Professional Documents
Culture Documents
ISSN: 2278-0181
Vol. 4 Issue 03, March-2015
The structural arrangement and sizes proposed by 2.3. Steps Involved in Analysis and Design
Architect should not generally be changed except where
Design of R.C.C. building is carried out in the following
structural design requirements cannot be fulfilled by using
steps.
other alternatives like using higher grade of concrete mix
or by using higher percentage of steel or by using any other 1. Prepare R.C.C. layout at different floor levels. In the
suitable structural arrangement. Any change so necessitated layout, the structural arrangement and orientation of
should be made in consultation with the Architect. Further columns, layout of beams, type of slab (with its design
design should be carried out accordingly. The design live load) at different floor levels should be clearly
should account for future expansion provision such as load mentioned.
to be considered for column and footing design if any. In 2. Decide the imposed live load and other loads such as
case of vertical expansion in future, the design load for the wind, seismic and other miscellaneous loads (where
present terrace shall be maximum of the future floor level applicable) as per I.S. 875, considering the
design load or present terrace level design load. contemplated use of space, and seismic zone of the site
of proposed building as per IS 1893.
2.2. General Practice Followed in Design
3. Fix the tentative slab and beam sizes. Using the value
The loading to be considered for design of different of beam sizes fix the column section based on strong
parts of the structure including wind loads shall be as column weak beam design.
per I.S. 875-1987 (Part I to V) and I.S. 1893- 4. As far as possible, for multistoried buildings, the same
2002(seismic loads) column size and concrete grade should be used for
Unless otherwise specified, the weight of various atleast two stories so as to avoid frequent changes in
materials shall be considered as given below. column size and concrete mix to facilitate easy and
o Brick masonry : 19.2 kN/m2 quick construction. Minimum grade of concrete to be
o Reinforced cement concrete : 25kN/m2 adopted for structural members at all floors is M20 for
o Floor finish : 1kN/m2 Non Coastal Region and M30 for Coastal Region.
Live load for sanitary block shall be 2kN/m2. 5. Feed the data of frame into the computer. The beam
Lift machine room slab shall be designed for a and column layouts were fixed using Autocad.
minimum live load of 10kN/m2. Modeling was done using software STAAD Pro. V8i.
Loading due to electrical installation e.g. AC ducting, Dead loads and Live loads calculated as per IS codes
exhaust fans etc. shall be got confirmed from the and their combinations were applied on the Space
Engineer of Electrical wing. frame.
Any other loads which may be required to be 6. Analyse the frame for the input data and obtain
considered in the designs due to special type or nature analysis output. From the analysis various load
of structure shall be documented and included. combinations were taken to obtain the maximum
Deduction in dead loads for openings in walls need not design loads, moments and shear on each member. All
the structural components shall be designed for the
be considered.
worst combination of the above loads as per IS 875
The analysis shall be carried out seperately for dead
Part III.
loads, live loads, temperature loads, seismic loads and
7. To design the structure for horizontal forces (due to
wind loads. Temperature loads cannot be neglected
seismic or wind forces) refer IS 1893 for seismic
especially if the buildings are long. All the structural
forces and IS 875 Part III for wind forces. All design
components shall be designed for the worst
parameters for seismic /wind analysis shall be
combination of the above loads as per IS 875 Part V.
carefully chosen. The proper selection of various
In case of tall buildings, if required Model analysis
parameters is a critical stage in design process.
shall be done for horizontal forces, as per I.S. 1893 and
8. The design was carried as per IS 456:2000 for the
I.S. 875( Part III)
above load combinations. However, it is necessary to
The R.C.C. detailing in general shall be as per SP 34
manually check the design especially for ductile
and as per ductile detailing code I.S. 13920.1993.
detailing and for adopting capacity design procedures
Preliminary dimensioning of slab and beam should be as per IS 13920.
such that:
o Thickness of slab shall not be less than 3. MODELING AND ANALYSIS OF THE BUILDING
100mm and in toilet and staircase blocks not 3.1. General
less than 150mm. Structural analysis, which is an integral part of any
o Depth of beam shall not be less than 230mm. engineering project, is the process of predicting the
o Minimum dimension of column is 230mm x performance of a given structure under a prescribed loading
230mm.
condition. The performance characteristics usually of and side restrictions as proposed in plans by the
interest in structural design are: Architect but will increase the reinforcements to
satisfy IS 13920:1993.
1. Stress or stress resultant (axial forces, shears and
5. As far as possible, column should not be closer than
bending moments)
2m c/c to avoid stripped/combined footings. Generally
2. Deflections the maximum distance between two columns should
not be more than 8m centre to centre.
3. Support reactions
6. Columns should be provided around staircases and lift
Thus the analysis of a structure typically involves wells.
the determination of these quantities caused by the given 7. Every column must be connected (tied) in both
loads and / or the external effects. Since the building frame directions with beams at each floor level, so as to
is three dimensional frames i.e. a space frame, manual avoid buckling due to slenderness effects.
analysis is tedious and time consuming. Hence the structure 8. When columns along with connecting beams form a
is analyzed with STAAD.Pro. In order to analyze in frame, the columns should be so orientated that as far
STAAD.Pro, We have to first generate the model as possible the larger dimension of the column is
geometry, specify member properties, specify geometric perpendicular to the major axis of bending. By this
constants and specify supports and loads. Modeling arrangement column section and the reinforcements
consists of structural discretization, member property are utilized to the best structural advantage.
specification, giving support condition and loading. 9. Normally beams shall be provided below all the walls.
Beams shall be provided for supporting staircase
3.2. Soil Profile
flights at floor levels and at mid landing levels.
The building site is located at Koratty, Thrissur. The plot 10. Beam should be positioned so as to restrict the slab
consists of clayey sand and fine sand to a larger depth and thickness to 150mm, satisfying the deflection criteria.
then rock. The soil strata also varies at diffetent points of To achieve this, secondary beams shall be provided
building. As per the soil report, shallow foundations of any where necessary.
kind cannot be provided in view of the heavy column 11. Where secondary beams are proposed to reduce the
loads, very poor sub soil conditions (above the rock) and slab thickness and to form a grid of beams, the
high water table. Deep foundations installed into the rock secondary beams shall preferably be provided of lesser
have to be adopted. The soil report recommends end depth than the depth of supporting beams so that main
bearing piles penetrated through the hard stratum. So the reinforcement of secondary beam shall always pass
foundation of the building has to be designed as end above the minimum beam reinforcement.
bearing piles penetrated through the hard stratum. Details
Then the structure was discretized. Discretization includes
of soil report was given in Appendix I.
fixing of joint coordinates and member incidences. Then
3.3. Generating Model Geometry the members were connected along the joint coordinates
The structure geometry consists of joint members, their using the member incidence command. The completed
coordinates, member numbers, the member connectivity floor with all structural members was replicated to other
information, etc. For the analysis of the apartment building floors and the required changes were made.
the typical floor plan was selected. The first step was fixing 3.4. Preliminary Design
the position of beams and columns. This step involves the
In this stage, the preliminary dimensions of beams,
following procedure.
columns and slab were fixed. It includes preparation of
1. Preparation of beam-column layout involves fixing of preliminary design of beam, column and slab. The
location of columns and beams, denoting slabs with procedure is described briefly as follows.
respect to design live load, type of slab and numbering
3.4.1. Preliminary Design of Beam
these structural elements.
2. Separate beam-column layouts are to be prepared for All beams of the same types having approximately
different levels i.e. plinth, typical or at each floor level equal span (+) or (-) 5% variation magnitude of
(if the plans are not identical at all floor levels). loading, support conditions and geometric property are
3. Normally the position of columns are shown by grouped together. All secondary beams may be treated
Architect in his plans. Columns should generally and as simply supported beams.
preferably be located at or near corners and The width of beam under a wall is preferably kept
intersection/ junctions of walls. equal to the width of that wall to avoid offsets, i.e. if
4. While fixing column orientation care should be taken the wall is 230mm, then provide the width of beam as
that it does not change the architectural elevation. This 230mm.
can be achieved by keeping the column orientations
Minimum width of main and secondary beam shall be 3.5. Specifying Member Property
230mm. However secondary beams can be less,
The next task is to assign cross section properties for the
satisfying IS 13920: 1993. The width of beam should
beams and columns the member properties were given as
also satisfy architectural considerations.
Indian. The width ZD and depth YD were given for the
The span to depth ratio for beam adopted is as follows: sections. The support conditions were given to the structure
o For building in seismic zone above III as fixed. Fig. 1, 2 gives the 3D view of framed structure
between 10 to 12 and its rendered view.
o For seismic zones I and II 12 to 15
3.4.2. Preliminary Design of Column
The dimension of a particular column section is decided in
the following way.
The column shall have minimum section 230mm x
230mm, if it is not an obligatory size column.
The size of obligatory column shall be taken as shown
on the architect's plan. For non-obligatory columns as
far as possible the smaller dimension shall equal to Fig. 1: 3D view of the model
wall thickness as to avoid any projection inside the
room. The longer dimension should be chosen such
that it is a multiple of 5cm and ratio Pu/fckbd
(restricted to 0.4 for non seismic area and .35 for
seismic regions).
If the size of column is obligatory or if size can be
increased to the desired size due to Architectural
constraints and if the ratio of Pu/fckbd works out more
than the limit specified above it will be necessary to
upgrade the mix of concrete.
Preferably, least number of column sizes should be Fig. 2: Rendered View of the Model
adopted in the entire building.
3.6. Specifying Geometric Constants
Dimensions of beams and column were changed when
some section was found to be failed after analyzing in In the absence of any explicit instructions, STAAD will
software. After preliminary design, section properties of orient the beams and columns of the structure in a pre-
structural members were selected by trial and error as defined way. Orientation refers to the directions along
shown in Table 1 below. which the width and depth of the cross section are aligned
Table 1: Properties of member sections with respect to the global axis system. We can change the
orientation by changing the beta angle
Member section Dimensions 3.7. Specifying Loads
Slab 150mm thickness The dead load and live load on the slabs were specified as
floor loads, wall loads were specified as member loads and
B1 300mm x 700mm
seismic loads were applied as nodal forces. Wind loads
B2 250mm x 700mm were specified by defining it in the STAAD itself. Various
B3 200mm x 700mm combinations of loads were assigned according to IS
Beams B4 300mm x 600mm 456:2000.
B5 300mm x 600mm The various loads considered for the analysis were:
B6- 200mm x 600mm
Vertical Loads : The vertical loads for a building are:
C1 300mm x 550mm Dead load includes self-weight of columns, beams,
C2 450mm x 600mm slabs, brick walls, floor finish etc. and Live loads as
Columns C3 400mm x 600mm
per IS: 875 (Part 2) 1987
3.7.1 Dead Loads (IS: 875 (Part 1) 1987) Self weight of 10 cm thick parapet wall
= 0.1 x 1.2 x 20 = 2.4 kN/m
These are self-weights of the structure to be designed. The
dimensions of the cross section are to be assumed initially 3.7.2 Live Loads (IS: 875 (Part 2) 1987)
which enable to estimate the dead load from the known
They are also known as imposed loads and consist of all
unit weights of the structure. The values of the unit weights
loads other than the dead loads of the structure. The values
of the materials are specified in IS 875:1987(Part-I). Dead
of the imposed loads depend on the functional requirement
load includes self-weight of columns, beams, slabs, brick
of the structure. Industrial building will have comparatively
walls, floor finish etc. The self-weight of the columns and
higher values of the imposed loads than those of the
beams were taken automatically by the software. The dead
commercial buildings. The standard values are stipulated in
loads on the building are as follows.
IS 875:1987(Part-II).
Dead load of slab (150 mm thick)
The live loads used for analysis are:
Self weight of slab(15 cm thick Reinforced Concrete slab)
Industrial units - 5-10 kN/m
= 0.15 x 25
Bath and toilet - 4 kN/m
= 3.75kN/m2
Passage, Stair case - 4 kN/m
Floor Finish(25 cm thick marble finish over 3cm thick Roof - 1.5 kN/m
cement sand mortar)
Total load on slab = 5 kN/m2
Dead load of slab for lift room (250mm thick)
Self weight of slab(25 cm thick Reinforced Concrete slab)
= 0.25 x 25
Floor Finish(5 cm thick Cement Sand mortar)
= .05 x 20.4
Total load on slab = 7.25 kN/m2
Self weight of slab(200mm thick 3.7.3 Wind loads (IS 875 (Part 3):1987)
Reinforced Concrete slab) = 0.2 x 25 These loads depend on the velocity of the wind at the
location of the structure, permeability of the structure,
Floor Finish(5cm thick Cement Sand mortar) height of the structure etc. They may be horizontal or
=.05 x 20.4 inclined forces depending on the angle of inclination of the
= 1kN/m2 roof for pitched roof structures. Wind loads are specified in
Total load on slab = 6 kN/m2 IS 875 ( Part-3).
Dead load of brick wall (Unit weight 20 kN/m3 ) Basic wind speed in Kerala, Vb = 39 m/sec
Self weight of 20 cm thick wall = 0.20 x 4.2 x 20 Design wind speed, Vz =Vb k1k2k3
= 16.8 kN/m Where:
Self weight of 10 cm thick wall = 0.10 x 4.2 x 20 k1 = probability factor
= 8.4 kN/m
k2 = terrain, height and structure size factor
Dead load of side wall for lift room
k3 = topography factor
Self weight of 20 cm thick wall = 0.20 x 2.82 x 20
= 11.28 kN/m Basic wind pressure, Pz= 0.6 Vz2
Dead load of side wall for water tank (RCC Wall) Wind loads are determined using the following
parameters:-
Self weight of 15cm thick wall = 0.15 x 1.6 x 25
= 6kN/m Basic wind speed Kerala : 39 m/s
Dead load of parapet wall Risk factor (50 years design life) K1: 1.0
Topography factor, K3: 1.0
Design wind
Sl.
Wind speed
Pz = 0.6 Vz2
pressure
Height
(m/s)
(m)
No k k2 k3
. 1
Wi = Seismic weight of floor i
hi= Height of floor i measured from base.
1 10 39 1 .98 1 38.22 .875
n = Number of storeys in the building is the
number of levels at which the masses are
2 15 39 1 1.02 1 39.78 0.949 located.
Seismic Analysis using was done by using STAAD.Pro. Z = 0.16 (Clause 6.4.2, Table 2)
The entire beam-column joint are made pinned and the
program was run for 1.0D.L + 0.5L.L. The live load shall RF = Response reduction factor.
be 0.25 times for loads up to 3kN/m2 and 0.5 times for
loads above 3kN/m2 (Clause 7.4.3 and Table 8). RF =5 (Clause 6.4.2, Table 7)
ST = 1 15. 1.5(DL-WLX)
16. 1.5(DL+WLY)
DM = Damping ratio to obtain multiplying factor for
calculating Sa/g for different damping. If no damping 17. 1.5(DL-WLY)
is specified 5% damping (default value 0.05) will be
18. 1.2(DL+LL+WLX)
considered corresponding to which multiplying factor
is 1.0. 19. 1.2(DL+LL-WLX)
20. 1.2(DL+LL+WLY)
21. 1.2(DL+LL-WLY)
22. 0.9DL+1.5WLX
23. 0.9DL-1.5WLX
24. 0.9DL+1.5WLY
25. 0.9DL-1.5WLY
All these combinations are built in the STAAD
Pro. Analysis results from the critical load combinations
Fig. 5: Seismic Forces in X-Direction are used for the design of the structural members.Where,
DL - Dead load ,LL - Live load
3.8. Load Combinations EQX Earthquake load in X-direction
Design of the structures would have become highly
expensive in order to maintain either serviceability and EQY Earthquake load in Y-direction
safety if all types of forces would have acted on all WLX Wind load in X-direction
structures at all times. Accordingly the concept of
characteristics loads has been accepted to ensure at least 95 WLY Wind load in Y-direction
percent of the cases, the characteristic loads considered will 3.9. Staad Analysis
be higher than the actual loads on the structure. However, The structure was analysed as Special moment resisting
the characteristic loads are to be calculated on the basis of space frames in the versatile software STAAD Pro.V8i.
average/mean load of some logical combinations of all Joint co-ordinate command allows specifying and
loads mentioned above. IS 456:2000 and IS 1893 (Part generating the co-ordinates of the joints of the structure,
1):2002 stipulates the combination of the loads to be initiating the specifications of the structure. Member
considered in the design of the structures. incidence command is used to specify the members by
The different combinations used were: defining connectivity between joints. The columns and
beams are modeled using beam elements. Member on the basis of most critical state and then checked for
properties have to be specified for each member. STAAD other limit states.
pro carries out the analysis of the structure by executing
As per IS 456:2000 the value of partial safety factor for
PERFORM ANALYSIS command followed by RUN
dead and live load combination which is the maximum is
ANALYSIS command. After the analysis the post
adopted for design of beams and columns. The following
processing mode of the program helps to get bending
are design examples of slab, beam, column etc.
moment, shear force, axial load values which are needed
for the design of the structure. The values corresponding to 4.2. Design of Beam
load combination was compared and higher values were Beams were designed as continuous beam. For better
taken for design. understanding a frame of two bays were taken as design
example. The ground floor beam of span 7.6m was
considered for the design.
Material Constants
For M 25 Concrete, fck = 25 N/mm2
For Fe 415 Steel, fy = 415 N/mm2
4. DESIGN OF RC BUILDING
4.1.General The bending moments and shear force from the analysis
The aim of structural design is to achieve an acceptable results are as follows.
probability that the structure being designed will perform
the function for which it is created and will safely
withstand the influence that will act on it throughout its
useful life. These influences are primarily the loads and the
other forces to which it will be subjected. The effects due
to temperature fluctuations, foundation settlements etc.
should be also considered.
The design methods used for the design of reinforced
concrete structures are working stress method, ultimate Fig.9: Bending Moment Diagram of Beam Envelope
load method and limit state method. Here we have adopted
the limit state method of design for slabs, beams, columns,
stairs and foundations.
In the limit state method, the structure is designed to
withstand safely all loads liable to act on it through its life
and also to satisfy the serviceability requirements, such as
limitation to deflection and cracking. The acceptable limit
of safety and serviceability requirements before failure is Fig.10:of
Assume clear cover Shear Force&
30mm Diagram
20 mm of
Beam
bars,
called limit state. All the relevant limit states should be
considered in the design to ensure adequate degrees of Effective depth, d = 700 30 = 660 mm
safety and serviceability .The structure should be designed
From Table C of SP-16,
= 7920 mm2 Hence, area of steel required is greater than minimum steel.
The lever arm for this additional moment of resistance is =702.26- 444.134
equal to the distance between centroids of tension =258.126 kNm
reinforcement and compression reinforcement, that is (d-
d). The lever arm for this additional moment of resistance is
equal to the distance between centroids of tension
d-d = 610 mm reinforcement and compression reinforcement that is (d-
From chart 20, SP 16, Ast2 = 800 mm2 d).
Provide 6 nos. of 25 mm dia bars and 2 nos. of 20mm dia =((428.846 103 )
bars at tension face and, 4 nos. 20mm bars on compression (0.74 300660))x10-3
face. = 282.3kN
Table 4: Beam design calculation results (Span BC)
Using 8 mm dia 4 legged vertical stirrup bars, =
Left end Right end
415N/mm2
Position on Mid
beam span Asv= 201.06 mm2
Top Bottom Top Bottom
0.87 f y A sv d
Stirrup Spacing, Sv= = 169.72 mm
Bending Vus
Moment, -679.66 17.025 513.698 -667.939 17.369
(kNm)
According to IS 456:2000, clause 26.5.1.5, the spacing of
stirrups in beams should not exceed the least of ;
Mu
5.2 0.13 3.93 5.11 .133 1. 0.75d = 0.75 660 = 495 mm
bd2
2. 300 mm
d/d 0.045 0.045 0.045 0.045 0.045
According to IS 13920:1993 up to a distance 2d =1320 mm
pt(%) 1.705 - 1.34 1.675 - from the supports, spacing of stirrups should not exceed the
least of
Ast Required
3375.90 - 2653.2 3316.50 - 1. of effective depth = 165 mm
(mm2)
2. 8 times the diameter of longitudinal bar
Ast Provided = 825= 200 mm
3573.56 - 3220.132 3573.56 -
(mm2)
Therefore provide 8 mm 4 legged stirrups bars @
2-20mm 4-25mm 2-20mm 150mm c/c upto a distance 1.32m from the face of support
Steel Provided
6-25mm
-
4-20mm 6-25mm
-
and provide 8 mm 4 legged stirrups bars @ 160 mm c/c
at all other places. Fig. 11 shows the reinforcement details
pc(%) 0.535 - 0.14 0.504 - of continuous beam.
Asc Required
1059.3 - 277.2 997.92 -
(mm2)
Asc Provided
402 _ 628.32 402 _
(mm2)
l b
Eccentricity in X direction, =
500 30
=20.76 mm > 20 mm
l D
Eccentricity in Y direction, =
500 30
= 25.76mm >20 mm
Moments due to minimum eccentricity
Mux =Puex= 3597.55 0.02076 = 74.68 kNm
Muy= Puey= 3597.55 0.02576= 92.67 kNm
Longitudinal reinforcement
Assume percentage of steel, pt = 2.8% ;
2.8
= = 0.093
30
Fig.11: Reinforcement details of Beam
(0.8% - 6% is the range of minimum steel area of column
as per IS 456: 2000)
Assume 40 mm clear cover and 25 mm bars,
4.3. Design of Column
d =40 + (25/2)=52.5mm
Material Constants:
Concrete, fck= 30 N/mm d'
(About X axis) = 52.5/450 = 0.1167
D
Steel,fy= 415 N/mm
Column size= 450 mm 600 mm
d'
(About Y axis) = 52.5/600 = 0.0875
D
Depth of column, D = 600 mm
Pu
Breadth of column, b = 450 mm = 0.487
bdf ck
leff/ b = 2.88 /0.45 = 6.4 < 12 = 0.227, = 0.211
1 1
So design as a short column with biaxial bending
Pu
Calculation of eccentricity For =0.211 and =0.592,(Refer chart 64, SP- 16)
1
Puz
(Ref:Clause.25.4 of IS 456:2000)
Permissible value of = 0.84; which is greater than the
1
actual value of
1
Hence safe.
12 mm bars
= 10kN/m2
Spacing of
Live load
(provided)
Ast Ast
Total service load = 15kN/m2 Location (required) (provided)
=180 mm2 Fig. 13 shows the reinforcement details of Two way slab.
Provide 12mm bar at 300mm centre to centre spacing as
distribution steel.
Check for shear
=
2
22.5 3.325
=
2
= 37.41kN
As per IS 456:2000 clause 40.1
=
37.4110 3
=
1000 125
= 0.299 N/mm2
100
=
100 1256 .64
= = 1.005
1000 125
At support
(Negative
= 5 kN/m2
moment)
Total dead load, WDL
bending
81.83 1693.98 376.99 300
Live load for Passage, WLL= 4kN/m2
Factored loads,
ve bending
span(Positi
moment)
Dead Load, Wu,DL = 5 1.5 = 7.5kN/m2 70.47 1962.34 753.98 150
=
Live Load, Wu,LL = 4 1.5 = 6kN/m2
At
Bending Moment and Shear force at critical sections
Minimum Reinforcement to be provided
According to IS 456:2000, table 12 and table 13 gives the
As per IS 456:2000 clause 26.5.2.1
bending moment coefficient and shear coefficient.
Astmin= 0.12% cross sectional area
Table 6: Moment and Shear coefficients
= 0.0012 x 1000 x 129
interior
(At
(At
support next to
middle of end
moment(Near
end support)
End support
moment
Support
Support
support
Span
First
the
=154.8mm2
load(DL)
c>v
Spacing required(mm)
Astprovided (mm2)
Ast required(mm2)
0.58 ( )
fs =
= 26 x 1.2
= 31.2
1.5
= = 11.628
0.129
max >
Fig. 15: Top view of staircase
Therefore safe.
Check for cracking Material Constants:
As per IS456:2000, clause 43.1: Concrete, fck = 25 N/mm2
4. Steel provided is less than 0.12% Steel, fy = 415 N/mm2
5. Spacing of main steel < 3d
Dimensioning:
= 3 x 129 = 387mm .
Height of each flight= = 2.1 m
6. Diameter of reinforcement < D/8
Let the tread of steps be 300 mm
= 18.75mm
Width of stair = 165 mm
Hence safe.
Effective span, Le = 6.2 m
Fig. 14 shows reinforcement details of One way slab.
Let the thickness of waist slab be 250 mm
Use 12 mm bars, Assume, clear cover= 25 mm
Effective depth = 219 mm
Loads on landing slab
Self-weight of Slab= 0.25 25
Finishes = 1.25 kN/m
Total = 11.5 kN/m
Factored load = 1.511.5
= 17.25 kN/m
Live Load on Slab
= 4 kN/m
Loads on waist slab
Fig. 14: Reinforcement details of One way slab
Dead load of waist slab
25 2 + 2
=
= 6.98 kN/m2
The self weight of the steps is calculated by treating the Maximum Spacing = 3d = 3 219
step to be equivalent horizontal slab of thickness equal to
R
= 657 mm (or) 300mm
half the rise
2
[whichever is less]
Self weight of step= 0.5 25
Hence, provide reinforcement of 12 mm bars at 80 mm
= 0.5 0.15 25 = 1.875 kN/m2 c/c
Floor finish = 1.25 kN/m2 Distribution steel= 0.12% cross sectional
=.0012 1000 219
As per IS: 875(Part 2)-1987- Table-1
= 262.8 mm2
Live load = 4kN/m2
2
Total service load = 14.105 kN/m Provide 8mm bars, Spacing =
.
=191.27mm
Consider 1 m width of waist slab Maximum Spacing = 4d
Total service load / m run = 14.105 1 Hence, Provide 8 mm diameter bars at 190mm c/c
= 14.105 kN/m Check for shear
Factored load, Wu= 1.5 14.105 (As per IS 456:2000, Clause 40)
= 21.1575 kN/m Maximum Shear force, V= 63.43kN
Nominal shear stress, v=
To get maximum Bending Moment, take Shear Force at x 100As/bd =.635; From IS 456: 2000, Table 19,
distance from support B=0. Thus obtained X as 3.109m
Maximum moment at X=3.109m: c= 0.534 N/ mm2
Mu = 96.73 kNm
v < c < c max ; So shear reinforcement is not required.
Mu
= (96.73 10 )/ (1000 219 )
6 2
bd 2
=2.01N/mm2
Percentage of steel,pt= 0.635%
(From SP16,Table 3)
Therefore,
P t bd
Ast = =
100
(0.635 1000 219)/ 100
= 1390.65 mm2
Minimum steel=0.12% cross sectional area
= .12 1000 219/100 Fig. 17: Reinforcement details of staircase.
2
=262.8 mm 4.6. Design of Water Tank
Use 12mm bars,
Material constants
1000 A 1000 4 12 2
Spacing = = = 81.32 mm fck = 25 N/mm2
A st 1390 .65
=12.67 kNm
Fe415 Steel
= 0.22% of cross- section
0.221000 200 Earth Density = 17kN/m3
=
100
Safe Bearing Capacity of soil,p = 100kN/m2
= 440 mm2
Angle of internal friction of soil =300
Area of one bar
Spacing = 1000
total area Coefficient of friction, (coarse grained soil) = 0.55
= 82.79mm Retaining wall has to support a bank of earth 4.2m high
Provide 10 mm bars at a spacing of 80mm c/c along short above the ground level at the Toe of the wall.
span Preliminary Proportions
Reinforcement required in long span direction Depth of retaining wall below ground level,
1 2 100 1 30 2
hd= ( ) = ( )
M 1+ 17 1+ 30
Ast req =
st jd = 0.654m
12.672 10 6
= = 880.734 mm2 But minimum depth of retaining wall below ground level is
150 0.872 110
1m.
Area of one bar
Spacing= 1000
total area To accommodate for thickness of base, keep depth as
=89.175mm 1.25m.
Total height of retaining wall = 4.2 + 1.25m
Provide 10 mm bars at a spacing of 85mm c/c along long
span = 5.45m
Check for effective depth Assume the thickness of footing to be about 10%
of the total height, i.e., 50cm.
dprovided =150-25-5 = 120 mm
Height of wall above the base, h =5.45-0.5
14.6710 6
drequired = = = 4.95m
1.422 1000
=101.57 mm < dprovided Base length, l= H
(1 )(1+3 )
Hence safe.
1 1
Ka, coefficient of active earth pressure = =
1+ 3
Downward load intensity due to self-weight of Percentage of steel, pt = 100 Ast /bd
Toe Slab = 0.5 x 25 =0.357
=12.5kN/m2
From Table 19 of IS 456: 2000,
Therefore, net upward pressure varies from 76.5kN/m2 to
40.54kN/m2 Permissible Stress, c= 0.42 N/mm2
Toe is treated as a cantilever beam with critical section for From Table 20 of IS 456: 2000, c max=3.5 N/mm2
shear at a distance d from the front face of the wall. v<candc<c max .Hence Toe slab is safe in shear.
Upward pressure at a distance 0.5m from the face
of wall =63.93kN/m2 B. Design of Heel slab
Neglecting the earth on the Toe, Shear Fore and Bending The heel is subjected to an upward pressure varying from
Moment are, 43.24N/mm2to 23.65N/mm2. The downward load intensity
Vu = 110.31kN due to earth, surcharge and concrete weight is
96.65N/mm2. Since the downward pressure is more than
Mu =131.69kNm
the upward pressure, tension is induced in the upper face of
Mu lim= 0.138fck bd2 the heel. Therefore, critical section for shear is at the face
Minimum depth of toe slab is given by, of the support.
= 84.78kN
Hence, safe.
(i)Reinforcement for Heel Slab
(i) Reinforcement for Toe Slab
Area of tension steel is given by, Mu = 0.87fyAst d(1- )
Mu = 0.87fyAst d (1- ) 40.138 106= 0.87415 Ast
440(1-415 Ast/(301000440))
131.69 x 106= 0.87x 415 Ast440
Ast = 212.66mm2
(1-415Ast/(301000440))
Minimum reinforcement = 0.12% bD
Ast = 717.27mm2
20 2 1000
=528.5mm2
Spacing, s = =437.9mm
717 .27 16 2 1000
Spacing, s =
528 .4
Maximum spacing, s =0.75d
= 380.44mm
=330mm
Provide 16mm dia bars @ 300mm c/c spacing
Provide 16mm dia bars @ 100mm c/c spacing (Ast
provided =1570.79mm2) and 10mm dia bars @140mm c/c (ii)Check for Shear
as distribution steel.
Maximum Shear force, Vu = 84.78 kN
Minimum reinforcement = 0.12% bD Vu
Shear Stress, v =
2 bd
=528.5mm
415
410 1
1000 410 30
= 1639.94mm2
16 2 1000
Spacing, s=
4 2969.38
=122.603mm
Provide 16mm dia bars @ 120mm c/c spacing.
5. CONCLUSIONS
The industrial training, taken through a period of one
month allowed to have ample exposure to various field
practices in the analysis and design of multi storied
buildings and also in various construction techniques used
in the industry. The analysis was done using the software
package STAAD Pro V8i, which proved to be premium
software of great potential in analysis and design sections
of construction industry. All the structural components
were designed manually and detailed using AutoCAD
2013. The analysis and design was done according to
standard specifications to the possible extend.
ACKNOWLEDGMENT
I express my sincere gratitude to all those who have
extended a helping hand, especially my guide Mr. Abhilash
Joy.I thank him from my heart for his valuable guidance. I
am also grateful to theHead of the Department, Civil
Engineering, SSET for the encouragement and co-
operation.
REFERENCES
1. Unnikrishna Pillai, S. and DevadasMenon ,Reinforced Concrete
Design, Tata McGraw-Hill Publishing Company Limited, New
Delhi, 2003
2. Ramamruthum S., Design of Reinforced Concrete Structures,
DhanpatRai Publishing Company (P) Ltd, New Delhi.
3. Dr. Punmia B.C., Ashok Kumar Jain, Arun Kumar Jain, Reinforced
Concrete Design, Laxmi publications Private Limited, New Delhi.
4. IS: 875 (Part 1)-1987, Indian Standard Code of Practice for Design
Loads (Other than earthquake) for Building and Structures, Bureau
of Indian Standards, New Delhi.
5. IS: 875 (Part 2)-1987, Indian Standard Code of Practice for Design
Loads (Other than earthquake) for Building and Structures, Bureau
of Indian Standards, New Delhi.
6. IS: 875 (Part 3)-1987, Indian Standard Code of Practice for Design
Loads (Other than earthquake) for Building and Structures, Bureau
of Indian Standards, New Delhi.
7. IS: 1893 (Part 1) 2002- Indian StandardCriteria for earthquake
resistant design of structures, Bureau of Indian Standards, New
Delhi.
8. IS: 13920:1993, Ductile detailing of reinforced concrete structures
subjected to seismic forces, Bureau of Indian Standards, New Delhi.
9. IS 456:2000, Indian standardPlain and reinforced concrete Code
of Practice,
Bureau of Indian standard, 2000, New Delhi.
10. SP 16: 1980, DesignAids for Reinforced Concrete to IS: 456-1978,
Bureau of Indian Standards, New Delhi.
11. SP 34: 1987, Hand Book on Concrete Reinforcement and Detailing,
Bureau of Indian Standards, New Delhi.