You are on page 1of 40

Vietracimex_VNT 19 Bid Document C7-042

VCX 400 Project for HVAC System

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -01 Chip Conveyning
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 76.2
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.3/16.6
24 Leaving air temperature DB & WB 14.74/13.25
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning compressed Air
34 Face velocity across filter (MPS) 1.78 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1465 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz

1
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1015
2 Overall Dimensions - W x D x H - mm 1950x3000x1530 mm
3 Overall weight - Kg 773.2 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 3970 l/s
8 Total Static pressure - mm wg 823.377 Pa
9 Operating speed - RPM 1506 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 9.754 m/s
14 Fan outlet area 645 x 645 mm
15 Static pressure at outlet ( in mm of water column) 400 Pa
Cooling coil
16 Capacity of cooling coil - TR 42.32 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 1.839 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI ( Fin per inch)
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.622 m/s
27 No of circuits 27
28 Pressure drop in coil (m of water) 39.591 kPa
29 Water flow - LPM 2.122 l/s
30 Water side Pressure drop - KSC 16.258 kPa
Air filter
31 Size and number of pre filters 24x24- 6pcs
32 Face area 2.23 m2
Motor
33 KW of motor 5.5 kW
34 Speed of motor 1455 RPM
35 Starting current of motor / Full Load current of Motor- Amps 10.6 A

2
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -02 - Cooking


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 80.61 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
gauge steel and mild steel

3
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

15 Material and thickness of housing Follow manufacture standard


16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23/15.5 oC
24 Leaving air temperature DB & WB 12.43/11.36 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning compressed Air
34 Face velocity across filter (MPS) 2.272 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1465 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1519
2 Overall Dimensions - W x D x H - mm 2350x3200x2030 mm
3 Overall weight - Kg 1287.6 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 7180 l/s
8 Total Static pressure - mm wg 831.975 Pa

4
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

9 Operating speed - RPM 1256 RPM


10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 11.219 m/s
14 Fan outlet area 810x810 mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 89.679 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 3.062 m2
19 No. of rows 4
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 12 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.789m/s
27 No of circuits 24
28 Pressure drop in coil (m of water) 69.988 kPa
29 Water flow - LPM 4.496 l/s
30 Water side Pressure drop - KSC 9.966 kPa
Air filter
31 Size and number of pre filters 24x24- 6 pcs
32 Face area 12x24
3.16 m2
5 pcs
Motor
33 KW of motor 11 kW
34 Speed of motor 1465 RPM
35 Starting current of motor / Full Load current of Motor- Amps 20.4 A

5
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -03 O2 Delignification


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 82.66
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil

6
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/16.4 oC
24 Leaving air temperature DB & WB 15.19/13.25 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.28 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1827
2 Overall Dimensions - W x D x H - mm 3150x3600x2350mm
3 Overall weight - Kg 1883.8 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 11447 l/s
8 Total Static pressure - mm wg 794.098 Pa
9 Operating speed - RPM 986 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 11.311 m/s
14 Fan outlet area 1010x1010 mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 114.224 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 5.351 m2
19 No. of rows 3

7
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 12 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.048 m/s
27 No of circuits 23
28 Pressure drop in coil (m of water) 41.813 kPa
29 Water flow - LPM 5.727 l/s
30 Water side Pressure drop - KSC 21.613 kPa
Air filter
31 Size and number of pre filters 24x24- 12 pcs
32 Face area 5.02 m2
Motor
33 KW of motor 15 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 27.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -04 Fiber Line
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 83.03
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard

8
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

16 Type of drive (Direct/belt) Belt


17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/16.4 oC
24 Leaving air temperature DB & WB 14.82/13.28 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.222 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-2033
2 Overall Dimensions - W x D x H - mm 3950x4100x2550mm
3 Overall weight - Kg 2744.2 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 17334 l/s
8 Total Static pressure - mm wg 883.784 Pa
9 Operating speed - RPM 805 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 10.813 m/s
14 Fan outlet area 1300x1300 mm
15 Static pressure at outlet ( in mm of water column) 450 Pa
Cooling coil

9
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

16 Capacity of cooling coil - TR 171.304 kW


17 Coil face area - sq.mt -
18 Total surface area - sq.mt 6.927 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.753 m/s
27 No of circuits 48
28 Pressure drop in coil (m of water) 46.715 kPa
29 Water flow - LPM 8.589 l/s
30 Water side Pressure drop - KSC 9.387 kPa
Air filter
31 Size and number of pre filters 24x24- 18 pcs
32 Face area 7.06 m2
Motor
33 KW of motor 30 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 53.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -05 CL02


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 76.94 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard

10
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23/16.4 oC
24 Leaving air temperature DB & WB 14.93/13.4 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 1.907 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1450 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-0715
2 Overall Dimensions - W x D x H - mm 1950X3000X1250mm
3 Overall weight - Kg 673.6 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 3185 l/s
8 Total Static pressure - mm wg 716.854 Pa
9 Operating speed - RPM 1621 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 9.873 m/s
14 Fan outlet area 575x575 mm
15 Static pressure at outlet ( in mm of water column) 300 Pa
Cooling coil
16 Capacity of cooling coil - TR 30.321 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 1.328 m2

11
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.64 m/s
27 No of circuits 20
28 Pressure drop in coil (m of water) 47.957 kPa
29 Water flow - LPM 1.52 l/s
30 Water side Pressure drop - KSC 10.657 kPa
Air filter
31 Size and number of pre filters 24x24- 3 pcs
32 Face area 1.67 m2
Motor
33 KW of motor 4 kW
34 Speed of motor 1450 RPM
35 Starting current of motor / Full Load current of Motor- Amps 7.84 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -06 Bleaching


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 79.43 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard

12
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

18 No. Of belts in case of belt driven Follow manufacture standard


Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23/16.5 oC
24 Leaving air temperature DB & WB 14.74/13.22 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.111 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1465 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1319
2 Overall Dimensions - W x D x H - mm 2350x3200x1850mm
3 Overall weight - Kg 1227.8 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 6670 l/s
8 Total Static pressure - mm wg 808.243 Pa
9 Operating speed - RPM 1212 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 10.422 m/s
14 Fan outlet area 810x810 mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 69.533 kW
17 Coil face area - sq.mt -

13
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

18 Total surface area - sq.mt 2.807 m2


19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.863 m/s
27 No of circuits 17
28 Pressure drop in coil (m of water) 60.265 kPa
29 Water flow - LPM 3.486 l/s
30 Water side Pressure drop - KSC 17.738 kPa
Air filter
31 Size and number of pre filters 24x24- 6 pcs
32 Face area 3.16 m2
Motor
33 KW of motor 11 kW
34 Speed of motor 1465 RPM
35 Starting current of motor / Full Load current of Motor- Amps 20.4 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -07 Drying Machine
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 81.92 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt

14
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

17 If Belt driven specify belt Details Follow manufacture standard


18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/15.5 oC
24 Leaving air temperature DB & WB 14.74/13.22 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.441 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1823
2 Overall Dimensions - W x D x H - mm 2750x3600x2350mm
3 Overall weight - Kg 1814.3 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 10886 l/s
8 Total Static pressure - mm wg 821.102 Pa
9 Operating speed - RPM 976 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 10.757 m/s
14 Fan outlet area 1010x1010mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 131.121 kW

15
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

17 Coil face area - sq.mt -


18 Total surface area - sq.mt 4.589 m2
19 No. of rows 4
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.231m/s
27 No of circuits 23
28 Pressure drop in coil (m of water) 62.693 kPa
29 Water flow - LPM 6.725 l/s
30 Water side Pressure drop - KSC 30.605 kPa
Air filter
31 Size and number of pre filters 24x24- 12 pcs
32 Face area 4.46 m2
Motor
33 KW of motor 15 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 27.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -08 Testing Lab
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 76.74 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard

16
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

16 Type of drive (Direct/belt) Belt


17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/116.4 oC
24 Leaving air temperature DB & WB 14.15/13.01 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 1.866 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1460 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1315
2 Overall Dimensions - W x D x H - mm 1950x3200x1850mm
3 Overall weight - Kg 1013.7 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 5206 l/s
8 Total Static pressure - mm wg 722.101 Pa
9 Operating speed - RPM 1310 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 10.208 m/s
14 Fan outlet area 720x720mm
15 Static pressure at outlet ( in mm of water column) 300 Pa
Cooling coil

17
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

16 Capacity of cooling coil - TR 55.564 kW


17 Coil face area - sq.mt -
18 Total surface area - sq.mt 2.248 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 12 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.69 m/s
27 No of circuits 17
28 Pressure drop in coil (m of water) 51.316 kPa
29 Water flow - LPM 2.786 l/s
30 Water side Pressure drop - KSC 10.463 kPa
Air filter
31 Size and number of pre filters 24x24- 6 pcs
32 Face area 2.79 m2
Motor
33 KW of motor 7.5 kW
34 Speed of motor 1460 RPM
35 Starting current of motor / Full Load current of Motor- Amps 14.5 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -09 Drying Machine 3
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 79.58 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy

18
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

15 Material and thickness of housing Follow manufacture standard


16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.3/16.6 oC
24 Leaving air temperature DB & WB 14.59/13.04 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.325 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1819
2 Overall Dimensions - W x D x H - mm 2350x3400x2350mm
3 Overall weight - Kg 1539.7 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 9066 l/s
8 Total Static pressure - mm wg 822.332 Pa
9 Operating speed - RPM 1118 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 11.248 m/s
14 Fan outlet area 910x910mm
15 Static pressure at outlet ( in mm of water column) 350 Pa

19
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

Cooling coil
16 Capacity of cooling coil - TR 102.442 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 3.827 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.442 m/s
27 No of circuits 15
28 Pressure drop in coil (m of water) 59.913 kPa
29 Water flow - LPM 5.136 l/s
30 Water side Pressure drop - KSC 40.616 kPa
Air filter
31 Size and number of pre filters 24x24- 9 pcs
32 Face area 3.9 m2
Motor
33 KW of motor 15 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 27.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -10 Drying Machine CR
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 79.28 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50

20
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.1/14.9 oC
24 Leaving air temperature DB & WB 11.57/10.25 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.298 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1819
2 Overall Dimensions - W x D x H - mm 2350x3400x2350mm
3 Overall weight - Kg 1612.9 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 8963 l/s
8 Total Static pressure - mm wg 835.308 Pa
9 Operating speed - RPM 1119 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 11.120 m/s
14 Fan outlet area 910x910mm

21
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

15 Static pressure at outlet ( in mm of water column) 350 Pa


Cooling coil
16 Capacity of cooling coil - TR 122.237 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 3.827 m2
19 No. of rows 5
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.122 m/s
27 No of circuits 23
28 Pressure drop in coil (m of water) 76.558 kPa
29 Water flow - LPM 6.129 l/s
30 Water side Pressure drop - KSC 30.733 kPa
Air filter
31 Size and number of pre filters 24x24- 9 pcs
32 Face area 3.9 m2
Motor
33 KW of motor 15 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 27.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -11 Evaporation


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 78.99 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes

22
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

13 Type of bearings Follow Standard L50


14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/15.1 oC
24 Leaving air temperature DB & WB 11.7/10.5 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 1.982 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1450 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1010
2 Overall Dimensions - W x D x H - mm 1450x3000x1550mm
3 Overall weight - Kg 622.1 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 2953 l/s
8 Total Static pressure - mm wg 761.79 Pa
9 Operating speed - RPM 2007 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 11.535 m/s

23
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

14 Fan outlet area 515x515mm


15 Static pressure at outlet ( in mm of water column) 300 Pa
Cooling coil
16 Capacity of cooling coil - TR 40.120 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 1.268 m2
19 No. of rows 5
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.941 m/s
27 No of circuits 18
28 Pressure drop in coil (m of water) 75.824 kPa
29 Water flow - LPM 2.012 l/s
30 Water side Pressure drop - KSC 28.014 kPa
Air filter
31 Size and number of pre filters 24x24- 4 pcs
32 Face area 1.49 m2
Motor
33 KW of motor 4 kW
34 Speed of motor 1450 RPM
35 Starting current of motor / Full Load current of Motor- Amps 7.84 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -12 Recovery Boiler
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 80.86 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward

24
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

12 Whether statically and dynamically balanced? - Yes/No Yes


13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/16.4 oC
24 Leaving air temperature DB & WB 15.24/13.25 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.228 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-2033
2 Overall Dimensions - W x D x H - mm 3750x4100x2550mm
3 Overall weight - Kg 2589.3 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 15728 l/s
8 Total Static pressure - mm wg 822.208 Pa
9 Operating speed - RPM 760 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -

25
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

13 Fan outlet velocity - MPS 9.812 m/s


14 Fan outlet area 1300 x1300 mm
15 Static pressure at outlet ( in mm of water column) 400 Pa
Cooling coil
16 Capacity of cooling coil - TR 156.942 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 6.927 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 8 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.380 m/s
27 No of circuits 24
28 Pressure drop in coil (m of water) 46.557 kPa
29 Water flow - LPM 7.869 l/s
30 Water side Pressure drop - KSC 41.074 kPa
Air filter
31 Size and number of pre filters 24x24- 15 pcs
32 Face area 7,06 m2
Motor
33 KW of motor 22 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 40.5 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -13 Turbine 1


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 79.41 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger

26
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

11 Type of fan (forward/backward) Backward


12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/15.7 oC
24 Leaving air temperature DB & WB 14.51/12.36 oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.563 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1475 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1827
2 Overall Dimensions - W x D x H - mm 3150x4100x2350 mm
3 Overall weight - Kg 2100.6 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 12864 l/s
8 Total Static pressure - mm wg 802.051 Pa
9 Operating speed - RPM 836 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -

27
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

12 BKW -
13 Fan outlet velocity - MPS 8.933 m/s
14 Fan outlet area 1200 x1200 mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 131.981 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 5.351 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.211 m/s
27 No of circuits 23
28 Pressure drop in coil (m of water) 48.178 kPa
29 Water flow - LPM 6.617 l/s
30 Water side Pressure drop - KSC 27.533 kPa
Air filter
31 Size and number of pre filters 24x24- 12 pcs
32 Face area 5.02 m2
Motor
33 KW of motor 18.5 kW
34 Speed of motor 1475 RPM
35 Starting current of motor / Full Load current of Motor- Amps 34.2 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -14 Turbine 2


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 78.41 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section

28
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

10 Make of blower Kruger


11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/15.5 oC
24 Leaving air temperature DB & WB 12.67/11.38oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.327 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1827
2 Overall Dimensions - W x D x H - mm 3150x3800x2350mm
3 Overall weight - Kg 2071.2 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 11683 l/s
8 Total Static pressure - mm wg 822.954 Pa
9 Operating speed - RPM 838 RPM
10 Critical speed RPM -

29
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

11 Fan wheel diameter(mm) -


12 BKW -
13 Fan outlet velocity - MPS 9.149 m/s
14 Fan outlet area 1200x1200 mm
15 Static pressure at outlet ( in mm of water column) 450 Pa
Cooling coil
16 Capacity of cooling coil - TR 145.286 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 5.351 m2
19 No. of rows 4
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.022 m/s
27 No of circuits 30
28 Pressure drop in coil (m of water) 53.89 kPa
29 Water flow - LPM 7.285 l/s
30 Water side Pressure drop - KSC 20.906 kPa
Air filter
31 Size and number of pre filters 24x24- 12 pcs
32 Face area 5.02 m2
Motor
33 KW of motor 15 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 27.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -15 Turbine Boiler
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 77.56 dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A

30
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/16.4 oC
24 Leaving air temperature DB & WB 14.32/13.08oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.292 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-2027
2 Overall Dimensions - W x D x H - mm 3150x3800x2550 mm
3 Overall weight - Kg 2230.9 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 13200 l/s
8 Total Static pressure - mm wg 768.946 Pa
9 Operating speed - RPM 703 RPM

31
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

10 Critical speed RPM -


11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 8.235 m/s
14 Fan outlet area 1300x1300 mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 138.277 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 5.708 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 12 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.608 m/s
27 No of circuits 48
28 Pressure drop in coil (m of water) 51.176 kPa
29 Water flow - LPM 6.933 l/s
30 Water side Pressure drop - KSC 5.39 kPa
Air filter
31 Size and number of pre filters 24x24- 12 pcs
32 Face area 5.76 m2
Motor
33 KW of motor 15 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 27.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -16 Power Boiler
data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 74.74 dBA
8 Noise level at 1m from the filter side (dBA) N/A

32
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

9 Vibration level N/A


Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/14.9 oC
24 Leaving air temperature DB & WB 11.61/10.22oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.013 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1465 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1321
2 Overall Dimensions - W x D x H - mm 2550x3400x1850 mm
3 Overall weight - Kg 1431.6 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 7487 l/s
8 Total Static pressure - mm wg 810.807 Pa

33
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

9 Operating speed - RPM 1040 RPM


10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 9.289 m/s
14 Fan outlet area 910x910 mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 138.277 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 5.708 m2
19 No. of rows 5
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 10 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 1.274 m/s
27 No of circuits 17
28 Pressure drop in coil (m of water) 81.651 kPa
29 Water flow - LPM 5.146 l/s
30 Water side Pressure drop - KSC 35.472 kPa
Air filter
31 Size and number of pre filters 24x24- 8 pcs
32 Face area 3.71 m2
Motor
33 KW of motor 11 kW
34 Speed of motor 1465 RPM
35 Starting current of motor / Full Load current of Motor- Amps 20.4 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -17 Recausticising


data to be furnished for all AHUS)
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3
7 Noise level at 1m from unit(dBA) 81.28 dBA

34
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

8 Noise level at 1m from the filter side (dBA) N/A


9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.2/16.4 oC
24 Leaving air temperature DB & WB 14.48/13.14oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.336 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1470 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1821
2 Overall Dimensions - W x D x H - mm 2750x3600x2350mm
3 Overall weight - Kg 1782.7 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1
7 Air flow - CMH 10420 l/s

35
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

8 Total Static pressure - mm wg 843.990Pa


9 Operating speed - RPM 969 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 10.296 m/s
14 Fan outlet area 1010x1010 mm
15 Static pressure at outlet ( in mm of water column) 400 Pa
Cooling coil
16 Capacity of cooling coil - TR 107.095 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 4.208 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 12 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.502 m/s
27 No of circuits 45
28 Pressure drop in coil (m of water) 49.498 kPa
29 Water flow - LPM 5.37 l/s
30 Water side Pressure drop - KSC 3.33 kPa
Air filter
31 Size and number of pre filters 24x24- 12 pcs
32 Face area 4.46 m2
Motor
33 KW of motor 15 kW
34 Speed of motor 1470 RPM
35 Starting current of motor / Full Load current of Motor- Amps 27.6 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -18 DM Plant Electric
data to be furnished for all AHUS) Room
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU
5 Density of insulation kg/cu.mtr 40 kg/m3

36
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

7 Noise level at 1m from unit(dBA) 76.14 dBA


8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.1/16.4 oC
24 Leaving air temperature DB & WB 14.71/13.28oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 1.919 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1460 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1021
2 Overall Dimensions - W x D x H - mm 2550x3200x1550mm
3 Overall weight - Kg 1068.8 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section
6 No. of fan drums 1

37
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

7 Air flow - CMH 5700 l/s


8 Total Static pressure - mm wg 766.449 Pa
9 Operating speed - RPM 1131 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 8.906 m/s
14 Fan outlet area 810x810 mm
15 Static pressure at outlet ( in mm of water column) 350 Pa
Cooling coil
16 Capacity of cooling coil - TR 56.403 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 2.525 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 12 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.441m/s
27 No of circuits 54
28 Pressure drop in coil (m of water) 48.983 kPa
29 Water flow - LPM 2.828 l/s
30 Water side Pressure drop - KSC 2.811 kPa
Air filter
31 Size and number of pre filters 24x24- 8 pcs
32 Face area 2.97 m2
Motor
33 KW of motor 7.5 kW
34 Speed of motor 1460 RPM
35 Starting current of motor / Full Load current of Motor- Amps 14.5 A

E FLOOR MOUNTED AIR HANDLING UNITS (Individual AHU -19&20 Tech Office
data to be furnished for all AHUS) R&D
1 Make / Manufacturer Daikin
2 Type of Unit Horizontal
3 Thickness of casing in mm:
a) Inner casing (Material & Thickness) 0.5 mm
b) Outer casing (Material & Thickness) 0.5 mm
4 Material of insulation PU

38
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

5 Density of insulation kg/cu.mtr 40 kg/m3


7 Noise level at 1m from unit(dBA) 79.27dBA
8 Noise level at 1m from the filter side (dBA) N/A
9 Vibration level N/A
Fan Section
10 Make of blower Kruger
11 Type of fan (forward/backward) Backward
12 Whether statically and dynamically balanced? - Yes/No Yes
13 Type of bearings Follow Standard L50
14 Material and thickness of Fan impeller and blades The blade is made of heavy
15 Material and thickness of housing Follow manufacture standard
16 Type of drive (Direct/belt) Belt
17 If Belt driven specify belt Details Follow manufacture standard
18 No. Of belts in case of belt driven Follow manufacture standard
Cooling coil
19 Manufacturer Daikin
20 Material of tube and fins Copper/Aluminum
21 Method of bonding tube and fins Follow manufacture standard
22 ADP - deg. C -
23 Entering air temperature DB & WB 23.3/16.4 oC
24 Leaving air temperature DB & WB 14.33/13.05oC
25 Entering water temperature - deg. C 7
26 Leaving water temperature - deg. C 12
Air filter
27 Manufacturer AAF
28 Type of pre filters G4
29 Media used Synthetic
30 Arrestance & efficiency 87-92%
31 Resistance when clean - mm -
32 Whether commissioning filter included-Yes/No No
33 Method of cleaning Compressed Air
34 Face velocity across filter (MPS) 2.486 m/s
35 Pressure drop across filter (mm of water) 200 Pa ( final)
Motor
36 Make of motor Teco
37 Type of motor TEFC
38 Speed of motor 1475 RPM
39 Degree of motor protection Follow manufacture standard
40 Class of insulation IP55
41 Operating voltage 380V/3Ph/50Hz
44 Whether door switch with light included-Yes/No Yes for fan section
General (To be specified for all AHUS)
1 Model DDM2-1827
2 Overall Dimensions - W x D x H - mm 3150x3800x2350 mm
3 Overall weight - Kg 2043.7 kg
4 Whether inbuilt sound attenuator for AHU included-Yes/No No
5 Depth of sound attenuator - mm N/A
Fan Section

39
Vietracimex_VNT 19 Bid Document C7-042
VCX 400 Project for HVAC System

6 No. of fan drums 1


7 Air flow - CMH 12478 l/s
8 Total Static pressure - mm wg 850.465 Pa
9 Operating speed - RPM 844 RPM
10 Critical speed RPM -
11 Fan wheel diameter(mm) -
12 BKW -
13 Fan outlet velocity - MPS 9.771 m/s
14 Fan outlet area 1200x1200 mm
15 Static pressure at outlet ( in mm of water column) 400 Pa
Cooling coil
16 Capacity of cooling coil - TR 131.913 kW
17 Coil face area - sq.mt -
18 Total surface area - sq.mt 5.351 m2
19 No. of rows 3
a. Vertical -
b. Horizontal Y
20 Diameter of tube - mm 12.7 mm
21 Tube thickness 0.406 mm
22 No. of fins/cm 12 FPI
23 Type of fins Corrugated
24 Fin thickness 0.115 mm
25 Test pressure 350psig ( 24 bar)
26 Velocity of water through tubes (MPS) 0.619m/s
27 No of circuits 45
28 Pressure drop in coil (m of water) 51.953 kPa
29 Water flow - LPM 6.614 l/s
30 Water side Pressure drop - KSC 5.363 kPa
Air filter
31 Size and number of pre filters 24x24- 12 pcs
32 Face area 5.02 m2
Motor
33 KW of motor 18.5 kW
34 Speed of motor 1475 RPM
35 Starting current of motor / Full Load current of Motor- Amps 34.2 A