo can be inserted here

8. INSTALLATION CHECK (IQ)

8.1 Objective
To verify that the refrigerator has been installed to a satisfactory standard and is safe to use.
To confirm there is adequate documentation to support the on-going operation and maintenance of the refrigerator.
8.2 Pre-Requisites
Pre-Requisite Description Initials Comments

Refrigerator is installed and handed over for verification

8.3 Test Method


Record the documentation provided to support the on-going operation and maintenance in the result table 1 below.
Carry out physical inspection checks on the refrigerator and complete the result table 2.
8.4 Acceptance Criteria
Operating & Maintenance manual must be available.
The installation checks identified in result table 2 must have been suitably addressed.
8.5 Results
Table 1
Document Title Reference / Issue Date Location

Table 2
Check Comment

The refrigerator is uniquely identifiable

The refrigerator has been installed in the correct location


and has no visual signs of defects or damage

Any drawings supplied with the equipment are accurate

The specified services and utilities have been provided


and are suitably connected and electrical safety checks
have been performed
Record any details of computer hardware and software
e.g. type/ versions (if applicable)

Performed By: Date: IOQ-insert doc reference and revision


Page 8 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

8.6 Conclusion
This section of the protocol has been completed and is deemed to (initial appropriate box below):

Pass Pass with comment Fail

Comments Non-conformance

Performed By: Date: IOQ-insert doc reference and revision


Page 9 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

9. COMMISSIONING CHECK (IQ)

9.1 Objective
To verify that the refrigerator has been satisfactorily commissioned and a commissioning report has been provided by
the supplier.
9.2 Pre Requisites
Pre-Requisite Description Initials Comments

Commissioning report is available for review

9.3 Test Method


Record the documentation provided to support the commissioning activity in result table 1.
Review the commissioning report and complete the result table 2.
9.4 Acceptance Criteria
The commissioning report must be available.
The commissioning results must meet the specifications and criteria in result table 2.
9.5 Results
Table 1
Document Title Reference / Issue Date Location

Table 2
Check Comment
The commissioning report has been adequately
completed and is signed and dated

All the test instrumentation used has a current calibration


certificate

Temperatures have been independently verified

Alarms have been set, documented and verified

Performed By: Date: IOQ-insert doc reference and revision


Page 10 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

9.6 Conclusion
This section of the protocol has been completed and is deemed to (initial appropriate box below):

Pass Pass with comment Fail

Comments Non-conformance

Performed By: Date: IOQ-insert doc reference and revision


Page 11 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

10. PRE-REQUISITES TO COMMENCE OQ SECTION

Pre-Requisite Description Initials Comments

The IQ section of this protocol has been completed

No non conformances from the IQ section, categorised as


high, remain outstanding

Performed By: Date: IOQ-insert doc reference and revision


Page 12 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

11. FUNCTION & ALARM CHECKS (OQ)

11.1 Objective
To verify that all refrigerator components function correctly as specified for normal operation.
To verify that all alarms function as specified.
11.2 Pre Requisites
Pre-Requisite Description Initials Comments

Refrigerator is installed and operational

11.3 Test Method


Carry out checks as detailed in result table 1 and record findings (including levels, limits and normal operating set
points).
11.4 Acceptance criteria
All functions must operate as specified and meet the criteria detailed in result table 1.
Environmental parameter operating and alarm limit set points must comply with the following:
Parameter Set Point Alarm Limit
Low Limit: +2oC
Temperature Level +5oC
High Limit: +8oC

Adjustments to environmental parameter operational set points must result in a corresponding response from the
refrigerator control system.
Environmental parameter alarms must trigger in accordance with the set points above.
11.5 Results
Table 1
Check Comment

Ensure all doors operate as expected

Ensure ON/OFF switches function correctly

Record temperature set points (for both operating level Operating Set Point:
and the alarm limits) and also confirm these meet the Low Alarm Set Point:
acceptance criteria High Alarm Set Point:
Hold door open to confirm the alarm activates and record
the delay time. Close door and confirm alarm de-
activates
Increase the temperature set point by 3oC. Confirm that
the refrigerator system responds to increase the
temperature and the alarm activates (visual and audible)
when temperature exceeds alarm high limit
Ensure temperature set point is returned to the original
value on completion and confirm alarm de-activates

Performed By: Date: IOQ-insert doc reference and revision


Page 13 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

Table 1
Check Comment
Decrease the temperature set point by 3oC. Confirm
that the refrigerator system responds to decrease the
temperature and the alarm activates (visual and audible)
when temperature exceeds alarm low limit
Ensure temperature set point is returned to the original
value on completion and confirm alarm de-activates

11.6 Conclusion
This section of the protocol has been completed and is deemed to (initial appropriate box below):

Pass Pass with comment Fail

Comments Non-conformance

Performed By: Date: IOQ-insert doc reference and revision


Page 14 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

12. TEMPERATURE MAPPING STUDY (OQ)

12.1 Objective
To verify that the refrigerator functions correctly in maintaining the correct temperature conditions throughout.
To determine how quickly temperature limits are exceeded when the door is opened or when there is a significant loss
of power, and how quickly temperature returns to within operating limits once the door is closed or and/or power
restored.
Note: By simulating a loaded refrigerator, this will provide data to support Performance Qualification requirements.
12.2 Pre Requisites
Pre-Requisite Description Initials Comments
Refrigerator is filled with simulated product to represent
a typical full load

12.3 Test Method


Initial Setup
Set up a minimum of six (6) temperature datalogging sensors (with downloadable data functionality) and confirm an
accuracy of +/-0.5C. Record the details of the test instrumentation on the test instrumentation table below.
Place a minimum of three (3) of those sensors inside the refrigerator in free space making sure there is a good
distribution around the edges and in the middle. Identify high risk areas and ensure sensors are located in these areas.
If possible attach one of the sensors to the controlling probe.
Place a minimum of three (3) of those sensors in simulated product (media dishes) to monitor simulated product
temperature (where applicable).
Record the locations of each sensor in the sensor location table below.
List the quantity and type of simulated product in the refrigerator (where applicable).
Ensure the refrigerator temperature has stabilised to the required operating range of 5C 3C.
Set the sensors to record temperatures at one minute intervals.
Following completion of the three tests identified below, remove the sensors and perform calibration verification (if
applicable).
Append all raw data from the sensors suitably signed/dated to this protocol.
Note: The order of the tests below can be changed to suit individual test environments.
Door Open Simulation Test
Start the logging and allow all the sensors to stabilise.
Open the refrigerator door, for 3 minutes (to simulate worst case conditions). Close the door and allow the temperature
to recover to the set limits.
Record the highest temperature measured during the door open test and the maximum time taken for all sensors to
recover to within the set limits.

Performed By: Date: IOQ-insert doc reference and revision


Page 15 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

Power Failure Simulation Test


Start the logging and allow all the sensors to stabilise.
Turn off the power and leave for 3 hours (to simulate worst case conditions). Re-instate the power supply and allow the
temperature to recover to the set limits.
Record the highest temperature measured during the door open test, the time taken for the first sensor to fall outside the
limit and the maximum time taken for all sensors to recover to within the set limits.
Mapping Study
Start the logging and allow the sensors to stabilise.
Leave the refrigerator on (with door closed throughout) for a minimum of a 12 hour period with the sensors monitoring
as programmed.
Record the highest and lowest temperatures measured during the study period.
Note: The above three tests should be carried out to provide data over at least a 24 hour period (in total).
12.4 Acceptance Criteria
During normal operation, all sensors are in the range 5C 3C.
Following the door open simulation test and once the door is closed, sensors recover efficiently to within the set limits.
Following the power failure simulation test and once the power has returned, sensors recover efficiently to within the
set limits.
Note: The effect on temperature of opening the door is for information only to determine recovery times. This
information may be used to determine standard operating procedures.
12.5 Test Instrumentation
Enter details of the test instrumentation (sensors) used in the table below and append calibration certificates to this
protocol
Test Instrument Serial Number Date Calibration Due

Performed By: Date: IOQ-insert doc reference and revision


Page 16 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

12.6 Sensor Locations


Enter details of the sensor locations in the table below.
Sensor Number Shelf Number Left/Centre/Right Front/Centre/Rear In Product (Y/N)

12.7 Simulated Product


List the type and quantity of simulated product items placed within the refrigerator during this mapping study.
Description Quantity

Performed By: Date: IOQ-insert doc reference and revision


Page 17 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

12.8 Results

Maximum Temp Rise Maximum Recovery Time


Door Open Simulation
(3 min)
C Sensor No. Minutes Sensor No.

Sensor (Free Space)

Sensor (Simulated Product)

Maximum Temp Rise Maximum Recovery Time


Power Failure Simulation
(3 hours)
C Sensor No. Minutes Sensor No.

Sensor (Free Space)

Sensor (Simulated Product)

Time For First Sensor Out Of Limits


Power Failure Simulation
(3 hours)
Minutes Sensor No.

Sensor (Free Space)

Sensor (Simulated Product)

Max Temp Min Temp


12 Hour Mapping Study
C Sensor No C Sensor No

Sensor (Free Space)

Sensor (Simulated Product)

Refrigerator Set Point (C) Refrigerator Display (C)


(logged at start of test) (logged at start of test)

Performed By: Date: IOQ-insert doc reference and revision


Page 18 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

12.9 Conclusion
This section of the protocol has been completed and is deemed to (initial appropriate box below):

Pass Pass with comment Fail

Comments Non-conformance

Performed By: Date: IOQ-insert doc reference and revision


Page 19 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

13. INTERNAL SOP AND TRAINING REVIEW (OQ)

13.1 Objective
To verify that appropriate Standard Operating Procedures (SOPs) have been identified to operate, clean and maintain
the refrigerator and these should be at least in draft format.
To confirm that a suitable level of training to operate, clean and maintain the refrigerator has been identified.
13.2 Pre Requisites
Pre-Requisite Description Initials Comments
A system is in place to formally issue and control
operating procedures and instructions
There is a system for identifying and documenting
training

13.3 Test Method


Review operating procedure records to verify that SOPs have been identified for the operation, cleaning and
maintenance of the refrigerator and that it is available in at least a draft format.
Record the SOP reference numbers and titles in result table 1.
Review the training records to confirm that training has been identified to cover operation, cleaning and maintenance of
the refrigerator.
Record the training requirement including identification of personnel requiring training in result table 2.
13.4 Acceptance Criteria
There should be suitable SOPs available to operate, clean and maintain the refrigerator. A draft issue will be
acceptable.
Any training requirements have been identified and have been performed or programmed.
13.5 Results
Table 1
SOP Reference Title / Description Pass / Fail

Table 2
Date
Personnel Identified Description Pass / Fail
Performed/Planned

Performed By: Date: IOQ-insert doc reference and revision


Page 20 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

13.6 Conclusion
This section of the protocol has been completed and is deemed to (initial appropriate box below):

Pass Pass with comment Fail

Comments Non-conformance

Performed By: Date: IOQ-insert doc reference and revision


Page 21 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

14. SUMMARY OF TESTS PERFORMED

The following provides an outline summary of the test sections in this protocol.
Non
Check Pass / Pass with Comment / Fail
Conformance

Installation Check (IQ)

Commissioning Check (IQ)

Function & Alarm Checks (OQ)

Temperature Mapping Study (OQ)

Internal SOP & training Review (OQ)

Performed By: Date: IOQ-insert doc reference and revision


Page 22 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

15. LIST OF APPENDICES

No Details

I Non Conformance Forms

II Test Instrumentation Calibration Certificates & Calibration Data

III Temperature Mapping Result Data

IV Additional Data

Performed By: Date: IOQ-insert doc reference and revision


Page 23 of insert total pages up to list of
.... appendices page
IOQ Centre logo can be inserted here

APPENDIX I
NON CONFORMANCE FORMS

IOQ-insert doc reference and revision


Appendices
IOQ Centre logo can be inserted here

APPENDIX II
TEST INSTRUMENTATION CALIBRATION
CERTIFICATES & CALIBRATION DATA

IOQ-insert doc reference and revision


Appendices
IOQ Centre logo can be inserted here

APPENDIX III
TEMPERATURE MAPPING RESULT DATA

IOQ-insert doc reference and revision


Appendices
IOQ Centre logo can be inserted here

APPENDIX IV
ADDITIONAL DATA

IOQ-insert doc reference and revision


Appendices

You might also like