You are on page 1of 2

01

Gateway

MiCOM A300-GTW
Communication front-end for electrical substations

The MiCOM A300- GTW is a substation front-end


communication device capable of interconnecting
bay IEDs to any remote monitoring and control
system. Its enhanced protocol converter
capability makes it a perfect match for versatile
solutions.

Simplified Commissioning and Maintenance


MiCOM A300-Gateway provides flexible interfaces
designed to deploy multiple LAN architectures.
This type of solution is typically chosen to minimize
network failure impact. Furthermore, the data segregation
promoted by multiple networks allows incremental
commissioning, minimizing the total intervention time.
The interoperability promoted by different standardized
protocols ensures a secure solution upgrade and extension.

CUSTOMER BENEFITS High level of availability


The MiCOM A300-GTW runs on robust hardware not
Simplified commissioning and containing any rotating parts.
maintenance Its EMC immunity, compliant to IEC 61850-3 requirements,
High level of availability allows it to work within the substation environment
constraints.
IEC 61850 standard compliant The optional hardware redundancy provides the ideal
alternative to significantly increase the system availability.
Smarter networks powered by
MiCOM A300-GTW is a scalable solution, based on modular
IEC 61131-3 automation engine
hardware, offering expansion capabilities that enable
connection to complex system networks.
Gateway Communication front-end for electrical substations 02

IEC 61850 standard compliant


MiCOM A300-GTW offers a certified TECHNICAL DATA
IEC 61850 solution to interface any
IEC 61850 compliant IED. The delivery General Hardware characteristics
includes an associated engineering toolsuite,
Mounting (Option): Wall/Panel/Stand
ensuring simple IEC 61850 configuration
Weight: 6 kg
and maintenance. MiCOM A300-GTW
Power Consumption: 27 W
also participates to create Cyber-Secure
Power supply: 24 Vdc; 36 - 60 Vdc; 90 - 350 Vdc; 100 - 240
solutions, offering restricted access to the
Vac (50-60 Hz)
substation and IEDs.
System Hardware
CPU: Celeron M 1.0 GHz or Pentium M 1.8 GHz
Memory: 1 GB SDRAM
Battery Backup: RAM 512 KB
Expansion Slots: 4 x PCI V 2.2
Indicators: LEDs for power, power input 1, power input 2,
power fault, IDE, diagnosis, 4 COM ports Tx/Rx

Environment and EMC


Humidity: 95% @ 40 C (non-condensing)
Operating Temperature: -20 to 55 C @ 5 to 85% RH
Shock Protection: IEC 60068 2-27
Vibration Protection: IEC 60068 2-64
EMC: IEC61000-4-4, 61400-6-2, Isolation 4kV (AC)

Communication capabilities
Master/Client protocols: IEC 61850 Client IEC 61850 servers,
MODBUS serial and TCP/ IP, Profibus DP
Slave/Server protocols: IEC 61850 Server, IEC 60870-5-101,
Smarter networks powered by
IEC 60870-5-104, MODBUS serial and TCP/ IP, OPC DA2
IEC 61131-3 automation engine
The MiCOM A300-GTW is designed to run Communications
real time automation based on a IEC 61131-3 LAN: 2 x 10/100Base-T RJ-45 ports
standard programming languages. Ethernet switch (Option): 2 x MiCOM H152 or H162
The capacity to execute distributed redundant Ethernet boards
automation over collaborative networks is a Serial Ports: 2 RS-232, 2 x RS-232/422/485 with DB9
significant step to smarter grids. USB Ports: 4 x USB Rev. 2.0 compliant

Software capabilities
multi-client IEC 60870-5-104
multi-client DNP3 over IP
2011 Schneider Electric Industries SAS - All rights reserved

more than 10000 data


multi-IEC 61131-3 resources

Schneider Electric Industries SAS


35, rue Joseph Monier As standards, specifications and designs change from time
CS 30323 to time, please ask for confirmation of the information given
F - 92506 Rueil Malmaison Cedex (France) in this publication.
Tel.: +33 (0) 1 41 29 70 00
RCS Nanterre 954 503 439 Design: Schneider Electric Industries SAS
Capital social 896 313 776 Photos: Schneider Electric Industries SAS This document has been
www.schneider-electric.com Printed: Made in France printed on recycled paper.

NRJED111337EN 12-2011