[Program Name : AMF]

[Section Name : INPUTS]

000001
I: 0.00 W0.00 DG-1
(000000) EMERGENCY
EMERGE <W000.00>
NCY
a024
STOP DG
-1

000002
I: 0.01 W0.01 WTH
(000002) <W000.01>
WTH
a027

000003
I: 0.02 W0.02 DG
(000004) CONTACTOR
DG-1 CLOSE
CONTAC FEEDBACK
TOR <W000.02>
CLOSE
b049 b059 b094
FEEDBA
CK b115 b124 b175
b185 b220 b242
b251

000004
I: 0.03 W0.03 RW PUMP ON
(000006)
RW
PUMP ON
000005
I: 0.04 W0.04 CT FAN ON
(000008)
CT FAN
ON
000006
I: 0.05 W0.05 COMMON
(000010) ENGINE FAULT
COMMON DG-1
ENGINE <W000.05>
FAULT
a025
DG-1

000007
I: 0.06 W0.06 COMMON
(000012) ELECT FAULT
COMMON DG-1
ELECT <W000.06>
FAULT
a026
DG-1

000008
I: 0.07 W0.07 PLC AUTO
(000014) SELECTED
PLC <W000.07>
AUTO
a029 a037 a042
SELECT
a051 a062 a070
b079 a083 a087
a091 a099 a103
a105 a108 a111
a126 a135 a139
a145 a155 a163
a168 a177 a188
a196 b205 a209
a213 a217 a225
a229 a231 a234
a238 a253 a262
a266 a272

000009
I: 0.08 W0.08 T/F VOLTAGE
(000016) AVL
T/F <W000.08>
VOLTAGE
b030 a038 a137
AVL
b156 a164 a264

000010
I: 0.09 W0.09 T/F
(000018) CONTACTOR
T/F CLOSE
CONTAC

www.automation-talk.blogspot.com www.automation-talk.blogspot.com
www.automation-talk.blogspot.com www.automation-talk.blogspot.com

TOR <W000.09>
CLOSE b035 b095 b161
b221

000011
I: 0.10 W0.10 DG VOLTAGE
(000020) AVAILABLE
DG RELAY
VOLTAGE <W000.10>
AVAILABL
a043 a045 b064
E RELAY
a078 a085 a169
a171 b190 a204
a211

000012
I: 0.11 W0.11 SPARE
(000022)
SPARE
000013
W0.00 W70.00 DG-1 ALARM
(000024) <W070.00>
DG-1
b052 b063 a118
EMERGE
NCY b130 b178 b189
a245 b257
W0.05

COMMON
ENGINE
FAULT
DG-1
W0.06

COMMON
ELECT
FAULT
DG-1
W0.01

WTH
000014
W0.07 W0.08 T001 W10.00 TRAFO UV
(000029) <W010.00>
PLC T/F TRAFO
a048 a061 a174
AUTO VOLTAGE VOLTAGE
SELECTE AVL NA a187
D
W0.09 TIM [OP1]
<T0001(bit)>
T/F 001
a032 b092 a158
CONTAC #60
TOR b218
CLOSE [OP2]

000015
W0.07 W0.08 TIM [OP1]
(000037) <T0002(bit)>
PLC T/F 002
b053 b065 a117
AUTO VOLTAGE #820
SELECTE AVL b179 b191 a244
D [OP2]
TIM [OP1]
<T0003(bit)>
003
a088 a093 a214
#220
a219
[OP2]
TIM [OP1]
<T0004(bit)>
004
b128 b255
#200
[OP2]

000016
W0.07 W0.10 W20.00 TIM [OP1]
(000042) <T0057(bit)>
PLC DG DG 057
a129 a256
AUTO VOLTAGE CRANK #150
SELECTE AVAILABL CMD [OP2]
D E RELAY

www.automation-talk.blogspot.com www.automation-talk.blogspot.com
www.automation-talk.blogspot.com www.automation-talk.blogspot.com

W0.10

DG
VOLTAGE
AVAILABL
E RELAY

000017 DG START COMMAND(CONTINUOUS)


(000048)

W10.00 W0.02 W0.07 W70.00 T002 CF114 W10.01 DG START


<W010.01>
TRAFO DG PLC DG-1 TRAFO P_Off
a050 a176
UV CONTAC AUTO ALARM VOLTAGE Always
TOR SELECTE AVAILABL OFF Flag
CLOSE D E
FEEDBA
CK
W10.01 W40.04 W0.02 TIM [OP1]
[OP2]
DG DG-1 ACB DG 010
START TRIP CONTAC #20
TOR
CLOSE
FEEDBA
CK

000018 DG START (CRANK)


(000061)

W10.00 W0.07 W70.00 W0.10 T002 <= W20.01 TIM [OP1]


<T0007(bit)>
(315)

TRAFO PLC DG-1 DG TRAFO C10 DG 007


a071 a197
UV AUTO ALARM VOLTAGE VOLTAGE #3 CRANK #50
SELECTE AVAILABL AVAILABL [OP1] OFF [OP2]
D E RELAY E
[OP2]

W20.00 DG CRANK CMD


<W020.00>
a044 a077 a113
a170 a203 a240

000019
W0.07 T007 T008 TIM [OP1]
(000070) <T0008(bit)>
PLC DG DG 008
b074 b200
AUTO CRANK CRANK #70
SELECTE TIME OFF TIME [OP2]
D
W20.01

DG
CRANK
OFF
W20.01 DG CRANK OFF
<W020.01>
b067 a072 b193
a198

000020
W20.00 CNTR [OP1]
<cC0010>
(012)
(000077)
DG 010
c066 c192
CRANK #3
CMD [OP2]
W0.10

DG
VOLTAGE
AVAILABL
E RELAY
W0.07

PLC
AUTO
SELECTE
D

www.automation-talk.blogspot.com www.automation-talk.blogspot.com
www.automation-talk.blogspot.com www.automation-talk.blogspot.com

000021
W0.07 Q: 100.00 W0.10 TIM [OP1]
(000083) [OP2]
PLC DG DG 018
AUTO START VOLTAGE #5
SELECTE AVAILABL
D E RELAY

000022
W0.07 T003 Q: 100.00 W40.04 DG-1 ACB TRIP
(000087) <W040.04>
PLC TRAFO DG
b058 b184
AUTO VOLT START
SELECTE AVAILABL
D E FOR
ACB
CLOSE

000023
W0.07 T001 T003 W0.02 W0.09 W60.00 TRAFO
(000091) CONTACTOR
PLC TRAFO TRAFO DG T/F CLOSE
AUTO VOLTAGE VOLT CONTAC CONTAC <W060.00>
SELECTE NA AVAILABL TOR TOR
a133 a260
D E FOR CLOSE CLOSE
ACB FEEDBA
CLOSE CK

000024
Q: 100.02 I: 0.04 W0.07 TIM [OP1]
(000097) <T0016(bit)>
DG CT FAN PLC 016
a106 a232
CONTAC ON AUTO #600
TOR SELECTE [OP2]
CLOSE D

000025
Q: 100.02 I: 0.04 W0.07 TIM [OP1]
(000101) <T0017(bit)>
DG CT FAN PLC 017
a109 a235
CONTAC ON AUTO #600
TOR SELECTE [OP2]
CLOSE D

000027
W0.07 T016 201.00 RW FAN ALARM
(000105)
PLC RW FAN
AUTO ALARM
SELECTE
D

000028
W0.07 T017 201.01 CT FAN ALARM
(000108)
PLC CT FAN
AUTO ALARM
SELECTE
D
W0.07 IL
000029
(002)
(000111)
PLC
AUTO
SELECTE
D

000030
(000113)

W20.00 Q: 100.00 DG START


<100.00>
DG
a084 a089 a210
CRANK
CMD a215
W0.02 TIM [OP1]
[OP2]
DG 100
CONTAC #60
TOR
CLOSE
FEEDBA
CK

000031
T002 T119 Q: 100.01 DG STOP
(000117) <100.01>
TRAFO DG STOP
b131 b258
VOLTAGE COMMAN
AVAILABL D TIME

www.automation-talk.blogspot.com www.automation-talk.blogspot.com
www.automation-talk.blogspot.com www.automation-talk.blogspot.com

W70.00 TIM [OP1]


<T0119(bit)>
DG-1 119
b120 b247
ALARM #200
[OP2]

000032
W0.02 W0.07 Q: 100.03 T004 T057 W70.00 Q: 100.01 Q: 100.02 DG
(000124) CONTACTOR
DG PLC TRAFO TRAFO DG ON DG-1 DG STOP CLOSE
CONTAC AUTO CONTAC VOLTS TIMER ALARM <100.02>
TOR SELECTE TOR AVAILABL
a097 a101 a125
CLOSE D CLOSE E FOR
FEEDBA DG CONT b136 a140 a223
CK OFF a227 a252 b263
a267
Q: 100.02

DG
CONTAC
TOR
CLOSE

000033
W60.00 W0.07 Q: 100.02 W0.08 Q: 100.03 TRAFO
(000133) CONTACTOR
TRAFO PLC DG T/F CLOSE
CONTAC AUTO CONTAC VOLTAGE <100.03>
TOR SELECTE TOR AVL
b127 a134 b254
CLOSE D CLOSE
a261

Q: 100.03

TRAFO
CONTAC
TOR
CLOSE

000034
W0.07 Q: 100.02 CF114 200.00 RW/CT FAN ON
(000139) <200.00>
PLC DG P_Off
a141 a146 a268
AUTO CONTAC Always
SELECTE TOR a273
OFF Flag
D CLOSE
200.00

RW/CT
FAN ON
000035
W0.07 200.00 CF114 Q: 100.04 RW PUMP ON
(000145)
PLC RW/CT P_Off
AUTO FAN ON Always
SELECTE OFF Flag
D
CF114 Q: 100.05 CT FAN ON

P_Off
Always
OFF Flag
000036 ILC
(003)
(000153)