Job Title: Typical Portal Frame Design for a Supermarket
Subject: Determination of Wind Loads
Client: CEMPS, Made by: 650047039 Date: Nov. 2016
University of Exeter Checked by: Date: Nov. 2016
REFERENCE CALCULATIONS OUTPUT
5m
16.00 m
Basic Data:
Dimensions of Supermarket
Height to eave, h = 5.00 m (Given)
Portal Span, d = 16.00 m (Given)
Frame spacing, ls = 6.00 m (assumed)
Duopitch roof slope, = 6.00 deg
Total length, b = 30.00 m
Total structure height, H = 5.84 m
Location
City: Exeter
Altitude: 50 m (a.s.l)
NB: The mean wind velocity [v m (z)] values for z > z min (i.e. from 2.0m to
5.84m) computed from eqn 4.3 are shown in Table 1.
NB: The wind turbulence [l v (z)] values computed from eqn 4.7 above
are shown in Table 1.
NB: The peak velcoity pressure [q p (z)] values computed from eqn 4.8
above are shown in Table 1.
d = 16m H = 5.84m
b = 30m
wind
D E A B C
= 00
e/5 (d - e)
(Plan) d = 16m
(End Elevation)
e = min (b, 2h) = 11.680 m < d = 16.00 m
Table 7.1 Recommended values of external pressure coefficients for walls, cpe
ratio (h / d) = (5.84 / 16) = 0.365
cpe = 0.715 [for Zone D] (obtained by linear interpolation )
cpe = -0.331 [for Zone E] (obtained by linear interpolation )
e/4 F
H I
d = 16m
e/4 F
ridge line
b = 30m
Fig. 7.8 wind
G H J I
= 00
e/4 F
e/10 e/10
Table 7.4 Recommended values of external pressure coeff. for duopitch roofs, cpe
Table 7.4(b) Wind direction, = 90 deg (blows perpendicular to frame span )
Zone F G H I
cpe (-ve) -1.57 -1.30 -0.69 -0.59
Zone F G H I J
cpe (-ve) -1.62 -1.16 -0.57 -0.58 -0.64
cpe (+ve) 0.02 0.02 0.02 0.00 0.18
6.211kN/m 6.211kN/m
0.84 m
2.741kN/m
1.269kN/m
D E 5.00 m
16.00 m
NB:
c pi = +0.20 is considered the Most Onerous as it results in a force which acts
in same direction with that caused by the external pressure coefficients making
its combination with the chosen c pe critical for the structure
Internal wind load on the column & roof per unit length, Wi (kN/m)
0.84 m
5.00 m
0.767kN/m
16.00 m
Job No.: ECMM150-CW1 Sheet of Rev.: 0
Job Title: Typical Portal Frame Design for a Supermarket
Subject: Determination of Wind Loads
Client: CEMPS, Made by: 650047039 Date: Nov. 2016
University of Exeter Checked by: Date: Nov. 2016
REFERENCE CALCULATIONS OUTPUT
Net wind load acting on the Portal Frame per unit length, WNet (We - Wi):
NB: The wind loads on the roof are measured perpendicular to the slope
6.978 6.978
0.84 m
2.036
5.00 m
(kN/m )
16.00 m
Resolving the above roof loads on plan results in the below loads:
W*sin W*sin
W*cos
0.729
0.84 m
2.036
5.00 m
(kN/m )
16.00 m