You are on page 1of 144

HORIZONTAL STIFFNESS OF WOOD DIAPHRAGMS

by

James Wescott Bott

Thesis submitted to the faculty of

Virginia Polytechnic Institute and State University

in partial fulfillment of the requirements for the degree of

MASTER OF SCIENCE

in

CIVIL ENGINEERING

APPROVED:

J. Daniel Dolan, Co-Chairman W. Samuel Easterling, Co-Chariman

Joseph R. Loferski

April 18, 2005

Blacksburg, Virginia

Keywords: wood diaphragm, shear stiffness, diaphragm stiffness, diaphragm deflection


HORIZONTAL STIFFNESS OF WOOD DIAPHRAGMS

by

James Wescott Bott

ABSTRACT

An experimental investigation was conducted to study the stiffness of wood diaphragms.

Currently there is no method to calculate wood diaphragm stiffness that can reliably account for

all of the various framing configurations. Diaphragm stiffness is important in the design of wood

framed structures to calculate the predicted deflection and thereby determine if a diaphragm may

be classified as rigid or flexible. This classification controls the method by which load is

transferred from the diaphragm to the supporting structure below.

Multiple nondestructive experimental tests were performed on six full-scale wood

diaphragms of varying sizes, aspect ratios, and load-orientations. Each test of each specimen

involved a different combination of construction parameters. The construction parameters

investigated were blocking, foam adhesive, presence of designated chord members, corner and

center sheathing openings, and presence of walls on top of the diaphragm.

The experimental results are analyzed and compared in terms of equivalent viscous

damping, global stiffness, shear stiffness, and flexural stiffness in order to evaluate the

characteristics of each construction parameter and combinations thereof. Recommendations are

presented at the end of this study as to the next steps toward development of an empirical method

for calculating wood diaphragm stiffness.


iii

ACKNOWLEDGEMENTS

The author would like to extend his warmest thanks to Dr. Daniel Dolan and Dr. Sam

Easterling for their unending guidance and support. A special thanks also goes to Dr. Joseph

Loferski for serving as a committee member, and to CUREE for sponsoring the research.

There are several individuals who proved invaluable during the experimental phase of the

project. They include Bob Carner, Kenny Albert, and Guy Anderson. A special thanks goes to

an undergraduate research assistant, Mike Boyce, who provided the greatly needed labor and

assistance during specimen construction and testing.

Finally the author would like to thank his loving and understanding wife and family for

their support and dedication.


iv

TABLE OF CONTENTS

ABSTRACT ii

ACKNOWLEDGEMENTS iii

TABLE OF CONTENTS iv

TABLE OF FIGURES vi

TABLE OF TABLES viii

CHAPTER

I. INTRODUCTION 1

1.1 Introduction 1
1.2 Objectives and Scope of Research 4
1.3 Literature Review 7
1.3.1 Early Testing 7
1.3.2 Dynamic Testing 10
1.3.3 Similar Diaphragms 12

II. EXPERIMENTAL PROCEDURE 15

2.1 Scope of Testing 15


2.2 Test Apparatus 16
2.3 Diaphragm Construction 23
2.4 Test Parameters 27
2.5 Instrumentation 38
2.6 Test Protocol 45
2.7 Test Data Analysis 46
2.7.1 Yielding 47
2.7.2 Global Deformation 49
2.7.3 Cyclic Stiffness 51
2.7.4 Shear Deformation 56
2.7.5 Shear Stiffness 58
2.7.6 Flexural Deformation 60
2.7.7 Flexural Stiffness 60
2.7.8 Hysteretic Energy 61
2.7.9 Equivalent Viscous Damping 63

III. RESULTS AND DISCUSSION 67


v

3.1 Introduction 67
3.2 Test Conditions 67
3.3 Nail Bending Test Results 69
3.4 Moisture Content and Density Results 71
3.5 Construction Parameter Results 73
3.6 Diaphragm Stiffening Methods 78

IV. SUMMARY, CONCLUSIONS, AND RECOMMENDATIONS 82

4.1 Summary 82
4.2 Conclusions 83

REFERENCES 86

APPENDIX A 88

APPENDIX B 95

APPENDIX C 119

APPENDIX D 120

APPENDIX E 128
vi

TABLE OF FIGURES

Figure Page

1.1 Cross-Section of a Typical Wood Framed Floor 2

1.2 Deep Beam Analogy 4

2.1 Load Frame, Actuator Connection, and Load Distribution Channel 17

2.2 Triangular Reaction Frame 18

2.3 Basic Test Apparatus and Configuration 20

2.4 Triangular Reaction Frame Plan View Schematic 21

2.4a Elevation View of Triangular Reaction Frame 21

2.5 Partial Section of Diaphragm Test Apparatus (loading parallel to joists) 22

2.6 Rim-Joist Splice for 10 x 40 ft. Specimens 24

2.7 Basic Specimen Sizes / Orientations (16 x 20 ft. and 20 x 16 ft.) 25

2.7 (Cont.) Basic Specimen Sizes / Orientations (10 x 40 ft.) 26

2.8 Fully Sheathed 10 x 40 ft. Specimen 27

2.9 Corner Sheathing Opening 29

2.10 Center Sheathing Opening 30

2.11 Test Configuration with Chords (and corner opening) 32

2.12 Test Configuration without Chords 32

2.13 Test Configuration with Walls 34

2.14 Wall-Lifting Davits 35

2.15 10 x 40 ft. Specimen with Walls and Wall-Braces 36

2.16 Application of Sprayed Foam Adhesive 37

2.17 Foam Adhesive Shown After Removal of a Sheathing Panel 38


vii

TABLE OF FIGURES, Contd

Figure Page

2.18 LVDTs and Mounting Bracket 40

2.19 Instrumentation Plan for 16 x 20 ft. Specimen 42

2.20 Instrumentation Plan for 20 x 16 ft. Specimen 43

2.21 Instrumentation Plan for 10 x 40 ft. Specimen 44

2.22 Idealized Elastoplastic Force-Deformation Curve 48

2.23 Simplified Diaphragm Deformation Curve with Sign Convention 50

2.24 Diaphragm Deformation Curve - Specimen 2, Test 8 50

2.25 Stiffness of a Linearly Elastic System 51

2.26 Cyclic Stiffness Calculation Methods 53

2.27 Global Load-Deformation Hysteresis, Specimen 3, Test 3 55

2.28 Global Load-Deformation Hysteresis, Specimen 3, Test 24 55

2.29 Diaphragm Deformation Theory 56

2.30 Diaphragm Shear Deformation 57

2.31 Numerical Integration of a Load-Deformation Hysteresis 62

2.32 Damping relationship to an equivalent viscous system 64

3.1 Diaphragm Specimen with Canopy 68

3.2 Floor Diaphragm with an Opening and Collector Ties 80


viii

TABLE OF TABLES

Table Page

3.1 Average Moisture Content and Density Results by Specimen 72

3.2 Average Percent Differences by Construction Parameter 74

A.1 Specimen 1 Test Results 89

A.2 Specimen 2 Test Results 90

A.3 Specimen 3 Test Results 92

A.4 Specimen 4 Test Results 93

A.5 Specimen 5 Test Results 94

A.6 Specimen 6 Test Results 94

B.1 Test Comparisons for the Effects of Blocking 96

B.2 Test Comparisons for the Effects of Foam Adhesive 99

B.3 Test Comparisons for the Effects of Blocking and Foam Adhesive 101

B.4 Test Comparisons for the Effects of Increased Nail Density 102

B.5 Test Comparisons for the Effects of Chords 103

B.6 Test Comparisons for the Effects of Walls 105

B.7 Test Comparisons for the Effects of Center Sheathing Openings 109

B.8 Test Comparisons for the Effects of Corner Sheathing Openings 113

C.1 Instrument Descriptions 119

D.1 Specimen 1 Joists Moisture Content and Density 121

D.2 Specimen 1 Sheathing Moisture Content and Density 122

D.3 Specimen 2 Joists Moisture Content and Density 123

D.4 Specimen 3 Joists Moisture Content and Density 124


ix

D.5 Specimen 4 Joists Moisture Content and Density 125

D.6 Specimen 5 Joists Moisture Content and Density 126

D.7 Specimen 6 Joists Moisture Content and Density 127

E.1 Specimen 1 Test Descriptions 129

E.2 Specimen 2 Test Descriptions 130

E.3 Specimen 3 Test Descriptions 132

E.4 Specimen 4 Test Descriptions 133

E.5 Specimen 5 Test Descriptions 134

E.6 Specimen 6 Test Descriptions 134


CHAPTER I: INTRODUCTION 1

CHAPTER I

INTRODUCTION

1.1 INTRODUCTION

Modern structural engineering frequently involves sheathed construction, a load

resistance method exemplified in various structural elements by many combinations of suitable

materials. A common form of sheathed construction, the diaphragm, is a thin, usually planar

system of sheathing and frame members, intended to withstand considerable in-plane forces.

When referring to residential housing, everyday plywood construction typically comes to mind.

Most apparent examples of diaphragms are walls, upper-story floors, and roofs of

everyday structures such as residential houses, office buildings, and warehouses. Though similar

in function, wall diaphragms, called shear walls, require different consideration for design and

analysis, and thus fall outside of the scope of this investigation. Roofs and above-grade floors,

when designed as such, fall into the classification as true diaphragms. Typical combinations of

materials employed are wood sheathing on wood frame, metal sheathing on wood frame, metal

sheathing on metal frame, wood sheathing on metal frame, and variations using concrete,

structural insulation panels, and other construction materials. This research project is limited to

wood-framed and plywood-sheathed floor diaphragms typical in residential housing.

The common floor and roof diaphragm serves dual purposes by supporting vertical forces

(from loads such as furniture, people, snow, uplift, and its own dead load) and by transmitting

horizontal forces (from wind pressure or earthquake accelerations) to the supporting shear walls.
CHAPTER I: INTRODUCTION 2

Floors and roofs are inherently able to carry gravitational loads due to the typical design by

which appropriately spaced framing members are covered with sheathing and fastened together.

Joists and rafters, the common framing members of floors and roofs, respectively, are oriented to

maximize the moment of inertia for resistance to flexure. Thus, a 2x10 floor joist would be

installed such that the nominal ten-inch side is vertical. The sheathing spans the distance

between and transmits loads to the framing members below. The framing members then

distribute the loads proportionally to supporting walls or posts. Also, when adequately fastened

together, the sheathing and framing can produce a flexurally efficient composite section.

Resistance to vertical forces, though a primary consideration in design and construction of floors

and roofs, is not the subject of this study.

Sheathing

Wood Floor Joists

Figure 1.1 Cross-Section of a Typical Wood Framed Floor


CHAPTER I: INTRODUCTION 3

Horizontal forces applied to diaphragms are almost exclusively from wind and

earthquakes. Wind pressure on the exterior walls is transmitted proportionately along the edge

of a diaphragm as a uniform load. In the case of wind-loaded floors, connections with the top

plate of the wall below and the bottom plate of the wall above provide paths for load transfer.

When subjected to earthquake accelerations, its own inertia, or resistance to motion, and that of

attached walls or partitions causes horizontal loading of a diaphragm. Diaphragms are usually

more than capable of withstanding these loadings due to high in-plane shear capacity. Sheathing

material itself exhibits considerable in-plane shear strength. Hence, the reason a sheet of

plywood is much more rigid when loaded along the thin edge (in-plane) as opposed to the large

flat surface (out of plane). Accordingly, a low aspect ratio system of sheathing panels, properly

fastened together end-to-end along the edges, has an effective shear capacity. The fact that it is

usually so thin makes sheathing an efficient and lightweight means of resisting in-plane loads.

Resistance to these in-plane loads through diaphragm action may be compared to the

loading of a deep wide-flange beam, as illustrated in Figure 1.2. The shear walls of a structure

are analogous to the simple supports of the beam and provide the reaction against the forces

transmitted through the diaphragm. The inter-connected sheathing panels behave like the web of

the beam to resist the shear component of in-plane loads. And, the extreme edges of the

sheathing and/or the boundary members running perpendicular to the direction of the loads

simulate the flanges of the beam by carrying the tension and compression from the flexural

reaction to the loads.


CHAPTER I: INTRODUCTION 4

Flange

Web

Figure 1.2 Deep Beam Analogy

The behavior of floor and roof diaphragms has become an important issue with respect to

lateral stiffness and deflection. It has been noted that there is seldom a problem with the strength

of diaphragms, because failures are predominantly associated with the connections between a

diaphragm and supporting walls. Though the occurrence of actual failures is rare, diaphragms

have sometimes been a controlling factor in the overall failure of structures during seismic events

(Dolan 1999). Poor understanding of wood diaphragm behavior has spurred the interest of

researchers to formulate more accurate methods of analysis and design similar to methods

already employed in the design of cold-formed steel diaphragms.

1.2 OBJECTIVES AND SCOPE OF RESEARCH

The objective of this study is to evaluate the stiffness effects of various diaphragm

construction parameters for use in the development of an accurate method to determine shear
CHAPTER I: INTRODUCTION 5

stiffness of wood diaphragms based on the formulas currently used in cold-formed steel design.

Such a formula would allow an improved method of predicting diaphragm deflections. The

capability to accurately calculate diaphragm stiffness and deflections will enhance the safety and

economy of wood diaphragms.

The current lack of an accurate method to predict diaphragm stiffness prevents designers

from knowing exactly how much stiffness to expect from any given design. Adequate

diaphragm stiffness is required in order to allow load sharing among the supporting shear walls.

In other words, flexible diaphragms resist loads locally (i.e., they can not transfer loads

horizontally very far). Thus, the loads induced into a flexible diaphragm must be transferred to

local supports (i.e., walls that are the closest to the location of the induced load). A perfectly

rigid diaphragm would be the other end of the spectrum where all of the supporting walls share

in resisting the load according to their relative stiffness. In reality, the diaphragm stiffness falls

somewhere in between these two extremes. However, the higher the diaphragm stiffness, the

better the load sharing capability is of the structural system and therefore, the better the expected

performance.

Currently, diaphragms must be classified as either flexible or rigid in order to select one

of two different design methods for the transfer of load to the supporting structure. Wood

diaphragms have been traditionally assumed as flexible, thereby allowing a load distribution

design based on the tributary area method. This method, however, is not applicable when

diaphragms exhibit torsional irregularities such as asymmetric geometry and openings (e.g.

stairwells) or differences in locations of center of rigidity and center of force. To account for

such torsional irregularities a designer must assume a rigid diaphragm and transfer the load based

on relative stiffness of the supporting walls.


CHAPTER I: INTRODUCTION 6

According to the NEHRP Recommended Provisions for Seismic Regulations for new

Buildings and Other Structures (1997) and as adopted in the Uniform Building Code (1997) and

the 2000 International Building Code a diaphragms classification changes from rigid to flexible

when diaphragm deflection under load is equal to or greater than twice the deflection of the

supporting walls. Thus, designers are now forced to calculate the stiffness of wood diaphragms,

(and convert the stiffness into a corresponding deflection) in order to even make the distinction

between rigid and flexible.

Predicting diaphragm stiffness (or deflection) is difficult because currently there is no

simple and accurate method that can account for geometrical irregularities as well as all of

todays varying construction practices. The one current method for calculating deflection of

wood diaphragms as developed by APA is complicated and is not able to incorporate many

factors such as sheathing openings, absence of chords, use of sheathing adhesive, and non-

rectangular shapes. Designers need a simple and accurate method to determine wood diaphragm

stiffness if they are expected to even begin to select the proper load distribution method.

The specific objective of this study is to evaluate several basic diaphragm construction

details for their individual and combined effects on diaphragm stiffness. These results will then

be used under another task of the CUREE-Caltech Woodframe Project to develop and calibrate a

finite element model for diaphragm analysis. The overall goal of the experimental diaphragm

testing and finite element modeling is the development of an equation to accurately predict wood

diaphragm stiffness in the form of shear stiffness, G, as already accomplished by the cold-

formed steel industry.

This specific task is accomplished by a series of experimental tests on full-scale

diaphragms followed by careful analysis of the results. The test materials and procedures are
CHAPTER I: INTRODUCTION 7

discussed in detail in Chapter II. Data collected from the tests is evaluated in Chapter III for

numerical trends indicating the effects of the various specimen configurations on stiffness.

These trends are used to make general observations regarding the stiffening characteristics of

each diaphragm construction parameter. All of the stiffness results for every test of each

specimen are listed for reference in Appendix A.

1.3 LITERATURE REVIEW

The objective of this literature review is to examine the studies in the field of theoretical

and experimental diaphragm research. A study of research performed in this field is important in

order to know what characteristics have already been established and what questions of

diaphragm behavior are still unanswered. Sporadic since the 1950s, most of the testing of wood

diaphragms has occurred at the facilities of the Douglas-fir Plywood Association (DFPA),

American Plywood Association (APA), Oregon State University, Oregon Forest Products

Laboratory, Washington State University, and West Virginia University. The volume of

literature available is small, therefore, rather than place the review in a separate chapter, the

reviewed literature is provided as a section within this chapter.

1.3.1 Early Testing

The DFPA sponsored some early tests in diaphragm behavior. Countryman (1952)

describes lateral tests on plywood-sheathed diaphragms. Four specimens, 12 x 40 ft. and 20 x 40

ft., and six one-quarter scale models, 5 x 10 ft., were tested by monotonic loading at fifth-points.

The specimens had varying parameters such as blocking, openings, staggered panels, gluing,

plywood thickness, nail size, and boundary nailing patterns. Stiffness of the diaphragms was

calculated from measured lateral deflection in the middle of the lower chord and applied load.
CHAPTER I: INTRODUCTION 8

Shear deformation, and not flexural deformation was determined to be the predominant form of

deflection. Load versus deflection plots show that the actual deflection was consistently higher

than calculated values using existing equations. It was found that diaphragms behave like a

horizontal girder with a shear-resistant web. Due to their location at the extreme edges, chord

members of a diaphragm act like the flanges of a girder by resisting the flexural tension and

compression forces. The sheathing serves as the web of the girder to resist the shear. Strength

and stiffness of the specimens was found to be primarily dependent on the strength of the nailed

plywood-to-frame connections.

Due to over conservative design codes, the DFPA pursued further studies in diaphragm

action. Countryman and Colbenson (1954) report on tests of fifteen full-scale diaphragms,

conducted to better understand the strength effects from:

1. Omission of blocking
2. Panel arrangement
3. Nailing schedules
4. Span-thickness combinations
5. Length-width ratio
6. Seasoning of frame lumber
7. Use of three inch lumber
8. Cut-in blocking for chords
9. Load application perpendicular to joists
10. Screwed cleats in lieu of blocking

All 24 x 24 ft. specimens were monotonically loaded with four equal lateral forces at fifth

points of the span, and deflections were measured from the middle of the unloaded chord.

Plywood thickness and nailing schedule, along with blocking to a lesser degree, were found to be

the predominant factors in determining strength and stiffness. Ultimate applied shears ranged
CHAPTER I: INTRODUCTION 9

from 733 to 2530 plf, while ultimate deflections occurred from 0.52 to 3.2 in. For blocked

diaphragms, the measured deflections are consistent with a formula produced as a result of the

DFPA Report No. 55 (Countryman 1952) with an average error of 15%.

In conjunction with the research described above, the DFPA also sponsored tests at the

Oregon Forest Products Laboratory. The two 20 x 60 ft. roof diaphragms tested, were

constructed with the lightest framing and plywood thickness permissible at that time for a roof of

this size (Stillinger and Countryman 1953). The 2 x 10 joists were framed at 24 in. o.c. and

sheathed with 3/8-in. thick plywood. One of diaphragms was blocked along the panel edges.

The diaphragms were loaded monotonically by hydraulic jacks at the fifth points. The 3/8-in.

thick plywood was found to be adequate, though not as strong as specimens with thicker

plywood. The lightweight framing system performed adequately. Lastly, it was found that for

unblocked diaphragms, no special boundary nailing detail was required regardless of the reduced

strength.

The APA became interested in lateral shear testing of diaphragms not composed of

Douglas-fir plywood. Tissell (1966) validated the DFPA tests from 1955 as well as going on to

test diaphragms of other various species of wood that were becoming popular in construction.

Nineteen full-scale 16 x 48 ft. diaphragms were tested. Plywood characteristics, sheathing-to-

framing connections, nail types, and framing member types were varied in the tests. Monotonic

loading from 16 hydraulic jacks at 3 ft. on center was used to approximate a uniform lateral load.

Lateral deflections were measured with dial gages at mid span of the tension chord. The design

shear values were found to be very conservative, with the average ultimate load being 1545 plf

and the average allowable design load being only 420 plf (includes factors of safety). Sheathing

of different species of wood was found to have a small but accountable change in shear strength
CHAPTER I: INTRODUCTION 10

and stiffness. However, effects from plywood grade and quality were found to be negligible.

Tissell concluded that shear strength equivalent to that of blocked diaphragms is possible by

stapling tongue-and-groove 2-4-1 plywood. Further, shorter ring-shank nails are permissible as

long as a minimum penetration is attained. Open-web steel joist-framed diaphragms were

slightly stronger than the lumber framed diaphragms. The DFPA design values determined from

the tests previously discussed (Countryman and Colbenson 1954) were found to adequately

conservative.

1.3.2 Dynamic Testing

GangaRao and Luttrell (1980) explain the efforts at West Virginia University to quantify

shear response of diaphragms with the ultimate goal being the preparation of accurate analysis

models for future design purposes. Since diaphragms had been mainly studied under static

loading conditions, they propose that stiffness characteristics are an equally critical issue in a

correct estimation of behavior under real-life dynamic loading. Preliminary dynamic results

from tests at West Virginia University were used to derive joint slip and shear deformation

response equations based on dynamic loading. They predicted that damping characteristics with

respect to joint slip are the critical factors needed to appropriately describe diaphragm behavior

under dynamic loads.

At the time, Polensek (1979) was the only researcher making attempts at quantifying

damping characteristics for horizontal dynamic loading. His tests of plywood sheathed

diaphragms with six or ten inch joists yielded average equivalent viscous damping ratios

between 0.07 and 0.11. However, he considered that the data accumulated had been too varied

for an accurate estimation of the damping ratio. It was apparent, however, that an increase in the

damping effect is directly proportional to floor span.


CHAPTER I: INTRODUCTION 11

At West Virginia University, Jewell (1981) performed experimental tests on partial

(cantilever) diaphragms in order to analyze a range of different parameters such as nail spacing,

boundary conditions, connection details, load type, and damping capacity. Three 16 x 24 ft.

diaphragms and six 16 x 16 ft. diaphragms were tested under monotonic, cyclic, and impact

loads in the directions perpendicular and parallel to the joists. Replica diaphragms were also

modeled in the same configurations as flexible composite members in a finite element analysis to

determine any inaccuracy in this theoretical approach. Based on a comparison of the theoretical

and experimental test results, Jewell was able to analyze relationships of plywood behavior, nail

slip, effect of loading, effect of joist hangers, and damping to the stiffness of diaphragms. In

most cases, the finite element approach yielded slightly less conservative results for stiffness

(i.e., predicted deflections were lower than actual), based on the parameters listed above.

Corda (1982) and Roberts (1983) performed additional cantilever diaphragms tests at

West Virginia University in another codependent study involving laboratory testing and finite

element modeling. Corda tested six 16 x 24 ft. specimens cyclically and statically to failure in

order to study local and global in-plane shear stiffness response to variations of blocking,

openings, plywood thickness, corner stiffeners, and framing nail sizes. It is noteworthy that nail

softening after loads up to 9 kips on some specimens caused a large decrease in stiffness.

Increased plywood thickness (without using longer nails) and corner openings reduced strength

but had little effect on stiffness. Roberts theoretical analysis of equivalent models of the

diaphragms tested by Corda, showed some evident discrepancies. Problems with the finite

element analysis program included the limitation to monotonic loading, inaccurate predictions of

panel slip, and the iterative processes of calculation of diaphragm deflection with respect to nail

slip, a bilinear relationship, demanding the modification of results to a nonlinear solution using
CHAPTER I: INTRODUCTION 12

the tangent stiffness method. Based on the problems encountered, Roberts suggested that the

limitations imposed on the program user in modeling plywood diaphragms need to be eliminated

by further experimental research into stiffness characteristics of panel slip, plywood layout and

connection, diaphragm openings, and nail slip under cyclic loading.

A recent APA report by Tissell and Elliott (1997) describes diaphragm testing for high

load conditions equivalent to earthquakes accelerations. The primary intent was to formulate

design and construction approaches for these high-load diaphragms, which may incorporate

use of two layers of plywood, thicker plywood, or stronger fastener conditions. Ten of the

diaphragms tested were 16 x 48 ft., and the dimensions of an eleventh specimen were changed to

10 x 50 ft. Hydraulic jacks at a spacing of 24 in. o.c. were used to apply a cyclic uniform load

along the long side of the diaphragms. Results show that it is possible to increase shear strength

by increasing the number of fasteners or adding another layer of sheathing in areas of high shear.

This report also notes that plywood panel shear capacity must be checked for high-load

diaphragms. Staples were found to be adequate fasteners in lieu of nailed sheathing-to-framing

connections. Along the same lines, field glued joints and a reduced number of nails are adequate

for these diaphragms.

1.3.3 Similar Diaphragms

The abundant studies of floors comprised of materials other than wood are important in

order to understand general behavior of diaphragms. It is possible that wood diaphragm design

methods may be simplified and accurately rationalized in terms of methods already in use for

other materials. A theoretical study of the behavior of composite steel beam and concrete deck

diaphragms was made by Widjaja (1993) at Virginia Polytechnic Institute and State University.

Similar to many efforts currently in progress for wood diaphragms, the purpose of this study was
CHAPTER I: INTRODUCTION 13

to develop an accurate finite element analysis model that predicts diaphragm behavior,

incorporates possible variations of design parameters, and derives design strength equations.

Similarly, experimental cantilever tests on cold-formed steel diaphragms are important in the

design of many steel-frame building roofs and composite floors (during construction, before

concrete). Post-frame diaphragm testing (wood frame and metal sheathing) is also significant in

terms of the more agricultural or shed type buildings.

With sponsorship from NUCOR Research and Development, Hankins et al. (1992)

performed eighteen cantilever diaphragm tests at Virginia Polytechnic Institute and State

University to determine strength and stiffness of cold-formed steel sheathing, 20 and 22 gage

thickness (Vulcraft 1.5B1 deck), welded or bolted to a steel frame. The 16 x 16 ft. specimens

were subjected to monotonic loads. Thirteen diaphragms utilized an 8 ft. span, requiring only

one filler beam. The other five specimens had a filler beam spacing of 4 ft., requiring three filler

beams. Bolt and puddle weld arrangement, used to secure the sheathing, was varied to determine

its effects on diaphragm behavior. Results from the tests indicate that specimens with thicker

gage sheathing have more strength and stiffness. However, even though specimens with smaller

filler beam spacing (three filler beams as opposed to one) had more strength, the diaphragm

stiffness was less in some cases.

Hausmann and Esmay (1977) report the results of tests on twenty-six full size post-frame,

metal-clad diaphragm panels. All specimens were 8 x 16 ft. with rafters at 4 ft. o.c. along the 16

ft. side and purlins at 2 ft. o.c. along the 8 ft. side. Loaded monotonically at the ends of the three

interior rafters, the panels were analyzed for strength and stiffness based on varying parameters

such as framing arrangement, type, number, and metal of fasteners, aluminum or steel sheathing,

and with or without insulation. It was determined that purlins laid flat to the rafters was the more
CHAPTER I: INTRODUCTION 14

suitable method of framing. Screw fasteners in the panel valleys increased diaphragm stiffness

and strength, especially for the steel clad specimens. Aluminum panels were more suitable with

nailing, due to a larger cover width for each sheet. Placing insulation between wood-framing

and metal cladding not only reduces diaphragm strength, but also seriously affects stiffness.

Fastener configurations have important and measurable effects on diaphragm behavior.

Anderson and Bundy (1990) performed additional post-frame diaphragm tests to outline

the effects of openings in the sheathing. Fifteen cantilever specimens, 7-2/3 x 12 ft. with two

interior rafters and seven purlins were tested monotonically with varying amounts of sheathing

missing. Diaphragms were constructed with SPF lumber, screw fasteners, and steel sheathing.

Fastener configurations were found to be extremely important for diaphragm stiffness.

Openings in the sheathing at normal intervals caused the specimens to be ineffective as

diaphragms. It was also found that spacing of purlins has little impact on strength or stiffness of

the diaphragms.

In addition to the physical testing, there has been a great deal of computer modeling of post-

frame diaphragms for scientific purposes in order to aid designers and validate experimental

results. For example, Wright and Manbeck (1993), among many others, conducted finite

element analyses of post-framed diaphragm panels. Following procedures provided by Woeste

and Townsend (1991), they modeled full size 8 x 12 ft. diaphragms with 2x4 in. purlins at 2 ft.

o.c., 2x6 in. rafters at 3 ft. o.c., and steel cladding secured with 16d nails. The finite element

model was compared to three identical experimental diaphragm tests. The finite element model

closely predicted diaphragm shear strength, but under-estimated shear stiffness by 28%. Results

show that discrepancies arise due to difficulties in modeling nonlinear behavior of fasteners and

intricate load paths between the wood frame and steel sheathing.
CHAPTER II: EXPERIMENTAL PROCEDURE 15

CHAPTER II

EXPERIMENTAL PROCEDURE

2.1 SCOPE OF TESTING

Multiple stiffness tests and one test to failure were performed on each of six full-scale

diaphragms at the Thomas M. Brooks Forest Products Center of the Virginia Polytechnic

Institute and State University located in Blacksburg, Virginia. Consortium of Universities for

Research in Earthquake Engineering (CUREE) sponsored the research under its Wood Frame

Project, Task 1.4.2 Diaphragm Studies.

Diaphragm dimensions for four specimens were 20 x 16 ft. with varying orientations,

while two high-aspect ratio specimens were 10 x 40 ft. Multiple tests on each specimen were

possible due to the non-damaging deflections being imposed, allowing an economical means of

incorporating multiple test parameters. Test parameters investigated for effects on diaphragms

stiffness were: 1) corner opening, 2) center opening, 3) fully sheathed, 4) 6-12 nail pattern, 5) 3-

12 nail pattern, 6) with/without chords, 7) with/without walls, 8) with/without blocking, and 9)

with/without foam adhesive. Specimens were subjected to non-destructive, low-amplitude

dynamic-cyclic loading by a computer-controlled hydraulic actuator, while load and deflection

values were being recorded by a computer data acquisition system. The final test on each

specimen, though not a primary focus of this study, was an attempt to cause diaphragm failure.
CHAPTER II: EXPERIMENTAL PROCEDURE 16

2.2 TEST APPARATUS

Diaphragm testing was conducted on a 22 X 50 ft. concrete pad with 42 in. wide by 27 in.

tall concrete back-walls along two adjacent sides. The heavily reinforced back-walls have two

7/8 in. diameter anchor bolts embedded in the concrete at 2 ft. on center with a 400,000 lb point-

load capacity at a minimum spacing of 6 feet.

A computer controlled hydraulic actuator was mounted horizontally at the midpoint of

the 50 ft. back-wall. The actuator had a 55 kip capacity with a 6 in. stroke, and included a 50

kip Interface load cell, screwed onto the end of the hydraulic cylinder. Load was transferred

from a ball joint at the end of the actuator, through a pin-connected gusset to a 20 ft. long

C6x10.5 steel channel. The channel, as shown in Figure 2.1, was fastened along the entire width

in the center of the specimen span with 5/8 in. diameter lag screws. In cases where a joist did not

fall in the center of the diaphragm, 4x4 blocks are placed under the sheathing to provide a

backing for the lag screws used to attach the steel load distribution channel.
CHAPTER II: EXPERIMENTAL PROCEDURE 17

Figure 2.1 Load Frame, Actuator Connection, and Load Distribution Channel

Offset equal distances (based on dimensions of diaphragm specimens) from the centerline

of the actuator were triangular reaction frames, as shown in the photograph of Figure 2.2. The

frames were constructed of 4 X 6 in. steel tubes welded together. Each reaction frame was
CHAPTER II: EXPERIMENTAL PROCEDURE 18

connected to the concrete back-wall with four 7/8 in. diameter anchor bolts. A one-inch thick

end plate was welded to the end of the steel tube of the reaction frame and was drilled and tapped

for a 1 in. threaded rod. A two-foot piece of threaded rod was screwed through the plate into

the steel tube leaving the desired length exposed. A shop-fabricated, full-bridge load cell made

of 2 in. diameter steel rod and strain gauges screwed onto the opposite end of the threaded rod.

The load cell had a large hex-nut welded to one end to connect to the threaded rod protruding

from the triangular reaction frame. Gusset plates welded to the opposite end of the load cell

provided a pinned connection to the diaphragm support frame.

Figure 2.2 Triangular Reaction Frame

Each end of the diaphragm was attached to a 20 ft.-L2x2x steel angle, which was

welded intermittently to the side of a 20 ft.-3 X 5 in. steel tube using lag screws. One end of

each steel tube was pin-connected to the gusset plates of the reaction load cells. This support
CHAPTER II: EXPERIMENTAL PROCEDURE 19

frame served the same purpose as shear walls by transmitting loads out of the diaphragm at each

end. The reaction frame load cells then measured these loads. The support frame served a

secondary purpose, to hold the diaphragm at the proper elevation for concentric loading from the

actuator. Several one-inch diameter PVC pipes were also placed on the concrete under the

specimen to help hold the interior of the specimen at the proper elevation, and to act as

frictionless rollers under the joists as load was applied. The schematic drawings of Figures

2.3, 2.4, and 2.5 illustrate all of the elements of the test apparatus including the specimen support

frame, the triangular reaction frame, and the load distribution channel.
CHAPTER II: EXPERIMENTAL PROCEDURE 20

Concrete Back Wall

Actuator
Triangular Reaction
Frame
Load Cell
Steel Channel Load Cell
(C6 x 10.5)

See Figure 2.4


for Detail
Support Frame
3" x 5" Steel Tube

Diaphragm Size
and Sheathing
Layout Varies

Fig.
2.5

Lag Screws

Figure 2.3 Basic Test Apparatus and Configuration


CHAPTER II: EXPERIMENTAL PROCEDURE 21

Steel Tube
Frame

Load Cell

Fig.
2.4a

Figure 2.4 Triangular Reaction Frame Plan View Schematic

Diaphragm Support Frame

Pinned Connection

Concrete
Backwall

Figure 2.4a Elevation View of Triangular Reaction Frame


CHAPTER II: EXPERIMENTAL PROCEDURE 22

3" x 5" x 3 8" Steel Tube

Steel Pipe
Steel Angle: Roller
-Welded to Steel Tube
-Lag Screwed to End Joist

Steel Channel (C6X10.5) - Lag


23 Screwed to non-structural blocks
32"T&G Plywood
Sheathing

2 x 12 Joists @ 16"
(Douglas Fir)
PVC Pipe Rollers
11 4 "

Figure 2.5 Partial Section of Diaphragm Test Apparatus


(for specimens loaded parallel to the joists)
CHAPTER II: EXPERIMENTAL PROCEDURE 23

2.3 DIAPHRAGM CONSTRUCTION

Of the six, full-scale diaphragm specimens, two were 16 x 20 ft. in dimension and were

loaded parallel to the direction of the joists on the 20 ft. side. Two specimens were 20 x 16 ft. in

dimension, loaded perpendicular to the joists on the 16 ft. side. The last two specimens were 10

x 40 ft. in dimension, loaded parallel to the joists on the 40 ft. side. Resembling the size and

shape of one side of a roof of a typical residential home, these 10 x 40 ft. specimens were

intended to test the envelope of diaphragm performance with respect to aspect ratio.

The diaphragm specimens were framed with Douglas-fir 2 x 12 joists spaced at 16 in. o.c.

and nailed with three 16d nails at each end to a 2 x 12 Douglas-fir rim joist. In the case of

specimens loaded parallel to the direction of the joists, the bottom of each end joist was attached

to the diaphragm support frame using lag screws as shown in Figure 2.5. Conversely, when

loading was applied perpendicular to the joists, the rim-joists were connected to the support

frames. Since the lumber used was 20 ft. in length, the rim joists of the 40 ft. long specimens

had to be spliced in the center with steel plates and bolts as shown in Figure 2.6 (while such a

splice may not be feasible in real-life construction due to interference with finish materials,

effective transfer of compression and tension forces in the chords was essential for valid test

results). The three main specimen configurations, including loading and reaction locations, are

schematically illustrated in Figures 2.7a-c. A photograph of a 10 x 40 ft diaphragm specimen is

presented in Figure 2.8.

A wood sample was taken from each joist of every specimen for moisture content and

density analysis. This information was recorded for possible use when evaluating test results,

since moisture content changes in lumber affects fastener performance.


CHAPTER II: EXPERIMENTAL PROCEDURE 24

Figure 2.6 Rim-Joist Splice for 10 x 40 ft. Specimens (typical both sides)
CHAPTER II: EXPERIMENTAL PROCEDURE 25

4'x8'x23 32" T&G


Plywood Sheathing Load Applied

Cut-out shows
framing layout below

16'

2 x 12 Joists @ 16"
(Douglas Fir)

2 x 4 Blocking
(on flat)

2 x 12 Rim-Joist
(Douglas Fir)
20'

(a) 16 x 20 ft. Specimen

Load Applied
16'

20'

(b) 20 x 16 ft. Specimen


Figure 2.7 Basic Specimen Sizes / Orientations
CHAPTER II: EXPERIMENTAL PROCEDURE
Load Applied
4'x8'x23 32" T&G Plywood
Sheathing

10'

40'

(c) 10 x 40 ft. Specimen

Figure 2.7 (Continued) Basic Specimen Sizes / Orientations

26
CHAPTER II: EXPERIMENTAL PROCEDURE 27

Figure 2.8 Fully Sheathed 10 x 40 ft. Specimen

The specimens were sheathed with nominal 4 x 8 ft. sheets of 23/32 in. tongue-and-

groove plywood in a staggered panel configuration. Sheathing was cut as required to complete

the desired panel configuration. Sheets were attached to the framing with 10d nails in a 6/12 nail

pattern, meaning nails are spaced at 6 in. around the perimeter and at 12 in. on the interior

supports of each sheathing panel. Typical sub-flooring construction adhesive was not used

between the joists and plywood sheathing; however some tests involved the use of sprayed foam

adhesive.

2.4 TEST PARAMETERS

Specimens were subjected to a number of different construction variations, including the

multiple combinations thereof. The variations tested were:

1. Sheathing openings fully sheathed, corner opening, center opening


CHAPTER II: EXPERIMENTAL PROCEDURE 28

2. Chord members with / without rim joist


3. Blocking with / without 2 x 4 blocking
4. Walls with / without 4 ft. tall stud-framed walls
5. Sprayed foam adhesive & nails versus nailed only
6. Sheathing nail density 6/12 versus 3/12 nail pattern

Variations to the basic specimen listed above, are individually discussed in detail in the

following paragraphs.

Openings in the plywood sheathing were intended to simulate common openings in floors

of residential homes for stairways, atriums, and vaulted ceilings. These openings weaken and/or

cause torsional irregularities that can dramatically affect the stiffness of diaphragms. Duplex

(double-headed) 10d nails were used to fasten the sheathing panels that were to be removed from

the specimens in order to simulate openings. The corner opening in all sizes and orientations of

specimens was easily achieved by removing one full 4 x 8 ft sheet of plywood from a corner.

However, the center opening presented more challenges due to the staggered sheathing

configuration and tongue-and-groove plywood. For both orientations of the 16 x 20 ft.

specimens, an 8 x 12 ft. rectangular opening was made by prying the unfastened sheets up in the

center along the tongue-and-groove seam like an army tent and lifting them out. Some sheets

had to be cut in half to achieve a rectangular opening. Due to the high aspect ratio of the 10 x 40

ft. specimens, a proportional rectangular opening in the center was not reasonable, since typical

roof and floor diaphragms would not have such an opening. A schematic drawing and

accompanying photograph of the two opening types used in the tests are presented in Figures 2.9

and 2.10.
CHAPTER II: EXPERIMENTAL PROCEDURE 29

Load Applied

Figure 2.9 Corner Sheathing Opening


CHAPTER II: EXPERIMENTAL PROCEDURE 30

Load Applied

Figure 2.10 Center Sheathing Opening


CHAPTER II: EXPERIMENTAL PROCEDURE 31

The chords of a diaphragm are the exterior framing members that are oriented

perpendicular to the direction of loading. They serve to resist bending moment induced in a

diaphragm while also supporting the extreme edges of the sheathing. In the case of floor

diaphragms, the chords may either be the rim joist or simply the last joist at each end of the floor,

depending on the orientation and direction of loading. Residential roof diaphragms typically do

not have a true rim joist, either at the lower edge along the fascia or at the ridge (unless the fascia

board or ridge beam is considered to be effective). The absence of an effective chord is

especially prevalent for roof systems utilizing metal plate connected trusses.

Though all testing was performed on floor diaphragm specimens, chord effects should be

similar for roof-like specimens. The effectiveness of chords was quantified by running tests with

and without the designated chord members (rim joists) in place. Only those specimens having

rim joists as the chords (specimens loaded parallel to the direction of the joists) could be tested in

this manner. The rim joists were nailed to the diaphragm at each joist with three 16d duplex

nails. Plywood edges were nailed to the rim joist with 10d duplex nails at 6 in. o.c. Duplex nails

were used for easy removal of the rim joists between different test specimen configurations. One

of the diaphragm specimens is shown in both configurations of having the rim joist acting as the

chord in place and removed in Figures 2.11 and 2.12 respectively.


CHAPTER II: EXPERIMENTAL PROCEDURE 32

Figure 2.11 Test Configuration with Chords (and corner opening)

Figure 2.12 Test Configuration without Chords


CHAPTER II: EXPERIMENTAL PROCEDURE 33

Blocking is the term used for the short framing members that span between joists and

serve to interlock the unsupported joints between sheathing panels. They can have the same

cross-sectional dimensions as the joists (full-depth blocking improves noise and vibration

dampening), or blocks can simply be smaller lumber laid on flat. In this investigation, specimen

configurations with blocking used 2 x 4s laid on flat installed between joists where each line of

unsupported sheathing panel joints would fall prior to installing the sheathing. The blocks were

fastened to the joists on each side with two 16d common toe nails. Plywood panel edges that fell

over the blocks were nailed every 6 in. with 10d duplex nails for easy removal to simulate

blocked and unblocked conditions. To reconfigure the specimen without blocking, the sheathing

nails were extracted, the diaphragm was tilted on-end with a forklift, and blocks were removed.

Likewise, replacing blocking involved tilting the diaphragm up to install new 2 x 4 blocks from

below, and then re-nailing the sheathing to the blocking.

A potentially significant unknown in diaphragm design is the effect of walls on the

horizontal stiffness. Walls of a structure transfer wind loads to the floors to which they are

connected. Also, the mass of the walls themselves present added lateral loads to diaphragms

during earthquakes. These walls, especially the flexural stiffness of their own bottom plate, may

also benefit a floor diaphragm by helping to resist these same lateral loads.

For testing purposes, four-foot high walls were installed along the two chord edges of

specimens. As shown in Figure 2.13 these walls were constructed of 2 x 4 studs at 16 in. o.c.

and 7/16 in. OSB sheathing on the outside. The 2 x 4 bottom plate of the walls was fastened

through the plywood sheathing to the floor joists below with 3 x in. self-tapping Simpson

screws for a strong connection yet easy removal. For the 16 x 20 ft. specimens, regardless of

orientation, the walls were set in place and removed with a long, cable-supported, boom attached
CHAPTER II: EXPERIMENTAL PROCEDURE 34

to a large forklift. Starting with the second specimen, lever-action davits, as shown by the

photographs of Figure 2.14, were welded to the side support frames at each end of the walls to

more quickly and safely facilitate raising and lowering for configurations with and without walls.

As shown in Figure 2.15 for the 40 ft. long specimens, the walls on each side were built in 20 ft.

sections, set in place with the boom, and connected in the center. From then on, the davits at

each end of the walls accompanied by braces in the center allowed for repeated installation and

removal of walls. Braces were required to laterally stabilize the wall segments for the 10 x 40 ft.

diaphragm specimens.

Figure 2.13 Test Configuration with Walls


CHAPTER II: EXPERIMENTAL PROCEDURE 35

(a) Walls Lowered and Attached (b) Walls Unfastened and Raised

Figure 2.14 Wall-Lifting Davits


CHAPTER II: EXPERIMENTAL PROCEDURE 36

Figure 2.15 10 x 40 ft. Specimen with Walls and Wall-Braces

Current trends in construction involve the use of adhesives for an ever-widening range of

applications. In this case the method of fastening sheathing panels to framing members was

varied between nailed only and nailed plus sprayed adhesive. The adhesive material used was a

sprayed, two-part, self-expanding, poly-isocyanurate foam adhesive manufactured by ITW

Foamseal. The foam adhesive was tested using coupon tests to quantify its stiffness as a

connection. The connection stiffness was determined to be equivalent to that obtained by using

elastomeric adhesives typically used in wood floor construction. While elastomeric adhesive

would have been more representative of traditional construction, it would have prevented the

possibility of removing sheathing without damage once fastened down, thereby making it costly

and difficult to alter specimen sheathing configurations. Sheathing fastened down with the foam

adhesive could be removed with minimal damage by cutting the adhesive at the joints with a
CHAPTER II: EXPERIMENTAL PROCEDURE 37

knife. Also, testing of the foam adhesive will provide useful information for its effectiveness in

roof retrofit applications. After having tested all of the nailed-only configurations, the foam

adhesive was applied to the underside of fully-constructed specimens that could be safely tilted

on-end (i.e. the two 16 x 20 ft. and the two 20 x 16 ft. specimens). Specifically, the adhesive was

sprayed along each side of every joist at the interface with the sheathing. Adhesives were not

used on the 10 x 40 ft. specimens due to the specimens flexibility, which made tilting the

specimens without damage impossible. A photograph of the foam adhesive being applied is

shown in Figure 2.16, and a photograph of a sheathing panel removed is shown in figure 2.17.

Figure 2.16 Application of Sprayed Foam Adhesive


CHAPTER II: EXPERIMENTAL PROCEDURE 38

Figure 2.17 Foam Adhesive Shown After Removal of a Sheathing Panel

Sheathing nail density was varied for a few tests on the third and fourth specimens, both

of which were 20 x 16 ft. loaded perpendicular to the joists. The nail pattern was changed from

6/12 to 3/12 on the fully sheathed and nailed only configurations. In other words, nail spacing

around the perimeter of each sheathing panel (where supported by joists or blocking) was

decreased from 6 in. to 3 in. o.c. using easily removable 10d duplex nails. The 3-12 nail pattern

was tested while the walls and blocking parameters remain variable.

2.5 INSTRUMENTATION

Movements, deflections, and loads were measured at multiple locations on the diaphragm

specimens using electronic sensors of various types in conjunction with a computer controlled

Data Acquisition system (DAQ). The DAQ used for this project LABTECH, a Windows PC-
CHAPTER II: EXPERIMENTAL PROCEDURE 39

based program. Prior to testing, all instruments used in this research project were carefully

calibrated for accurate results. Before any series of tests in a day, all instruments were checked

to make sure they were correctly mounted, functioning properly, and zeroed. Due to the exposed

conditions of the outside testing facility, all instruments were demounted and taken inside or

covered with plastic daily to protect from inclement weather, dew, and frost.

An internal Linear Variable Displacement Transducer (LVDT) measured the deflections

caused by the hydraulic actuator. Signals from this highly sensitive device were transmitted to

the computer controller, which in turn used the information as the feedback channel to control

the actuator. Loads measured by the 50 kip Interface load cell were recorded by the DAQ and

had no effect on the displacement-controlled actuator.

The custom-built load cells at each end of the diaphragm measured the reaction loads,

both in tension and compression due to the cyclic loads from the actuator. These reactions

simulated the shear loads that supporting walls of an actual structure must withstand. Prior to

use, these load cells, as described in Section 2.2, were separately calibrated in tension only on a

universal testing machine with an excitation of 10 Volts (compression was not feasible due to a

pinned-pinned condition when using special calibration fixtures). Both were loaded

incrementally to 40 kips tension, and in each case the linear calibration plot proved that no

yielding within the load cell occurred. The slopes of these lines were used in the DAQ as

multipliers to convert the output voltage signals from the load cells into equivalent values of

load.

Horizontal movement of the plywood sheathing relative to the framing members below

was measured at two locations with external LVDTs. An aluminum bracket mounted to the

end-joist at each rear corner held the barrels of a pair of LVDTs in place horizontally. The
CHAPTER II: EXPERIMENTAL PROCEDURE 40

plungers of these instruments react against metal tabs, which were screwed and glued to the

plywood at the rear corners of the diaphragm. The LVDTs of each pair pointed in orthogonal

directions to account for biaxial sheathing movement. A photogragh of the LVDT mounting

setup is shown in Figure 2.18.

Figure 2.18 LVDTs and Mounting Bracket


CHAPTER II: EXPERIMENTAL PROCEDURE 41

String Potentiometers (abbreviated, string-pot) were used at multiple locations to

determine diaphragm movement, deformation, and slippage relative to the test frame. Seven

string-pots were set along the front face of the specimens to measure the global deflection. A

string-pot was attached to each steel side support frame to determine the slip in the side load cell

connections and between the steel frame and the diaphragm itself. Likewise, a string-pot was

mounted to the steel load channel in the center to determine any slip its lag screw connection to

the specimen. Two string-pots were mounted diagonally on each side of the diaphragm

centerline to record the deformation caused by shear deflection during testing. Schematics

illustrating the positions of each displacement sensor for each specimen configuration are

presented in Figures 2.19 through 2.21. A list describing each instrument is presented in

Appendix C.
CHAPTER II: EXPERIMENTAL PROCEDURE 42

Concrete Back Wall


SlipL GL1 GL2 GL3 GC GR1 GR2 GR3 SlipR

SlipC

DL1 DL2 DR1 DR2

3" x 5"
Steel Tube

LVDT
LVDT
R-EW
L-EW

LVDT LVDT
L-NS R-NS

Figure 2.19 Instrumentation Plan for 16 x 20 ft. Specimen


CHAPTER II: EXPERIMENTAL PROCEDURE 43

Concrete Back Wall


SlipL GL1 GL2 GL3 GC GR1 GR2 GR3 SlipR

SlipC

DL1 DL2 DR1 DR2

LVDT
LVDT
R-EW
L-EW

LVDT LVDT
L-NS R-NS

Figure 2.20 Instrumentation Plan for 20 x 16 ft. Specimen


CHAPTER II: EXPERIMENTAL PROCEDURE
Concrete Back Wall
SlipL GL1 GL2 GL3 GC GR1 GR2 GR3 SlipR

SlipC

DL1 DL2 DR1 DR2

LVDT
LVDT
R-EW
L-EW

LVDT LVDT
L-NS R-NS

Figure 2.21 Instrumentation Plan for 10 x 40 ft. Specimen

44
CHAPTER II: EXPERIMENTAL PROCEDURE 45

2.6 TEST PROTOCOL

In most cases of experimental research, how a specimen is stressed and to what extent, is

equally as important as the specimens characteristics. In this project great care was taken to

NOT apply deflections so large that specimens reached or exceeded their yield point and were

damaged. On the other hand, it is critical to apply sufficient deflection to obtain valid test data.

This limit was found for each specimen size and orientation by loading monotonically in small

increasing increments until signs of diaphragm damage are seen or heard, or until the slope of the

load/deflection curve, shown in real-time on the DAQ computer screen, appeared to be

decreasing. The deflection amount used for all tests was slightly lower than the largest

monotonic deflection. Additionally, deflections for this project followed a cyclic pattern that

somewhat simulates the cyclic loading of earthquakes, only not nearly as rapid, since this

apparatus is not intended or equipped to perform shake-table testing.

The load protocol for all tests, except those to failure, was five sinusoidal cycles at the

predetermined deflection, 0.25 for specimens one and two (20 ft. wide), 0.20 for specimens

three and four (16 ft. wide), and 0.80 for specimens five and six (40 ft. wide). The frequency

of these cycles was set in the actuator controller at 0.0833 Hz for test durations of 60 seconds.

Five cycles, or even possibly less, are adequate since this project does not incorporate the effects

of load fatigue.

While not a primary focus of this project, the last test of each specimen was an attempt to

cause failure. The CUREE protocol (Krawinkler et al. 2000) used for these tests is a deflection-

controlled quasi-static cyclic load history. This protocol is based on a finite series of cycles with

plateaus and peaks of increasing amplitude. Yield deflection, , was estimated for each
CHAPTER II: EXPERIMENTAL PROCEDURE 46

specimen and used as the reference deflection from which amplitudes of other cycles were

determined. If failure did not occur by the end of the series, the CUREE protocol allows for

additional cycles at higher amplitudes until the specimen fails.

2.7 TEST DATA ANALYSIS

As with any physical experiment, manipulation of raw test data (in this case, load and

deflection values) is required for a logical comparison of the different specimen configurations.

In this study, several specific variables are calculated in order to weigh the benefits and

detriments caused by changing test parameters as described in Section 2.4. These variables and

the methods used for their calculation are presented in the following sections.

Test data from each deflection and load measuring instrument was recorded by the DAQ

computer and entered into a spreadsheet format. Each column of data in the spreadsheet

corresponds to one of the twenty-four channels (instruments) being used, and is ordered

chronologically with time from the start of each test. A table listing each of these instruments,

its model and serial number, and calibration coefficient is in Appendix C.

These text-format spreadsheet files were later imported individually into a Microsoft

Excel calculation template. This template was programmed with the calculations necessary for

automatic computation of stiffness results and other important variables. The template also

provided instant load-deformation graphs for the data.

The first step of the calculations was to take the raw deflection data and convert it into

tared values by subtracting out the initial reading. For example, a string potentiometer with a

range of 10 in. is drawn out 5.25 in. and attached to the specimen. The first data entry for this

channel will indicate a deflection of 5.25 in. Therefore each of the data points in that column
CHAPTER II: EXPERIMENTAL PROCEDURE 47

must be tared by either subtracting or adding 5.25 in. depending on the direction of deflection in

order to attain the actual change in deflection.

Because the DAQ system had to be manually started and stopped in conjunction with the

independently controlled actuator, a section of data from the beginning and end of each test was

invalid. Therefore, the template was also programmed to shorten the data columns to include

only the meaningful data acquired during testing.

2.7.1 Yielding

While not a desired outcome of small-deformation stiffness testing, yielding is an

important concept to understand in terms of elastic versus plastic behavior. A material subjected

to a static load will undoubtedly undergo some deformation, though potentially immeasurably

small depending on its physical properties. If once unloaded, the material returns to its original

state, it is considered to have behaved elastically. However, if the material is loaded beyond its

elastic range causing permanent deformation even after being unloaded, then it has experienced

yielding. The force, fy, required to cause yielding is referred to as the yield point. Further

yielding caused by continued loading past this point, but before failure, is called plastic

deformation. Idealized elastoplastic response of a material subjected to force, f, causing

deformation, , is illustrated in Figure 2.22.


CHAPTER II: EXPERIMENTAL PROCEDURE 48

force (f)

fy

deformation ()
y failure

elastic behavior plastic behavior

Figure 2.22 Idealized Elastoplastic Force-Deformation Curve


CHAPTER II: EXPERIMENTAL PROCEDURE 49

2.7.2 Global Deformation

Maximums and minimums were established from deflection or load readings of each

instrument. The rigid body motion determined from string potentiometers measuring slip in test

frame connections was subtracted from maximum positive and negative global deformations.

The resulting adjusted maximum global deformations were plotted against instrument location

distances along the length of the specimen. This curve represents a diaphragms shape at

maximum deformation, and also aids in visualizing effects of torsional irregularity. The sign

convention used for the purposes of this study is illustrated in Figure 2.23. Outward deformation

caused when the hydraulic actuator pushes out is considered positive. An actual diaphragm

deformation curve from Specimen 2, Test 8 (16 x 20 ft., no chords, with walls, corner opening,

blocked, nailed only) is presented in Figure 2.24. Note, the lop-sidedness (towards the right)

caused by a torsional irregularity due to the corner sheathing opening on that side.
CHAPTER II: EXPERIMENTAL PROCEDURE 50

Global
(g ) g
Deformation

+ +

Distance Along
Diaphragm Edge

- -
Figure 2.23 Simplified Diaphragm Deformation Curve with Sign Convention

0.3
Global Deformation, RBM Subtracted (in)

0.24
0.23
0.2 0.19 0.19
0.13
0.1

-0.1
-0.12
-0.16 -0.15
-0.2 -0.20
-0.21

-0.3
0 2 4 6 8 10 12 14 16 18 20

Distance, L to R (ft)

Figure 2.24 Diaphragm Deformation Curve - Specimen 2, Test 8


CHAPTER II: EXPERIMENTAL PROCEDURE 51

2.7.3 Cyclic Stiffness

Stiffness is the most basic and yet also the most useful of all the variables determined for

this study. In lay terms stiffness is simply a measurement of a structures capacity for resisting

deformation. Although stiffness can be expressed in several different forms, in general it is the

amount of force required to cause a known unit of elastic deformation. Thus, if a system is

linearly elastic, then its stiffness, k, can be described as the slope of the force-deformation curve

as illustrated in Figure 2.25.

k
1

Figure 2.25 Stiffness of a Linearly Elastic System

Cyclic loading requires a different approach to calculating stiffness. Cyclic loads change

the force-deformation plot from a straight line to an elliptical loop known as a hysteresis as

shown in Figure 2.26. Because the slope changes along the hysteresis, cyclic stiffness must be

approximated. A visual comparison of two common methods of determining cyclic stiffness

and their associated equations is presented in Figure 2.26. The peak-to-peak method shown in

Figure 2.26a approximates stiffness as the slope of an imaginary line between the points of

maximum positive and maximum negative deflection. Figure 2.26b shows the origin-to-peak
CHAPTER II: EXPERIMENTAL PROCEDURE 52

method where stiffness is an average of slopes of imaginary lines from the origin out to the

points of maximum positive and negative deflection.


CHAPTER II: EXPERIMENTAL PROCEDURE 53

f
+
f max + f max
k= + k
max + max f max+

max-

max+

f max-

(a) Peak-to-Peak Method

f
k + k+
k= k+
2

max-

max+

k-

(b) Origin-to-Peak Method

Figure 2.26 Cyclic Stiffness Calculation Methods


CHAPTER II: EXPERIMENTAL PROCEDURE 54

The spreadsheet program determined cyclic stiffness values using both the origin-to-

peak method and the peak-to-peak method. The first value calculated was cyclic stiffness

based on the force required from the actuator to cause a unit amount of deformation (excluding

rigid body motion) at the center of the diaphragm specimen. For tests in which the load-

deformation hysteresis is not centered on the origin due to uneven loading of the specimen, the

origin-to-peak method may not seem appropriate. While the peak-to-peak method may

seem better suited for such cases of uneven loading, a comparison of the two methods shows that

the cyclic stiffness results never varied by more than 3% in all 132 tests. Therefore, both

methods are assumed to be valid for test data exhibiting uneven loading. Due to the similar

results under either method and for brevity, this study will focus on analysis using the peak-to-

peak method from this point forward. (Note: the cause of uneven loading is assumed to be

residual stresses stored in the specimen from the previous test due to friction.)

As shown by Figure 2.27, either method produces similar results for a load hysteresis that

is well centered on the origin. Likewise, for hysteresis loops that are not centered on the origin

as shown by Figure 2.28, the two methods still yield similar results.
CHAPTER II: EXPERIMENTAL PROCEDURE 55

20
Origin-to-Peak:

9.46 - 9.45
9.46 kips +
0.18 - 0.17
k cyclic = = 54.1 kip/ft
2
Load (kips)

-0.17 in
0 Peak-to-Peak:
0.18 in

9.46 + 9.45
k cyclic = = 54.0 kip/ft
-9.45 kips 0.18 + 0.17

0.2% Difference of 0.1 kip/ft.

-20
-0.25 0 0.25
Deformation (in)

Figure 2.27 Cyclic Load-Deformation Hysteresis, Specimen 3, Test 3


(Loops symmetric about the origin.)

20
Origin-to-Peak:

9.01 - 15.18
+
9.01 kips
0.15 0.20
k cyclic = = 68.0 kip/ft
2
Load (kips)

-0.20 in
0 Peak-to-Peak:
0.15 in

9.01 + 15.18
k cyclic = = 69.1 kip/ft
0.15 + 0.20

1.6% Difference of 1.1 kip/ft.


-15.18 kips

-20
-0.25 0 0.25
Deformation (in)

Figure 2.28 Cyclic Load-Deformation Hysteresis, Specimen 3, Test 24


(Loops not symmetric about the origin due to uneven loading.)
CHAPTER II: EXPERIMENTAL PROCEDURE 56

2.7.4 Shear Deformation

Global deformation is the sum of diaphragm shear deformation and flexural deformation

as illustrated in Figure 2.29. Since the load is applied at the center of diaphragm specimens, then

theoretically the shear deformation for each half of the diaphragm is equal. Diaphragm shear

deformation, visually detailed in Figure 2.30, can be determined from a geometric manipulation

of deflection results from the diagonal string potentiometers.

FLEXURAL SHEAR (s)


DEFORMATION
(f) DEFORMATION

GLOBAL DEFORMATION (g )
(Neglecting Rigid Body Motion)

Figure 2.29 Diaphragm Deformation Theory


CHAPTER II: EXPERIMENTAL PROCEDURE 57

b b

Diagonal String Pot.


(at deflection )
L

Diagonal String Pot.


(at zero deflection)
F F
2 2 d

L L
2 2

Figure 2.30 Diaphragm Shear Deformation

First, the maximum diagonal deformation values in each direction for each half of the

diaphragm are determined, then averaged together, giving an average diagonal deformation, L,

for each half of the diaphragm, and for both positive and negative deformation. Using small

angle assumptions, shear deformation, s, can be expressed as:

L
s = (2.7.1)
2
CHAPTER II: EXPERIMENTAL PROCEDURE 58

where is shear strain of the diaphragm and is calculated from the diagonal string potentiometer

deflections and geometric diaphragm properties by:

b2 + d 2
= L (2.7.2)
bd

The data spreadsheet program calculated a s value for both halves of the specimen as

well as for maximum positive and negative diaphragm deformation. In some cases, shear

deformation for the left side of the diaphragm did not equal that of the right side and the positive

maximum did not equal the negative maximum. Though uneven loading can be attributed to

differences in positive versus negative shear deformation results, the differences in left side

versus right side shear deformation are due to different shear stiffness of each side.

2.7.5 Shear Stiffness

Shear stiffness is equal to shear force divided by shear deformation. Using the shear

deformations just determined, the spreadsheet program calculates shear stiffness for both sides of

the diaphragm using:

V +V+
k shear = (2.7.3)
S + +S

where V- and V+ are the maximum positive and negative shear forces applied to a side of the

diaphragm.

Under symmetric loading conditions and torsionally regular construction, the shear force

resisted by either side of the diaphragm is theoretically half of the load applied at the center by

the actuator. Thus, theoretically for torsionally regular test configurations, V equals the reaction

force F/2 as shown by Figure 2.30, and can be verified by the load readings from the reaction

load cells at each side. However, asymmetric configurations such as a corner sheathing opening
CHAPTER II: EXPERIMENTAL PROCEDURE 59

may cause the diaphragm to resist more of the actuator-applied load on the stiff side of the

diaphragm and less on the soft side. In such instances, V should be determined independently

for the left and right sides using the maximum readings from the left and right side load cells,

respectively. Accordingly, for torsionally irregular configurations (corner opening being the

only case for this study) the left and right side shear stiffness values must be kept separate.

As a caveat to this approach, a recurring problem during testing of Specimens 3, 4, and 5

was electrical malfunction of the side load cells, especially on the left side. An alternate method

by statics had to be used for tests in which there was reaction load cell malfunction. As

previously indicated, for a torsionally regular and symmetrically loaded specimen, each reaction

force equals half of the actuator-applied force. Similarly, for torsionally irregular specimens (i.e.

corner opening) the reaction forces combined, though not necessarily equal, should add up to the

actuator-applied force, F. If for example, the left side load cell malfunctions, its load can be

approximated by:

RL = F RR (2.7.4)

With the experimental shear stiffness, kshear, calculated for both the left and right sides of

the diaphragm specimen, the spreadsheet program uses elastic beam theory where:

L
V
s = 2 (2.7.5)
G As

where GAs is a more commonly accepted form of shear stiffness. Using the relationship:

V
k shear = (2.7.6)
s

Equation 2.7.5 may be solved for GAs in terms of kshear to give:

L
G As = k shear (2.7.7)
2
CHAPTER II: EXPERIMENTAL PROCEDURE 60

A shear stiffness value, GAs, is calculated for both the left and right sides of the

diaphragm. The left and right side values are averaged together for torsionally regular

specimens, but kept separate for torsionally irregular specimens in order to allow proper

comparison of results. For such cases it is possible that the shear stiffness on one side may be

considerably higher than the other.

2.7.6 Flexural Deformation

As shown visually by Figure 2.29, flexural deformation can be determined by:

f = g s (2.7.8)

The spreadsheet program averaged the maximum s values for each half of the specimen for both

positive and negative deflection. These average shear deformation values were then subtracted

from the corresponding maximum positive and negative global deformations to give a maximum

positive and a maximum negative flexural deformation.

2.7.7 Flexural Stiffness

Experimental flexural stiffness, kf, may be expressed as:

F+ + F
kf = +
(2.7.9)
f + f

The spreadsheet uses the above peak-to-peak equation in order to arrive at one flexural stiffness

value.

Elastic beam theory offers an approach to a more common form of flexural stiffness.

Theoretical flexural deformation of a beam with a concentrated load applied at the center is:

FL 3
f = (2.7.10)
48 EI
CHAPTER II: EXPERIMENTAL PROCEDURE 61

where EI is the flexural stiffness of the beam, or, as in this case, the diaphragm. Solving

Equation 2.7.10 for EI in terms of kf (recalling that kf = F / f ) gives:

L3
EI = k f (2.7.11)
48

The spreadsheet program calculated flexural stiffness in the above form for each diaphragm test.

2.7.8 Hysteretic Energy

Hysteretic energy is the energy dissipated during one cyclic loading of a structure and

may be quantified as the area inside a load-deformation hysteresis for one cycle. The area within

a hysteresis from an experimental test can be approximated by numerical integration. Numerical

integration involves averaging the load values of two consecutive points along the curve.

Multiplying this average load by the difference between deformation values of the same two

consecutive data points gives the area under the curve between those two data points.

Geometrically, the calculation equates to determining the area of very narrow trapezoid. This

process must be repeated for every pair of consecutive data points all the way around the loop.

Depending on the location along the curve with respect to the deformation axis, the area is

considered either positive or negative. The net total of these incremental areas is the hysteretic

energy as represented algebraically in Equation 2.7.12:

f n + f n +1
Ed =
n
( n +1 n ) (2.7.12)
n +1
2

where the integer n represents the individual data points around the entire loop. The spreadsheet

program follows the same process described above to arrive at a value for hysteretic energy for

each diaphragm test. However, for greater accuracy, the program calculates a total area for three

consecutive loops around the hysteresis (using data points only from the middle three loops) and
CHAPTER II: EXPERIMENTAL PROCEDURE 62

then divides the total by three, yielding an average area inside only one loop. See Figure 2.31 for

a visual description of numerical integration of a hysteresis.

fb
b Area under curve between points

fa a a and b to be considered positive
+

a b

fc c Area under curve between points


fd c and d to be considered negative
d
-
d c

Figure 2.31 Numerical Integration of a Load-Deformation Hysteresis


CHAPTER II: EXPERIMENTAL PROCEDURE 63

2.7.9 Equivalent Viscous Damping

Damping is the mechanism that causes gradual reduction of vibration in a system and

thereby a loss of energy. In structures, damping and the resulting energy loss is caused by a

variety of conditions such as internal friction of materials subjected to repeated deformations,

friction from movements at connections, opening and closing of cracks, and friction with

external or nonstructural systems with which the structure is in contact. Since the systems that

can cause damping are seemingly limitless and difficult to identify, a mathematical model

capable of predicting actual damping is nearly impossible.

Thus, a concept called equivalent viscous damping is used to represent all of the damping

mechanisms for a simplified approach under the assumption that the structure behaves as a

Kelvin solid viscoelastic element (Fischer and Filiatrault 2000). Equivalent viscous damping is

defined by equating the energy loss during a vibration cycle (i.e. the hysteretic energy as defined

in Section 2.7.8 and graphically as shown in Figure 2.32) in an actual structure to that of an

equivalent viscous system.


CHAPTER II: EXPERIMENTAL PROCEDURE 64

ko+
A

Xo- B
O
D
Xo+

Ed = Hysteretic Energy
C
(Area enclosed by hysteresis loop)
k o-

Figure 2.32 Damping relationship to an equivalent viscous system

Using Figure 2.32 and setting the hysteretic energy, Ed, from one experimental cycle

equal to that of the equivalent viscous system gives:

Ed = 2 eq ko X o
2
(2.7.13)
n

where eq is the equivalent viscous damping ratio, is the experimental test frequency, n is the

natural frequency of the test structure. Strain energy, ESo, is equal to the area of triangle OAB

(or triangle OCD) from Figure 2.32 and can be calculated from experimental stiffness, ko at

maximum deformation Xo:

2
ko X o
E So = AOAB = (2.7.14)
2

Substituting Equation 2.7.14 into Equation 2.7.13 gives:

Ed = 4 eq AOAB (2.7.15)
n
CHAPTER II: EXPERIMENTAL PROCEDURE 65

Although for this experiment does not actually equal n, for simplicity the assumption as such

does allow for an acceptable approximation of eq (Chopra 1995). Assuming = n and

solving for the equivalent viscous damping ratio gives:

Ed
eq = (2.7.16)
4AOAB

As shown in Figure 2.32, the maximum deformations in both the positive and negative directions

are not necessarily equal. Therefore, the equivalent viscous damping ratios should be calculated

for triangle OAB using ko+ and triangle OCD using ko- and then averaged. Thus, equivalent

viscous damping ratio, eq, is commonly expressed as:

Ed
eq = (2.7.17)
4ESo

where ESo is strain energy (equal to the area of triangle OAB or OCD).

For the purposes of this study, the spreadsheet program calculates the areas on both the positive

and negative sides of the curve using cyclic stiffness values determined by the origin-to-peak

method. The spreadsheet takes an average of the two strain energy values and the hysteretic

energy previously calculated, and uses a formula based on Equation 2.7.17 to determine the

equivalent viscous damping ratio for each diaphragm test.

Although equivalent viscous damping is not technically correct for the tests in this study

due to some non-linearity in the load-deformation response, the maximum specimen deflections

were kept low to minimize error. The viscous damping term is a measure of all of the damping

in the system (hysteretic and material) and is used for modeling the more complex system as a

simplified mass-spring-dash pot system. The equivalent viscous damping is the value for the

dash pot. While the design community views the concept of equivalent viscous damping as very
CHAPTER II: EXPERIMENTAL PROCEDURE 66

inaccurate for calculating damping in an actual structure, it is used in research simply as a means

of comparing damping capability.


CHAPTER III: RESULTS AND DISCUSSION 67

CHAPTER III

RESULTS AND DISCUSSION

3.1 INTRODUCTION

The objective of this diaphragm study was to test the stiffness of wood diaphragm

specimens under varying configurations in order to develop a method for determining shear

stiffness similar to that already used by the cold formed steel industry. Combined, 132 non-

destructive stiffness tests were performed on 6 different specimens. Due to the high volume of

data produced, a test-by-test analysis and comparison of results would be monotonous and not in

the best interest of the reader. Therefore, the calculations applied to each set of test data will be

thoroughly explained step-by-step in general terms. The remainder of this chapter will be

devoted to discussion of trends in test results and relating those trends back to the various

construction parameters. The individual test results are presented in Appendix A.

3.2 TEST CONDITIONS

As a foreword to discussion of results, the reader needs to be aware of the ever-changing

conditions encountered during testing, namely weather. Testing of diaphragm specimens began

on January 12, 2001 and continued until July 6, 2001. Throughout those six months the weather

played a substantial role in the test schedule, specimen moisture content, and periodic

malfunction of instruments and equipment.


CHAPTER III: RESULTS AND DISCUSSION 68

As indicated in Chapter 2, the diaphragm testing facility is an outside concrete slab with

no protection from the weather. A large tarp was always used to cover specimens and equipment

overnight and during inclement weather. Snow and ice from winter storms accumulated on top

of the tarp and managed to leak under the tarp in several locations, wetting some sheathing on

Specimens 1 and 2. Frequent high wind continually blew the tarp off exposing the specimen to

rain, snow, frost, and dew. To continue testing during the near daily rain of the extremely wet

Spring 2001, a canopy made of a simple ridge board and poly sheeting was built over Specimens

3 and 4. Though the canopy as shown in Figure 3.1 would allow testing during light rain, it

would not keep specimens completely dry from wind-blown rain. The effects of wet specimen

sheathing on test data are nearly impossible to quantify. However, one can assume that some

degradation of specimen stiffness occurred as a result.

Figure 3.1 Diaphragm Specimen with Canopy


CHAPTER III: RESULTS AND DISCUSSION 69

Moisture also had negative impacts on the instrumentation and test equipment. Although

all string potentiometers, LVDTs, and load cells were covered with plastic, moisture continually

caused malfunctions predominately from electrical short circuits. Notably prone to failure was

the left side reaction load cell. Failure of the reaction load cells is not an issue for symmetrical

specimen configurations (i.e. fully sheathed and center sheathing opening), since the assumption

can be made that the reaction loads are each equal to half of the load being applied at the center.

However, for torsionally irregular configurations (i.e. corner sheathing opening), this assumption

is not valid. Thus, statics was used to determine the loads at the reactions when only one load

cell failed.

The Test Description tables in Appendix E indicate notable weather conditions such as

rain, snow, and wind. The tables also indicate any significant test information such as, load

protocol, test configuration, specimen repairs, and any known malfunctioning instruments.

3.3 NAIL BENDING TEST RESULTS

Nail bending tests were performed on all four different nails used in the construction of

the diaphragm specimens. Nail bending capacity is important when determining what effect, if

any, a certain nail has on the stiffness of an overall specimen or any of its sub-components. The

four different nails used and their corresponding uses are:

Nail Description Nail Use


10d 0.132, collated, clipped-head, nail-gun Permanent sheathing fasteners
10d Duplex 0.149, double-headed Removable sheathing fasteners
16d 0.132, collated, clipped-head, nail-gun Permanent framing fasteners
16d Duplex 0.162, double-headed Removable rim-joist fasteners
CHAPTER III: RESULTS AND DISCUSSION 70

The 10d duplex (double-headed) nails allowed easy removal of sheathing panels in order to

simulate floor openings. The 16d duplex were used for easy removal of the rim-joists on

specimens loaded parallel to the joists (Specimens 1, 2, 5, and 6).

Nail bending test results showed that the 10d duplex nails had a 20% higher modulus of

elasticity than the 10d gun nails, indicating a higher material stiffness. The duplex nails also had

a 13% greater diameter than the gun nails. Combining the nail material variations with the

differences in nail diameter validates the 38% higher yield load developed in bending tests of the

10d duplex nail. Therefore, assuming all other nail properties constant (i.e. nail head size and

shape, nail coatings, penetration, wood damage), in the fastening of diaphragm sheathing the 10d

duplex nails can be expected to resist more load than the 10d gun-nails. No tests were performed

to determine the overall effects of the duplex nails on diaphragm stiffness, because duplex nails

are not used in real-life construction. However, for the purposes of thorough data analysis, it

should be noted that the higher yield capacity of the duplex nail could cause a small (though

likely negligible) amount of additional diaphragm stiffness. This increased stiffness would be

limited to the fully sheathed specimens with rim joists for which the 10d duplex nails were used

to replace center-opening and corner-opening sheathing as well as fasten the sheathing edge to

the re-attached rim joist. Nails were always replaced in new positions with new nail holes when

re-nailing the sheathing, thus minimizing the realized stiffness degradation caused by damage to

the plywood sheathing and joists from repeated nailing and nail pulling.

The 16d duplex nails have a less significant structural effect on diaphragm specimens.

These duplex nails are only used for temporary fastening of the rim joist (chord member) to the

ends of each floor joist. Test configurations of Specimens 3 and 4 did not include removal of the

rim joist, because their orientation (loading applied parallel to floor joists) required that the rim
CHAPTER III: RESULTS AND DISCUSSION 71

joists be the members permanently fastened to the steel frame at each side. For the in-plane

shear loading of diaphragm specimens, the fastener used to connect the rim joist to the joists is

less of a concern, since the predominant force exerted on the nailed connections is withdrawal

due to the bending of the chord. The important connections to consider with respect to the rim

joist are the nails fastening the plywood sheathing to the top edge of the rim joist. Though nail

bending tests showed that the 16d duplex nails exhibited an 11.2% higher yield capacity than the

16d gun nails, no increase in diaphragm stiffness can be expected, because the rim joist joist

connection experiences negligible shear load. No diaphragm tests were performed to actually

determine the effect of 16d duplex versus gun-driven nails in the connection of rim joists.

3.4 MOISTURE CONTENT AND DENSITY RESULTS

Moisture content and density are important factors in the strength of wood connections.

Moisture content is defined as the percentage weight of water to weight of oven-dry wood.

Lower moisture content corresponds to higher wood strength and stiffness. Likewise, a higher

density wood (more wood is present per unit volume) will exhibit greater strength and stiffness.

Higher wood strength and stiffness has a direct influence on the strength of wood connections.

In the case of nailed connections, a higher wood strength will force deflections to occur as

inelastic deformation of the nails rather than damage to the wood around the nails.

Moisture content and density tests were performed on a sample cut from a scrap piece

from each joist of every specimen. Tests of the samples were performed during construction of

the specimens. A summary of the average results for the joists of each specimen is provided in

Table 3.1 below. All of the bulk moisture content and density data for each specimen can be

found in Appendix D.
CHAPTER III: RESULTS AND DISCUSSION 72

Table 3.1 Average Moisture Content and Density Results by Specimen

Specimen # Moisture Content Density


% (g / cc)
Specimen 1 22 0.47
Specimen 2 22 0.48
Specimen 3 29 0.48
Specimen 4 23 0.51
Specimen 5 21 0.48
Specimen 6 15 0.48
Average 22 0.48

The 2x12 Douglas-fir lumber used for the joists of each specimen was stored outside for

several months prior to the start of testing. Before and during the testing phase, the lumber was

covered with plastic sheeting to protect it from the weather with only minimal success. Wind

frequently blew the plastic off the stack exposing it to rain and ice. Water vapor under the

plastic also condensed, adding more moisture to the wood. Moisture evidently made contact

with most of the lumber in the stack because, damp mildewed wood was found throughout. As a

result the lumber exhibited higher average moisture content than the standard maximum 19% for

seasoned Douglas-fir as shown in Table 3.1 above.

The average moisture contents of lumber used for Specimens 1 and 2 were equal at 22%.

The average moisture contents for Specimens 3 and 4 were the highest, while the values dropped

steadily for Specimens 5 and 6. Specimens 3 and 4 were tested during the unusually wet Spring

of 2001 when the lumber was most susceptible to humid air and rain. Conversely, Specimens 5

and 6 were tested during dryer summer weather after the lumber had dried some of the moisture

acquired during the winter and spring. Comparison of stiffness results from tests of identical
CHAPTER III: RESULTS AND DISCUSSION 73

configurations between Specimens 3 and 4 (20 x 16 ft.) and between Specimens 5 and 6 (10 x 40

ft.) did not support the logical assumption that higher moisture content in the lumber would

decrease diaphragm stiffness. In fact, comparison of data showed exactly the opposite in all but

one instance. There was no appreciable variation in wood density from one specimen to the

next. This indicates that while the wood was wet when the diaphragm specimens were

constructed, they dried over time and the water experienced after construction probably did not

re-wet more than the surface of the lumber and sheathing.

3.5 CONSTRUCTION PARAMETER RESULTS

Each construction parameter was examined for its effect on diaphragm stiffness and

damping by comparison of test results with and without the parameter, while holding all

other variables constant. In other words, there was no baseline standard test configuration used

for data comparison. For example, if the effects of blocking were desired, then results from a

test on Specimen X with the configuration of nailed only, fully sheathed, with chords, with walls,

but NO BLOCKING would be compared against the results from a test on Specimen X that is

nailed only, fully sheathed, with chords, with walls, and WITH BLOCKING. Comparisons are

presented in the form of percent difference between each pair of test results of equivalent viscous

damping, cyclic stiffness, shear stiffness, and flexural stiffness. For the purpose of this study, the

percent difference is calculated from test results as the difference between the with and

without values divided by the without value. Only results from pairs of tests within the

same specimen are compared. Except for corner opening and center opening configurations,

which are compared against the fully sheathed counterpart, only the fully sheathed specimen

configuration is considered when comparing results for blocking, adhesives, walls, chords, and
CHAPTER III: RESULTS AND DISCUSSION 74

nail density. Shear stiffness results for the left and right side of specimens are averaged together

for the comparison of all parameters except corner sheathing opening. Because the corner

sheathing opening did not necessarily occur on the same side for all specimens, the averaged

shear stiffness comparison results are differentiated as either full side meaning the side that is

fully sheathed, or opening side meaning the side with the sheathing opening. All comparison

results for each pair of tests are tabulated in Appendix B. The percent difference values from

each comparison within the same parameter were averaged together. For example, all of the

cyclic stiffness percent difference values from with and without chords comparisons were

averaged together to produce a 40% average percent difference as shown in Table 3.2. Table 3.2

provides the average percent difference from all of the comparisons broken down by equivalent

viscous damping, cyclic stiffness, shear stiffness, and flexural stiffness for each construction

parameter evaluated.

Table 3.2 Average Percent Differences by Construction Parameter

Average Percent Difference


Construction
Parameter Equivalent Viscous
Cyclic Stiffness Shear Stiffness Flexural Stiffness
Damping
Blocking -49% 72% 135% 12%
Adhesive -41% 47% 89% 10%
Blocking & Adhesive -67% 106% 259% 5%
3-12 Nail Pattern -16% 25% 37% 7%
Chords -5% 40% 8% 154%
Walls 0% 19% 5% 54%
Center Opening 19% -30% -37% -12%
Full Side Opening Side
Corner Opening 5% -21% -6%
4% -48%
CHAPTER III: RESULTS AND DISCUSSION 75

Inspection of the comparison tables in Appendix B that make up Table 3.2 shows that

many of the percent differences are significantly higher or lower than average. This can be

attributed to error from several factors: unevenly excited side load cells, recurring failure of the

left side load cell, higher stiffness results at the outset of testing on each specimen, specimen

damage from repeated construction parameter changes, and deterioration of plywood sheathing

from repeated exposure to weather. The averaged values in Table 3.2 appear to diminish the

influence of the inordinately high and low percent differences. For example, comparing tests 4

and 44 of Specimen 2 for the effects of foam adhesive (versus nailed only) on shear stiffness

results in an actual decrease of 17% while the average was an increase of 89%. Similarly,

comparing tests 1 and 2 of Specimen 5 for the effects of walls on flexural stiffness yields an

increase of 295% while the average was only 54%.

Blocking under the otherwise unsupported edges of sheathing panels was found to have

the greatest overall impact on diaphragm stiffness and damping. As shown in Table 3.2, the

average percent difference in shear stiffness between corresponding tests of unblocked versus

blocked configurations within the same specimen was 135%. This means that on average and

with all other parameters constant, the shear stiffness of a specimen more than doubles from the

addition of blocking. Blocking also provides a 72% increase in cyclic stiffness, largely

attributable to shear stiffness due to the sharp contrast of only a 12% gain in flexural stiffness.

This makes sense because the blocking enhances the transfer of shear forces that are carried by

the sheathing. Blocking decreases the damping capability of wood diaphragms by as much as

49%.

Foam adhesive follows blocking as the second most effective method to increase

diaphragm shear stiffness. Shear stiffness and cyclic stiffness increased by 89% and 47%,
CHAPTER III: RESULTS AND DISCUSSION 76

respectively. Similar to blocking, the use of adhesives caused a limited gain in flexural stiffness

of only 10%. These results provide a sound basis for recommending that all horizontal light-

frame diaphragm sheathing (floor and roof) should be glued as well as nailed.

The combination of blocking and foam adhesive together is shown to cause a tremendous

increase in shear stiffness of 259% as compared to either of the two parameters alone. It makes

sense that the shear stiffness increase for configurations that combine blocking and foam

adhesive is even greater than the sum of the individual shear stiffness gains of either parameter

alone, because when blocking is present, there are more joints to which foam adhesive can be

applied, and the transfer of shear force from one sheet of sheathing to the next is enhanced.

The 3-12 nail pattern that was only investigated for four tests on Specimens 3 and 4 each

provided only modest shear and cyclic stiffness gains in comparison to blocking or adhesive.

However, this detail should be further investigated to determine if it could be used to enhance

soft portions of diaphragms due to the presence of openings.

Center and corner sheathing openings had inconsistent effects on diaphragm stiffness.

By removing only one 4 x 8 ft. sheet of plywood (10% sheathed area reduction) from a corner,

the shear stiffness on the side with the opening decreased by 48%. Also exhibited by the corner

opening configuration, was an actual 4% increase in the shear stiffness on the side that remained

fully sheathed, due to the tendency of a torsionally irregular diaphragm to absorb more of an

applied load on its stiff side. In contrast to the 10% sheathing reduction from a corner

opening, the center opening configuration reduced the sheathed surface area by 30% (8 x 12 ft.

opening), but the shear stiffness only decreased by 37%. Thus, shear stiffness is more dependent

on the location of the opening than the size of the opening. Conversely, the decreases in cyclic

stiffness of 30% and flexural stiffness of 12% were appreciably greater for the large center
CHAPTER III: RESULTS AND DISCUSSION 77

opening than for the smaller corner opening. Thus, it appears that the reduction in cyclic

stiffness varies proportionally with the percentage of sheathing removed, and, the relationship is

potentially linear for a center opening.

The presence of chords caused a 154% increase in flexural stiffness. However, because

diaphragm stiffness is largely a function of shear stiffness, this significant flexural increase only

translated into a 40% gain in cyclic stiffness. The flexural stiffness gained is mostly attributable

to the resistance to tension (or compression, depending on the direction of the flexure and the

side of the diaphragm) in the 2 x 12 chords. The diaphragm configuration without chords must

resist the same tension and compression forces with only the sheathing located along the extreme

edges.

The four feet high walls attached to the front and back edges of diaphragm specimens

produced a 54% increase in flexural stiffness, though only a 19% gain in cyclic stiffness. Similar

to chords, resistance to tension (or compression) force due to bending action is the only

significant advantage that walls offer with respect to diaphragm stiffness.

It is important to note how methods for stiffening a diaphragm can impact shear stiffness,

but not flexural stiffness, or vice versa. Sheathing and in particular any method that stiffens the

connections between adjacent sheathing panel edges will produce an increase in shear stiffness,

GAs, of the diaphragm. Loads applied to a diaphragm produce shear forces in the sheathed area,

which are transmitted from one sheathing panel to the next (depending on the connection

stiffness) until they can be transferred out of the diaphragm at the supports. Shear forces pass

from the edge of one sheathing panel to another through the sheathing connections to a local

framing member, then from the framing member to the sheathing connection of the adjacent

panel, and finally into the adjacent panel. While the considerable in-plane shear stiffness of each
CHAPTER III: RESULTS AND DISCUSSION 78

individual sheathing panel is not a concern, the means used to interconnect the panels together to

create one large homogenous sheathing system has a direct impact on the overall diaphragm

shear stiffness. As shown by the results, the sheathing connections that employ blocking or

adhesives produce large increases in diaphragm shear stiffness by forcing the shear to be

transferred out of the diaphragm instead of being dissipated by local deflections along adjacent

sheathing panel edges.

In contrast, flexural stiffness, EI, is derived from construction techniques that simulate

the flanges of a wide-flange beam. As evidenced from test results, chord members effectively

serve this role by resisting the tension and compression forces that develop at the extreme edges

of a diaphragm. As can be expected from 2x lumber turned on-edge, chords offer a negligible

increase in shear stiffness.

3.6 DIAPHRAGM STIFFENING METHODS

When a certain aspect of the construction of a diaphragm causes an appreciable decrease

in stiffness, other construction techniques can be employed to replace the stiffness lost. The

construction parameter evaluations discussed above can be used to develop suggestions for

altering diaphragm stiffness as necessary for real-life applications.

For instance, openings in a diaphragm are the most significant stiffness decreasing

construction factors. Typical openings in floor diaphragms are for stairs, atriums, ductwork

shafts, etc. The most common occurrence of openings in roof diaphragms is due to the presence

of skylights. In either case, if the opening is in roughly the same proportion as tested in this

study, it may be possible to make up the difference in lost stiffness by increasing the nail density.

As shown in Table 3.2, the gain in stiffness due to increasing the nail density from a 6-12 pattern
CHAPTER III: RESULTS AND DISCUSSION 79

to a 3-12 pattern is roughly equivalent to the stiffness lost from center and corner openings. An

opening that is significantly larger in proportion to the overall size of the diaphragm than the

configurations tested in this study may need a more effective approach to replace the stiffness,

such as installation of blocking and/or foam adhesive. Because corner openings create a

significant decrease in shear stiffness only on the side with the opening, the method used to

replace the shear stiffness may only be needed on that side.

Though outside the scope of this study, another construction method for stiffening a

diaphragm with an opening is to transfer the forces that concentrate in the framing around the

opening to the surrounding diaphragm sheathing. When the framing around an opening

experiences tension or compression forces due to diaphragm deformation, these framing

members behave like struts. Transferring these forces from the ends of the opening framing into

the diaphragm will diminish the effects of the opening and can be accomplished by extending the

framing into the diaphragm some distance in the direction perpendicular to the joists. It is

generally accepted that three or four joist spacings is enough distance to adequately transfer the

forces, but this was not investigated as part of this project. As shown in Figure 3.2, the extended

framing member, called a collector tie, is simply a line of blocking installed between floor joists.

By themselves, the collector ties can only transfer compression forces, but with the addition of

steel strapping (attached along the top of the collectors and fastened back to the opening

framing), they can also handle tension forces. Additionally, by restraining the tension and

compression forces, the collector ties essentially cause the opening framing to behave as chords.

The resulting increase in flexural stiffness (concentrated around the opening) from chord-action

can offset the loss in shear stiffness originally caused by the opening.
CHAPTER III: RESULTS AND DISCUSSION 80

APPLIED
LOAD
23
32" T&G PLYWOOD JOISTS @ 16" o.c.
SHEATHING

OPENING FRAMING COLLECTOR TIES


(TYP)

Figure 3.2 Floor Diaphragm with an Opening and Collector Ties

Another factor that could limit the stiffness of a diaphragm is the lack of an effective

chord member. In the case of a floor diaphragm, the chords are typically referred to as rim-joists

or band-joists. For roof diaphragms, fascia boards can serve as the chords. The stiffness gain

that is attributable to the presence of effective chords is predominately in the form of flexural

stiffness. While overall cyclic stiffness is largely proportional to the shear stiffness of a
CHAPTER III: RESULTS AND DISCUSSION 81

diaphragm, Table 3.2 shows that in the case of presence of chords, a substantial gain in flexural

stiffness can result in a moderate increase in cyclic stiffness as well. Note, the effectiveness of a

chord member is highly dependent on proper splicing if necessary and proper fastening of the

overhanging edge of sheathing to the top edge of the chord. If the rim-joist of a floor diaphragm

is ineffectively installed, the associated loss of stiffness can be counteracted to some degree by

ensuring that the perimeter walls over the rim joist are well fastened to the floor. This would

entail increasing the frequency with which the bottom plate of the wall is nailed down to the

floor. One method that may increase the effectiveness of the walls is by using a double-

thickness bottom plate and staggering the boards so that the end-joints are offset. Since most of

the stiffening properties of walls attached to a diaphragm are derived from the flexural resistance

of the bottom plate itself, another method to augment the effectiveness of the walls would be to

use a 2x6 bottom plate in lieu of the standard 2x4. While the use of enlarged bottom plates was

not investigated as a part of this study, a 2x6 bottom plate would generate coordination issues

with regards to how finish materials would be attached to the wall unless the wall studs are also

enlarged accordingly.
CHAPTER IV: SUMMARY AND CONCLUSIONS 82

CHAPTER IV

SUMMARY AND CONCLUSIONS

4.1 SUMMARY

The objective of Task 1.4.2 of the CUREE-Caltech Woodframe Project is the

experimental evaluation of varying diaphragm construction parameters for use in the

development of a simpler and more easily adaptable formula to accurately predict the stiffness of

wood diaphragms. Under this study, six diaphragm specimens were tested under cyclic

nondestructive loads and with varying construction configurations in order to evaluate the effect

on stiffness caused by each of the construction parameters. Specifically, the results for each

construction parameter are intended for use in the validation and calibration of a general-use

finite element model for diaphragm analysis under another task of the above-referenced project.

In order to achieve realistic results, these construction parameters were applied to specimens of

varying aspect ratios (4:5, 5:4, and 1:4) and orientations with respect to the direction of the loads.

The construction parameters evaluated were:

Blocking with / without 2 x 4 blocking


Sprayed foam adhesive & nails versus nailed only
Sheathing openings corner opening and center opening (versus fully sheathed)
Chord members with / without rim joist
Walls with / without 4 ft. tall stud-framed walls
Sheathing nail density 6/12 versus 3/12 nail pattern
CHAPTER IV: SUMMARY AND CONCLUSIONS 83

Testing consisted of a full-scale specimen mounted to a steel test frame as described in

Chapter II. Specimens were tested under varying combinations of the above parameters. All

specimens were subjected to five equal displacement-based sinusoidal load cycles from a

computer-controlled hydraulic actuator. Each cycle included a positive and negative (push and

pull) displacement of the specimen. The maximum displacement used for testing was

determined individually for each diaphragm aspect ratio by loading the first specimen

monotonically with incrementally increasing amplitude until the load-deflection plot on the data

acquisition computer began showing signs of stiffness degradation. The amplitude used for all

of the following cyclic tests of that specimen was a slightly smaller value than the maximum

monotonic displacement.

Chapter III provides the summarized stiffness results from all 132 tests in the form of

average percent differences for each parameter. The numerical results are used to qualitatively

evaluate and rank each parameter in terms of its diaphragm stiffening performance. Based on the

results, several suggestions are made for stiffness enhancement of diaphragms that exhibit a lack

of stiffness for reasons such as openings or lack of effective chords.

4.2 CONCLUSIONS

Based on the numerical analysis of test results, several conclusions can be made

regarding the effects of the above construction parameters on diaphragm stiffness:

Foam adhesive and blocking is the most effective combination of parameters with an

increase in shear stiffness of 259% and an increase in cyclic stiffness of 106%.


CHAPTER IV: SUMMARY AND CONCLUSIONS 84

Blocking under the otherwise-unsupported sheathing panel edges provides the greatest

individual increase in diaphragm stiffness with an average 135% increase in shear

stiffness and a 72% increase in cyclic stiffness.

The use of foam adhesive (when blocking is not present) is the second most effective

single parameter. The application of foam adhesive causes an 89% increase in shear

stiffness and a 47% increase in cyclic stiffness. Further investigation is warranted to

determine if foam adhesive alone, surface-applied to the unsupported sheathing panel

joints (where blocking would typically be installed), is nearly as effective as blocking

alone at locking the two panel edges together against horizontal shear. If determined to

be an effective means of restraining the shear in the joints between unsupported

sheathing edges, it may be a cost-saving alternative to blocking.

Diaphragm shear stiffness is directly related to the quality of the sheathing connections.

Any construction techniques that serve to better interlock sheathing panels into one

large sheathing system against horizontal shear, will result in increased shear stiffness.

Results indicate that because overall diaphragm stiffness is mostly comprised of shear

stiffness, increases in shear stiffness will usually cause similar increases in overall

diaphragm stiffness.

Center and corner sheathing openings had disproportionate effects on diaphragm

stiffness. A smaller corner opening (10% sheathing removal) caused a greater reduction

in shear stiffness (on the side with the opening) than a larger center opening (30%

sheathing removal). Thus, shear stiffness is more dependent on the location of the

opening than the size of the opening. However, it appears that the reduction in cyclic
CHAPTER IV: SUMMARY AND CONCLUSIONS 85

stiffness varies proportionally with the percentage of sheathing removed, and, the

relationship is potentially linear for a center opening.

As can be expected for torsionally irregular diaphragms such as the corner opening

configuration, the side that remains fully sheathed can be expected to absorb more of

an applied load than the softer side with the corner opening, actually causing an

increase in shear stiffness on the fully sheathed side.

The presence of effective chord members (rim joists in the case of floor diaphragms)

causes a significant increase in flexural stiffness. However, because diaphragm stiffness

is largely a function of shear stiffness, this significant flexural increase only translated

into a moderate cyclic stiffness increase. The flexural stiffness gained is attributable to

the resistance to tension and compression forces by the rim joist boards themselves.

Proper splicing and adequate fastening of the overhanging edge of sheathing is important

to the performance of chords.

Perimeter walls can effectively stiffen a diaphragm if the bottom plate is continuous and

adequately fastened-down. Due to the resistance of the bottom plate to the tension forces

developed through bending action, the primary effect of walls on diaphragms is

increased flexural stiffness.


REFERENCES 86

REFERENCES

Anderson, G.A. and Bundy, D.S. (1990). Stiffness Of Screw-Fastened, Metal-Clad, Timber-
Framed Roof Diaphragms With Openings In The Sheathing, Transactions in Agriculture, ASAE
33(1), 266-273.

Building Seismic Safety Council. (1998a). NEHRP Recommended Provisions for Seismic
Regulations for New Buildings and Other Structures, Part 1 - Provisions, 1997 Edition, FEMA
302, Washington, D.C.

Chopra, A.K. (1995). Dynamics of Structures: Theory and Applications to Earthquake


Engineering, Prentice Hall, Upper Saddle River, NJ, 97-99.

Corda, D.N. (1982). The In-Plane Shear Response of Timber Diaphragms, Masterss Thesis,
West Virginia University, Morgantown, WV.

Countryman, D. (1952). Lateral Tests On Plywood Sheathed Diaphragms, Laboratory Report


No. 55, Douglas-fir Plywood Association, Tacoma, WA.

Countryman, D. and Colbenson, P. (1954). 1954 Horizontal Plywood Diaphragm Tests,


Laboratory Report No. 63, Douglas-fir Plywood Association, Tacoma, WA.

Dolan, J.D. (1999). Design Guidelines for Wood Diaphragms, Proposal to CUREe-Caltech
Wood Frame Project Task 1.4.2 Diaphragm Studies, Blacksburg, VA.

Fischer, D. and Filiatrault, A. (2000). Quasi-Static Test Results of Floor Diaphragms, Report for
CUREe-Caltech Wood Frame Project Task 1.1.1, University of California, San Diego, CA.

GangaRao, H.V.S. and Luttrell, L.D. (1980). Preliminary Investigations Into The Response of
Timber Diaphragms, Proceedings of a Workshop on Design Of Horizontal Wood Diaphragms,
Applied Technology Council, Berkely, CA, November 19-20, 1979, 277-295.

Hankins, S.C., Easterling, W.S., and Murray, T.M. (1992). Vulcraft 1.5BI Cantilever
Diaphragm Tests, Virginia Polytechnic Institute and State University, Report No. CE/VPI-ST-
92/01, Blacksburg, VA.

Hausmann, C.T. and Esmay, M.L. (1977). The Diaphragm Strength of Pole Buildings,
Transactions of the ASAE, 20(1), 114-116.

International Building Code 2000. International Code Council, Falls Church, VA.

Jewell, R.B. (1981). The Static and Dynamic Experimental Analysis Of Wooden Diaphragms,
Masterss Thesis, West Virginia University, Morgantown, WV.
REFERENCES 87

Krawinkler, H., Parisi, F., Ibarra, L., Ayoub, A., Medina, R. (2000). Development of a Testing
Protocol for Wood Frame Structures, Stanford University, Stanford, CA.

Polensek, A. (1979). Damping Capacity of a Nailed Wood-Joist Floor, Wood Science, 11(3),
155-159.

Roberts, J.D. (1983). Finite Element Analysis Of Horizontal Timber Diaphragms, Masterss
Thesis, West Virginia University, Morgantown, WV.

Stillinger, J.R. and Countryman, D. (1953). Lateral Tests on Full-Scale Plywood Sheathed Roof
Diaphragms, Laboratory Report No. T-5, Oregon Forest Products Laboratory, Corvallis, OR.

Tissell, J.R. and Elliott, J.R. (1997). Plywood Diaphragms, Laboratory Report No. 138,
American Plywood Association, Tacoma, WA.

Tissell, J.R. (1966). 1966 Horizontal Plywood Diaphragm Tests. Laboratory Report No. 106,
American Plywood Association, Tacoma, WA.

Uniform Building Code 1997. International Conference of Building Officials, Whittier, CA.

Widjaja, B.R. (1993). Analytical Investigation of Composite Diaphragms Strength and


Behavior, Masters Thesis, Virginia Polytechnic Institute and State University, Blacksburg, VA.

Woeste, F. and Townsend, M. (1991). Simple-Beam Diaphragm Test Considerations, ASAE


Paper No. 91-4059, ASAE, St. Joseph, MI.

Wright, B.W. and Manbeck, H.B. (1993). Finite Element Analysis of Wood-Framed, Metal-Clad
Diaphragm Panels, Transactions of the ASAE, 36(3), 895-904.
APPENDIX A TEST RESULTS 88

APPENDIX A TEST RESULTS

A.1 INTRODUCTION

Presented below are tables of the test results for each specimen. The tables include

values in the form of equivalent viscous damping, cyclic stiffness, shear stiffness, and flexural

stiffness. The following abbreviations are used to describe the test configurations:

NC = No Chords
WC = With Chords
NW = No Walls
WW = With Walls
Full = Fully Sheathed
Center = Center Sheathing Opening
Corner = Corner Sheathing Opening
B = Blocked
UB = UnBlocked
NO = Nailed Only
N&A = Nailed and Foam Adhesive Applied
3-12 = 3-12 Nail Pattern (versus the default 6-12 nail pattern)
APPENDIX A TEST RESULTS 89

Table A.1 Specimen 1 Test Results

Equiv. Viscous Cyclic Left Shear Right Shear Flexural


Test Damping Stiffness Stiffness Stiffness Stiffness
Test Configuration
No. eq kcyclic GAsL GAsR EI
(%) (kips/in) (kips) (kips) (kips-in2)

1 NC; NW; Corner; UB; NO 13.5 29.2 3,369 1,642 26.9E+6


2 WC; NW; Corner; UB; NO 10.9 30.7 3,098 1,432 68.6E+6
3 WC; WW; Corner; UB; NO 9.9 33.0 3,183 1,573 76.0E+6
4 NC; WW; Corner; UB; NO 11.9 37.5 3,347 1,858 83.1E+6
5 NC; WW; Full; UB; NO 11.6 43.7 3,145 58.3E+6
6 WC; WW; Full; UB; NO 10.4 48.2 3,258 83.2E+6
7 WC; NW; Full; UB; NO 11.3 44.5 3,091 66.3E+6
8 NC; NW; Full; UB; NO 12.8 29.4 2,410 26.1E+6
9 NC; NW; Center; UB; NO 12.0 18.1 1,266 18.5E+6
10 WC; NW; Center; UB; NO 10.8 29.1 1,845 58.3E+6
11 WC; WW; Center; UB; NO 8.8 30.2 1,904 61.9E+6
12 NC; WW; Center; UB; NO 9.1 22.9 1,438 41.5E+6
13 WC; NW; Center; UB; N&A 3.7 42.6 2,894 87.2E+6
14 WC; WW; Center; UB; N&A 3.8 41.3 2,912 73.1E+6
15 NC; WW; Center; UB; N&A 5.1 29.9 2,193 40.6E+6
16 NC; NW; Center; UB; N&A 4.8 21.0 1,621 21.4E+6
17 WC; NW; Full; UB; N&A 4.6 51.2 4,166 58.6E+6
18 WC; WW; Full; UB; N&A 4.4 51.3 4,054 63.2E+6
19 NC; WW; Full; UB; N&A 5.0 43.3 3,645 43.4E+6
20 NC; NW; Full; UB; N&A 4.5 35.4 3,234 28.1E+6
21 NC; NW; Corner; UB; N&A 4.9 30.5 3,559 2,031 25.1E+6
22 WC; NW; Corner; UB; N&A 4.5 37.7 3,735 2,043 58.2E+6
23 WC; WW; Corner; UB; N&A 4.3 39.5 3,973 2,064 72.7E+6
24 NC; WW; Corner; UB; N&A 5.1 35.5 3,685 2,067 44.4E+6
APPENDIX A TEST RESULTS 90

Table A.2 Specimen 2 Test Results

Equiv. Viscous Cyclic Left Shear Right Shear Flexural


Test Damping Stiffness Stiffness Stiffness Stiffness
Test Configuration
No. eq kcyclic GAsL GAsR EI
(%) (kips/in) (kips) (kips) (kips-in2)

1 WC; NW; Full; B; NO 6.8 66.2 6,183 52.8E+6


2 WC; WW; Full; B; NO 6.6 71.8 6,387 62.1E+6
3 NC; WW; Full; B; NO 6.8 65.3 6,002 52.9E+6
4 NC; NW; Full; B; NO 6.9 55.5 5,627 38.2E+6
5 NC; NW; Corner; B; NO 7.2 38.6 5,028 2,824 29.3E+6
6 WC; NW; Corner; B; NO 7.3 44.5 5,368 2,519 51.7E+6
7 WC; WW; Corner; B; NO 7.0 46.7 5,378 2,643 57.2E+6
8 NC; WW; Corner; B; NO 7.4 44.1 4,942 2,506 55.6E+6
9 NC; NW; Center; B; NO 9.7 24.3 2,039 22.3E+6
10 WC; NW; Center; B; NO 9.2 34.5 2,419 55.5E+6
11 WC; WW; Center; B; NO 8.6 36.9 2,489 63.0E+6
12 NC; WW; Center; B; NO 9.7 31.2 2,173 46.6E+6
13 WC; NW; Full; UB; NO 12.9 35.6 2,640 56.9E+6
14 WC; WW; Full; UB; NO 12.5 36.4 2,555 66.1E+6
15 NC; WW; Full; UB; NO 12.8 32.9 2,413 47.5E+6
16 NC; NW; Full; UB; NO 12.5 27.5 2,347 25.1E+6
17 NC; NW; Corner; UB; NO 11.0 22.6 2,841 1,330 22.2E+6
18 WC; NW; Corner; UB; NO 10.9 26.7 2,753 1,215 60.2E+6
19 WC; WW; Corner; UB; NO 9.7 27.9 2,746 1,275 68.5E+6
20 NC; WW; Corner; UB; NO 9.9 25.0 2,698 1,164 49.8E+6
21 NC; NW; Center; UB; NO 11.0 19.4 1,570 20.3E+6
22 WC; NW; Center; UB; NO 11.2 24.9 1,609 82.2E+6
23 WC; WW; Center; UB; NO 10.9 28.2 1,831 79.4E+6
24 NC; WW; Center; UB; NO 11.5 23.5 1,603 49.5E+6
25 WC; NW; Center; UB; N&A 4.6 32.1 2,288 57.0E+6
26 WC; WW; Center; UB; N&A 8.6 36.7 2,549 76.1E+6
27 NC; WW; Center; UB; N&A 9.5 29.4 2,065 50.3E+6
28 NC; NW; Center; UB; N&A 8.9 22.9 1,793 24.8E+6
29 WC; NW; Full; UB; N&A 6.4 47.0 3,829 52.6E+6
30 WC; WW; Full; UB; N&A 6.9 47.3 3,501 74.9E+6
31 NC; WW; Full; UB; N&A 8.0 41.0 3,338 49.4E+6
32 NC; NW; Full; UB; N&A 7.8 33.4 3,284 25.7E+6
33 NC; NW; Corner; UB; N&A 8.2 26.4 3,841 1,646 22.0E+6
34 WC; NW; Corner; UB; N&A 7.2 31.7 3,883 1,505 53.1E+6
35 WC; WW; Corner; UB; N&A 7.0 33.3 3,770 1,564 67.3E+6
APPENDIX A TEST RESULTS 91

Table A.2 (Continued) Specimen 2 Test Results

Equiv. Viscous Cyclic Left Shear Right Shear Flexural


Test Damping Stiffness Stiffness Stiffness Stiffness
Test Configuration
No. eq kcyclic GAsL GAsR EI
(%) (kips/in) (kips) (kips) (kips-in2)

36 NC; WW; Corner; UB; N&A 7.7 29.4 3,605 1,426 47.5E+6
37 WC; NW; Center; B; N&A 5.4 38.7 2,989 49.6E+6
38 WC; WW; Center; B; N&A 5.9 41.3 3,082 63.6E+6
39 NC; WW; Center; B; N&A 6.8 33.9 2,599 45.6E+6
40 NC; NW; Center; B; N&A 6.0 25.9 2,244 23.2E+6
41 WC; NW; Full; B; N&A 4.1 67.5 6,185 54.7E+6
42 WC; WW; Full; B; N&A 4.6 67.9 6,086 59.7E+6
43 NC; WW; Full; B; N&A 5.6 54.9 5,099 43.6E+6
44 NC; NW; Full; B; N&A 4.4 46.4 4,692 31.3E+6
45 NC; NW; Corner; B; N&A 4.6 37.4 4,688 2,509 30.0E+6
46 WC; NW; Corner; B; N&A 4.3 47.9 5,880 2,557 57.2E+6
47 WC; WW; Corner; B; N&A 4.3 51.0 6,171 2,684 66.0E+6
48 NC; WW; Corner; B; N&A 4.9 44.6 5,480 2,420 51.6E+6
APPENDIX A TEST RESULTS 92

Table A.3 Specimen 3 Test Results

Equiv. Viscous Cyclic Left Shear Right Shear Flexural


Test Damping Stiffness Stiffness Stiffness Stiffness
Test Configuration
No. eq kcyclic GAsL GAsR EI
(%) (kips/in) (kips) (kips) (kips-in2)

1 NW; Full; B; NO 7.1 65.0 4,417 32.7E+6


2 WW; Full; B; NO 6.0 68.0 4,506 36.6E+6
3 WW; Corner; B; NO 6.6 53.8 1,784 4,334 37.0E+6
4 NW; Corner; B; NO 6.7 49.7 1,801 4,129 28.5E+6
5 NW; Center; B; NO 7.7 35.3 2,006 35.3E+6
6 WW; Center; B; NO 7.5 39.6 2,388 30.2E+6
7 NW; Full; B; NO; 3-12 6.1 83.9 6,425 33.2E+6
8 WW; Full; B; NO; 3-12 5.8 86.2 6,312 36.9E+6
9 WW; Full; UB; NO; 3-12 17.2 58.6 3,803 35.1E+6
10 NW; Full; UB; NO; 3-12 18.5 49.2 3,047 34.9E+6
11 NW; Full; UB; NO 18.6 46.3 2,880 32.1E+6
12 WW; Full; UB; NO 17.6 54.3 3,453 36.8E+6
13 WW; Corner; UB; NO 16.5 47.3 2,075 2,713 30.9E+6
14 NW; Corner; UB; NO 17.6 42.0 1,675 2,536 25.9E+6
15 NW; Center; UB; NO 17.0 24.1 996 26.2E+6
16 WW; Center; UB; NO 15.5 29.1 1,347 29.1E+6
17 NW; Full; UB; N&A 10.6 79.2 4,630 44.3E+6
18 WW; Full; UB; N&A 11.9 68.6 4,272 33.4E+6
19 WW; Corner; UB; N&A 12.2 63.2 2,128 3,647 59.2E+6
20 NW; Corner; UB; N&A 12.0 63.8 2,056 3,101 120.9E+6
21 NW; Corner; B; N&A 4.3 95.3 4,668 12,078 29.7E+6
22 WW; Corner; B; N&A 4.7 89.7 4,174 10,582 30.0E+6
23 WW; Full; B; N&A 6.5 71.6 6,296 23.5E+6
24 NW; Full; B; N&A 6.3 69.0 6,134 22.3E+6
APPENDIX A TEST RESULTS 93

Table A.4 Specimen 4 Test Results

Equiv. Viscous Cyclic Left Shear Right Shear Flexural


Test Damping Stiffness Stiffness Stiffness Stiffness
Test Configuration
No. eq kcyclic GAsL GAsR EI
(%) (kips/in) (kips) (kips) (kips-in2)

1 NW; Full; B; NO 6.8 62.3 5,613 19.7E+6


2 WW; Full; B; NO 6.5 64.0 5,828 20.0E+6
3 WW; Corner; B; NO 7.1 51.7 2,691 5,800 16.7E+6
4 NW; Corner; B; NO 7.4 48.7 2,501 5,028 16.8E+6
5 NW; Center; B; NO 8.3 31.8 1,934 13.7E+6
6 WW; Center; B; NO 7.8 34.6 2,160 13.9E+6
7 NW; Full; B; NO; 3-12 4.7 77.3 7,178 21.4E+6
8 WW; Full; B; NO; 3-12 4.7 80.1 7,969 20.9E+6
9 WW; Full; UB; NO; 3-12 8.2 42.1 2,765 17.0E+6
10 NW; Full; UB; NO; 3-12 8.2 38.2 2,394 16.3E+6
11 NW; Full; UB; NO 10.7 26.6 1,418 13.7E+6
12 WW; Full; UB; NO 11.2 30.4 1,732 14.4E+6
13 WW; Corner; UB; NO 11.4 25.3 1,122 1,688 12.3E+6
14 NW; Corner; UB; NO 11.0 22.3 962 1,375 11.3E+6
15 NW; Center; UB; NO 14.9 20.5 1,058 11.0E+6
16 WW; Center; UB; NO 13.7 24.1 1,276 12.3E+6
17 WW; Full; UB; N&A 6.0 65.0 5,048 22.0E+6
18 NW; Full; UB; N&A 6.8 54.9 4,119 18.3E+6
19 NW; Corner; UB; N&A 7.4 43.2 2,361 3,679 16.4E+6
20 WW; Corner; UB; N&A 7.5 43.6 2,306 3,666 16.6E+6
21 WW; Corner; B; N&A 3.1 72.3 4,754 10,232 18.9E+6
22 NW; Corner; B; N&A 3.2 67.4 4,389 9,980 17.5E+6
23 NW; Full; B; N&A 2.7 93.3 12,857 21.4E+6
24 WW; Full; B; N&A 2.7 91.7 11,821 21.6E+6
APPENDIX A TEST RESULTS 94

Table A.5 Specimen 5 Test Results

Equiv. Viscous Cyclic Left Shear Right Shear Flexural


Test Damping Stiffness Stiffness Stiffness Stiffness
Test Configuration
No. eq kcyclic GAsL GAsR EI
(%) (kips/in) (kips) (kips) (kips-in2)

1 NW; NC; Full; B; NO 7.9 4.0 2,010 12.2E+6


2 WW; NC; Full; B; NO 8.3 8.8 1,891 48.4E+6
3 WW; WC; Full; B; NO 8.9 11.7 2,022 102.2E+6
4 NW; WC; Full; B; NO 9.2 9.4 1,728 68.2E+6
5 NW; WC; Corner; B; NO 13.3 8.4 833 3,409 54.9E+6
6 WW; WC; Corner; B; NO 13.1 9.2 812 3,443 79.4E+6

Table A.6 Specimen 6 Test Results

Equiv. Viscous Cyclic Left Shear Right Shear Flexural


Test Damping Stiffness Stiffness Stiffness Stiffness
Test Configuration
No. eq kcyclic GAsL GAsR EI
(%) (kips/in) (kips) (kips) (kips-in2)

1 NW; NC; Full; B; NO 16.3 3.4 996 12.5E+6


2 WW; NC; Full; B; NO 16.2 5.1 850 35.2E+6
3 WW; WC; Full; B; NO 15.0 6.3 833 103.2E+6
4 NW; WC; Full; B; NO 15.1 5.7 764 80.2E+6
5 NW; WC; Corner; B; NO 14.2 4.2 331 994 86.1E+6
6 WW; WC; Corner; B; NO 14.3 4.5 367 1,030 101.5E+6
APPENDIX B TEST COMPARISONS 95

APPENDIX B TEST COMPARISONS

B.1 INTRODUCTION

The tables below provide numerical comparisons in the form of percent difference for

each of the diaphragm construction parameters evaluated in this study. The variables compared

for each pair of corresponding tests include equivalent viscous damping, cyclic stiffness, shear

stiffness, and flexural stiffness. Only tests of the same specimen are compared. The following

abbreviations are used to describe the test configurations:

NC = No Chords
WC = With Chords
NW = No Walls
WW = With Walls
Full = Fully Sheathed
Center = Center Sheathing Opening
Corner = Corner Sheathing Opening
B = Blocked
UB = UnBlocked
NO = Nailed Only
N&A = Nailed and Foam Adhesive Applied
3-12 = 3-12 Nail Pattern (versus the default 6-12 nail pattern)
APPENDIX B TEST COMPARISONS 96

Table B.1 Test Comparisons for the Effects of Blocking

Specimen Tests Compared


(Unblocked / Blocked)
Unblocked Blocked Percent Difference
(due to addition of blocking)

2 13 / 1 Eq. Viscous Damping, eq 12.9 6.8 -47%


Cyclic Stiffness, kcyclic 35.6 66.2 86%
Constants: 16x20, full, NO, WC, NW Shear Stiffness, GAs 2,640 6,183 134%
Flexural Stiffness, EI 56.9E+6 52.8E+6 -7%
2 14 / 2 Eq. Viscous Damping, eq 12.5 6.6 -47%
Cyclic Stiffness, kcyclic 36.4 71.8 97%
Constants: 16x20, full, NO, WC, WW Shear Stiffness, GAs 2,555 6,387 150%
Flexural Stiffness, EI 66.1E+6 62.1E+6 -6%
2 15 / 3 Eq. Viscous Damping, eq 12.8 6.8 -47%
Cyclic Stiffness, kcyclic 32.9 65.3 99%
Constants: 16x20, full, NO, NC, WW Shear Stiffness, GAs 2,413 6,002 149%
Flexural Stiffness, EI 47.5E+6 52.9E+6 11%
2 16 / 4 Eq. Viscous Damping, eq 12.5 6.9 -45%
Cyclic Stiffness, kcyclic 27.5 55.5 102%
Constants: 16x20, full, NO, NC, NW Shear Stiffness, GAs 2,347 5,627 140%
Flexural Stiffness, EI 25.1E+6 38.2E+6 52%
2 29 / 41 Eq. Viscous Damping, eq 6.4 4.1 -36%
Cyclic Stiffness, kcyclic 47.0 67.5 44%
Constants: 16x20, full, N&A, WC, NW Shear Stiffness, GAs 3,829 6,185 62%
Flexural Stiffness, EI 52.6E+6 54.7E+6 4%
2 30 / 42 Eq. Viscous Damping, eq 6.9 4.6 -33%
Cyclic Stiffness, kcyclic 47.3 67.9 44%
Constants: 16x20, full, N&A, WC, WW Shear Stiffness, GAs 3,501 6,086 74%
Flexural Stiffness, EI 74.9E+6 59.7E+6 -20%
2 31 / 43 Eq. Viscous Damping, eq 8.0 5.6 -30%
Cyclic Stiffness, kcyclic 41.0 54.9 34%
Constants: 16x20, full, N&A, NC, WW Shear Stiffness, GAs 3,338 5,099 53%
Flexural Stiffness, EI 49.4E+6 43.6E+6 -12%
2 32 / 44 Eq. Viscous Damping, eq 7.8 4.4 -44%
Cyclic Stiffness, kcyclic 33.4 46.4 39%
Constants: 16x20, full, N&A, NC, NW Shear Stiffness, GAs 3,284 4,692 43%
Flexural Stiffness, EI 25.7E+6 31.3E+6 22%
APPENDIX B TEST COMPARISONS 97

Table B.1 (Continued) Test Comparisons for the Effects of Blocking

Specimen Tests Compared


(Unblocked / Blocked)
Unblocked Blocked Percent Difference
(due to addition of blocking)

3 11 / 1 Eq. Viscous Damping, eq 18.6 7.1 -62%


Cyclic Stiffness, kcyclic 46.3 65.0 40%
Constants: 20x16, full, NO, NW Shear Stiffness, GAs 2,880 4,417 53%
Flexural Stiffness, EI 32.1E+6 32.7E+6 2%
3 12 / 2 Eq. Viscous Damping, eq 17.6 6.0 -66%
Cyclic Stiffness, kcyclic 54.3 68.0 25%
Constants: 20x16, full, NO, WW Shear Stiffness, GAs 3,453 4,506 31%
Flexural Stiffness, EI 36.8E+6 36.6E+6 -1%
3 10 / 7 Eq. Viscous Damping, eq 18.5 6.1 -67%
Cyclic Stiffness, kcyclic 49.2 83.9 71%
Constants: 20x16, full, 3-12, NO, NW Shear Stiffness, GAs 3,047 6,425 111%
Flexural Stiffness, EI 34.9E+6 33.2E+6 -5%
3 9/8 Eq. Viscous Damping, eq 17.2 5.8 -66%
Cyclic Stiffness, kcyclic 58.6 86.2 47%
Constants: 20x16, full, 3-12, NO, WW Shear Stiffness, GAs 3,803 6,312 66%
Flexural Stiffness, EI 35.1E+6 36.9E+6 5%
3 17 / 24 Eq. Viscous Damping, eq 10.6 6.3 -41%
Cyclic Stiffness, kcyclic 79.2 69.0 -13%
Constants: 20x16, full, N&A, NW Shear Stiffness, GAs 4,630 6,134 32%
Flexural Stiffness, EI 44.3E+6 22.3E+6 -50%
3 18 / 23 Eq. Viscous Damping, eq 11.9 6.5 -45%
Cyclic Stiffness, kcyclic 68.6 71.6 4%
Constants: 20x16, full, N&A, WW Shear Stiffness, GAs 4,272 6,296 47%
Flexural Stiffness, EI 33.4E+6 23.5E+6 -30%
4 11 / 1 Eq. Viscous Damping, eq 10.7 6.8 -36%
Cyclic Stiffness, kcyclic 26.6 62.3 134%
Constants: 20x16, full, NO, NW Shear Stiffness, GAs 1,418 5,613 296%
Flexural Stiffness, EI 13.7E+6 19.7E+6 43%
4 12 / 2 Eq. Viscous Damping, eq 11.2 6.5 -42%
Cyclic Stiffness, kcyclic 30.4 64.0 111%
Constants: 20x16, full, NO, WW Shear Stiffness, GAs 1,732 5,828 236%
Flexural Stiffness, EI 14.4E+6 20.0E+6 39%
APPENDIX B TEST COMPARISONS 98

Table B.1 (Continued) Test Comparisons for the Effects of Blocking

Specimen Tests Compared


(Unblocked / Blocked)
Unblocked Blocked Percent Difference
(due to addition of blocking)

4 10 / 7 Eq. Viscous Damping, eq 8.2 4.7 -43%


Cyclic Stiffness, kcyclic 38.2 77.3 103%
Constants: 20x16, full, 3-12 nails, NO,
NW Shear Stiffness, GAs 2,394 7,178 200%
Flexural Stiffness, EI 16.3E+6 21.4E+6 31%
4 9/8 Eq. Viscous Damping, eq 8.2 4.7 -43%
Cyclic Stiffness, kcyclic 42.1 80.1 90%
Constants: 20x16, full, 3-12 nails, NO,
WW Shear Stiffness, GAs 2,765 7,969 188%
Flexural Stiffness, EI 17.0E+6 20.9E+6 23%
4 17 / 24 Eq. Viscous Damping, eq 6.0 2.7 -55%
Cyclic Stiffness, kcyclic 65.0 91.7 41%
Constants: 20x16, full, N&A, WW Shear Stiffness, GAs 5,048 11,821 134%
Flexural Stiffness, EI 22.0E+6 21.6E+6 -2%
4 18 / 23 Eq. Viscous Damping, eq 6.8 2.7 -60%
Cyclic Stiffness, kcyclic 54.9 93.3 70%
Constants: 20x16, full, N&A, NW Shear Stiffness, GAs 4,119 12,857 212%
Flexural Stiffness, EI 18.3E+6 21.4E+6 17%
APPENDIX B TEST COMPARISONS 99

Table B.2 Test Comparisons for the Effects of Foam Adhesive

Nails and
Specimen Tests(NO
Compared Nailed Only Percent Difference
/ N&A) Adhesive (due to addition of adhesive)

2 13 / 29 Eq. Viscous Damping, eq 12.9 6.4 -50%


Cyclic Stiffness, kcyclic 35.6 47.0 32%
Constants: 16x20, full, UB, WC, NW Shear Stiffness, GAs 2,640 3,829 45%
Flexural Stiffness, EI 56.9E+6 52.6E+6 -7%
2 14 / 30 Eq. Viscous Damping, eq 12.5 6.9 -45%
Cyclic Stiffness, kcyclic 36.4 47.3 30%
Constants: 16x20, full, UB, WC, WW Shear Stiffness, GAs 2,555 3,501 37%
Flexural Stiffness, EI 66.1E+6 74.9E+6 13%
2 15 / 31 Eq. Viscous Damping, eq 12.8 8.0 -38%
Cyclic Stiffness, kcyclic 32.9 41.0 25%
Constants: 16x20, full, UB, NC, WW Shear Stiffness, GAs 2,413 3,338 38%
Flexural Stiffness, EI 47.5E+6 49.4E+6 4%
2 16 / 32 Eq. Viscous Damping, eq 12.5 7.8 -38%
Cyclic Stiffness, kcyclic 27.5 33.4 21%
Constants: 16x20, full, UB, NC, NW Shear Stiffness, GAs 2,347 3,284 40%
Flexural Stiffness, EI 25.1E+6 25.7E+6 2%
2 1 / 41 Eq. Viscous Damping, eq 6.8 4.1 -40%
Cyclic Stiffness, kcyclic 66.2 67.5 2%
Constants: 16x20, full, B, WC, NW Shear Stiffness, GAs 6,183 6,185 0%
Flexural Stiffness, EI 52.8E+6 54.7E+6 4%
2 2 / 42 Eq. Viscous Damping, eq 6.6 4.6 -30%
Cyclic Stiffness, kcyclic 71.8 67.9 -5%
Constants: 16x20, full, B, WC, WW Shear Stiffness, GAs 6,387 6,086 -5%
Flexural Stiffness, EI 62.1E+6 59.7E+6 -4%
2 3 / 43 Eq. Viscous Damping, eq 6.8 5.6 -18%
Cyclic Stiffness, kcyclic 65.3 54.9 -16%
Constants: 16x20, full, B, NC, WW Shear Stiffness, GAs 6,002 5,099 -15%
Flexural Stiffness, EI 52.9E+6 43.6E+6 -18%
2 4 / 44 Eq. Viscous Damping, eq 6.9 4.4 -36%
Cyclic Stiffness, kcyclic 55.5 46.4 -16%
Constants: 16x20, full, B, NC, NW Shear Stiffness, GAs 5,627 4,692 -17%
Flexural Stiffness, EI 38.2E+6 31.3E+6 -18%
APPENDIX B TEST COMPARISONS 100

Table B.2 (Continued) Test Comparisons for the Effects of Foam Adhesive

Nails and
Specimen Tests(NO
Compared Nailed Only Percent Difference
/ N&A) Adhesive (due to addition of adhesive)

3 11 / 17 Eq. Viscous Damping, eq 18.6 10.6 -43%


Cyclic Stiffness, kcyclic 46.3 79.2 71%
Constants: 20x16, full, UB, NW Shear Stiffness, GAs 2,880 4,630 61%
Flexural Stiffness, EI 32.1E+6 44.3E+6 38%
3 12 / 18 Eq. Viscous Damping, eq 17.6 11.9 -32%
Cyclic Stiffness, kcyclic 54.3 68.6 26%
Constants: 20x16, full, UB, WW Shear Stiffness, GAs 3,453 4,272 24%
Flexural Stiffness, EI 36.8E+6 33.4E+6 -9%
3 2 / 23 Eq. Viscous Damping, eq 6.0 6.5 8%
Cyclic Stiffness, kcyclic 68.0 71.6 5%
Constants: 20x16, full, B, WW Shear Stiffness, GAs 4,506 6,296 40%
Flexural Stiffness, EI 36.6E+6 23.5E+6 -36%
3 1 / 24 Eq. Viscous Damping, eq 7.1 6.3 -11%
Cyclic Stiffness, kcyclic 65.0 69.0 6%
Constants: 20x16, full, B, NW Shear Stiffness, GAs 4,417 6,134 39%
Flexural Stiffness, EI 32.7E+6 22.3E+6 -32%
4 12 / 17 Eq. Viscous Damping, eq 11.2 6.0 -46%
Cyclic Stiffness, kcyclic 30.4 65.0 114%
Constants: 20x16, full, UB, WW Shear Stiffness, GAs 1,732 5,048 191%
Flexural Stiffness, EI 14.4E+6 22.0E+6 53%
4 11 / 18 Eq. Viscous Damping, eq 10.7 6.8 -36%
Cyclic Stiffness, kcyclic 26.6 54.9 106%
Constants: 20x16, full, UB, NW Shear Stiffness, GAs 1,418 4,119 190%
Flexural Stiffness, EI 13.7E+6 18.3E+6 33%
4 1 / 23 Eq. Viscous Damping, eq 6.8 2.7 -60%
Cyclic Stiffness, kcyclic 62.3 93.3 50%
Constants: 20x16, full, B, NW Shear Stiffness, GAs 5,613 12,857 129%
Flexural Stiffness, EI 19.7E+6 21.4E+6 9%
4 2 / 24 Eq. Viscous Damping, eq 6.5 2.7 -58%
Cyclic Stiffness, kcyclic 64.0 91.7 43%
Constants: 20x16, full, B, WW Shear Stiffness, GAs 5,828 11,821 103%
Flexural Stiffness, EI 20.0E+6 21.6E+6 8%
APPENDIX B TEST COMPARISONS 101

Table B.3 Test Comparisons for the Effects of Blocking and Foam Adhesive

Unblocked Blocked
Specimen Tests Compared Percent Difference
(UB, NO / B, N&A) No Adhes. Adhesive (due to blocking & adhesive)

2 13 / 41 Eq. Viscous Damping, eq 12.9 4.1 -68%


Cyclic Stiffness, kcyclic 35.6 67.5 90%
Constants: 16x20, full, NO, WC, NW Shear Stiffness, GAs 2,640 6,185 134%
Flexural Stiffness, EI 56.9E+6 54.7E+6 -4%
2 14 / 42 Eq. Viscous Damping, eq 12.5 4.6 -63%
Cyclic Stiffness, kcyclic 36.4 67.9 87%
Constants: 16x20, full, NO, WC, WW Shear Stiffness, GAs 2,555 6,086 138%
Flexural Stiffness, EI 66.1E+6 59.7E+6 -10%
2 15 / 43 Eq. Viscous Damping, eq 12.8 5.6 -56%
Cyclic Stiffness, kcyclic 32.9 54.9 67%
Constants: 16x20, full, NO, NC, WW Shear Stiffness, GAs 2,413 5,099 111%
Flexural Stiffness, EI 47.5E+6 43.6E+6 -8%
2 16 / 44 Eq. Viscous Damping, eq 12.5 4.4 -65%
Cyclic Stiffness, kcyclic 27.5 46.4 68%
Constants: 16x20, full, NO, NC, NW Shear Stiffness, GAs 2,347 4,692 100%
Flexural Stiffness, EI 25.1E+6 31.3E+6 25%
3 11 / 24 Eq. Viscous Damping, eq 18.6 6.3 -66%
Cyclic Stiffness, kcyclic 46.3 69.0 49%
Constants: 20x16, full, NO, NW Shear Stiffness, GAs 2,880 6,134 113%
Flexural Stiffness, EI 32.1E+6 22.3E+6 -31%
3 12 / 23 Eq. Viscous Damping, eq 17.6 6.5 -63%
Cyclic Stiffness, kcyclic 54.3 71.6 32%
Constants: 20x16, full, NO, WW Shear Stiffness, GAs 3,453 6,296 82%
Flexural Stiffness, EI 36.8E+6 23.5E+6 -36%
4 11 / 23 Eq. Viscous Damping, eq 10.7 2.7 -75%
Cyclic Stiffness, kcyclic 26.6 93.3 250%
Constants: 20x16, full, NO, NW Shear Stiffness, GAs 1,418 12,857 807%
Flexural Stiffness, EI 13.7E+6 21.4E+6 56%
4 12 / 24 Eq. Viscous Damping, eq 11.2 2.7 -76%
Cyclic Stiffness, kcyclic 30.4 91.7 202%
Constants: 20x16, full, NO, WW Shear Stiffness, GAs 1,732 11,821 583%
Flexural Stiffness, EI 14.4E+6 21.6E+6 50%
APPENDIX B TEST COMPARISONS 102

Table B.4 Test Comparisons for the Effects of Increased Nail Density
(3-12 Nail Pattern versus Standard 6-12 Nail Pattern)

6-12 Nail 3-12 Nail


Specimen Tests Compared Percent Difference
(6-12 pattern / 3-12 pattern) Pattern Pattern (due to additional nailing)

3 1/7 Eq. Viscous Damping, eq 7.1 6.1 -14%


Cyclic Stiffness, kcyclic 65.0 83.9 29%
Constants: 20x16, full, NO, B, NW Shear Stiffness, GAs 4,417 6,425 45%
Flexural Stiffness, EI 32.7E+6 33.2E+6 1%
3 2/8 Eq. Viscous Damping, eq 6.0 5.8 -3%
Cyclic Stiffness, kcyclic 68.0 86.2 27%
Constants: 20x16, full, NO, B, WW Shear Stiffness, GAs 4,506 6,312 40%
Flexural Stiffness, EI 36.6E+6 36.9E+6 1%
3 12 / 9 Eq. Viscous Damping, eq 17.6 17.2 -2%
Cyclic Stiffness, kcyclic 54.3 58.6 8%
Constants: 20x16, full, NO, UB, WW Shear Stiffness, GAs 3,453 3,803 10%
Flexural Stiffness, EI 36.8E+6 35.1E+6 -5%
3 11 / 10 Eq. Viscous Damping, eq 18.6 18.5 -1%
Cyclic Stiffness, kcyclic 46.3 49.2 6%
Constants: 20x16, full, NO, UB, NW Shear Stiffness, GAs 2,880 3,047 6%
Flexural Stiffness, EI 32.1E+6 34.9E+6 9%
4 1/7 Eq. Viscous Damping, eq 6.8 4.7 -31%
Cyclic Stiffness, kcyclic 62.3 77.3 24%
Constants: 20x16, full, NO, B, NW Shear Stiffness, GAs 5,613 7,178 28%
Flexural Stiffness, EI 19.7E+6 21.4E+6 9%
4 2/8 Eq. Viscous Damping, eq 6.5 4.7 -28%
Cyclic Stiffness, kcyclic 64.0 80.1 25%
Constants: 20x16, full, NO, B, WW Shear Stiffness, GAs 5,828 7,969 37%
Flexural Stiffness, EI 20.0E+6 20.9E+6 5%
4 12 / 9 Eq. Viscous Damping, eq 11.2 8.2 -27%
Cyclic Stiffness, kcyclic 30.4 42.1 38%
Constants: 20x16, full, NO, UB, WW Shear Stiffness, GAs 1,732 2,765 60%
Flexural Stiffness, EI 14.4E+6 17.0E+6 18%
4 11 / 10 Eq. Viscous Damping, eq 10.7 8.2 -23%
Cyclic Stiffness, kcyclic 26.6 38.2 43%
Constants: 20x16, full, NO, UB, NW Shear Stiffness, GAs 1,418 2,394 69%
Flexural Stiffness, EI 13.7E+6 16.3E+6 19%
APPENDIX B TEST COMPARISONS 103

Table B.5 Test Comparisons for the Effects of Chords

Specimen Tests Compared


(No Chords / Chords)
No Chords Chords Percent Difference
(due to addition of chords)

1 5/6 Eq. Viscous Damping, eq 11.6 10.4 -10%


Cyclic Stiffness, kcyclic 43.7 48.2 10%
Constants: 16x20, NO, UB, full, WW Shear Stiffness, GAs 3,145 3,258 4%
Flexural Stiffness, EI 58.3E+6 83.2E+6 43%
1 8/7 Eq. Viscous Damping, eq 12.8 11.3 -12%
Cyclic Stiffness, kcyclic 29.4 44.5 51%
Constants: 16x20, NO, UB, full, NW Shear Stiffness, GAs 2,410 3,091 28%
Flexural Stiffness, EI 26.1E+6 66.3E+6 154%
1 20 / 17 Eq. Viscous Damping, eq 4.5 4.6 2%
Cyclic Stiffness, kcyclic 35.4 51.2 45%
Constants: 16x20, N&A, UB, full, NW Shear Stiffness, GAs 3,234 4,166 29%
Flexural Stiffness, EI 28.1E+6 58.6E+6 108%
1 19 / 18 Eq. Viscous Damping, eq 5.0 4.4 -12%
Cyclic Stiffness, kcyclic 43.3 51.3 18%
Constants: 16x20, N&A, UB, full, WW Shear Stiffness, GAs 3,645 4,054 11%
Flexural Stiffness, EI 43.4E+6 63.2E+6 45%
2 4/1 Eq. Viscous Damping, eq 6.9 6.8 -1%
Cyclic Stiffness, kcyclic 55.5 66.2 19%
Constants: 16x20, NO, B, full, NW Shear Stiffness, GAs 5,627 6,183 10%
Flexural Stiffness, EI 38.2E+6 52.8E+6 38%
2 3/2 Eq. Viscous Damping, eq 6.8 6.6 -3%
Cyclic Stiffness, kcyclic 65.3 71.8 10%
Constants: 16x20, NO, B, full, WW Shear Stiffness, GAs 6,002 6,387 6%
Flexural Stiffness, EI 52.9E+6 62.1E+6 17%
2 16 / 13 Eq. Viscous Damping, eq 12.5 12.9 3%
Cyclic Stiffness, kcyclic 27.5 35.6 29%
Constants: 16x20, NO, UB, full, NW Shear Stiffness, GAs 2,347 2,640 12%
Flexural Stiffness, EI 25.1E+6 56.9E+6 126%
2 15 / 14 Eq. Viscous Damping, eq 12.8 12.5 -2%
Cyclic Stiffness, kcyclic 32.9 36.4 11%
Constants: 16x20, NO, UB, full, WW Shear Stiffness, GAs 2,413 2,555 6%
Flexural Stiffness, EI 47.5E+6 66.1E+6 39%
APPENDIX B TEST COMPARISONS 104

Table B.5 (Continued) Test Comparisons for the Effects of Chords

Specimen Tests Compared


(No Chords / Chords)
No Chords Chords Percent Difference
(due to addition of chords)

2 32 / 29 Eq. Viscous Damping, eq 7.8 6.4 -18%


Cyclic Stiffness, kcyclic 33.4 47.0 41%
Constants: 16x20, N&A, UB, full, NW Shear Stiffness, GAs 3,284 3,829 17%
Flexural Stiffness, EI 25.7E+6 52.6E+6 105%
2 31 / 30 Eq. Viscous Damping, eq 8.0 6.9 -14%
Cyclic Stiffness, kcyclic 41.0 47.3 15%
Constants: 16x20, N&A, UB, full, WW Shear Stiffness, GAs 3,338 3,501 5%
Flexural Stiffness, EI 49.4E+6 74.9E+6 52%
2 44 / 41 Eq. Viscous Damping, eq 4.4 4.1 -7%
Cyclic Stiffness, kcyclic 46.4 67.5 46%
Constants: 16x20, N&A, B, full, NW Shear Stiffness, GAs 4,692 6,185 32%
Flexural Stiffness, EI 31.3E+6 54.7E+6 75%
2 43 / 42 Eq. Viscous Damping, eq 5.6 4.6 -18%
Cyclic Stiffness, kcyclic 54.9 67.9 24%
Constants: 16x20, N&A, B, full, wW Shear Stiffness, GAs 5,099 6,086 19%
Flexural Stiffness, EI 43.6E+6 59.7E+6 37%
5 1/4 Eq. Viscous Damping, eq 7.9 9.2 16%
Cyclic Stiffness, kcyclic 4.0 9.4 132%
Constants: 10x40, NO, B, full, NW Shear Stiffness, GAs 2,010 1,728 -14%
Flexural Stiffness, EI 12.2E+6 68.2E+6 457%
5 2/3 Eq. Viscous Damping, eq 8.3 8.9 7%
Cyclic Stiffness, kcyclic 8.8 11.7 33%
Constants: 10x40, NO, B, full, WW Shear Stiffness, GAs 1,891 2,022 7%
Flexural Stiffness, EI 48.4E+6 102.2E+6 111%
6 1/4 Eq. Viscous Damping, eq 16.3 15.1 -7%
Cyclic Stiffness, kcyclic 3.4 5.7 66%
Constants: 10x40, NO, B, full, NW Shear Stiffness, GAs 996 764 -23%
Flexural Stiffness, EI 12.5E+6 80.2E+6 542%
6 2/3 Eq. Viscous Damping, eq 16.2 15.0 -7%
Cyclic Stiffness, kcyclic 5.1 6.3 25%
Constants: 10x40, NO, B, full, WW Shear Stiffness, GAs 850 833 -2%
Flexural Stiffness, EI 35.2E+6 103.2E+6 193%
APPENDIX B TEST COMPARISONS 105

Table B.6 Test Comparisons for the Effects of Walls

Specimen Tests Compared


(No Walls / Walls)
No Walls Walls Percent Difference
(due to addition of walls)

1 8/5 Eq. Viscous Damping, eq 12.8 11.6 -9%


Cyclic Stiffness, kcyclic 29.4 43.7 48%
Constants: 16x20, NO, UB, full, NC Shear Stiffness, GAs 2,410 3,145 31%
Flexural Stiffness, EI 26.1E+6 58.3E+6 124%
1 7/6 Eq. Viscous Damping, eq 11.3 10.4 -8%
Cyclic Stiffness, kcyclic 44.5 48.2 8%
Constants: 16x20, NO, UB, full, WC Shear Stiffness, GAs 3,091 3,258 5%
Flexural Stiffness, EI 66.3E+6 83.2E+6 26%
1 17 / 18 Eq. Viscous Damping, eq 4.6 4.4 -4%
Cyclic Stiffness, kcyclic 51.2 51.3 0%
Constants: 16x20, N&A, UB, full, WC Shear Stiffness, GAs 4,166 4,054 -3%
Flexural Stiffness, EI 58.6E+6 63.2E+6 8%
1 20 / 19 Eq. Viscous Damping, eq 4.5 5.0 11%
Cyclic Stiffness, kcyclic 35.4 43.3 23%
Constants: 16x20, N&A, UB, full, NC Shear Stiffness, GAs 3,234 3,645 13%
Flexural Stiffness, EI 28.1E+6 43.4E+6 54%
2 1/2 Eq. Viscous Damping, eq 6.8 6.6 -3%
Cyclic Stiffness, kcyclic 66.2 71.8 8%
Constants: 16x20, NO, B, full, WC Shear Stiffness, GAs 6,183 6,387 3%
Flexural Stiffness, EI 52.8E+6 62.1E+6 18%
2 4/3 Eq. Viscous Damping, eq 6.9 6.8 -1%
Cyclic Stiffness, kcyclic 55.5 65.3 18%
Constants: 16x20, NO, B, full, NC Shear Stiffness, GAs 5,627 6,002 7%
Flexural Stiffness, EI 38.2E+6 52.9E+6 38%
2 13 / 14 Eq. Viscous Damping, eq 12.9 12.5 -3%
Cyclic Stiffness, kcyclic 35.6 36.4 2%
Constants: 16x20, NO, UB, full, WC Shear Stiffness, GAs 2,640 2,555 -3%
Flexural Stiffness, EI 56.9E+6 66.1E+6 16%
2 16 / 15 Eq. Viscous Damping, eq 12.5 12.8 2%
Cyclic Stiffness, kcyclic 27.5 32.9 19%
Constants: 16x20, NO, UB, full, NC Shear Stiffness, GAs 2,347 2,413 3%
Flexural Stiffness, EI 25.1E+6 47.5E+6 89%
APPENDIX B TEST COMPARISONS 106

Table B.6 (Continued) Test Comparisons for the Effects of Walls

Specimen Tests Compared


(No Walls / Walls)
No Walls Walls Percent Difference
(due to addition of walls)

2 29 / 30 Eq. Viscous Damping, eq 6.4 6.9 8%


Cyclic Stiffness, kcyclic 47.0 47.3 1%
Constants: 16x20, N&A, UB, full, WC Shear Stiffness, GAs 3,829 3,501 -9%
Flexural Stiffness, EI 52.6E+6 74.9E+6 42%
2 32 / 31 Eq. Viscous Damping, eq 7.8 8.0 3%
Cyclic Stiffness, kcyclic 33.4 41.0 23%
Constants: 16x20, N&A, UB, full, NC Shear Stiffness, GAs 3,284 3,338 2%
Flexural Stiffness, EI 25.7E+6 49.4E+6 92%
2 41 / 42 Eq. Viscous Damping, eq 4.1 4.6 12%
Cyclic Stiffness, kcyclic 67.5 67.9 1%
Constants: 16x20, N&A, B, full, WC Shear Stiffness, GAs 6,185 6,086 -2%
Flexural Stiffness, EI 54.7E+6 59.7E+6 9%
2 44 / 43 Eq. Viscous Damping, eq 4.4 5.6 27%
Cyclic Stiffness, kcyclic 46.4 54.9 18%
Constants: 16x20, N&A, B, full, NC Shear Stiffness, GAs 4,692 5,099 9%
Flexural Stiffness, EI 31.3E+6 43.6E+6 39%
3 1/2 Eq. Viscous Damping, eq 7.1 6.0 -15%
Cyclic Stiffness, kcyclic 65.0 68.0 5%
Constants: 20x16, NO, B, full Shear Stiffness, GAs 4,417 4,506 2%
Flexural Stiffness, EI 32.7E+6 36.6E+6 12%
3 7/8 Eq. Viscous Damping, eq 6.1 5.8 -5%
Cyclic Stiffness, kcyclic 83.9 86.2 3%
Constants: 20x16, NO, B, full, 3-12 Shear Stiffness, GAs 6,425 6,312 -2%
Flexural Stiffness, EI 33.2E+6 36.9E+6 11%
3 10 / 9 Eq. Viscous Damping, eq 18.5 17.2 -7%
Cyclic Stiffness, kcyclic 49.2 58.6 19%
Constants: 20x16, NO, UB, full, 3-12 Shear Stiffness, GAs 3,047 3,803 25%
Flexural Stiffness, EI 34.9E+6 35.1E+6 0%
3 11 / 12 Eq. Viscous Damping, eq 18.6 17.6 -5%
Cyclic Stiffness, kcyclic 46.3 54.3 17%
Constants: 20x16, NO, UB, full Shear Stiffness, GAs 2,880 3,453 20%
Flexural Stiffness, EI 32.1E+6 36.8E+6 15%
APPENDIX B TEST COMPARISONS 107

Table B.6 (Continued) Test Comparisons for the Effects of Walls

Specimen Tests Compared


(No Walls / Walls)
No Walls Walls Percent Difference
(due to addition of walls)

3 17 / 18 Eq. Viscous Damping, eq 10.6 11.9 12%


Cyclic Stiffness, kcyclic 79.2 68.6 -13%
Constants: 20x16, N&A, UB, full Shear Stiffness, GAs 4,630 4,272 -8%
Flexural Stiffness, EI 44.3E+6 33.4E+6 -25%
3 24 / 23 Eq. Viscous Damping, eq 6.3 6.5 3%
Cyclic Stiffness, kcyclic 69.0 71.6 4%
Constants: 20x16, N&A, B, full Shear Stiffness, GAs 6,134 6,296 3%
Flexural Stiffness, EI 22.3E+6 23.5E+6 5%
4 1/2 Eq. Viscous Damping, eq 6.8 6.5 -4%
Cyclic Stiffness, kcyclic 62.3 64.0 3%
Constants: 20x16, NO, B, full Shear Stiffness, GAs 5,613 5,828 4%
Flexural Stiffness, EI 19.7E+6 20.0E+6 1%
4 7/8 Eq. Viscous Damping, eq 4.7 4.7 0%
Cyclic Stiffness, kcyclic 77.3 80.1 4%
Constants: 20x16, NO, B, full, 3-12 Shear Stiffness, GAs 7,178 7,969 11%
Flexural Stiffness, EI 21.4E+6 20.9E+6 -2%
4 10 / 9 Eq. Viscous Damping, eq 8.2 8.2 0%
Cyclic Stiffness, kcyclic 38.2 42.1 10%
Constants: 20x16, NO, UB, full, 3-12 Shear Stiffness, GAs 2,394 2,765 16%
Flexural Stiffness, EI 16.3E+6 17.0E+6 4%
4 11 / 12 Eq. Viscous Damping, eq 10.7 11.2 5%
Cyclic Stiffness, kcyclic 26.6 30.4 14%
Constants: 20x16, NO, UB, full Shear Stiffness, GAs 1,418 1,732 22%
Flexural Stiffness, EI 13.7E+6 14.4E+6 5%
4 18 / 17 Eq. Viscous Damping, eq 6.8 6.0 -12%
Cyclic Stiffness, kcyclic 54.9 65.0 18%
Constants: 20x16, N&A, UB, full Shear Stiffness, GAs 4,119 5,048 23%
Flexural Stiffness, EI 18.3E+6 22.0E+6 20%
4 23 / 24 Eq. Viscous Damping, eq 2.7 2.7 0%
Cyclic Stiffness, kcyclic 93.3 91.7 -2%
Constants: 20x16, N&A, B, full Shear Stiffness, GAs 12,857 11,821 -8%
Flexural Stiffness, EI 21.4E+6 21.6E+6 1%
APPENDIX B TEST COMPARISONS 108

Table B.6 (Continued) Test Comparisons for the Effects of Walls

Specimen Tests Compared


(No Walls / Walls)
No Walls Walls Percent Difference
(due to addition of walls)

5 1/2 Eq. Viscous Damping, eq 7.9 8.3 5%


Cyclic Stiffness, kcyclic 4.0 8.8 119%
Constants: 10x40, NO, B, full, NC Shear Stiffness, GAs 2,010 1,891 -6%
Flexural Stiffness, EI 12.2E+6 48.4E+6 295%
5 4/3 Eq. Viscous Damping, eq 9.2 8.9 -3%
Cyclic Stiffness, kcyclic 9.4 11.7 25%
Constants: 10x40, NO, B, full, WC Shear Stiffness, GAs 1,728 2,022 17%
Flexural Stiffness, EI 68.2E+6 102.2E+6 50%
6 1/2 Eq. Viscous Damping, eq 16.3 16.2 -1%
Cyclic Stiffness, kcyclic 3.4 5.1 48%
Constants: 10x40, NO, B, full, NC Shear Stiffness, GAs 996 850 -15%
Flexural Stiffness, EI 12.5E+6 35.2E+6 182%
6 4/3 Eq. Viscous Damping, eq 15.1 15.0 -1%
Cyclic Stiffness, kcyclic 5.7 6.3 11%
Constants: 10x40, NO, B, full, WC Shear Stiffness, GAs 764 833 9%
Flexural Stiffness, EI 80.2E+6 103.2E+6 29%
APPENDIX B TEST COMPARISONS 109

Table B.7 Test Comparisons for the Effects of Center Sheathing Openings

Fully Center
Specimen Tests Compared Percent Difference
(Full / Center Opening) Sheathed Opening (due to center sheathing opening)

1 8/9 Eq. Viscous Damping, eq 12.8 12.0 -6%


Cyclic Stiffness, kcyclic 29.4 18.1 -38%
Constants: 16x20, NO, UB, NC, NW Shear Stiffness, GAs 2,410 1,266 -47%
Flexural Stiffness, EI 26.1E+6 18.5E+6 -29%
1 7 / 10 Eq. Viscous Damping, eq 11.3 10.8 -4%
Cyclic Stiffness, kcyclic 44.5 29.1 -35%
Constants: 16x20, NO, UB, WC, NW Shear Stiffness, GAs 3,091 1,845 -40%
Flexural Stiffness, EI 66.3E+6 58.3E+6 -12%
1 6 / 11 Eq. Viscous Damping, eq 10.4 8.8 -15%
Cyclic Stiffness, kcyclic 48.2 30.2 -37%
Constants: 16x20, NO, UB, WC, wW Shear Stiffness, GAs 3,258 1,904 -42%
Flexural Stiffness, EI 83.2E+6 61.9E+6 -26%
1 5 / 12 Eq. Viscous Damping, eq 11.6 9.1 -22%
Cyclic Stiffness, kcyclic 43.7 22.9 -47%
Constants: 16x20, NO, UB, NC, wW Shear Stiffness, GAs 3,145 1,438 -54%
Flexural Stiffness, EI 58.3E+6 41.5E+6 -29%
1 20 / 16 Eq. Viscous Damping, eq 4.5 4.8 7%
Cyclic Stiffness, kcyclic 35.4 21.0 -41%
Constants: 16x20, N&A, UB, NC, NW Shear Stiffness, GAs 3,234 1,621 -50%
Flexural Stiffness, EI 28.1E+6 21.4E+6 -24%
1 19 / 15 Eq. Viscous Damping, eq 5.0 5.1 2%
Cyclic Stiffness, kcyclic 43.3 29.9 -31%
Constants: 16x20, N&A, UB, NC, WW Shear Stiffness, GAs 3,645 2,193 -40%
Flexural Stiffness, EI 43.4E+6 40.6E+6 -6%
1 18 / 14 Eq. Viscous Damping, eq 4.4 3.8 -14%
Cyclic Stiffness, kcyclic 51.3 41.3 -20%
Constants: 16x20, N&A, UB, WC, WW Shear Stiffness, GAs 4,054 2,912 -28%
Flexural Stiffness, EI 63.2E+6 73.1E+6 16%
1 17 / 13 Eq. Viscous Damping, eq 4.6 3.7 -20%
Cyclic Stiffness, kcyclic 51.2 42.6 -17%
Constants: 16x20, N&A, UB, WC, NW Shear Stiffness, GAs 4,166 2,894 -31%
Flexural Stiffness, EI 58.6E+6 87.2E+6 49%
APPENDIX B TEST COMPARISONS 110

Table B.7 (Continued) Test Comparisons for the Effects of Center Sheathing Openings

Fully Center
Specimen Tests Compared Percent Difference
(Full / Center Opening) Sheathed Opening (due to center sheathing opening)

2 1 / 10 Eq. Viscous Damping, eq 6.8 9.2 35%


Cyclic Stiffness, kcyclic 66.2 34.5 -48%
Constants: 16x20, NO, B, WC, NW Shear Stiffness, GAs 6,183 2,419 -61%
Flexural Stiffness, EI 52.8E+6 55.5E+6 5%
2 2 / 11 Eq. Viscous Damping, eq 6.6 8.6 30%
Cyclic Stiffness, kcyclic 71.8 36.9 -49%
Constants: 16x20, NO, B, WC, WW Shear Stiffness, GAs 6,387 2,489 -61%
Flexural Stiffness, EI 62.1E+6 63.0E+6 1%
2 3 / 12 Eq. Viscous Damping, eq 6.8 9.7 43%
Cyclic Stiffness, kcyclic 65.3 31.2 -52%
Constants: 16x20, NO, B, NC, WW Shear Stiffness, GAs 6,002 2,173 -64%
Flexural Stiffness, EI 52.9E+6 46.6E+6 -12%
2 4/9 Eq. Viscous Damping, eq 6.9 9.7 41%
Cyclic Stiffness, kcyclic 55.5 24.3 -56%
Constants: 16x20, NO, B, NC, NW Shear Stiffness, GAs 5,627 2,039 -64%
Flexural Stiffness, EI 38.2E+6 22.3E+6 -42%
2 13 / 22 Eq. Viscous Damping, eq 12.9 11.2 -13%
Cyclic Stiffness, kcyclic 35.6 24.9 -30%
Constants: 16x20, NO, UB, WC, NW Shear Stiffness, GAs 2,640 1,609 -39%
Flexural Stiffness, EI 56.9E+6 82.2E+6 44%
2 14 / 23 Eq. Viscous Damping, eq 12.5 10.9 -13%
Cyclic Stiffness, kcyclic 36.4 28.2 -23%
Constants: 16x20, NO, UB, WC, WW Shear Stiffness, GAs 2,555 1,831 -28%
Flexural Stiffness, EI 66.1E+6 79.4E+6 20%
2 15 / 24 Eq. Viscous Damping, eq 12.8 11.5 -10%
Cyclic Stiffness, kcyclic 32.9 23.5 -29%
Constants: 16x20, NO, UB, NC, WW Shear Stiffness, GAs 2,413 1,603 -34%
Flexural Stiffness, EI 47.5E+6 49.5E+6 4%
2 16 / 21 Eq. Viscous Damping, eq 12.5 11.0 -12%
Cyclic Stiffness, kcyclic 27.5 19.4 -30%
Constants: 16x20, NO, UB, NC, NW Shear Stiffness, GAs 2,347 1,570 -33%
Flexural Stiffness, EI 25.1E+6 20.3E+6 -19%
APPENDIX B TEST COMPARISONS 111

Table B.7 (Continued) Test Comparisons for the Effects of Center Sheathing Openings

Fully Center
Specimen Tests Compared Percent Difference
(Full / Center Opening) Sheathed Opening (due to center sheathing opening)

2 29 / 25 Eq. Viscous Damping, eq 6.4 4.6 -28%


Cyclic Stiffness, kcyclic 47.0 32.1 -32%
Constants: 16x20, N&A, UB, WC, NW Shear Stiffness, GAs 3,829 2,288 -40%
Flexural Stiffness, EI 52.6E+6 57.0E+6 8%
2 30 / 26 Eq. Viscous Damping, eq 6.9 8.6 25%
Cyclic Stiffness, kcyclic 47.3 36.7 -22%
Constants: 16x20, N&A, UB, WC, WW Shear Stiffness, GAs 3,501 2,549 -27%
Flexural Stiffness, EI 74.9E+6 76.1E+6 2%
2 31 / 27 Eq. Viscous Damping, eq 8.0 9.5 19%
Cyclic Stiffness, kcyclic 41.0 29.4 -28%
Constants: 16x20, N&A, UB, NC, WW Shear Stiffness, GAs 3,338 2,065 -38%
Flexural Stiffness, EI 49.4E+6 50.3E+6 2%
2 32 / 28 Eq. Viscous Damping, eq 7.8 8.9 14%
Cyclic Stiffness, kcyclic 33.4 22.9 -31%
Constants: 16x20, N&A, UB, NC, NW Shear Stiffness, GAs 3,284 1,793 -45%
Flexural Stiffness, EI 25.7E+6 24.8E+6 -3%
2 41 / 37 Eq. Viscous Damping, eq 4.1 5.4 32%
Cyclic Stiffness, kcyclic 67.5 38.7 -43%
Constants: 16x20, N&A, B, WC, NW Shear Stiffness, GAs 6,185 2,989 -52%
Flexural Stiffness, EI 54.7E+6 49.6E+6 -9%
2 42 / 38 Eq. Viscous Damping, eq 4.6 5.9 28%
Cyclic Stiffness, kcyclic 67.9 41.3 -39%
Constants: 16x20, N&A, B, WC, WW Shear Stiffness, GAs 6,086 3,082 -49%
Flexural Stiffness, EI 59.7E+6 63.6E+6 7%
2 43 / 39 Eq. Viscous Damping, eq 5.6 6.8 21%
Cyclic Stiffness, kcyclic 54.9 33.9 -38%
Constants: 16x20, N&A, B, NC, WW Shear Stiffness, GAs 5,099 2,599 -49%
Flexural Stiffness, EI 43.6E+6 45.6E+6 5%
2 44 / 40 Eq. Viscous Damping, eq 4.4 6.0 36%
Cyclic Stiffness, kcyclic 46.4 25.9 -44%
Constants: 16x20, N&A, B, NC, NW Shear Stiffness, GAs 4,692 2,244 -52%
Flexural Stiffness, EI 31.3E+6 23.2E+6 -26%
APPENDIX B TEST COMPARISONS 112

Table B.7 (Continued) Test Comparisons for the Effects of Center Sheathing Openings

Fully Center
Specimen Tests Compared Percent Difference
(Full / Center Opening) Sheathed Opening (due to center sheathing opening)

3 1/5 Eq. Viscous Damping, eq 7.1 7.7 8%


Cyclic Stiffness, kcyclic 65.0 35.3 -46%
Constants: 20x16, NO, B, NW Shear Stiffness, GAs 4,417 2,006 -55%
Flexural Stiffness, EI 32.7E+6 35.3E+6 8%
3 2/6 Eq. Viscous Damping, eq 6.0 7.5 25%
Cyclic Stiffness, kcyclic 68.0 39.6 -42%
Constants: 20x16, NO, B, WW Shear Stiffness, GAs 4,506 2,388 -47%
Flexural Stiffness, EI 36.6E+6 30.2E+6 -17%
3 11 / 15 Eq. Viscous Damping, eq 18.6 17.0 -9%
Cyclic Stiffness, kcyclic 46.3 24.1 -48%
Constants: 20x16, NO, UB, NW Shear Stiffness, GAs 2,880 996 -65%
Flexural Stiffness, EI 32.1E+6 26.2E+6 -19%
3 12 / 16 Eq. Viscous Damping, eq 17.6 15.5 -12%
Cyclic Stiffness, kcyclic 54.3 29.1 -46%
Constants: 20x16, NO, UB, WW Shear Stiffness, GAs 3,453 1,347 -61%
Flexural Stiffness, EI 36.8E+6 29.1E+6 -21%
4 1/5 Eq. Viscous Damping, eq 6.8 8.3 22%
Cyclic Stiffness, kcyclic 62.3 31.8 -49%
Constants: 20x16, NO, B, NW Shear Stiffness, GAs 5,613 1,934 -66%
Flexural Stiffness, EI 19.7E+6 13.7E+6 -30%
4 2/6 Eq. Viscous Damping, eq 6.5 7.8 20%
Cyclic Stiffness, kcyclic 64.0 34.6 -46%
Constants: 20x16, NO, B, WW Shear Stiffness, GAs 5,828 2,160 -63%
Flexural Stiffness, EI 20.0E+6 13.9E+6 -30%
4 11 / 15 Eq. Viscous Damping, eq 10.7 14.9 39%
Cyclic Stiffness, kcyclic 26.6 20.5 -23%
Constants: 20x16, NO, UB, NW Shear Stiffness, GAs 1,418 1,058 -25%
Flexural Stiffness, EI 13.7E+6 11.0E+6 -20%
4 12 / 16 Eq. Viscous Damping, eq 11.2 13.7 22%
Cyclic Stiffness, kcyclic 30.4 24.1 -21%
Constants: 20x16, NO, UB, WW Shear Stiffness, GAs 1,732 1,276 -26%
Flexural Stiffness, EI 14.4E+6 12.3E+6 -15%
APPENDIX B TEST COMPARISONS 113

Table B.8 Test Comparisons for the Effects of Corner Sheathing Openings

Fully Corner
Specimen Tests Compared Percent Difference
(Full / Corner Opening) Sheathed Opening (due to corner sheathing opening)

1 8/1 Eq. Viscous Damping, eq 12.8 13.5 5%


Cyclic Stiffness, kcyclic 29.4 29.2 -1%
Constants: 16x20, NO, UB, NC, NW Left Shear Stiffness, GAsL 2,608 3,369 29%
Right Shear Stiffness, GAsR 2,212 1,642 -26%
Flexural Stiffness, EI 26.1E+6 26.9E+6 3%
1 7/2 Eq. Viscous Damping, eq 11.3 10.9 -4%
Cyclic Stiffness, kcyclic 44.5 30.7 -31%
Constants: 16x20, NO, UB, WC, NW Left Shear Stiffness, GAsL 3,033 3,098 2%
Right Shear Stiffness, GAsR 3,179 1,432 -55%
Flexural Stiffness, EI 66.3E+6 68.6E+6 3%
1 6/3 Eq. Viscous Damping, eq 10.4 9.9 -5%
Cyclic Stiffness, kcyclic 48.2 33.0 -31%
Constants: 16x20, NO, UB, WC, wW Left Shear Stiffness, GAsL 3,193 3,183 0%
Right Shear Stiffness, GAsR 3,324 1,573 -53%
Flexural Stiffness, EI 83.2E+6 76.0E+6 -9%
1 5/4 Eq. Viscous Damping, eq 11.6 11.9 3%
Cyclic Stiffness, kcyclic 43.7 37.5 -14%
Constants: 16x20, NO, UB, NC, wW Left Shear Stiffness, GAsL 3,140 3,347 7%
Right Shear Stiffness, GAsR 3,150 1,858 -41%
Flexural Stiffness, EI 58.3E+6 83.1E+6 42%
1 20 / 21 Eq. Viscous Damping, eq 4.5 4.9 9%
Cyclic Stiffness, kcyclic 35.4 30.5 -14%
Constants: 16x20, N&A, UB, NC, NW Left Shear Stiffness, GAsL 3,535 3,559 1%
Right Shear Stiffness, GAsR 2,933 2,031 -31%
Flexural Stiffness, EI 28.1E+6 25.1E+6 -11%
1 19 / 24 Eq. Viscous Damping, eq 5.0 5.1 2%
Cyclic Stiffness, kcyclic 43.3 35.5 -18%
Constants: 16x20, N&A, UB, NC, WW Left Shear Stiffness, GAsL 3,967 3,685 -7%
Right Shear Stiffness, GAsR 3,323 2,067 -38%
Flexural Stiffness, EI 43.4E+6 44.4E+6 2%
1 18 / 23 Eq. Viscous Damping, eq 4.4 4.3 -2%
Cyclic Stiffness, kcyclic 51.3 39.5 -23%
Constants: 16x20, N&A, UB, WC, WW Left Shear Stiffness, GAsL 4,226 3,973 -6%
Right Shear Stiffness, GAsR 3,883 2,064 -47%
Flexural Stiffness, EI 63.2E+6 72.7E+6 15%
APPENDIX B TEST COMPARISONS 114

Table B.8 (Continued) Test Comparisons for the Effects of Corner Sheathing Openings

Fully Corner
Specimen Tests Compared Percent Difference
(Full / Corner Opening) Sheathed Opening (due to corner sheathing opening)

1 17 / 22 Eq. Viscous Damping, eq 4.6 4.5 -2%


Cyclic Stiffness, kcyclic 51.2 37.7 -26%
Constants: 16x20, N&A, UB, WC, NW Left Shear Stiffness, GAsL 4,332 3,735 -14%
Right Shear Stiffness, GAsR 3,999 2,043 -49%
Flexural Stiffness, EI 58.6E+6 58.2E+6 -1%
2 1/6 Eq. Viscous Damping, eq 6.8 7.3 7%
Cyclic Stiffness, kcyclic 66.2 44.5 -33%
Constants: 16x20, NO, B, WC, NW Left Shear Stiffness, GAsL 6,179 5,368 -13%
Right Shear Stiffness, GAsR 6,187 2,519 -59%
Flexural Stiffness, EI 52.8E+6 51.7E+6 -2%
2 2/7 Eq. Viscous Damping, eq 6.6 7.0 6%
Cyclic Stiffness, kcyclic 71.8 46.7 -35%
Constants: 16x20, NO, B, WC, WW Left Shear Stiffness, GAsL 6,421 5,378 -16%
Right Shear Stiffness, GAsR 6,352 2,643 -58%
Flexural Stiffness, EI 62.1E+6 57.2E+6 -8%
2 3/8 Eq. Viscous Damping, eq 6.8 7.4 9%
Cyclic Stiffness, kcyclic 65.3 44.1 -33%
Constants: 16x20, NO, B, NC, WW Left Shear Stiffness, GAsL 5,910 4,942 -16%
Right Shear Stiffness, GAsR 6,094 2,506 -59%
Flexural Stiffness, EI 52.9E+6 55.6E+6 5%
2 4/5 Eq. Viscous Damping, eq 6.9 7.2 4%
Cyclic Stiffness, kcyclic 55.5 38.6 -30%
Constants: 16x20, NO, B, NC, NW Left Shear Stiffness, GAsL 5,334 5,028 -6%
Right Shear Stiffness, GAsR 5,919 2,824 -52%
Flexural Stiffness, EI 38.2E+6 29.3E+6 -23%
2 13 / 18 Eq. Viscous Damping, eq 12.9 10.9 -16%
Cyclic Stiffness, kcyclic 35.6 26.7 -25%
Constants: 16x20, NO, UB, WC, NW Left Shear Stiffness, GAsL 3,082 2,753 -11%
Right Shear Stiffness, GAsR 2,198 1,215 -45%
Flexural Stiffness, EI 56.9E+6 60.2E+6 6%
2 14 / 19 Eq. Viscous Damping, eq 12.5 9.7 -22%
Cyclic Stiffness, kcyclic 36.4 27.9 -23%
Constants: 16x20, NO, UB, WC, WW Left Shear Stiffness, GAsL 2,896 2,746 -5%
Right Shear Stiffness, GAsR 2,214 1,275 -42%
Flexural Stiffness, EI 66.1E+6 68.5E+6 4%
APPENDIX B TEST COMPARISONS 115

Table B.8 (Continued) Test Comparisons for the Effects of Corner Sheathing Openings

Fully Corner
Specimen Tests Compared Percent Difference
(Full / Corner Opening) Sheathed Opening (due to corner sheathing opening)

2 15 / 20 Eq. Viscous Damping, eq 12.8 9.9 -23%


Cyclic Stiffness, kcyclic 32.9 25.0 -24%
Constants: 16x20, NO, UB, NC, WW Left Shear Stiffness, GAsL 2,738 2,698 -1%
Right Shear Stiffness, GAsR 2,088 1,164 -44%
Flexural Stiffness, EI 47.5E+6 49.8E+6 5%
2 16 / 17 Eq. Viscous Damping, eq 12.5 11.0 -12%
Cyclic Stiffness, kcyclic 27.5 22.6 -18%
Constants: 16x20, NO, UB, NC, NW Left Shear Stiffness, GAsL 2,636 2,841 8%
Right Shear Stiffness, GAsR 2,058 1,330 -35%
Flexural Stiffness, EI 25.1E+6 22.2E+6 -12%
2 29 / 34 Eq. Viscous Damping, eq 6.4 7.2 13%
Cyclic Stiffness, kcyclic 47.0 31.7 -33%
Constants: 16x20, N&A, UB, WC, NW Left Shear Stiffness, GAsL 4,575 3,883 -15%
Right Shear Stiffness, GAsR 3,083 1,505 -51%
Flexural Stiffness, EI 52.6E+6 53.1E+6 1%
2 30 / 35 Eq. Viscous Damping, eq 6.9 7.0 1%
Cyclic Stiffness, kcyclic 47.3 33.3 -30%
Constants: 16x20, N&A, UB, WC, WW Left Shear Stiffness, GAsL 4,110 3,770 -8%
Right Shear Stiffness, GAsR 2,892 1,564 -46%
Flexural Stiffness, EI 74.9E+6 67.3E+6 -10%
2 31 / 36 Eq. Viscous Damping, eq 8.0 7.7 -4%
Cyclic Stiffness, kcyclic 41.0 29.4 -28%
Constants: 16x20, N&A, UB, NC, WW Left Shear Stiffness, GAsL 4,076 3,605 -12%
Right Shear Stiffness, GAsR 2,600 1,426 -45%
Flexural Stiffness, EI 49.4E+6 47.5E+6 -4%
2 32 / 33 Eq. Viscous Damping, eq 7.8 8.2 5%
Cyclic Stiffness, kcyclic 33.4 26.4 -21%
Constants: 16x20, N&A, UB, NC, NW Left Shear Stiffness, GAsL 3,999 3,841 -4%
Right Shear Stiffness, GAsR 2,569 1,646 -36%
Flexural Stiffness, EI 25.7E+6 22.0E+6 -14%
2 41 / 46 Eq. Viscous Damping, eq 4.1 4.3 5%
Cyclic Stiffness, kcyclic 67.5 47.9 -29%
Constants: 16x20, N&A, B, WC, NW Left Shear Stiffness, GAsL 6,375 5,880 -8%
Right Shear Stiffness, GAsR 5,996 2,557 -57%
Flexural Stiffness, EI 54.7E+6 57.2E+6 5%
APPENDIX B TEST COMPARISONS 116

Table B.8 (Continued) Test Comparisons for the Effects of Corner Sheathing Openings

Fully Corner
Specimen Tests Compared Percent Difference
(Full / Corner Opening) Sheathed Opening (due to corner sheathing opening)

2 42 / 47 Eq. Viscous Damping, eq 4.6 4.3 -7%


Cyclic Stiffness, kcyclic 67.9 51.0 -25%
Constants: 16x20, N&A, B, WC, WW Left Shear Stiffness, GAsL 6,723 6,171 -8%
Right Shear Stiffness, GAsR 5,449 2,684 -51%
Flexural Stiffness, EI 59.7E+6 66.0E+6 11%
2 43 / 48 Eq. Viscous Damping, eq 5.6 4.9 -13%
Cyclic Stiffness, kcyclic 54.9 44.6 -19%
Constants: 16x20, N&A, B, NC, WW Left Shear Stiffness, GAsL 5,441 5,480 1%
Right Shear Stiffness, GAsR 4,757 2,420 -49%
Flexural Stiffness, EI 43.6E+6 51.6E+6 18%
2 44 / 45 Eq. Viscous Damping, eq 4.4 4.6 5%
Cyclic Stiffness, kcyclic 46.4 37.4 -19%
Constants: 16x20, N&A, B, NC, NW Left Shear Stiffness, GAsL 4,725 4,688 -1%
Right Shear Stiffness, GAsR 4,658 2,509 -46%
Flexural Stiffness, EI 31.3E+6 30.0E+6 -4%
3 1/4 Eq. Viscous Damping, eq 7.1 6.7 -6%
Cyclic Stiffness, kcyclic 65.0 49.7 -23%
Constants: 20x16, NO, B, NW Left Shear Stiffness, GAsL 4,249 1,801 -58%
Right Shear Stiffness, GAsR 4,585 4,129 -10%
Flexural Stiffness, EI 32.7E+6 28.5E+6 -13%
3 2/3 Eq. Viscous Damping, eq 6.0 6.6 10%
Cyclic Stiffness, kcyclic 68.0 53.8 -21%
Constants: 20x16, NO, B, WW Left Shear Stiffness, GAsL 4,273 1,784 -58%
Right Shear Stiffness, GAsR 4,740 4,334 -9%
Flexural Stiffness, EI 36.6E+6 37.0E+6 1%
3 11 / 14 Eq. Viscous Damping, eq 18.6 17.6 -5%
Cyclic Stiffness, kcyclic 46.3 42.0 -9%
Constants: 20x16, NO, UB, NW Left Shear Stiffness, GAsL 3,287 1,675 -49%
Right Shear Stiffness, GAsR 2,473 2,536 3%
Flexural Stiffness, EI 32.1E+6 25.9E+6 -20%
3 12 / 13 Eq. Viscous Damping, eq 17.6 16.5 -6%
Cyclic Stiffness, kcyclic 54.3 47.3 -13%
Constants: 20x16, NO, UB, WW Left Shear Stiffness, GAsL 4,101 2,075 -49%
Right Shear Stiffness, GAsR 2,805 2,713 -3%
Flexural Stiffness, EI 36.8E+6 30.9E+6 -16%
APPENDIX B TEST COMPARISONS 117

Table B.8 (Continued) Test Comparisons for the Effects of Corner Sheathing Openings

Fully Corner
Specimen Tests Compared Percent Difference
(Full / Corner Opening) Sheathed Opening (due to corner sheathing opening)

3 24 / 21 Eq. Viscous Damping, eq 6.3 4.3 -32%


Cyclic Stiffness, kcyclic 69.0 95.3 38%
Constants: 20x16, N&A, B, NW Left Shear Stiffness, GAsL 6,617 4,668 -29%
Right Shear Stiffness, GAsR 5,651 12,078 114%
Flexural Stiffness, EI 22.3E+6 29.7E+6 33%
3 23 / 22 Eq. Viscous Damping, eq 6.5 4.7 -28%
Cyclic Stiffness, kcyclic 71.6 89.7 25%
Constants: 20x16, N&A, B, WW Left Shear Stiffness, GAsL 6,871 4,174 -39%
Right Shear Stiffness, GAsR 5,720 10,582 85%
Flexural Stiffness, EI 23.5E+6 30.0E+6 28%
4 1/4 Eq. Viscous Damping, eq 6.8 7.4 9%
Cyclic Stiffness, kcyclic 62.3 48.7 -22%
Constants: 20x16, NO, B, NW Left Shear Stiffness, GAsL 5,604 2,501 -55%
Right Shear Stiffness, GAsR 5,622 5,028 -11%
Flexural Stiffness, EI 19.7E+6 16.8E+6 -14%
4 2/3 Eq. Viscous Damping, eq 6.5 7.1 9%
Cyclic Stiffness, kcyclic 64.0 51.7 -19%
Constants: 20x16, NO, B, WW Left Shear Stiffness, GAsL 5,908 2,691 -54%
Right Shear Stiffness, GAsR 5,747 5,800 1%
Flexural Stiffness, EI 20.0E+6 16.7E+6 -16%
4 11 / 14 Eq. Viscous Damping, eq 10.7 11.0 3%
Cyclic Stiffness, kcyclic 26.6 22.3 -16%
Constants: 20x16, NO, UB, NW Left Shear Stiffness, GAsL 1,430 962 -33%
Right Shear Stiffness, GAsR 1,406 1,375 -2%
Flexural Stiffness, EI 13.7E+6 11.3E+6 -18%
4 12 / 13 Eq. Viscous Damping, eq 11.2 11.4 2%
Cyclic Stiffness, kcyclic 30.4 25.3 -17%
Constants: 20x16, NO, UB, WW Left Shear Stiffness, GAsL 1,759 1,122 -36%
Right Shear Stiffness, GAsR 1,704 1,688 -1%
Flexural Stiffness, EI 14.4E+6 12.3E+6 -15%
4 17 / 20 Eq. Viscous Damping, eq 6.0 7.5 25%
Cyclic Stiffness, kcyclic 65.0 43.6 -33%
Constants: 20x16, N&A, UB, WW Left Shear Stiffness, GAsL 5,426 2,306 -58%
Right Shear Stiffness, GAsR 4,671 3,666 -22%
Flexural Stiffness, EI 22.0E+6 16.6E+6 -24%
APPENDIX B TEST COMPARISONS 118

Table B.8 (Continued) Test Comparisons for the Effects of Corner Sheathing Openings

Fully Corner
Specimen Tests Compared Percent Difference
(Full / Corner Opening) Sheathed Opening (due to corner sheathing opening)

4 18 / 19 Eq. Viscous Damping, eq 6.8 7.4 9%


Cyclic Stiffness, kcyclic 54.9 43.2 -21%
Left Shear Stiffness, GAsL 4,169 2,361 -43%
Constants: 20x16, N&A, UB, NW
Right Shear Stiffness, GAsR 4,070 3,679 -10%
Flexural Stiffness, EI 18.3E+6 16.4E+6 -10%
4 24 / 21 Eq. Viscous Damping, eq 2.7 3.1 15%
Cyclic Stiffness, kcyclic 91.7 72.3 -21%
Left Shear Stiffness, GAsL 12,337 4,754 -61%
Constants: 20x16, N&A, B, WW
Right Shear Stiffness, GAsR 11,305 10,232 -9%
Flexural Stiffness, EI 21.6E+6 18.9E+6 -13%
4 23 / 22 Eq. Viscous Damping, eq 2.7 3.2 19%
Cyclic Stiffness, kcyclic 93.3 67.4 -28%
Left Shear Stiffness, GAsL 15,027 4,389 -71%
Constants: 20x16, N&A, B, NW
Right Shear Stiffness, GAsR 10,686 9,980 -7%
Flexural Stiffness, EI 21.4E+6 17.5E+6 -18%
5 4/5 Eq. Viscous Damping, eq 9.2 13.3 45%
Cyclic Stiffness, kcyclic 9.4 8.4 -10%
Left Shear Stiffness, GAsL 1,353 833 -38%
Constants: 10x40, NO, B, WC, NW
Right Shear Stiffness, GAsR 2,104 3,409 62%
Flexural Stiffness, EI 68.2E+6 54.9E+6 -20%
5 3/6 Eq. Viscous Damping, eq 8.9 13.1 47%
Cyclic Stiffness, kcyclic 11.7 9.2 -22%
Left Shear Stiffness, GAsL 1,561 812 -48%
Constants: 10x40, NO, B, WC, WW
Right Shear Stiffness, GAsR 2,482 3,443 39%
Flexural Stiffness, EI 102.2E+6 79.4E+6 -22%
6 4/5 Eq. Viscous Damping, eq 15.1 14.2 -6%
Cyclic Stiffness, kcyclic 5.7 4.2 -27%
Left Shear Stiffness, GAsL 682 331 -51%
Constants: 10x40, NO, B, WC, NW
Right Shear Stiffness, GAsR 846 994 17%
Flexural Stiffness, EI 80.2E+6 86.1E+6 7%
6 3/6 Eq. Viscous Damping, eq 15.0 14.3 -5%
Cyclic Stiffness, kcyclic 6.3 4.5 -28%
Left Shear Stiffness, GAsL 745 367 -51%
Constants: 10x40, NO, B, WC, WW
Right Shear Stiffness, GAsR 921 1,030 12%
Flexural Stiffness, EI 103.2E+6 101.5E+6 -2%
APPENDIX C SPECIMEN INSTRUMENTATION 119

APPENDIX C SPECIMEN INSTRUMENTATION

C.1 INTRODUCTION

The following table provides a description of each device used in this study to measure

deflections and loads. Refer to Section 2.5 for diagrams of diaphragm instrumentation layout.

Table C.1 Instrument Descriptions

Label Description Model & S/N Conversion Coeff. Offset


utpDisp Actuator Displacement Transducer n/a -0.60 V/V/inch n/a
utpLoad Actuator Load Cell Moog 50 kip 1032AGQ / 64693A -5500.0 lbs/V n/a
DL1 String Pot. Left Diagonal No.1 PA-20 / 30110380 0.048720 V/V/inch 9.750V = 10
DL2 String Pot. Left Diagonal No.2 PA-20 / 30110381 0.048480 V/V/inch 9.727V = 10
DR1 String Pot. Right Diagonal No.1 PA-20 / 30110382 0.048680 V/V/inch 9.740V = 10
DR2 String Pot. Right Diagonal No.2 PA-20 / 30110383 0.048698 V/V/inch 9.744V = 10
SlipL String Pot. Left Test Frame Slip PA-2 / 28060335 0.475924 V/V/inch 4.777V = 1
SlipC String Pot. Center Test Frame Slip PA-2 / 28060336 0.465603 V/V/inch 4.827V = 1
SlipR String Pot. Right Test Frame Slip PA-2 / 28060337 0.476062 V/V/inch 4.772V = 1
GL1 String Pot. Global Defl., Far Left PA-5 / 28060339 0.196702 V/V/inch 4.905V = 2.5
GL2 String Pot. Global Defl., Left Center PA-20 / 30110384 0.048563 V/V/inch 9.725V = 10
GL3 String Pot. Global Defl., Center Left PA-20 / 30110385 0.048673 V/V/inch 9.742V = 10
GC String Pot. Global Deflection, Center PA-20 / 30110386 0.048628 V/V/inch 9.730V = 10
GR1 String Pot. Global Defl., Center Right PA-20 / 30110387 0.048470 V/V/inch 9.707V = 10
GR2 String Pot. Global Defl., Right Center PA-20 / 27060431 0.048147 V/V/inch 9.644V = 10
GR3 String Pot. Global Defl., Far Right PT101 / A43043 0.092441 V/V/inch 4.613V = 5
L-Load Reaction Load Cell Left-side Custom-Built 40 kip 4124.1 lbs/V n/a
R-Load Reaction Load Cell Right-side Custom-Built 40 kip 4098.5 lbs/V n/a
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 120

APPENDIX D MOISTURE CONTENT AND DENSITY DATA

D.1 INTRODUCTION

Moisture content and density was determined from a sample from each joist of every

specimen. Samples from the plywood sheathing of only Specimen 1 were also analyzed for

moisture content and density. The joist samples were cut from the scraps and analyzed at the

time of the construction of each specimen. All samples were measured for initial mass, dried

mass, and volumetric displacement (in a water bath following a wax coating). The following

tables provide moisture content and density information for each specimen.
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 121

Table D.1 Specimen 1 Joists Moisture Content and Density

Sample # Initial Mass Dried Mass H2O Displaced Moisture Content Density
Left to Right (g) (g) (g) : 1g = 1cc H2O (g / cc)
1 2.59 2.14 4.91 0.21 0.44
2 4.24 3.43 7.14 0.24 0.48
3 3.76 3.13 6.69 0.20 0.47
4 4.25 3.48 7.16 0.22 0.49
5 2.80 2.31 5.04 0.21 0.46
6 2.99 2.51 5.73 0.19 0.44
7 3.75 2.99 6.14 0.25 0.49
8 3.36 2.77 5.97 0.21 0.46
9 2.83 2.35 5.09 0.20 0.46
10 3.62 3.00 5.81 0.21 0.52
11 4.10 3.29 6.83 0.25 0.48
12 3.84 3.13 6.31 0.23 0.50
13 4.04 3.30 6.76 0.22 0.49
14 3.54 2.89 6.07 0.22 0.48
15 3.09 2.61 5.69 0.18 0.46
16 3.07 2.57 5.75 0.19 0.45
Average: 0.22 0.47
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 122

Table D.2 Specimen 1 Sheathing Moisture Content and Density

Sample # Initial Mass Dried Mass H2O Displaced Moisture Content Density
(g) (g) (g) : 1g = 1cc H2O (g / cc)
1 22.67 20.96 34.80 0.08 0.60
2 19.29 17.42 29.05 0.11 0.60
3 20.69 18.12 32.03 0.14 0.57
4 30.25 28.30 46.01 0.07 0.62
5 19.56 18.14 31.03 0.08 0.58
6 21.32 19.30 35.22 0.10 0.55
7 22.30 20.24 37.10 0.10 0.55
8 23.36 21.04 36.63 0.11 0.57
9 21.10 19.51 33.51 0.08 0.58
10 18.59 16.59 28.45 0.12 0.58
11 17.70 15.96 24.64 0.11 0.65
12 22.05 19.36 33.27 0.14 0.58
13 22.01 19.29 32.83 0.14 0.59
14 17.97 16.39 29.38 0.10 0.56
15 27.38 25.47 46.39 0.07 0.55
Average: 0.10 0.58
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 123

Table D.3 Specimen 2 Joists Moisture Content and Density

Sample # Initial Mass Dried Mass H2O Displaced Moisture Content Density
Left to Right (g) (g) (g) : 1g = 1cc H2O (g / cc)
1 46.39 38.05 79.58 0.22 0.48
2 46.14 37.55 64.70 0.23 0.58
3 45.93 37.22 72.77 0.23 0.51
4 35.81 28.56 62.40 0.25 0.46
5 44.12 37.27 76.33 0.18 0.49
6 48.64 39.15 79.68 0.24 0.49
7 50.74 41.89 76.67 0.21 0.55
8 33.87 28.25 60.25 0.20 0.47
9 35.45 27.72 56.98 0.28 0.49
10 36.09 30.83 67.73 0.17 0.46
11 39.38 33.65 76.79 0.17 0.44
12 35.24 30.11 66.08 0.17 0.46
13 28.16 22.25 52.14 0.27 0.43
14 43.95 35.51 76.04 0.24 0.47
15 36.87 30.47 64.36 0.21 0.47
16 30.40 26.03 66.56 0.17 0.39
Average: 0.22 0.48
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 124

Table D.4 Specimen 3 Joists Moisture Content and Density

Sample # Initial Mass Dried Mass H2O Displaced Moisture Content Density
Front to Back (g) (g) (g) : 1g = 1cc H2O (g / cc)
1 33.16 25.60 51.68 0.30 0.50
2 32.20 24.67 52.15 0.31 0.47
3 38.59 29.86 49.20 0.29 0.61
4 28.28 21.99 47.04 0.29 0.47
5 25.30 19.74 42.05 0.28 0.47
6 26.96 20.46 50.20 0.32 0.41
7 29.30 22.49 46.77 0.30 0.48
8 25.46 19.30 43.20 0.32 0.45
9 32.70 24.73 49.45 0.32 0.50
10 21.54 16.32 33.68 0.32 0.48
11 18.72 15.60 31.40 0.20 0.50
12 40.37 31.71 69.45 0.27 0.46
13 34.89 29.64 70.87 0.18 0.42
14 39.78 30.02 61.21 0.33 0.49
15 40.40 29.24 61.35 0.38 0.48
16 29.72 23.38 49.85 0.27 0.47
Average: 0.29 0.48
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 125

Table D.5 Specimen 4 Joists Moisture Content and Density

Sample # Initial Mass Dried Mass H2O Displaced Moisture Content Density
Front to Back (g) (g) (g) : 1g = 1cc H2O (g / cc)
1 59.40 48.27 99.80 0.23 0.48
2 54.70 45.05 117.01 0.21 0.39
3 61.60 51.20 91.25 0.20 0.56
4 76.40 63.16 108.13 0.21 0.58
5 55.70 45.90 97.49 0.21 0.47
6 101.70 82.75 139.36 0.23 0.59
7 64.90 53.11 105.92 0.22 0.50
8 72.60 58.11 106.32 0.25 0.55
9 70.90 57.39 108.95 0.24 0.53
10 82.60 67.72 105.25 0.22 0.64
11 54.90 45.03 100.53 0.22 0.45
12 61.10 49.78 103.35 0.23 0.48
13 60.70 49.03 109.34 0.24 0.45
14 82.90 67.08 111.28 0.24 0.60
15 56.90 44.43 108.17 0.28 0.41
16 65.50 51.49 112.11 0.27 0.46
Average: 0.23 0.51
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 126

Table D.6 Specimen 5 Joists Moisture Content and Density

Sample # Initial Mass Dried Mass H2O Displaced Moisture Content Density
Left to Right (g) (g) (g) : 1g = 1cc H2O (g / cc)
1 15.57 12.30 31.47 0.27 0.39
2 17.73 15.10 28.20 0.17 0.54
3 16.97 14.16 25.53 0.20 0.55
4 15.57 13.77 33.94 0.13 0.41
5 11.80 9.69 19.17 0.22 0.51
6 15.13 12.32 25.84 0.23 0.48
7 15.55 12.15 27.44 0.28 0.44
8 11.70 10.34 21.17 0.13 0.49
9 18.43 14.31 29.07 0.29 0.49
10 17.39 14.06 28.56 0.24 0.49
11 11.62 10.21 24.97 0.14 0.41
12 12.39 10.66 23.37 0.16 0.46
13 14.82 12.58 26.42 0.18 0.48
14 15.43 13.62 23.35 0.13 0.58
15 10.73 9.03 19.00 0.19 0.48
16 11.99 10.21 24.04 0.17 0.42
17 13.39 10.81 28.00 0.24 0.39
18 15.82 12.93 19.05 0.22 0.68
19 22.46 17.85 31.68 0.26 0.56
20 14.10 11.29 25.30 0.25 0.45
21 13.94 11.66 23.27 0.20 0.50
22 16.66 13.49 31.06 0.23 0.43
23 18.40 13.32 29.23 0.38 0.46
24 13.88 11.46 23.61 0.21 0.49
25 13.83 12.01 25.66 0.15 0.47
26 19.04 14.86 31.35 0.28 0.47
27 18.40 13.73 31.54 0.34 0.44
28 19.53 16.40 30.69 0.19 0.53
29 14.18 12.17 24.75 0.17 0.49
30 15.69 13.83 33.38 0.13 0.41
31 16.37 13.56 32.00 0.21 0.42
Average: 0.21 0.48
APPENDIX D MOISTURE CONTENT AND DENSITY DATA 127

Table D.7 Specimen 6 Joists Moisture Content and Density

Sample # Initial Mass Dried Mass H2O Displaced Moisture Content Density
Left to Right (g) (g) (g) : 1g = 1cc H2O (g / cc)
1 21.30 18.89 37.06 0.13 0.51
2 23.58 19.56 39.76 0.21 0.49
3 10.71 9.38 22.23 0.14 0.42
4 18.43 16.14 37.40 0.14 0.43
5 18.43 16.14 37.40 0.14 0.43
6 18.50 16.38 35.88 0.13 0.46
7 18.50 16.38 35.88 0.13 0.46
8 26.17 23.16 45.85 0.13 0.51
9 26.17 23.16 45.85 0.13 0.51
10 24.00 19.44 41.64 0.23 0.47
11 24.00 19.44 41.64 0.23 0.47
12 18.95 16.65 35.93 0.14 0.46
13 18.95 16.65 35.93 0.14 0.46
14 18.23 16.01 31.40 0.14 0.51
15 18.23 16.01 31.40 0.14 0.51
16 23.58 19.56 39.76 0.21 0.49
17 15.59 13.71 32.58 0.14 0.42
18 15.59 13.71 32.58 0.14 0.42
19 12.58 11.01 22.38 0.14 0.49
20 12.58 11.01 22.38 0.14 0.49
21 10.72 9.45 17.62 0.13 0.54
22 10.72 9.45 17.62 0.13 0.54
23 25.31 22.03 41.37 0.15 0.53
24 21.30 18.89 37.06 0.13 0.51
25 25.31 22.03 41.37 0.15 0.53
26 19.69 17.29 37.45 0.14 0.46
27 19.69 17.29 37.45 0.14 0.46
28 18.29 16.21 32.46 0.13 0.50
29 18.29 16.21 32.46 0.13 0.50
30 19.68 17.18 37.08 0.15 0.46
31 19.68 17.18 37.08 0.15 0.46
Average: 0.15 0.48
APPENDIX E TEST DESCRIPTIONS 128

APPENDIX E TEST DESCRIPTIONS

E.1 INTRODUCTION

The tables below provide descriptions of each test of every specimen in terms of test date,

load protocol, test configuration, and other significant comments such weather conditions,

malfunctioning equipment, specimen repairs, and other observations. The following are

definitions of some commonly used abbreviations found in the tables below:

NC = No Chords
WC = With Chords
NW = No Walls
WW = With Walls
Full = Fully Sheathed
Center = Center Sheathing Opening
Corner = Corner Sheathing Opening
B = Blocked
UB = UnBlocked
NO = Nailed Only
N&A = Nailed and Foam Adhesive Applied
3-12 = 3-12 Nail Pattern (versus the default 6-12 nail pattern)
DAQ = Data Acquisition System
LC = Load Cell
No SlipC = The SlipC string potentiometer is malfunctioning.
No Left LC = The left side load cell is malfunctioning.
APPENDIX E TEST DESCRIPTIONS 129

Table E.1 Specimen 1 Test Descriptions

Test
Test Date Loading Configuration Comments
No.
1 12-Jan-01 5 dynamic cycles 0.13" NC; NW; Corner; UB; NO Icy
DAQ timer set for 146 rows of useable data.
2 16-Jan-01 5 dynamic cycles 0.25" WC; NW; Corner; UB; NO Snow

3 17-Jan-01 5 dynamic cycles 0.25" WC; WW; Corner; UB; NO Reprogrammed DAQ for pre-tared data. Snow

4 22-Jan-01 5 dynamic cycles 0.25" NC; WW; Corner; UB; NO Snow / Icy
5 22-Jan-01 5 dynamic cycles 0.25" NC; WW; Full; UB; NO
6 24-Jan-01 5 dynamic cycles 0.25" WC; WW; Full; UB; NO
7 24-Jan-01 5 dynamic cycles 0.25" WC; NW; Full; UB; NO
8 24-Jan-01 5 dynamic cycles 0.25" NC; NW; Full; UB; NO Snow
9 26-Jan-01 5 dynamic cycles 0.25" NC; NW; Center; UB; NO
10 26-Jan-01 5 dynamic cycles 0.25" WC; NW; Center; UB; NO
11 26-Jan-01 5 dynamic cycles 0.25" WC; WW; Center; UB; NO Rainy / Icy
12 29-Jan-01 5 dynamic cycles 0.25" NC; WW; Center; UB; NO
13 24-Feb-01 5 dynamic cycles 0.25" WC; NW; Center; UB; N&A Increased DAQ data sampling rate to 100 Hz.
14 24-Feb-01 5 dynamic cycles 0.25" WC; WW; Center; UB; N&A
15 24-Feb-01 5 dynamic cycles 0.25" NC; WW; Center; UB; N&A
16 24-Feb-01 5 dynamic cycles 0.25" NC; NW; Center; UB; N&A
17 27-Feb-01 5 dynamic cycles 0.25" WC; NW; Full; UB; N&A
18 27-Feb-01 5 dynamic cycles 0.25" WC; WW; Full; UB; N&A
19 27-Feb-01 5 dynamic cycles 0.25" NC; WW; Full; UB; N&A
20 27-Feb-01 5 dynamic cycles 0.25" NC; NW; Full; UB; N&A
21 28-Feb-01 5 dynamic cycles 0.25" NC; NW; Corner; UB; N&A
22 28-Feb-01 5 dynamic cycles 0.25" WC; NW; Corner; UB; N&A
23 28-Feb-01 5 dynamic cycles 0.25" WC; WW; Corner; UB; N&A
24 28-Feb-01 5 dynamic cycles 0.25" NC; WW; Corner; UB; N&A
APPENDIX E TEST DESCRIPTIONS 130

Table E.2 Specimen 2 Test Descriptions

Test
Test Date Loading Configuration Comments
No.
1 9-Mar-01 5 dynamic cycles 0.25" WC; NW; Full; B; NO
2 9-Mar-01 5 dynamic cycles 0.25" WC; WW; Full; B; NO
3 9-Mar-01 5 dynamic cycles 0.25" NC; WW; Full; B; NO
4 9-Mar-01 5 dynamic cycles 0.25" NC; NW; Full; B; NO
5 12-Mar-01 5 dynamic cycles 0.25" NC; NW; Corner; B; NO
6 12-Mar-01 5 dynamic cycles 0.25" WC; NW; Corner; B; NO
7 12-Mar-01 5 dynamic cycles 0.25" WC; WW; Corner; B; NO Rainy / Icy
8 12-Mar-01 5 dynamic cycles 0.25" NC; WW; Corner; B; NO
9 14-Mar-01 5 dynamic cycles 0.25" NC; NW; Center; B; NO
10 14-Mar-01 5 dynamic cycles 0.25" WC; NW; Center; B; NO
11 14-Mar-01 5 dynamic cycles 0.25" WC; WW; Center; B; NO Rainy / Icy
12 14-Mar-01 5 dynamic cycles 0.25" NC; WW; Center; B; NO
13 19-Mar-01 5 dynamic cycles 0.25" WC; NW; Full; UB; NO
14 19-Mar-01 5 dynamic cycles 0.25" WC; WW; Full; UB; NO
15 19-Mar-01 5 dynamic cycles 0.25" NC; WW; Full; UB; NO
16 19-Mar-01 5 dynamic cycles 0.25" NC; NW; Full; UB; NO
17 20-Mar-01 5 dynamic cycles 0.25" NC; NW; Corner; UB; NO
18 20-Mar-01 5 dynamic cycles 0.25" WC; NW; Corner; UB; NO
19 20-Mar-01 5 dynamic cycles 0.25" WC; WW; Corner; UB; NO
20 20-Mar-01 5 dynamic cycles 0.25" NC; WW; Corner; UB; NO
21 21-Mar-01 5 dynamic cycles 0.25" NC; NW; Center; UB; NO
22 21-Mar-01 5 dynamic cycles 0.25" WC; NW; Center; UB; NO
23 21-Mar-01 5 dynamic cycles 0.25" WC; WW; Center; UB; NO Windy
24 21-Mar-01 5 dynamic cycles 0.25" NC; WW; Center; UB; NO Windy
25 26-Mar-01 5 dynamic cycles 0.25" WC; NW; Center; UB; N&A
26 2-Apr-01 5 dynamic cycles 0.25" WC; WW; Center; UB; N&A Replaced GR3 stringpot. Using new wall hoists.

27 2-Apr-01 5 dynamic cycles 0.25" NC; WW; Center; UB; N&A


28 2-Apr-01 5 dynamic cycles 0.25" NC; NW; Center; UB; N&A
Broke left end-joist during tilt-up and replaced
29 10-Apr-01 5 dynamic cycles 0.25" WC; NW; Full; UB; N&A it.
30 10-Apr-01 5 dynamic cycles 0.25" WC; WW; Full; UB; N&A
31 10-Apr-01 5 dynamic cycles 0.25" NC; WW; Full; UB; N&A
32 10-Apr-01 5 dynamic cycles 0.25" NC; NW; Full; UB; N&A
33 10-Apr-01 5 dynamic cycles 0.25" NC; NW; Corner; UB; N&A
34 10-Apr-01 5 dynamic cycles 0.25" WC; NW; Corner; UB; N&A
APPENDIX E TEST DESCRIPTIONS 131

Table E.2 (Continued) Specimen 2 Test Descriptions

Test
Test Date Loading Configuration Comments
No.
35 10-Apr-01 5 dynamic cycles 0.25" WC; WW; Corner; UB; N&A
36 10-Apr-01 5 dynamic cycles 0.25" NC; WW; Corner; UB; N&A
37 18-Apr-01 5 dynamic cycles 0.25" WC; NW; Center; B; N&A Windy
38 18-Apr-01 5 dynamic cycles 0.25" WC; WW; Center; B; N&A Windy
39 18-Apr-01 5 dynamic cycles 0.25" NC; WW; Center; B; N&A Windy
40 18-Apr-01 5 dynamic cycles 0.25" NC; NW; Center; B; N&A Windy
41 24-Apr-01 5 dynamic cycles 0.25" WC; NW; Full; B; N&A
42 24-Apr-01 5 dynamic cycles 0.25" WC; WW; Full; B; N&A
43 24-Apr-01 5 dynamic cycles 0.25" NC; WW; Full; B; N&A
44 24-Apr-01 5 dynamic cycles 0.25" NC; NW; Full; B; N&A
45 24-Apr-01 5 dynamic cycles 0.25" NC; NW; Corner; B; N&A No SlipC
46 25-Apr-01 5 dynamic cycles 0.25" WC; NW; Corner; B; N&A No SlipC
47 25-Apr-01 5 dynamic cycles 0.25" WC; WW; Corner; B; N&A No SlipC
48 25-Apr-01 5 dynamic cycles 0.25" NC; WW; Corner; B; N&A No SlipC
APPENDIX E TEST DESCRIPTIONS 132

Table E.3 Specimen 3 Test Descriptions

Test
Test Date Loading Configuration Comments
No.
1 13-May-01 5 dynamic cycles 0.20" NW; Full; B; NO No SlipC, No Left LVDT's, No Left LC.
2 13-May-01 5 dynamic cycles 0.20" WW; Full; B; NO No SlipC, No Left LVDT's, No Left LC.
3 13-May-01 5 dynamic cycles 0.20" WW; Corner; B; NO No SlipC, No Left LVDT's, No Left LC.
4 13-May-01 5 dynamic cycles 0.20" NW; Corner; B; NO No SlipC, No Left LVDT's, No Left LC.
5 14-May-01 5 dynamic cycles 0.20" NW; Center; B; NO No SlipC, No Left LVDT's, No Left LC.
6 14-May-01 5 dynamic cycles 0.20" WW; Center; B; NO No SlipC, No Left LVDT's, No Left LC.
No SlipC, No Left LC. No extra nails added along
7 14-May-01 5 dynamic cycles 0.20" NW; Full; B; NO; 3-12 edge where walls attach due to conflict b/w duplex
nails and bottom plate.

No SlipC, No Left LC. No extra nails added along


8 14-May-01 5 dynamic cycles 0.20" WW; Full; B; NO; 3-12 edge where walls attach due to conflict b/w duplex
nails and bottom plate.

No SlipC, No Left LC. No extra nails added along


9 19-May-01 5 dynamic cycles 0.20" WW; Full; UB; NO; 3-12 edge where walls attach due to conflict b/w duplex
nails and bottom plate.

No SlipC, No Left LC. No extra nails added along


10 19-May-01 5 dynamic cycles 0.20" NW; Full; UB; NO; 3-12 edge where walls attach due to conflict b/w duplex
nails and bottom plate.

11 19-May-01 5 dynamic cycles 0.20" NW; Full; UB; NO No SlipC, No Left LC. Rainy
12 19-May-01 5 dynamic cycles 0.20" WW; Full; UB; NO No SlipC, No Left LC. Rainy
13 19-May-01 5 dynamic cycles 0.20" WW; Corner; UB; NO No SlipC. Rainy
14 19-May-01 5 dynamic cycles 0.20" NW; Corner; UB; NO No SlipC. Rainy
15 20-May-01 5 dynamic cycles 0.20" NW; Center; UB; NO No SlipC. Rainy
16 20-May-01 5 dynamic cycles 0.20" WW; Center; UB; NO No SlipC. Rainy
17 22-May-01 5 dynamic cycles 0.20" NW; Full; UB; N&A No SlipC. Rainy, Windy
18 22-May-01 5 dynamic cycles 0.20" WW; Full; UB; N&A No SlipC. Rainy, Windy
19 22-May-01 5 dynamic cycles 0.20" WW; Corner; UB; N&A No SlipC. Rainy, Windy
20 22-May-01 5 dynamic cycles 0.20" NW; Corner; UB; N&A No SlipC. Rainy, Windy
21 24-May-01 5 dynamic cycles 0.20" NW; Corner; B; N&A No SlipC, No Left LC. Rainy
22 24-May-01 5 dynamic cycles 0.20" WW; Corner; B; N&A No SlipC, No Left LC. Rainy

No SlipC, No Left LC. Right LC unbal., UTP Load


23 24-May-01 5 dynamic cycles 0.20" WW; Full; B; N&A unbal. (>5kip higher neg.), Damage from accidental
high loading repaired. Rainy

No SlipC, No Left LC. Right LC unbal., UTP Load


24 24-May-01 5 dynamic cycles 0.20" NW; Full; B; N&A unbal. (>5kip higher neg.), Rainy
APPENDIX E TEST DESCRIPTIONS 133

Table E.4 Specimen 4 Test Descriptions

Test
Test Date Loading Configuration Comments
No.
1 29-May-01 5 dynamic cycles 0.20" NW; Full; B; NO No Left LC. No SlipC.
2 29-May-01 5 dynamic cycles 0.20" WW; Full; B; NO No Left LC. No SlipC.
3 29-May-01 5 dynamic cycles 0.20" WW; Corner; B; NO No Left LC. No SlipC.
4 29-May-01 5 dynamic cycles 0.20" NW; Corner; B; NO No Left LC. No SlipC. Windy
5 30-May-01 5 dynamic cycles 0.20" NW; Center; B; NO No SlipC. Windy
6 30-May-01 5 dynamic cycles 0.20" WW; Center; B; NO No SlipC. Windy
No SlipC. No extra nails added along edge where
7 30-May-01 5 dynamic cycles 0.20" NW; Full; B; NO; 3-12 walls attach due to conflict b/w duplex nails and
bottom plate.

No SlipC. No extra nails added along edge where


8 30-May-01 5 dynamic cycles 0.20" WW; Full; B; NO; 3-12 walls attach due to conflict b/w duplex nails and
bottom plate.

No SlipC. No extra nails added along edge where


9 31-May-01 5 dynamic cycles 0.20" WW; Full; UB; NO; 3-12 walls attach due to conflict b/w duplex nails and
bottom plate.

No SlipC. No extra nails added along edge where


10 31-May-01 5 dynamic cycles 0.20" NW; Full; UB; NO; 3-12 walls attach due to conflict b/w duplex nails and
bottom plate.

11 31-May-01 5 dynamic cycles 0.20" NW; Full; UB; NO No SlipC


12 31-May-01 5 dynamic cycles 0.20" WW; Full; UB; NO No SlipC
13 31-May-01 5 dynamic cycles 0.20" WW; Corner; UB; NO No SlipC
14 31-May-01 5 dynamic cycles 0.20" NW; Corner; UB; NO No SlipC
15 1-Jun-01 5 dynamic cycles 0.20" NW; Center; UB; NO No SlipC. Rainy
16 1-Jun-01 5 dynamic cycles 0.20" WW; Center; UB; NO No SlipC. Rainy
17 4-Jun-01 5 dynamic cycles 0.20" WW; Full; UB; N&A No SlipC
18 4-Jun-01 5 dynamic cycles 0.20" NW; Full; UB; N&A No SlipC. Windy
19 4-Jun-01 5 dynamic cycles 0.20" NW; Corner; UB; N&A No SlipC
20 4-Jun-01 5 dynamic cycles 0.20" WW; Corner; UB; N&A No SlipC
21 6-Jun-01 5 dynamic cycles 0.20" WW; Corner; B; N&A No Left LC. No SlipC.
22 6-Jun-01 5 dynamic cycles 0.20" NW; Corner; B; N&A No Left LC. No SlipC.
23 8-Jun-01 5 dynamic cycles 0.20" NW; Full; B; N&A No Left LC
24 8-Jun-01 5 dynamic cycles 0.20" WW; Full; B; N&A No Left LC
APPENDIX E TEST DESCRIPTIONS 134

Table E.5 Specimen 5 Test Descriptions

Test
Test Date Loading Configuration Comments
No.
1 19-Jun-01 5 dynamic cycles 0.80" NW; NC; Full; B; NO No side LC's
2 19-Jun-01 5 dynamic cycles 0.80" WW; NC; Full; B; NO No side LC's
3 19-Jun-01 5 dynamic cycles 0.80" WW; WC; Full; B; NO No side LC's
4 19-Jun-01 5 dynamic cycles 0.80" NW; WC; Full; B; NO No side LC's
No SlipC. Newly repaired/calibrated side LC's.
5 26-Jun-01 5 dynamic cycles 0.80" NW; WC; Corner; B; NO Rainy
6 26-Jun-01 5 dynamic cycles 0.80" WW; WC; Corner; B; NO Rainy

Table E.6 Specimen 6 Test Descriptions

Test
Test Date Loading Configuration Comments
No.
1 5-Jul-01 5 dynamic cycles 0.80" NW; NC; Full; B; NO Windy, Rainy
2 5-Jul-01 5 dynamic cycles 0.80" WW; NC; Full; B; NO Windy, Rainy
3 5-Jul-01 5 dynamic cycles 0.80" WW; WC; Full; B; NO Windy, Rainy
4 5-Jul-01 5 dynamic cycles 0.80" NW; WC; Full; B; NO Windy, Rainy
5 6-Jul-01 5 dynamic cycles 0.80" NW; WC; Corner; B; NO Rainy
6 6-Jul-01 5 dynamic cycles 0.80" WW; WC; Corner; B; NO Rainy
VITA

James Wescott Bott was born in the town of Nassawadox on the Eastern Shore of

Virginia on February 5, 1977. He graduated from Broadwater Academy in Exmore, Virginia in

1995. In 1999, he graduated from the Virginia Military Institute in Lexington, Virginia with the

degree of Bachelor of Science in Civil Engineering. He went directly to graduate school in the

Structural Engineering and Materials Program of the Civil and Environmental Engineering

Department at Virginia Polytechnic Institute and State University in Blacksburg, VA. He

worked for three years for The Whiting-Turner Contracting Company and now works at R.

Stuart Royer & Associates, Inc. in Richmond, Virginia.

You might also like