Genesis Range

Numerical
Biased Differential MIB 202
Protection

High Frequency IEC 60255-22-1 class III Description Magnetic Inrush Inhibit
Disturbance PART CASE CUT OUT BEZEL Second harmonic quantities are calculated from the signal l1-l2
MIB 202 takes the current inputs from both the ends of two
2.5 KV Common (Longitudinal) mode SIZE A B C D to provide an inhibit signal, which prevents the protection from
winding power transormer and auto transformer, it is working
1.0 KV Series (Transverse) mode 01 2/3V 149.5 148 170 170 operation for magnetic inrush conditions.
on current differential principle. It provides stability against
Electrostatic IEC 60255-22-2 class III magnetic inrush conditions. Load/through fault stability is Biased Differential
Note:
Discharge achieved through bias setting provided in the relay. It operates The relay is provided with triple slope characteristics.
1. All dimensions are in mm
6 KV Contact Discharge only for internal faults. The zero slope characteristics, which extend upto load current,
2. All dimensions are measured equidistant from centre line
8 KV Air Discharge will give better sensitivity during internal fault with load current.
3. Maximum depth of equipment inside panel : 200mm
Radio Frequency IEC 60255-22-3 class III Design The middle part of the characteristic (normal slope) is used to
Interference The MIB 202 protection consists of the following modules have stability for normal through fault condition. Since the bias
20 MHz to 1000 MHz, 10V/m Ordering Information with in its compact dimensions. slope is variable in the relay, this allows operating current to
Input Module increase automatically to the extent it is required (due to CT
Fast Transient IEC 60255-22-4 class III Relay rating mismatches). Because of this, the relay senses internal faults in
2 KV , 5/50 ns, 2.5 KHz repetitive Power Supply and Output Relay Module
Auxiliary supply range a better way during an external fault.
Measuring Module
Vibration (Sinusoidal) IEC 60255-21-1 class I The last portion of the characteristics is with high slope, which
Front Fascia
Shock & bump IEC 60255-21-2 class I gives more stability during CT saturation for heavy through fault.
The three modules viz. Input, power supply and measuring
Qualification module are plugged into the front fasia which houses switches, Differential Highset
Cutout Details LEDs and LED display for the human machine interface. All The relay is also provided with differential highset protection.
ISO 9001 - 2000
PCBs are well protected from one another and from external The highset protection operates when the DC removed RMS
environment with best shielding for better electromagnetic value of the signal l1-l2 is greater than a preset value which can
compatibility and housed in the enclosed chasis, which is with- be varied. If not required, highset can also be put OFF. The
highset is not restrained by the magnetic inrush detector.
drawable from the outer case. The relay has 6 input current
transformers. The reduced output from current transformer is
digitized by means of analog to digital converter.
The sampled signals are processed by means of micro controller
to derive the RMS value I1, I2. Here I1 represents the current on
HV side and I2 represents the current on LV side computed after
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may any necessary phase and amplitude modification has been
differ slightly from that described and illustrated in this publication. applied. From the values of I1 and I2 the relay will process and
computes operate and restraint signals. Based on this and the
HOSUR WORKS BANGALORE WORKS settings, decisions are taken either to operate or to restrain the

FACT/MIB 202/12-05/REV 0
#98, Sipcot Industrial Complex, #17/3 Arakere, relay.
Hosur 635 126, India. Bannerghatta Road,
Tel: +91 4344 401600/01/02 Bangalore-560 076, India.
Fax: +91 4344 276397 Tel: +91 80 26581023 / 3268 The same relay is suitable for 1A and 5A rating. Different rating
Fax: +91 80 26580642 can be adapted for HV and LV side.
Email: blrworks@easunreyrolle.net
SWITCHGEAR WORKS AUTOMATION DIVISION EXPORTS DIVISION This relay has independent power supply provided with galvanic
Ernavur, Ashirwad, #25, 29th Main, #17/3 Arakere,
Chennai-600 057, India. 4th B Cross, BTM Layout 2nd Stage, Bannerghatta Road, isolation. The relay is suitable for wide range of auxiliary input
Tel: +91 44 25733715/358 Bangalore-560 076, India. Bangalore-560 076, India. supply.
Fax: +91 44 25733468 Tel: +91 80 26685496/51311405 Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: switchgear@easunreyrolle.net Fax: +91 80 26685446 Email: exports@easunreyrolle.net Vector Group Compensation
Email: smabp@easunreyrolle.net The line currents are combined to correct for phase and
magnitude differences and to remove zero sequence
Sales Offices components. These corrections can be applied by selecting the Numerical Biased Differential Protection Relay - MIB 202
Mumbai Delhi Kolkata suitable interposing CT configuration settings.
Tel: +91 22 22022270/22855415 Tel: +91 11 25747321/25747322 Tel: +91 33 22848320
Fax: +91 22 22825703 Fax: +91 11 25747320 Fax: +91 33 22848326
Email: mumbai@easunreyrolle.net Email: delhi@easunreyrolle.net Email: kolkata@easunreyrolle.net
Bangalore Chennai Secunderabad
Tel: +91 80 26685496/51311405 Tel: +91 44 24346425/24347608 Telefax: +91 40 27817847
Fax: +91 22 26685446 Fax: +91 44 24346435 Email: hyderabad@easunreyrolle.net Corporate Office
Email: blroffice@easunreyrolle.net Email: chennai@easunreyrolle.net Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Bhopal Hosur 635 126 India. Tel: +91 4344 401600/01/02
Telefax: +91 755 2684221 Fax: +91 4344 276397
Email: bhopal@easunreyrolle.net www.easunreyrolle.com
Over Excitation Typical Wiring Diagram Monitoring Characteristics
The MIB202 relay contains filtering circuit, which attenuate the Self-monitoring facility The relay operates when
5th harmonic. This allows the relay to remain stable during over I1-I2 >I and
excitation condition with application of suitable relay setting. User Interface
I1+I2
Seven segment LED display I1-I2 >bS x ( ) and
2
Indication LED indications
I1-I2 > X2- K2 for X > (SL)
The relay is provided with easy Human Machine Interface with
Sealable front cover to prevent unauthorised access 2
four push switches and 6 seven-segment LED displays. The Where,
seven-segment display is used to view the settings and tripping I = Current seting
Other Features
details.
Both 1A & 5A CT inputs in one relay X = ( I1+ I2 )
There are four LEDs in front fascia. 2
Both DC & AC auxiliary supply available
Protection Healthy-Green K2 = (SL)2 - 2 (bS)2 (SL)2
Trip indication - Red Drawout modular case SL = bias slope limit
High set trip - Red Compact design bS = bias slope
Sub menu - Red (to set the relay) Non-volatile memory for trip indication
Typical Operating Time
Current Transformer Requirement Current diferential 30ms at 2 x setting
For high-speed operation under all fault conditions the minimum Technical Information Highset overcurrent 25ms at 2 x setting
current transformer knee point voltage should equal or exceed
Vk > 4 * lF (A + C) CT Input Rating 1A & 5A
Output Contacts
Where, (Any one can be adapted The relay has 5 output contacts
lF = Either the maximum three phase at site) Trip (biased diff & highset)
through-fault current (as limited by the
Frequency 50Hz HV trip and LV trip 2N/O
transformer impedance) or the high-set
Alarm
setting, whichever is greater
Auxiliary Supply Differential Highset 1N/O
A = The secondary winding resistance of each
star connected CT Nominal Voltage Voltage range Biased Differential 1N/O
C = The CT secondary loop lead resistance Protection unhealthy 1N/C
30/48/110V DC 24 - 135V DC
for internal earth faults Contact Rating
110/220V DC or 110V AC 88-280V DC
Carry continuously 5A AC rms or DC
Applications Settings Make and carry 20A for 0.2 sec
Current Differential
Two winding power transformers Burden
Auto transformers Initial differential setting
AC Burden
Biased differential protection for generators I 10% to 50% of In in steps of 5%
5 A Rating 0.4VA
Bias slope 1 A Rating 0.05VA
Features bS 10% to 70% in steps of 5%
Auxiliary Supply Input
Protection Bias slope limit
Quiescent (typical) 6W
Biased differential (87) SL 200% to 2000% of In in steps of 100%
Instantenous differential highset (87 HS) Current amplitude correction for HV winding Environmental
Numerical, true RMS measurement Ah 0.50 to 2.50 in steps of 0.01 Temperature IEC 60068-2-1/2
Integral current amplitude multiplier and vector group Operating Range -10 C to +55C
Current amplitude correction for LV winding
compensation Storage Range -25 C to +70C
3-slope adjustable bias setting AL 0.50 to 2.50 in steps of 0.01
Immune to magnetic inrush Vector group compensation for HV winding Humidity IEC 60068-2-3
Interposing CTs are not required 4 days at 40C and 93%RH
Vh Yy0, Yy2, Yy4, Yy6, Yy8, Yy10, Yd1, Yd3, Yd5,
Control Yd7, Yd9, Yd11, Ydy0 and Ydy6 Transient Overvoltage IEC 60255-5
The relay has 5 output contacts Vector group compensation for LV winding 5KV, 1.2/50 s, 0.5J between all terminals and earth or between any
Trip (biased diff & highset) VL Yy0, Yy2, Yy4, Yy6, Yy8, Yy10, Yd1, Yd3, Yd5, two terminals without damage or flashover
HV trip and LV trip 2N/O Yd7, Yd9, Yd11, Ydy0 and Ydy6 Insulation IEC 60255-5
Alarm
Differential Highset 2.0 KVrms for 1 min between all terminals and earth
Differential Highset 1N/O
H Off, 400% to 2500% of In in steps of 100% 2.0 KVrms for 1 min between independent circuits
Biased Differential 1N/O
1.0 KVrms for 1 min across normally open contacts
Protection unhealthy 1N/C Typical Application Diagram and Differential Characteristics
Over Excitation Typical Wiring Diagram Monitoring Characteristics
The MIB202 relay contains filtering circuit, which attenuate the Self-monitoring facility The relay operates when
5th harmonic. This allows the relay to remain stable during over I1-I2 >I and
excitation condition with application of suitable relay setting. User Interface
I1+I2
Seven segment LED display I1-I2 >bS x ( ) and
2
Indication LED indications
I1-I2 > X2- K2 for X > (SL)
The relay is provided with easy Human Machine Interface with
Sealable front cover to prevent unauthorised access 2
four push switches and 6 seven-segment LED displays. The Where,
seven-segment display is used to view the settings and tripping I = Current seting
Other Features
details.
Both 1A & 5A CT inputs in one relay X = ( I1+ I2 )
There are four LEDs in front fascia. 2
Both DC & AC auxiliary supply available
Protection Healthy-Green K2 = (SL)2 - 2 (bS)2 (SL)2
Trip indication - Red Drawout modular case SL = bias slope limit
High set trip - Red Compact design bS = bias slope
Sub menu - Red (to set the relay) Non-volatile memory for trip indication
Typical Operating Time
Current Transformer Requirement Current diferential 30ms at 2 x setting
For high-speed operation under all fault conditions the minimum Technical Information Highset overcurrent 25ms at 2 x setting
current transformer knee point voltage should equal or exceed
Vk > 4 * lF (A + C) CT Input Rating 1A & 5A
Output Contacts
Where, (Any one can be adapted The relay has 5 output contacts
lF = Either the maximum three phase at site) Trip (biased diff & highset)
through-fault current (as limited by the
Frequency 50Hz HV trip and LV trip 2N/O
transformer impedance) or the high-set
Alarm
setting, whichever is greater
Auxiliary Supply Differential Highset 1N/O
A = The secondary winding resistance of each
star connected CT Nominal Voltage Voltage range Biased Differential 1N/O
C = The CT secondary loop lead resistance Protection unhealthy 1N/C
30/48/110V DC 24 - 135V DC
for internal earth faults Contact Rating
110/220V DC or 110V AC 88-280V DC
Carry continuously 5A AC rms or DC
Applications Settings Make and carry 20A for 0.2 sec
Current Differential
Two winding power transformers Burden
Auto transformers Initial differential setting
AC Burden
Biased differential protection for generators I 10% to 50% of In in steps of 5%
5 A Rating 0.4VA
Bias slope 1 A Rating 0.05VA
Features bS 10% to 70% in steps of 5%
Auxiliary Supply Input
Protection Bias slope limit
Quiescent (typical) 6W
Biased differential (87) SL 200% to 2000% of In in steps of 100%
Instantenous differential highset (87 HS) Current amplitude correction for HV winding Environmental
Numerical, true RMS measurement Ah 0.50 to 2.50 in steps of 0.01 Temperature IEC 60068-2-1/2
Integral current amplitude multiplier and vector group Operating Range -10 C to +55C
Current amplitude correction for LV winding
compensation Storage Range -25 C to +70C
3-slope adjustable bias setting AL 0.50 to 2.50 in steps of 0.01
Immune to magnetic inrush Vector group compensation for HV winding Humidity IEC 60068-2-3
Interposing CTs are not required 4 days at 40C and 93%RH
Vh Yy0, Yy2, Yy4, Yy6, Yy8, Yy10, Yd1, Yd3, Yd5,
Control Yd7, Yd9, Yd11, Ydy0 and Ydy6 Transient Overvoltage IEC 60255-5
The relay has 5 output contacts Vector group compensation for LV winding 5KV, 1.2/50 s, 0.5J between all terminals and earth or between any
Trip (biased diff & highset) VL Yy0, Yy2, Yy4, Yy6, Yy8, Yy10, Yd1, Yd3, Yd5, two terminals without damage or flashover
HV trip and LV trip 2N/O Yd7, Yd9, Yd11, Ydy0 and Ydy6 Insulation IEC 60255-5
Alarm
Differential Highset 2.0 KVrms for 1 min between all terminals and earth
Differential Highset 1N/O
H Off, 400% to 2500% of In in steps of 100% 2.0 KVrms for 1 min between independent circuits
Biased Differential 1N/O
1.0 KVrms for 1 min across normally open contacts
Protection unhealthy 1N/C Typical Application Diagram and Differential Characteristics
Genesis Range

Numerical
Biased Differential MIB 202
Protection

High Frequency IEC 60255-22-1 class III Description Magnetic Inrush Inhibit
Disturbance PART CASE CUT OUT BEZEL Second harmonic quantities are calculated from the signal l1-l2
MIB 202 takes the current inputs from both the ends of two
2.5 KV Common (Longitudinal) mode SIZE A B C D to provide an inhibit signal, which prevents the protection from
winding power transormer and auto transformer, it is working
1.0 KV Series (Transverse) mode 01 2/3V 149.5 148 170 170 operation for magnetic inrush conditions.
on current differential principle. It provides stability against
Electrostatic IEC 60255-22-2 class III magnetic inrush conditions. Load/through fault stability is Biased Differential
Note:
Discharge achieved through bias setting provided in the relay. It operates The relay is provided with triple slope characteristics.
1. All dimensions are in mm
6 KV Contact Discharge only for internal faults. The zero slope characteristics, which extend upto load current,
2. All dimensions are measured equidistant from centre line
8 KV Air Discharge will give better sensitivity during internal fault with load current.
3. Maximum depth of equipment inside panel : 200mm
Radio Frequency IEC 60255-22-3 class III Design The middle part of the characteristic (normal slope) is used to
Interference The MIB 202 protection consists of the following modules have stability for normal through fault condition. Since the bias
20 MHz to 1000 MHz, 10V/m Ordering Information with in its compact dimensions. slope is variable in the relay, this allows operating current to
Input Module increase automatically to the extent it is required (due to CT
Fast Transient IEC 60255-22-4 class III Relay rating mismatches). Because of this, the relay senses internal faults in
2 KV , 5/50 ns, 2.5 KHz repetitive Power Supply and Output Relay Module
Auxiliary supply range a better way during an external fault.
Measuring Module
Vibration (Sinusoidal) IEC 60255-21-1 class I The last portion of the characteristics is with high slope, which
Front Fascia
Shock & bump IEC 60255-21-2 class I gives more stability during CT saturation for heavy through fault.
The three modules viz. Input, power supply and measuring
Qualification module are plugged into the front fasia which houses switches, Differential Highset
Cutout Details LEDs and LED display for the human machine interface. All The relay is also provided with differential highset protection.
ISO 9001 - 2000
PCBs are well protected from one another and from external The highset protection operates when the DC removed RMS
environment with best shielding for better electromagnetic value of the signal l1-l2 is greater than a preset value which can
compatibility and housed in the enclosed chasis, which is with- be varied. If not required, highset can also be put OFF. The
highset is not restrained by the magnetic inrush detector.
drawable from the outer case. The relay has 6 input current
transformers. The reduced output from current transformer is
digitized by means of analog to digital converter.
The sampled signals are processed by means of micro controller
to derive the RMS value I1, I2. Here I1 represents the current on
HV side and I2 represents the current on LV side computed after
The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may any necessary phase and amplitude modification has been
differ slightly from that described and illustrated in this publication. applied. From the values of I1 and I2 the relay will process and
computes operate and restraint signals. Based on this and the
HOSUR WORKS BANGALORE WORKS settings, decisions are taken either to operate or to restrain the

FACT/MIB 202/12-05/REV 0
#98, Sipcot Industrial Complex, #17/3 Arakere, relay.
Hosur 635 126, India. Bannerghatta Road,
Tel: +91 4344 401600/01/02 Bangalore-560 076, India.
Fax: +91 4344 276397 Tel: +91 80 26581023 / 3268 The same relay is suitable for 1A and 5A rating. Different rating
Fax: +91 80 26580642 can be adapted for HV and LV side.
Email: blrworks@easunreyrolle.net
SWITCHGEAR WORKS AUTOMATION DIVISION EXPORTS DIVISION This relay has independent power supply provided with galvanic
Ernavur, Ashirwad, #25, 29th Main, #17/3 Arakere,
Chennai-600 057, India. 4th B Cross, BTM Layout 2nd Stage, Bannerghatta Road, isolation. The relay is suitable for wide range of auxiliary input
Tel: +91 44 25733715/358 Bangalore-560 076, India. Bangalore-560 076, India. supply.
Fax: +91 44 25733468 Tel: +91 80 26685496/51311405 Tel: +91 80 26581023 / 3268
Fax: +91 80 26580642
Email: switchgear@easunreyrolle.net Fax: +91 80 26685446 Email: exports@easunreyrolle.net Vector Group Compensation
Email: smabp@easunreyrolle.net The line currents are combined to correct for phase and
magnitude differences and to remove zero sequence
Sales Offices components. These corrections can be applied by selecting the Numerical Biased Differential Protection Relay - MIB 202
Mumbai Delhi Kolkata suitable interposing CT configuration settings.
Tel: +91 22 22022270/22855415 Tel: +91 11 25747321/25747322 Tel: +91 33 22848320
Fax: +91 22 22825703 Fax: +91 11 25747320 Fax: +91 33 22848326
Email: mumbai@easunreyrolle.net Email: delhi@easunreyrolle.net Email: kolkata@easunreyrolle.net
Bangalore Chennai Secunderabad
Tel: +91 80 26685496/51311405 Tel: +91 44 24346425/24347608 Telefax: +91 40 27817847
Fax: +91 22 26685446 Fax: +91 44 24346435 Email: hyderabad@easunreyrolle.net Corporate Office
Email: blroffice@easunreyrolle.net Email: chennai@easunreyrolle.net Easun Reyrolle Limited. 98 Sipcot Industrial Complex
Bhopal Hosur 635 126 India. Tel: +91 4344 401600/01/02
Telefax: +91 755 2684221 Fax: +91 4344 276397
Email: bhopal@easunreyrolle.net www.easunreyrolle.com