You are on page 1of 4

GEP165-3

Diesel Generator Set


Exclusively from your Cat dealer

Image shown may not reflect actual package


Output Ratings

Generating Set Model - 3 Phase Prime* Standby*

380/220 V, 50 Hz 135.0 kVA 150.0 kVA


108.0 kW 120.0 kW

220/127V, 60 Hz 150.0 kVA 165.0 kVA


120.0 kW 132.0 kW

* Refer to ratings definitions on page 4.


Ratings at 0.8 power factor.

Technical Data
Engine Make & Model: Perkins 1006TAG

Alternator Model: GTA 251AE27


Control Panel: PowerWizard 1.1

Base Frame Type: Heavy Duty Fabricated Steel

Circuit Breaker Type: 3 Pole MCCB

Frequency: 50 Hz 60 Hz

Engine Speed: RPM 1500 1800


Fuel Tank Capacity: litres (US gal) 327 (86.4)
Fuel Consumption, Prime: l/hr (US gal/hr) 31.1 (8.2) 37.5 (9.9)

Fuel Consumption, Standby : l/hr (US gal/hr) 34.5 (9.1) 41.0 (10.8)

LEHF0254-00
Engine Technical Data
Physical Data Lubrication System
Manufacturer: Perkins Oil Filter Type: Spin-On, Full Flow
Model: 1006TAG Total Oil Capacity l (US gal): 19.0 (5.0)
No. of Cylinders/Alignment: 6 / In Line Oil Pan l (US gal): 16.0 (4.2)
Cycle: 4 Stroke Oil Type: API CD 15W-40
Induction: Turbocharged Air To Air Cooling Method: Water
Charge Cooled
Cooling Method: Water
Governing Type: Electronic Performance 50 Hz 60 Hz
Governing Class: ISO 8528 G2
Engine Speed: RPM 1500 1800
Compression Ratio: 17.0:1
Gross Engine Power: kW (hp)
Displacement: l (cu.in) 6.0 (365.5)
-Standby: 141.0 (189.0) 158.5 (213.0)
Bore/Stroke: mm (in) 100.0 (3.9)/127.0 (5.0)
-Prime: 128.4 (172.0) 144.2 (193.0)
Moment of Inertia: kg m (lb. in) 1.61 (5502) BMEP: kPa (psi)
Engine Electrical System: -Standby: 1885.0 (273.4) 1766.0 (256.1)
-Voltage/Ground: 12/Negative -Prime: 1716.0 (248.9) 1606.0 (233.0)
-Battery Charger Amps: 55 Regenerative Power: kW 12.6 16.2
Weight: kg (lb) - Dry: 586 (1292)
- Wet: 630 (1389)
Fuel System
Fuel Filter Type: Replaceable Element
Air System 50 Hz 60 Hz Recommended Fuel: Class A2 Diesel or BSEN590
Fuel Consumption: l/hr (US gal/hr)
Air Filter Type: Replaceable Element
110% 100% 75% 50%
Combustion Air Flow:
Load Load Load Load
m/min (cfm) -Standby: 8.8 (310) 11.2 (394)
Prime
-Prime: 8.4 (296) 10.7 (379)
50 Hz 34.5 (9.1) 31.1 (8.2) 24.0 (6.3) 17.0 (4.5)
Max. Combustion Air Intake
60 Hz 41.0 (10.8) 37.5 (9.9) 29.1 (7.7) 20.6 (5.4)
Restriction: kPa (in H2O) 5.0 (20.1) 5.0 (20.1)
Radiator Cooling Air Flow:
Standby
m/min (cfm) 231.0 (8158) 283.8 (10022)
50 Hz 34.5 (9.1) 26.3 (6.9) 18.6 (4.9)
External Restriction to
60 Hz 41.0 (10.8) 31.6 (8.3) 22.3 (5.9)
Cooling Air Flow: Pa (in H2O) 125 (0.5) 125 (0.5)
(based on diesel fuel with a specific gravity of 0.85 and conforming to
BS2869, Class A2)

Cooling System 50 Hz 60 Hz Exhaust System 50 Hz 60 Hz


Cooling System Capacity: Silencer Type: Industrial
l (US gal) 21.0 (5.5) 21.0 (5.5) Silencer Model & Quantity: EXSY1 (1)
Water Pump Type: Centrifugal Pressure Drop Across
Heat Rejected to Water & Silencer System: kPa (in Hg) 0.15 (0.044) 0.23 (0.068)
Lube Oil: kW (Btu/min) Silencer Noise Reduction
-Standby: 70.0 (3981) 76.7 (4362) Level: dB 15 14
-Prime: 65.5 (3725) 68.0 (3867) Max. Allowable Back
Heat Radiation to Room: Heat radiated from engine and alternator Pressure: kPa (in. Hg) 6.0 (1.8) 6.0 (1.8)
kW (Btu/min) -Standby: 39.3 (2235) 47.9 (2724) Exhaust Gas Flow:
-Prime: 26.3 (1496) 30.6 (1740) m/min (cfm) -Standby: 25.7 (908) 31.4 (1109)
Radiator Fan Load: kW (hp) 4.5 (6.0) 8.0 (10.7) -Prime: 24.1 (852) 29.8 (1051)
Exhaust Gas Temperature: C (F)
-Standby: 584 (1083) 551 (1024)
Cooling system designed to operate in ambient conditions up to 50C -Prime: 584 (1083) 551 (1024)
(122F). Contact your local OlympianTM dealer for power ratings at
specific site conditions.

LEHF0254-00 2
Alternator Performance Data
50 Hz 60 Hz
Data Item
380/220V 208/120V 220/127V

Motor Starting
Capability* kVA - - 399 - - - 385 - 439

Short Circuit
Capacity % - - 300 - - - 300 - 300

Reactances:
Per Unit

Xd - - 2.829 - - - 3.380 - 2.910

X'd - - 0.157 - - - 0.174 - 0.155

X''d - - 0.102 - - - 0.104 - 0.094

Reactances shown are applicable to prime ratings.


* Based on 30% voltage dip at 0.6 power factor.

Alternator Technical Data

Physical Data Operating Data

Manufactured for Olympian by: OLYMPIAN Overspeed: RPM 2250

Model: GTA 251AE27 Voltage Regulation: (steady state) +/- 0.5%

No. of Bearings: 1 Wave Form NEMA = TIF: 50

Insulation Class: H Wave Form IEC = THF: 2.0%

Winding Pitch - Code: 2/3 - NA Total Harmonic Content LL/LN: 5.0%

Supression is in line with European


Wires: 12 Radio Interference: Standard EN61000-6

Ingress Protection Rating: IP21 Radiant Heat: kW (Btu/min)

Excitation System: -50 Hz: 13.6 (773)


AUX COIL

-60 Hz: 14.3 (813)


AVR Model: GRT7-TH4E

LEHF0254-00 3
Technical Data

Voltage Voltage
Prime Standby Prime Standby
50 Hz 60 Hz
kVA kW kVA kW kVA kW kVA kW

220/127V 150.0 120.0 165.0 132.0


380/220V 135.0 108.0 150.0 120.0

208/120V 150.0 120.0 165.0 132.0

Weights & Dimensions


Weights: kg (lb) Dimensions: mm (in)
Net (+ lube oil) 1413 (3115) Length 2450 (96.5)
Wet (+ lube oil & coolant) 1439 (3172) Width 1010 (39.8)
Fuel, lube oil & coolant 1716 (3783) Height 1544 (60.8)

Note: General configuration not to be used


for installation. See general dimension
drawings for detail.

Definitions General Data


Standby Rating Documents
These ratings are applicable for supplying continuous electrical A full set of operation and maintenance manuals and circuit wiring
power (at variable load) in the event of a utility power failure. No diagrams.
overload is permitted on these ratings. The alternator on this model
is peak continuous rated (as defined in ISO 8528-3).
Quality Standards
Prime Rating The equipment meets the following standards: BS5000, ISO 8528,
ISO 3046, IEC 60034, NEMA MG-1.22.
These ratings are applicable for supplying continuous electrical
power (at variable load) in lieu of commercially purchased power.
There is no limitation to the annual hours of operation and this Warranty
model can supply 10% overload power for 1 hour in 12 hours.
All prime equipment carries a one year manufacturer's warranty.
Standby equipment, limited to 500 running hours per year, has a
Standard Reference Conditions two year manufacturer's warranty. For details on warranty cover
please contact your local Dealer, or visit our website:
Note: Standard reference conditions 25C (77F) air inlet temp, www.OlympianPower.com.
100m (328ft) A.S.L. 30% relative humidity. Fuel consumption data
at full load with diesel fuel with specific gravity of 0.85 and
conforming to BS2869: 1998, Class A2.

Information contained in this publication may be considered confidential. www.OlympianPower.com


Discretion is recommended when distributing.
2014 Caterpillar
Materials and specifications are subject to change without notice.
Market: International
CAT, CATERPILLAR, their respective logos OLYMPIAN, "Caterpillar Yellow," the "Power Edge" trade dress, as well as All rights reserved.
LEHF0254-00 (11/14) corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.

You might also like