You are on page 1of 24

COOPER POWER

Instructional Literature IL0104001E Effective November 2014 SERIES

NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase


microprocessor-controlled; installation and operation
instructions (S280-43-1)
Ratings and specifications
Check recloser ratings prior to installation. . . 3
Dimensions
NOVA i mechanism interface
Control-powered interface . . . . . . . . . . . . . . . 5
Installation procedure
Moving the recloser . . . . . . . . . . . . . . . . . . . 6
Lifting the recloser . . . . . . . . . . . . . . . . . . . . 6
Remove recloser from service . . . . . . . . . . . 8
Grounding the nova i recloser . . . . . . . . . . 8
Operation
Electrical operation . . . . . . . . . . . . . . . . . . . . 11
Open/close contact position indicator . . . . . 11
Figure 1.
Hotstick operation (manual open, electrical
NOVA i Three-phase, microprocessor-controlled recloser.
close) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
(shown with four-hole, flat-pad terminal accessory.)
Internal voltage sensing option
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Contents
Form 6/FXD control settings . . . . . . . . . . . . . 14
Safety information
Accessories
Hazard statement definitions . . . . . . . . . . . . . 2
Auxiliary switch . . . . . . . . . . . . . . . . . . . . . . . 15
Safety instructions . . . . . . . . . . . . . . . . . . . . . 2
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Product information
Pole-mounting hanger . . . . . . . . . . . . . . . . . . 15
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Arrester-mounting brackets . . . . . . . . . . . . . . 16
Read this manual first . . . . . . . . . . . . . . . . . 3
Substation-mounting frame . . . . . . . . . . . . . . 17
Additional information . . . . . . . . . . . . . . . . . . 3
Service information
Acceptance and initial inspection . . . . . . . . . 3
Service requirements . . . . . . . . . . . . . . . . . . 18
Handling and storage . . . . . . . . . . . . . . . . . . . 3
Frequency of inspection. . . . . . . . . . . . . . . . . 18
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Testing operation . . . . . . . . . . . . . . . . . . . . . . 18
Description of operation . . . . . . . . . . . . . . . . 3
High-potential withstand testing . . . . . . . . . . 19
Inspection of nova i module . . . . . . . . . . . . . 20
Troubleshooting
Unit will not close . . . . . . . . . . . . . . . . . . . . . 20
Unit will not open electrically . . . . . . . . . . . . 20
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

Safety for life Safety instructions


Cooper Power Systems products meet or exceed all applicable Following are general caution and warning statements that apply
industry standards relating to product safety. We actively promote to this equipment. Additional statements, related to specific tasks
safe practices in the use and maintenance of our products through and procedures, are located throughout the manual.
our service literature, instructional training programs, and the
continuous efforts of all Cooper Power Systems employees
involved in product design, manufacture, marketing, and service. DANGER
We strongly urge that you always follow all locally approved safety
Hazardous voltage. Contact with hazardous voltage will cause death or
procedures and safety instructions when working around high
severe personal injury. Follow all locally approved safety procedures
voltage lines and equipment and support our Safety For Life
mission. when working around high- and low-voltage lines and equipment.

Safety information
WARNING
The instructions in this manual are not intended as a substitute for
proper training or adequate experience in the safe operation of the Before installing, operating, maintaining, or testing this equipment,
equipment described. Only competent technicians who are carefully read and understand the contents of this manual. Improper
familiar with this equipment should install, operate, and service it. operation, handling or maintenance can result in death, severe personal
injury, and equipment amage.
A competent technician has these qualifications:
Is thoroughly familiar with these instructions.
Is trained in industry-accepted high- and low-voltage safe
operating practices and procedures. WARNING
Is trained and authorized to energize, de-energize, clear, and
This equipment is not intended to protect human life. Follow all locally
ground power distribution equipment.
approved procedures and safety practices when installing or operating
Is trained in the care and use of protective equipment such as this equipment. Failure to comply can result in death, severe personal
flash clothing, safety glasses, face shield, hard hat, rubber
injury and equipment damage.
gloves, hotstick, etc.
Following is important safety information. For safe installation and
operation of this equipment, be sure to read and understand all
cautions and warnings. WARNING
Power distribution and transmission equipment must be properly
Hazard statement definitions selected for the intended application. It must be installed and serviced by
This manual may contain four types of hazard statements: competent personnel who have been trained and understand proper
safety procedures. These instructions are written for such personnel and
are not a substitute for adequate training and experience in safety
DANGER: Indicates an imminently hazardous situation procedures. Failure to properly select, install, or maintain power
which, if not avoided, will result in death or serious distribution and transmission equipment can result in death, severe
injury.
personal injury, and equipment damage.

WARNING: Indicates a potentially hazardous situation


which, if not avoided, could result in death or serious
injury.

CAUTION: Indicates a potentially hazardous situation


which, if not avoided, may result in minor or moderate
injury.

CAUTION: Indicates a potentially hazardous situation


which, if not avoided, may result in equipment damage
only.

1
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Product information
Introduction Handling and storage
Service Information S280-43-1 provides installation, operation, and Be careful during handling and storage of the recloser to minimize
maintenance instructions for the NOVA i three-phase, the possibility of damage. Refer to the Moving the Recloser and
microprocessor-controlled recloser. Before installing and operating Lifting the Recloser sections. If the recloser is to be stored for any
this recloser, carefully read and understand the contents of this length of time prior to installation, provide a clean, dry storage
manual. area.

Read this manual first Standards


Read and understand the contents of this manual and follow all NOVA i reclosers are designed and tested in
locally approved procedures and safety practices before installing accordance with:
or operating this equipment. This recloser is used in conjunction
IEC 62271-111 2005
with a Cooper Power Systems microprocessor-based recloser
control. Refer to Service Information S280-70-18 for installation IEEE Standard C37.60-2012.
information on the Form 6/FXD pole mount control. QUALITY STANDARDS
ISO 9001:2000 Certified Quality Management System.
Additional information
These instructions cannot cover all details or variations in the
equipment, procedures, or process described nor provide
Description of operation
directions for meeting every possible contingency during The NOVA i recloser is a three-phase, vacuum-interrupting
installation, operation, or maintenance. For additional information, recloser designed for electrical distribution systems through 38
please contact your Cooper Power Systems representative. kV. The NOVA i recloser is designed and tested to be compatible
with Cooper Power Systems control-powered Form 6/FXD
control.
Acceptance and initial inspection
Each recloser is completely assembled, tested, and inspected at The solid polymer insulation system does not rely on a gaseous,
the factory. It is in good condition when accepted by the carrier liquid, or foam dielectric. The NOVA i recloser is highly resistant to
for shipment. Upon receipt, inspect the shipping container for ozone, oxygen, moisture, contamination, and ultraviolet light. The
signs of damage. Unpack the recloser and inspect it thoroughly for NOVA i recloser has three solid-polymer interrupter modules,
damage incurred during shipment. If damage is discovered, file a polymer current transformers, and a low-energy magnetic actuator
claim with the carrier immediately. mechanism. It is suitable for operation through a temperature
range of -40C to +65C.

2
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

Ratings and specifications

Check recloser ratings prior to installation


The recloser must be applied within its specified ratings. Check nameplate ratings and compare with the
system characteristics at the point of application prior to installation. Tables 1, 2, 3, and 4 list the ratings and
specifications for the NOVA i recloser.

Table 1
Voltage ratings (kV)
Description 15 kV 27 kV 38 kV

Rated Basic Impulse Level (BIL) 15.5 kV 27 kV 38 kV


Radio Noise Limit (v) 110 kV 125 kV* 170 kV
Power Frequency Withstand, Dry 100 @ 9.4 kV 100 @ 16.4 kV 100 @ 23.0 kV
50 kV 60 kV 70 kV
Power Frequency Withstand, Wet 45 kV 50 kV 60 kV
*150kV option available.

Table 2
Current ratings (A)
Description 15 kV 27 kV 38 kV

Short circuit current, 630 A* 630 A* 630 A*


Symmetrical making current, 12.5 kA** 12.5 kA** 12.5 kA
Asymmetrical peak making current, 31.0 kA 31.0 kA 31.0 kA
20.0 kA 20.0 kA 20.0 kA
Asymmetrical rms
*800 A option available.
** 16.0 kA option available.

Table 3
Mechanical ratings
Description 15 kV 27 kV 38 kV

Min. Mechanical/electrical operations


Without maintenance (c-o) 10,000 10,000 10,000
Mass (weight) - kg (lbs.) 110 (242) 115 (253) 125 (275)

Table 4
Duty cycle*
Percentage of Number of Minimum
Type Interrupting Rating Unit Operations Circuit X/R Value
NOVA i 15-20 44 4
45-55 56 8
90-100 16 17
Total 116
*Compliant with IEC 62271-111 2005
*Compliant with IEEE Standard C37.60-2012

3
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

E
394 394
Terminal
connectors
A A

Terminal C
connectors

298

1000
285

D Note: All dimensions are mm. Dimensions shown are approximate.

Figure 2.
NOVA i Three-phase recloser dimensions.

Terminal options A B C D E

Eyebolt, 1/0-500mcm
89 NOVA 15i 809 528 400.5 285
Cable range (630 a max.)
Eyebolt, 4/0 - 1000 mcm
111 NOVA 27i 908 627 400.5 285
Cable range (800 a max.)
Flat Pad, 2-hole
119 NOVA 38i 1007 676 441.1 298.6
(630 a max.)
Flat Pad, 4-hole
121
(800 a max.)

Creepage distances
Description Creepage distance (mm) Creep (mm/kV)

Terminal to terminal 1180 79


NOVA 15i
Lower terminal to ground/earth 671 45
Terminal to terminal 1473 55
NOVA 27i
Lower terminal to ground/earth 951 35
Terminal to terminal 1763 46
NOVA 38i
Lower terminal to ground/earth 1215 32

4
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

NOVA i mechanism interface


figure

Control-powered interface
The NOVA i recloser mechanism (see Figures 3 and 4) with the
control-powered interface is fully operational with a Form 6/FXD
microprocessor-based control equipped with the required dc-to-dc
converter, interface circuit, and a fully shielded 19-pin cable. The
control-powered interface includes a 19-pin receptacle on the
recloser and an internal heater (for humidity control) powered from
the control input power supply.
The dc-to-dc converter board converts the controls 24 V dc battery
supply to 53 V dc to charge the trip/close capacitors in the NOVA i
mechanism. The dc-to-dc converter board also houses voltage
monitoring and conditioning circuits that protect the battery from
failure and provide trip/close operations without ac power. In the
absence of ac power to the electronic control, the control battery
will provide the trip and close operations. A complete four-trip
sequence with minimal reclose intervals as configured for each
control is obtainable without ac power. The recloser and control
system is capable of exceeding over one thousand operations on
battery power only.

Figure 4.
Control-powered NOVA i recloser configuration with potential
transformer input power.

Magnetic actuator Mechanical


Trip-and-close Manual open handle operations counter Heater
capacitors
Heater

Open/close
Aluminum mechanism contact position Control cable Ground connector
housing (standard) indicator Actuator board Ct protection board receptacle #10 - #2 stranded

Figure 3.
NOVA i recloser mechanism with control-powered interface (view from bottom of recloser with bottom cover removed).

5
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Installation procedure

WARNING CAUTION
This equipment is not intended to protect human life. Follow all locally Personal injury. Bushings have sharp edges. Wear protective gloves
approved procedures and safety practices when installing or operating when handling the unit. Failure to do so can result in cuts and abrasions.
this equipment. Failure to comply can result in death, severe personal
injury, and equipment damage.
3. Install the recloser. Install the recloser in the appropriate
Cooper Power Systems pole- or substation-mounting frame. See
Figure 6 for moving and lifting instructions.
WARNING CAUTION
Hazardous voltage. Always use a hotstick when working with this Follow all locally approved safety practices when lifting and mounting
equipment. Failure to do so could result in contact with high voltage, the equipment. Use the lifting lugs provided. Lift the unit smoothly and do
which will cause death or severe personal injury. not allow the unit to shift. Improper lifting can result in equipment
damage.
When installing the recloser, refer to the applicable
recloser-mounting frame instructions. Installation instructions are
included with the mounting frame. Moving the recloser
1. Check the nameplate ratings. Make sure the ratings, settings, NOVA i reclosers are shipped in an enclosed crate and palletized.
and interface options on the recloser nameplate (see Figures 5 When moving with a fork truck/lift, the recloser must remain
and 12) are correct for the planned installation. bolted to the pallet to avoid damage to the OPEN/CLOSE contact
position indicator.

Lifting the recloser


Follow all approved safety practices when making hitches and
lifting the equipment. Lift the unit smoothly and do not allow the
unit to shift.

CAUTION
Tip-over Hazard. High center of gravity. Use a 4-point hitch to prevent
switchgear from overturning during lifting operations. Improper lifting
can result in personal injury or equipment damage.

Figure 5.
Nameplate.

2. Perform high-potential withstand tests. Prior to installing the


NOVA i recloser, perform high-potential withstand tests. Refer
to the Service Information section for high-potential withstand
test procedures.

A: Sling height (H) for 15 kV units: 875 mm


Sling height (H) for 27 kV units: 1115 mm
Sling height (H) for 38 kV units: 1250 mm

B: Center of gravity (Cg) is approximately 100 mm


below plane of lower terminals.

Figure 6.
Moving and lifting the NOVA i recloser.

6
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

WARNING Bypass
switch
Hazardous voltage. Solidly ground all equipment. Failure to comply can
result in death, severe personal injury, and equipment damage.

4. Ground the recloser. Make the ground connection to the


ground connector. The ground connector is located on the back Disconnect Disconnect
of the mechanism housing. See Figure 3 for ground connector switch switch
location. The ground clamp accepts #10 to #2 stranded cables.
5 6
See Figures 9, 10, and 11 for recommended grounding for the
Recloser
NOVA i recloser.
5. Install the control. Refer to the control installation manual and 3 4
install the control. Make sure the control cable is connected
between the control and the recloser, the control is properly 1 2
programmed for the planned installation, and the control is
grounded.
Surge Surge
6. Make high-voltage line connections (See Figure 7). arresters arresters
Note: Disconnect switches and bypass switches are not
required but are highly recommended as they facilitate switching
and isolation.

CAUTION Figure 7.
Equipment Damage. Do not adjust or rotate bushing terminals. The ushing Connection diagram shows complete surge protection
terminals are factory-calibrated to meet the continuous current and illustrates bypass and disconnect switches.
requirement of the switchgear. Adjusting or rotating the bushing
terminals can damage the encapsulated interrupter resulting in
equipment damage or personal injury.

A. Connect high-voltage lines to recloser bushing terminals. 6 4 2


Refer to Figure 8 for terminal identification of the NOVA i
recloser. Terminal connection to copper conductors only are
recommended.

IMPORTANT 5 3 1

The default connections use the horizontal bushing as the source side and the
vertical bushing as the load side. Also, the horizontal bushing may be used as the
load side and the vertical bushing as the source side. Note that reversing the
source and load bushings has no effect on overcurrent protection but may require
setting or wiring changes to the control for correct metering.
If equipped with internal voltage sensors, the horizontal bushings (1, 3, 5) must be
connected to the source. The internal voltage sensors cannot monitor source-side
voltage when the NOVA i recloser is in the OPEN position if the horizontal
bushings are connected to the load.

B. Provide surge arrester protection. Surge arrester protection


should be provided on both sides. Figure 8.
Terminal identification of NOVA i recloser.

7
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Remove recloser from service Grounding the NOVA i recloser


1. Block ground tripping via the control panel.
2. Close all three bypass switches. IMPORTANT
3. Pull down the yellow operating handle with a hotstick. The In pole-mounted applications, a ground connection must be made between the
yellow operating handle is located under the recloser sleet recloser, transformer, recloser control, and SCADA equipment for proper
hood. protection of the equipment. It is recommended to use a minimum of 50 sq mm
4. The control will sense that the recloser is open and provide copper wire for the pole ground connection to the recloser.
OPEN/LOCKOUT indication on the front panel.
5. Open the source and load disconnect switches.
6. Remove high-voltage connections from recloser. IMPORTANT
All external inputs to the control must be routed within 203 mm of their
WARNING corresponding ground. During a surge, a potential of approximately 1.5 kV per foot
can develop in the conductors. Differences between conductor and ground path
Hazardous Voltage. If the recloser is energized while the control cable is lengths can add additional stress to the control components in the event of a
disconnected, the CT secondaries can generate high voltages. Contact power surge.
with high voltage can cause severe personal injury or death.

7. Remove control cables, power cables, and ground leads from IMPORTANT
recloser.
Note: Disconnecting the control cable on an energized Any external voltage sensor installed with the NOVA i recloser must have its
recloser will not damage the integrated CTs. ground referenced to the recloser ground.
8. Follow standard utility procedures regarding removal of
recloser from service.
3-wire ungrounded and impedance grounded systems
The use of a grounding mat may be required depending upon the
local safety regulations defining the permissible step and touch
potential levels. Consult local regulations for proper grounding
procedures.

8
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

Grounding with a local supply voltage Grounding with a remote supply voltage
transformer: 4-wire multi-grounded, 3-wire transformer: 4-wire multi-grounded, 3-wire
ungrounded, or impedance-grounded ungrounded, or impedance-grounded
Installation with a local supply voltage transformer must include Installation with a remote supply voltage transformer must include
the following (refer to Figure 9): the following (refer to Figure 10):
Protection of the recloser bushings and the supplying Protection of the recloser bushings and the supplying
transformer with lightning arresters. transformer with lightning arresters.
Grounding of the recloser head and tank. Grounding of the recloser head and tank.
Grounding of the transformer tank. Grounding of the transformer tank.
Grounding of the control cabinet. Grounding of the control cabinet.
Grounding of the SCADA equipment. Grounding of the SCADA equipment.

Figure 10.
Recommended grounding method for NOVA i reclosers
with microprocessor-based control and remote supply
Figure 9. voltage transformer.
Recommended grounding method for NOVA i recloser
with microprocessor-based control and local supply
voltage transformer.

9
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Grounding on a 3-wire uni-grounded system


CAUTION
Installation on a 3-wire uni-grounded system must include the
following (refer to Figure 11): Hazardous Voltage. Do not use a shared low-voltage network to power
the recloser control unless the network is specifically designed to
Protection of the recloser bushings and the supplying
transformer with lightning arresters. withstand maximum ground potential rise. Ground faults on a
high-voltage network can create a rise in ground potential.
Grounding of the recloser head and tank.
Grounding of the transformer tank.
Grounding of the control cabinet.
Grounding of the SCADA equipment. IMPORTANT
In pole-mounted applications, a ground connection must be made between the
recloser, transformer, recloser control, and SCADA equipment for proper
WARNING
protection of the equipment. It is recommended to use a minimum of 50 sq mm
Hazardous Voltage. Use locally approved operator safety procedures for copper wire for the pole ground connection to the recloser.
proper insulation when maintaining this equipment. High voltage step
and touch potential is characteristic in uni-ground systems. Failure to
comply can cause death or severe personal injury.
IMPORTANT
All external inputs to the control must be routed within 203 mm of their
CAUTION corresponding ground. During a surge, a potential of approximately 1.5 kV per foot
can develop in the conductors. Differences between conductor and ground path
Exported Potential. Do not make direct electrical connections to remote lengths can add additional stress to the control components in the event of a
devices. All SCADA equipment must be mounted locally or connected power surge.
using the fiber-optic or radio communication accessory. Direct
connections to remote devices can produce exported potential causing
equipment damage or personal injury.

Figure 11.
Recommended grounding method for NOVA i reclosers with microprocessor-based control on a 3-wire
uni-grounded system. 10
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

Operation Hotstick operation (manual open, electrical


close)
WARNING
This equipment is not intended to protect human life. Follow all locally WARNING
approved procedures and safety practices when installing or operating Hazardous voltage. Always use a hotstick when working with this
this equipment. Failure to comply can result in death, severe personal equipment. Failure to do so could result in contact with high voltage,
injury, and equipment damage. which will cause death or severe personal injury.

The recloser may be opened manually by using a hotstick to pull


WARNING down the yellow manual OPEN handle, located on the front of the
recloser (see Figure 12). To close the recloser after a manual
Hazardous voltage. Do not rely on the open position of the yellow opening, first, push the yellow manual open handle up. Then, using
operating handle or the contact position indicator; it does not ensure that the microprocessor control, close the recloser.
the line has been de-energized. Always establish a visible disconnect.
Failure to follow proper safety practices can result in contact with high
voltage, which will cause death or severe personal injury. IMPORTANT
If the yellow manual OPEN handle remains in the down position, the recloser
Electrical operation cannot be closed electrically from the control.

The NOVA i recloser utilizes an interface circuit located in the


mechanism housing. The electronic interface circuit controls the
opening and closing signals to the magnetic actuator.

OPEN/CLOSE contact position indicator

WARNING
Hazardous voltage. Never rely on the open position of the operating
handle or the contact position indicator; it does not ensure that the line is
Nameplate
de-energized. Follow all locally approved safety practices. Failure to
comply can result in contact with high voltage, which will cause death or
severe personal injury.
Manual
The OPEN/CLOSE contact position indicator consists of a red OPEN/CLOSE Contact OPEN Handle
CLOSED and a green OPEN indicator located on the bottom of the Position Indicator
mechanism housing (see Figure 12).
Figure 12.
NOVA i recloser OPEN/CLOSE contact position indicator,
nameplate, and manual OPEN handle.

11
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Internal voltage sensing option Refer to the Installation section of this manual for information on
the NOVA i recloser installation procedure. Refer to Service
The internal voltage sensor is located internal to the NOVA i Information S280-70-18 for further information on installing the
module and connected to the horizontal bushing. The internal Form 6/FXD Pole-Mount control.
voltage sensor is used to provide low voltage input to the Form
6/FXD recloser control for metering and/or protective functionality. Verify the correct load-side and source-side terminal connections.
This is required for correct operation of the internal voltage sensor.
The sensing option, cable, and control support a magnitude
accuracy of 2% or better and a phase degree accuracy of 1.5 Verify correct grounding of the NOVA i recloser and control prior to
throughout the temperature range of -40C to +55C. making any high-voltage connections and before high-potential
testing. A proper ground connection consists of a good electrical
ground connection to the surge ground connector located on the
Installation mechanism housing. Provide a good electrical ground connection
to the control cabinet ground.
WARNING Note: Painted surfaces of the mechanism housing may prevent a
This equipment is not intended to protect human life. Follow all locally ground connection to the recloser housing. Always provide a
approved procedures and safety practices when installing or operating good electrical connection to the recloser surge ground
connector.
this equipment. Failure to comply can result in death, severe personal
injury, and equipment damage. Poor grounding of the recloser housing may result in the
presence of high voltage on the housing associated with the
high-voltage resistor connections used with internal voltage
sensing.
WARNING
Hazardous voltage. Always use a hotstick when working with this CAUTION
equipment. Failure to do so could result in contact with high voltage,
which will cause death or severe personal injury. Hazardous voltage. Do not touch the female receptacle connections of the
voltage sensing cable. If the recloser is energized and the voltage
sensing cable is disconnected from the recloser or the control, a voltage
clamped at 250 V ac will be present at the female receptacle. Contact
WARNING with this voltage can result in personal injury.

Hazardous voltage. Solidly ground all equipment. Failure to comply can


result in death, severe personal injury, and equipment damage. The recloser is equipped with a 4-pin female receptacle (see Figure
13) that connects to the control with a shielded, 4-conductor cable.
The control accessory includes a 4-pin male receptacle on the
control and appropriate circuitry; refer to Figure 14.
IMPORTANT
Disconnect switches for ac control power are necessary to isolate the control for
testing and servicing.

Power supply Internal voltage sensor receptacle


Control interface receptacle

Optional Auxiliary
Switch Receptacle
Voltage Sensor Label

Figure 13.
NOVA i recloser cable receptacles with internal voltage sensing option. (NOVA i recloser with 19-pin control interface shown.)
12
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

CAUTION
Equipment misoperation. Verify all connector pins and both mating
interface surfaces are clean and dry before connecting cables. Voltage
sensing errors can result from contamination. Failure to comply can
result in control and recloser misoperation. Internal Voltage Sensor
Receptacle

The electrical connectors of the recloser, control, and cable must


be clean and dry. Contaminated surfaces may be cleaned with
denatured alcohol and wet connector surfaces may be dried with a
Internal Voltage Sensor
heat gun. Dry surfaces are particularly important for the internal Receptacle
voltage sensor cable connections. The accuracy of the sensors can
be influenced by moisture contamination.

CAUTION
Equipment Misoperation. Do not connect this control to an energized
recloser until all control settings have been properly programmed and
verified. Refer to the programming information for this control. Failure to
comply can result in control and recloser misoperation, equipment Figure 14.
damage, and personal injury. Form 6/FXD control voltage sensor receptacle.

Connect control cables, power cables, and sensor cables to the


control. Verify that the proper cable/receptacle connections are
made. Improper cable connections can result in damage to the
recloser and/or control.
Complete the control programming before making the high-voltage
line connections. See the Operation section of this manual.
Make appropriate electrical connections to the terminals of the
recloser. Verify correct load-side (vertical bushings) and source-side
(horizontal bushings) terminal connections. This is required for
correct operation of the internal voltage sensor. Energize recloser
and confirm the voltage outputs in the control.
When the recloser is energized, the output of the internal voltage
sensor in 6 V, based upon the Form 6/FXD controls input
impedance. If the sensor cable is disconnected at either the
control or the recloser, the voltage sensing output signal is 250 V
ac. The receptacles on both the NOVA i recloser and the voltage
sensing cable (control end) are 4-pin female connectors to
minimize accidental contact with the voltage sensor outputs. The
recloser control input impedance to the voltage sensors lowers the
voltage to 6 V during normal operation.

13
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Form 6/FXD control settings Table 6


Form 6/FXD phase angle adjustment
The Form 6/FXD control must be programmed with a PT ratio and
a phase angle adjustment; refer to Tables 5 and 6. These are Voltage Sensor Phase Shift, NOVA 15i
entered in the System Configuration screen; see Figure 15. Cable Length

When programming the Form 6/FXD, the PT connection must be 3.05 m N/A
set for a Wye connection. Also, the Phantom Phase feature must 6.10 m N/A
be disabled. Refer to Service Information S280-70-4 for more 9.15 m N/A
information on programming the Form 6/FXD control. Phase Shift, NOVA 27i
3.05 m N/A
Table 5 6.10 m N/A
Form 6 adjusted PT ratio 9.15 m N/A
Description PT Ratio Phase Shift, NOVA 38i

NOVA 15i 11001 3.05 m N/A


NOVA 27i 22001 6.10 m N/A
NOVA 38i 22001 9.15 m N/A

FXD adjusted PT ratio

Description PT Ratio

NOVA 15i 10011


NOVA 27i 20011
NOVA 38i 20011

Figure 15.
Form 6/FXD control system configuration screen.
14
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

Accessories Terminals
The standard terminal is a 2-hole flat-pad terminal rated 630 A. An
Auxiliary switch eyebolt, 1/0500 mcm (630 A), eyebolt 4/01000 mcm (800 A), and
A three-stage auxiliary switch can be provided as an accessory. 4-hole flat-pad terminals, are available as an accessory (see Figure
Each stage has two independent contacts that permit any desired 16).
combination of a (follow state of recloser contacts) and b
The eyebolt and fixed-pad terminals are made of copper alloys.
(opposite recloser contacts) positions. The switch contacts are
Cooper Power Systems recommends terminal connection to
insulated for 600 V and have a continuous current rating of 10 A.
copper wires to optimize the electrical connection.
Their interrupting ratings are shown in Table 7.
Anti-oxide coatings for temporary protection of wire-brushed
Table 7 aluminum cable connections to flat-pad terminals must be
Auxiliary switch interrupting ratings maintained at intervals determined by the customer based on load
current, climate, and other installation conditions.
Inductive Non-Inductive Inductive Non-Inductive
ac ac dc dc Eyebolt terminals are recommended for copper conductors only.
Volts (A) (A) (A) (A)

24 15.0 20.0
48 7.5 10.0
Pole-mounting hanger
120 60 80
125 1.5 2.0 A pole-mounting hanger (see Figure 16), which bolts directly to the
recloser frame, is available for pole-mounting installation.
240 30 60
250 0.45 0.5

Terminal options A
Eyebolt, 1/0 - 500 mcm
89
Cable range (630 A max.)
Eyebolt, 4/0 - 1000 mcm
111
Cable range (800 A max.)
Flat Pad, 2-hole 119
(630 A max.)
Flat Pad, 4-hole 121
(800 A max.)

POLE

1085
637 B

NOVA 15i 809


617 A
Min. NOVA 27i 908

NOVA 38i 1007

290

779 Note: All dimensions are mm.


POLE Dimensions shown are approximate.

POLE

Figure 16.
Dimensions of NOVA i recloser with pole-mounting hanger accessory.

15
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Arrester-mounting brackets
The arrester-mounting bracket accessory (see Figure 17) can be bolted to the recloser frame and pole-mounting hanger for the addition
of inboard and outboard arresters. The arresters are not included with the brackets.

Note: All dimensions are mm.


Dimensions shown are approximate.

Figure 17.
Dimensions of NOVA i recloser with pole-mounting hanger and arrester-mounting bracket accessories.

16
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

Substation-mounting frame
A substation-mounting frame accessory (see Figure 18) is available for substation-mounting applications.

NOTE: All dimensions are mm.


Dimensions shown are approximate.

Terminal options A B C
Eyebolt, 1/0 - 500 mcm NOVA 15i
89 809 528
Cable range (630 A maximum) 110 kV BIL
Eyebolt, 4/0 - 1000 mcm NOVA 27i
111 908 627
Cable range (800 A maximum) 150 kV BIL
Flat Pad, 2-hole NOVA 38i
119 1007 676
(630 A maximum) 170 kV BIL
Flat Pad, 4-hole
121
(800 A maximum)

Figure 18.
Dimensions of NOVA i recloser with substation-mounting frame accessory.

17
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Service information 1. Check the nameplate ratings. Make sure the ratings, settings,
and interface options on the recloser nameplate (see Figure 5)
Service requirements are correct for the planned testing.
The NOVA i recloser has been designed with a minimum 2. Test electrical open and close operation. Close and open the
mechanical life of 10,000 operations. The NOVA i recloser requires recloser contacts using the microprocessor control. Confirm that
routine inspection to check for physical damage and verify proper the contacts have closed and opened by:
operation.
A. The OPEN/CLOSE contact position indicator, or
B. By a continuity check between the recloser terminals.
Frequency of inspection
Because these reclosers are applied under widely varying 3. Test manual open. Pull the yellow manual open handle (see
operating and climatic conditions, service intervals are best Figure 12) down to open the recloser contacts. Confirm that the
determined by the user based on actual operating experience. contacts have opened by:
A. The OPEN/CLOSE contact position indicator, or
Testing operation
This recloser is used with the Form 6/FXD microprocessor-based B. By a continuity check between the recloser terminals.
recloser controls. Refer to the control operation manual. 4. To close the recloser contacts:
A. First, push the yellow manual open handle up.
WARNING
B. Close the recloser using the microprocessor-based control.
This equipment is not intended to protect human life. Follow all locally
approved procedures and safety practices when installing or operating
this equipment. Failure to comply can result in death, severe personal
injury and equipment damage.

18
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

High-potential withstand testing


TEST 1 TEST 2
Phase to ground Phase to phase
WARNING
Hazardous voltage. The switchgear and high voltage transformer must be 5 6 5 6
in a test cage or similar protective device to prevent accidental contact
ac ac
with the high voltage parts. Solidly ground all equipment. Failure to
3 4 3 4
comply can result in death, severe personal injury, and equipment
damage.
1 2 1 2

WARNING
Radiation. At voltages up to the specified test voltages, the radiation
emitted by the vacuum interrupter is negligible. However, above these
voltages, radiation injurious to personnel can be emitted. See Service
Information S280-90-1, Vacuum Interrupter Withstand Test Voltage
Ratings Information for further information.
TEST 3
Use the following procedures to perform high-potential withstand Open contact Open contact
tests at 75% of the rated low-frequency withstand voltage for 60
seconds. See Table 8 for test voltages and Figure 19 for test
5 6 5 6
connection diagrams.
ac ac
Test results for NOVA i reclosers equipped with the internal 3 4 3 4
voltage sensing option will be influenced by the source-to-ground
connected sensing resistor, especially if dc high-potential testing is 1 2 1 2
performed.

Table 8
NOVA i Recloser withstand test voltage ratings information.

75% of Rated Low-Frequency


Withstand Voltage
(1 minute dry) (kV rms)
Description ac dc
NOVA 15i 37.5 53.0 * Figure 19.
NOVA 27i 45.0 63.5 Connection diagrams for high-potential withstand testing.
NOVA 38i 52.5 74.2 **

* Approximately 0.53mA additional leakage current with internal TEST 3


voltage sensors.
1. Open the recloser contacts.
Approximately 0.32mA additional leakage current with internal
voltage sensors.
2. Ground the recloser.
3. Connect and ground terminals 1, 3, and 5 (see Figure 8).
* * Approximately 0.37mA additional leakage current with internal 4. Connect terminals 2, 4, and 6.
voltage sensors.
5. Apply proper test voltage to terminals 2, 4, and 6.
TEST 1 6. The recloser should withstand the test voltage for 60 seconds.
1. Close the recloser contacts. 7. Reverse the connections: ground terminals 2, 4, and 6.
2. Ground the recloser. 8. Apply test voltage to terminals 1, 3, and 5 for 60 seconds.
3. Connect terminals 2, 4, and 6 (see Figure 8) together. 9. The recloser should withstand the test voltage for 60 seconds.
4. Apply proper test voltage (see Table 8) to terminals 2, 4, and 6.
5. The recloser should withstand the test voltage for 60 seconds.

TEST 2
1. Close the recloser contacts.
2. Ground the recloser.
3. Ground Phase A (terminal 2) and Phase C (terminal 6).
4. Apply proper test voltage to Phase B (terminal 3).
5. The recloser should withstand the test voltage for 60 seconds.

19
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

Withstand test results Troubleshooting


The high-potential withstand tests provide information on the If the NOVA i recloser does not perform as described in the
dielectric condition of the recloser and the vacuum integrity of the OPERATION section of this manual, the following information may
interrupters. assist in troubleshooting:
If the recloser passes the closed-contacts tests (Tests 1 and 2), but
fails the open-contacts test (Test 3), the cause is likely to be in the Unit will not close
interrupter assembly. Retest each phase individually to determine
the failed phase or phases. Make sure the yellow manual open handle is completely up.

If the recloser does not pass Tests 1, 2, or 3, contact an authorized Check all cables for proper connection.
service center or your Cooper Power Systems representative. Verify that the control has power.
Test results for NOVA i reclosers equipped with the internal Upon loss of ac power, check recloser control battery level.
voltage sensing option will be influenced by the source-to-ground
connected sensing resistor, especially if dc high-potential testing is Check the fusing on the dc-to-dc converter board located in the
performed. control cabinet.

Inspection of nova i module Unit will not open electrically


If the NOVA i module was exposed to an external flashover, an Check all cables for proper connection.
inspection process is recommended to assure proper operation of
Verify that the control has power.
the recloser. Should the NOVA i exhibit external flashover
attributes (carbon tracking or discoloration), the following Check the fusing on the dc-to-dc converter board located in the
procedure is recommended to restore the encapsulation back to its control cabinet.
original condition:
1. Bypass and remove the recloser from service as described
in this manual.
2. Inspect module for damage to the terminals. Remove any
damaged terminals and replace.
3. Inspect module for damage to the module rods. If there is
damage to the module rods, the conductor module must be
replaced.
4. Verify through careful inspection that there is no damage to
the housing that could inhibit proper operation. Check the
integrity of the lifting lugs.
5. Clean the damaged module with isopropyl alcohol and a
scratch-free, nylon scouring pad to remove any carbon
deposit.
6. Confirm the dielectric strength of the module by performing
high-potential withstand testing. Confirm both
phase-to-ground and phase-to-phase conditions. See the
High-Potential Withstand Testing section of this manual.

20
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

AUXILIARY SWITCH ACCESSORY


C.T. PROTECT OR 1 R3-C
CIRCUIT BO ARD b
2 R3-D
CONTR OL CABLE
RECEPT ACLE 3 R3-A
a
A R1-G 4 R3-B
A CT
X1

5 R3-G
B R1-H b
B CT 6
X1 R3-H
K R1-K

7 R3-E
C R1-J a
C CT 8 R3-F
X1

"CTP"
9 R3-L
CURRENT TRANSFORME R b
10 R3-M

11 R3-J
a
1 12 R3-K
2
"C1" "AS"
"CC " +
3 +
"AB" 4
ACTUATOR 5
CIRCUIT BO ARD 6
7 + "C2"
+
"TC" LEGEND
8
53Vdc SYMBOL DESCRIPTIO N
9 R1-T
53Vdc AB Actuator Circuit Board
10 R1-S
AS Auxiliary Switch - 3 Stage
53Vdc
11 R1-R C1 Close Capacitor
Common C2 Trip Capacitor
"P1" 12 R1-P
CC Close Coil
13 Common
R1-N TC Trip Coil
Common MS1 Micro Switch, Contact Position Indicator
14 R1-L
MS2 Micro Switch, Contact Position Indicator
15 MS3 Micro Switch, Open Handle - Disables
16 Closing Circuit
COM 52a or a Contact - Open When Unit is Open
17 "MS3" 52b or b Contact - Closed When Unit is Open
N.O.
18 R1 Receptacle, Control - 19-Pin Male
R3 Receptacle, Auxiliary Switch - 14-Pin Male
19 H1 Resistive Heater
COM N.C. Open H2 Resistive Heater
20 R1-C
"MS1" 52a VTC Pull Up 2 CTP Current Transformer Protector
21 R1-A CT Current Transformer
COM N.O. Close
22 R1-E
"MS2" 52b VTC Pull Up 1
23 R1-B
R1-M

R1-U
"H2" "H1"
R1-V

Figure 20.
Wiring diagram for NOVA i recloser with control-powered interface (19-pin receptacle).

21
NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase Instructional Literature IL0104001E
microprocessor-controlled; installation and operation Effective November 2014
instructions (S280-43-1)

22
Instructional Literature IL0104001E NOVA 15i, NOVA 27i, and NOVA 38i; Three-phase
Effective November 2014 microprocessor-controlled; installation and operation
instructions (S280-43-1)

Electrical Sector Asia Pacific


No.3, Lane 280, Linhong Road,
Changning District,
Shanghai 200335
Tel: 86-21-52000099
Fax: 86-21-52000200

2014 Eaton Corporation Eaton is a registered trademark


All Rights Reserved of Eaton Corporation.
Printed in China
Publication No. IL01004001E All other trademarks are property
November 2014 of their respective owners.

You might also like