MiCOM P111
Three phase and earth fault overcurrent relays
Models
Functions overview
A B C E F
50/51 Three-phase overcurrent I>> (DT)
CB or contactor control;
Local (via input) / Remote
86 Output relay latching
Setting groups
1 2 2 2 2
(front panel, remote or inputs)
Measurements
Events records
MAIN FUNCTIONS
The relays of these ranges are compromised of
full suite of protection functions and auxiliaries;
each function can be individually configured or
disabled to suit any particular application.
The available functions, including protection,
inputs and outputs are easily programmable by
means of user friendly front panel interface and
the S1 software interface.
The 4 digit LED display provides the user with key
information (faults, measurements, settings etc.).
The menus have a pull-down structure for easy
use and quick access to any data.
FUNCTIONAL OVERVIEW
(Description of ANSI code nos. see Functions overview)
Communication
Measurement
R E AR Up to 4 binary outputs
P O RT Fault records
3
RS485 port 86
to setting software S1 Event recording
to SCADA systems 200
Up to 4 digital inputs
I
Conventional
signalling
Io>
Time
Time
tIp>
tIo>
I> Io>>
tI> tIo>>
I>>
tI>>
Current Current
If T1-T2 input is configured as PTC input MiCOM P111 allows controlling of circuit breaker
and resistance of the sensors loop connected to or contactor. The user may select switch type by
input : T1- T2 increase, then protection operates
programming main output relays. The selection
instantaneously.
changes logic of control.
Up to 6 PTC sensors can be connected in series.
The PTC input operates instantaneously. It is possible to make local (via selected binary
This function can be configured to make a trip or input) or remote (via RS485) trip or close
alarm. command. Blocking of remote command could
be done via selected binary input (switch : local/
External protection trip
remote).
The external protection trip operates if an input The remote control is not possible in model
state, which is programmed to this function (ZZ), A and F (which have no RS485 port).
changes its state.
Setting groups
The protection can be configured to trip or
send a warning signal (alarm).
An external condition may request the need for
Trip operation is instantaneous. different settings. MiCOM P111 provides two
Output relay latching (86) setting group.
Binary Binary
inputs IL1 IL2 IL3 inputs
V1 V2 C 33 34 41 44 42 1 2 3 4 5 6 V1 V2 C 33 34 41 44 42
L3 L2 L1
P3 P4 Model C, E, F P3 P4 Model C, E, F
A1 I / O card A1 I / O card
Vx Vx
A2 Model B, C, E, F A2 Model B, C, E, F
P1 P2 Io P1 P2 Io RS 485
RS 485
13 14 23 24 T1 T2 S 1 S2 K L Tr+ Tr- 13 14 23 24 T1 T 2 S 1 S2 K L Tr+ Tr-
The P111 includes configurable digital inputs The menus have a pull-down structure allowing
and output relays for CB (contactor) control and easy and quick access to any data.
signalling.
4 digit LED display with 5 additional signalling
Inputs can be configured for blocking, resetting, LEDs informs the user about settings,
control, etc. measurements, faults, etc.
The number of binary inputs and output relays
can be selected by choosing the type of model. 4 digit LED display
Model A and B have 2 free-potential logic inputs
and 2 relay outputs. Model C, E and F have
additional 2 potential logic inputs and 2 additional
relay outputs.
Signalling LEDs
Cursor key
Schneider Electric
35, rue Joseph Monier As standards, specifications and designs change from time to time, please ask for confirmation
CS 30323 of the information given in this publication.
92506 Rueil-Malmaison Cedex, France
Tel: +33 (0) 1 41 29 70 00 This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 Publishing: Schneider Electric
www.schneider-electric.com Design: Schneider Electric
Printing:
NRJED111029EN 11-2011