BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
EarthingSystem
ProtectionAgainstElectricShocks
EarthFaultsProtection
ProtectionAgainstVoltageSurges
1
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Earth:TheconductivemassoftheEarth,whose
electricpotentialatanypointisconventionally
l ti t ti l t i ti ti ll
takenaszero.
Anearth isdefinedasaconnectiontothe
generalmassofearth.
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
(1)Earthelectrode
(2)Earthing conductor
(3)Protectiveconductor
(4)Electricalinstallation
(5)Bondingconductor
(6)Mainearthing terminal
(7)Removablelink
2
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Aconductororothermetalisearthedwhenit
iseffectuallyconnectedtothegeneralmassof
i ff t ll t d t th l f
earth bymeansofametalrodorasystemof
metalwaterpipesorotherconductingobject.
SolidlyearthedorBoltedearthedwhenitis
earthedwithout theinterventionofafuse,,
switch,circuitbreaker,resistor,reactor,or
solenoid.
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Earthing ismeantbyhavingeveryitemof
apparatust andeveryconductorshallbe
d d t h ll b
preventedfromgivingrisetoearthleakage
currents.
Itiscarriedoutbyensuringanymetalliableto
becomecharge g shouldbeearthandeverypart
yp
oftheearthing circuitshouldbeproperly
installed.
3
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Grounding
Connectingequipmentandpointsonelectricalsystems
Connecting eq ipment and points on electrical s stems
totheearth oranearthsubstitute.
Purposeistolimitovervoltages betweentheequipment
andtheearthduetolightning,faults,etc.
Bonding
Connecting
Connectingequipmenttogetherandtothesystem
equipment together and to the system
neutral point.
Purposeistolimitvoltages betweenequipmentandto
provideapathforgroundfaultcurrent.
4
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Reason(1) Minimiseovervoltages
Lightning
strike
Utilityphase conductor
Lightning transformer
arrester
Utilityneutral
Utility neutral conductor
Transformerearthrod Serviceearthrod
10
5
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Reason(2) Limitvoltagepotentialon
equipmentenclosures
i t l
Ungrounded Insulation Grounded Insulation
motorframe breakdown motorframe breakdown
415V
feeder 240V Equipment 0V
conductors earthing
conductor
400Vmotor 400Vmotor
Earthing surface Earthing surface
11
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Reason(3) Providealowimpedancepathfor
faultcurrent
f lt t
Ungrounded Insulation Grounded Insulation
motorframe breakdown motorframe breakdown
Overcurrent Overcurrent
devices devices
415V IF
I = 0A
I=0A IF
feeder Equipment IF
conductors earthing
IF
conductor
400Vmotor 400Vmotor
12
6
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Designingasafeearthing systemmeans
providingtheeasiestandshortest
idi th i t d h t t pathforthe
th f th
faultcurrentwithoutexposingapersonto
electricshock.
Satisfactoryearthing isthemostimportantpart
ofanelectricalinstallationbecauseoperation
p
ofalltheprotectivedevicesdependuponit.
13
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Thetotalimpedanceoftheconductor,
connectingthemetalwork
connecting the metal work oftheinstallation
of the installation
totheearthelectrode(earthcontinuity
conductor)measuredbetweentheearth
electrodeandanyotherpart oftheinstallation
atsupplyfrequencyshouldnotexceed1.0.
If the resistance is higher than 1 0 (excessive
Iftheresistanceishigherthan1.0 (excessive
resistance),itisanindicationofimproper
earthing.
14
7
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Earthlugterminalrusty
Loosewireconnection
Layersofpaintontheelectricapparatus
Looseconnectionofearthwiretotheplugand
socketoutlet
Looseconnectionbetweenconduitand
terminalbox
15
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
8
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TTsystem(earthedneutral)
One point at the supply source is connected directly to earth. All exposed and
extraneousconductiveparts are connected to a separate earth electrode at the
installation. This electrode may or may not be electrically independent of the source
electrode.
17
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TNCsystem
Theneutralconductorisalsousedasaprotectiveconductorandisreferredtoasa
PEN(ProtectiveEarthandNeutral)conductor.
18
9
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TNSsystem
19
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TNCSsystem
In the TNCS system, the TNC (4 wires) system must never be used downstream of
the TNS (5 wires) system, since any accidental interruption in the neutral on the
upstream part would lead to an interruption in the protective conductor in the
downstream part and therefore a danger.
20
10
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
ITsystem(isolatedneutral)
No intentional connection is made between the neutral point of the supply source
and earth. Exposed and extraneousconductiveparts of the installation are
connected to an earth electrode.
21
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
ITsystem(impedanceearthedneutral)
22
11
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
23
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
12
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TNCsystem
TNSsystem
25
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
26
13
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
27
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Solutionofferingthebestcontinuityofserviceduring
operation.
Indicationofthefirstinsulationfault,followedbymandatory
locationandclearing,ensuressystematicpreventionof
supplyoutages.
GenerallyusedininstallationssuppliedbyaprivateMV/LVor
LV/LVtransformer.
Requiresmaintenancepersonnelformonitoringand
operation.
p
Requiresahighlevelofinsulationinthenetwork(implies
breakingupthenetworkifitisverylargeandtheuseof
circuitseparationtransformerstosupplyloadswithhigh
leakagecurrents).
28
14
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Zonestime/currentofeffectsofACcurrentonhumanbodywhenpassingfromlefthandtofeet
30
15
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Adirectcontactreferstoapersoncominginto
contactwithaconductor
t t ith d t whichislive
hi h i li in
i
normalcircumstances.
Is=Touchcurrent
31
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Anindirectcontactreferstoapersoncoming
i t t t ith d d ti
intocontactwithanexposedconductivepart t
whichisnotnormallyalive,buthasbecome
aliveaccidentally(duetoinsulationfailureor
someothercause).
Is=Touchcurrent
Id=Insulationfaultcurrent
32
16
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
33
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Protectionbytheinsulation ofliveparts
Protectionbymeansofbarriersorenclosures
Useofresidualcurrentoperatingdevice,which
operateat30mA orless,andarereferredtoas
RCDs ofhighsensitivity
RCD
Insulation
Envelope
34
17
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Theearthing ofallexposedconductivepartsof
electricalequipmentintheinstallationandthe
electrical equipment in the installation and the
constitutionofanequipotentialbonding
network.
Automaticdisconnection ofthe
supplyofthesectionofthe
installation concerned in such a
installationconcerned,insucha
waythatthetouchvoltage/time
safetyrequirementsare
respectedforanyleveloftouch
voltage(Vc). 35
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Maximumsafeduration(disconnectingtime)of
theassumedvaluesofACtouchvoltage(in
the assumed values of AC touch voltage (in
seconds)notexceeding32A:
Vc (V) 50<Vc 120 120<Vc 230 230<Vc 400 Vc >400
TNorIT 0.8 0.4 0.2 0.1
System
TT 0.3 0.2 0.07 0.04
36
18
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
37
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Theimpedanceoftheearthfaultloopconsistsmainly
inthetwoearthelectrodes(i.e.thesourceand
in the two earth electrodes (i e the source and
installationelectrodes)inseries.
Themagnitudeoftheearthfaultcurrentisgenerally
toosmalltooperateovercurrent relayorfuses,and
theuseofaresidualcurrentoperateddeviceis
essential.
essential
Protectionbyautomaticdisconnectionofthesupply
usedinTTsystemisbyRCD ofsensitivity:
50
I n RA istheresistanceoftheearthelectrodefortheinstallation
RA
38
19
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TNC
39
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
InallTNsystems,anyinsulationfaulttoearth
resultsinaphasetoneutralshort
results in a phase to neutral shortcircuit
circuit.
Highfaultcurrentlevelsallowtouseovercurrent
protectionbutcangiverisetotouchvoltages
exceeding50%ofthephasetoneutralvoltageat
thefaultpositionduringtheshortdisconnection
time.
time
TheuseofCB,fuses,andRCDs maybenecessary
onTNearthedsystems.
40
20
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
41
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Apermanentmonitoringoftheinsulationtoearth
mustbeprovided,coupledwithanalarmsignal(audio
must be provided coupled with an alarm signal (audio
and/orflashinglights,etc.)operatingintheeventofa
firstearthfault.
Duringaphasetoearthfault,thecurrentpassing
throughtheelectroderesistanceRnA isthevectorsum
of the capacitive currents in the two healthy phases
ofthecapacitivecurrentsinthetwohealthyphases.
TheuseofCB,fuses,andRCDs maybenecessaryon
ITearthedsystems
42
21
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Earthleakagedevicesarebasedontheprinciple
thattheamountofcurrententering
that the amount of current entering adevice
a device
shouldbeexactlythesameastheamountof
currentleaving thedevice.
Earthleakageprotectiondevicesaredesignedto
tripforfaultcurrentsbetween10and100mA and
forinterrupttimesbetween40and100
p
millisecondsafterafaultcurrentissensed.
Ithasbeengraduallyreplaced byResidueCurrent
Devices (RCD)suchasRCCB.
43
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
44
22
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Forregularhouses40A/63A,singlephaseor
dependsonsupplydemandandmainswitch
depends on supply demand and main switch
capacity,ELCB's sensitivityisnotexceeding
100mA.
Forheaterwater,itshouldpossesseparate
additionalELCB(otherthanno.1above)with
sensitivity is not exceeding 10mA is needed
sensitivityisnotexceeding10mAisneeded.
Forloadwhichhigherthan100A,3phases,
ELCB's sensitivitymustnotexceed100mA.
45
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
To load
fault
earth
Current Transformer
Trip
p coil Circuit Breaker
46
23
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
DuringnormaloperationthecurrentfromsupplyLflows
throughN1,totheloadandthenflowthroughN2before
returningtoN.
SincethenumberofturnsofN1andN2arethesame
Since the number of turns of N1 and N2 are the same
andthecurrentthroughthemisalsothesamethe
resultingfluxintheironcoreiszero.
However,ifthereisaleakagefromtheloadtothe
ground,acertainamountofcurrentwillflowtothe
ground.
AssuchcurrentthroughN1andN2willnotbethesame
resultinginsomemagneticfluxsettingupinthecore.
Thefaultsensingwindingwilltripthetrippingdeviceif
theleakagecurrentfallswithin10to100milliampere.
Atestcircuitconsistingofapushbuttonandatest
resistorisnormallyincludedintheELCBasshown.Its
functionistocreateanunbalancecurrentintheN1and
N2windings,andthecurrentflowthroughthetest
resistorisgreatenoughforthefaultsensingwindingto
tripthecircuitbreaker.
47
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TherearetwomainreasonswhyRCDsareused:
To p
provide additional and a higher
g level of p
protection than
that given by direct earthing, against electric shock and also
against fire risk caused by earth leakage currents. Where
fuses and miniature circuit breakers (MCBs) are the only
means of earth fault protection, it is possible for earth fault
currents to flow undetected and cause fire risk (or touch
voltage problems).
The use of an RCD will prevent the flow of a sustained
leakage current above the sensitivity of the RCD thus
greatly reducing shock and fire risk. All live conductors in
the protected circuits should be disconnected in the event
of earth leakage current flowing.
48
24
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
TermsassociatedwithRCDs:
RCCB:
ResidualCurrentCircuitBreakerusedindistributionboardstoprotectindividual
orgroupsofcircuits
RCBO:
ResidualCircuitBreakerwithovercurrent protection.Thisisacombined
MCB/RCDandprovidesoverload,shortcircuitandearthfaultprotectioninone
unit
SRCD:
SocketoutletwithcombinedRCD
PRCD:
ThisisaportableRCDunitwithaninbuiltplugtopandsocket
outlet
49
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Phase
LOAD
Detection Coil
Neutral
Relay
Test Button
50
25
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Test Resistor
LOAD
L1
L2
L3
Earthed
Neutral Metalwork
Detection Coil
Magnetic Core
51
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
26
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Asinglephase240V,15kW50Hzmotorcircuit
operatingat0.8powerfactorlaggingisprotectedbya
operating at 0.8 power factor lagging is protected by a
cartridgefusehavingblowingcurrentof110A.Afault
occursinthecircuitcausesacurrentof220amperesto
flowthroughtheearthcontinuitypath.Asaresultof
poorcontactduetoalocknutandbushconnectinga
steelconduittoametalbox,theresistanceofthis
conduitconnectionaloneis1.35.State:
a) whetherthefusewillrupture
b) theamountofheatproducedatthemetalbox
c) thedegreeofrisk,ifany,ofafiredeveloping
53
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Yes.Theratingcurrent:
15kW Sinceaccordingtoregulation
Since according to regulation
Ir = = 78.125 A D22,theprotectionisbya
240V 0.8
cartridgehavingafusingfactor
Fusingfactor: notexceeding1.5.Thenthe
maximumcurrentinthefaultis
110 A
FF = = 1.41 2.4x78.125A=187.5A.
78.125 A
I2R=(220)2 x1.35Ohms=65.34kW.
HighRisk
54
27
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Whatisavoltagesurge?
Avoltagesurgeisavoltageimpulseorwavewhich
issuperposedontheratednetworkvoltage.
55
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Voltagesurgeischaracterisedby:
Therisetime(t
Th i ti (tf)measuredins
) di
Thegradient(S)measuredinkV/s
Avoltagesurgedisturbsequipmentandcauses
electromagneticradiation.
Furthermore,thedurationofthevoltagesurge
(T)causesasurgeofenergy intheelectrical
circuitswhichislikelytodestroy the
equipment.
56
28
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
57
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Atmosphericvoltagesurges
Operatingvoltagesurges
Transientovervoltage atindustrialfrequency
Voltagesurgescausedbyelectrostatic
discharge
58
29
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Lightning risk.Between2,000and5,000stormsare
constantlyformingaroundtheearth.Thesestorms
constantly forming around the earth These storms
areaccompaniedbylightningwhichconstitutesa
seriousriskforbothpeopleandequipment.
Strokesoflightninghitthegroundatarateof30to
100strokespersecond.
Lightningaffectstransformers,electricitymeters,
householdappliances,andallelectricaland
electronicinstallationsintheresidentialsectorand
inindustry.
59
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
LightningdischargevaluesgivenbytheIEC
lightningprotectioncommittee:
li ht i t ti itt
Beyondpeak Currentpeak, Gradient, Totalduration Numberof
probability I(kA) S(kA/s) (s) discharges
P% n
95 7 9.1 0.001 1
50 33 24 0.01 2
5 85 65 1.1 6
60
30
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Asuddenchangeintheestablishedoperating
conditionsinanelectricalnetworkcauses
diti i l ti l t k
transientphenomenatooccur.
Thesearegenerallyhighfrequencyordamped
oscillationvoltagesurgewaves.
61
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Theopeningofprotectiondevices(fuse,circuit
breaker),andtheopeningorclosingofcontrol
), p g g
devices(relays,contactors,etc.).
Inductivecircuitsduetomotorsstartingand
stopping,ortheopeningoftransformers suchas
MV/LVsubstations.
Capacitivecircuitsduetotheconnectionof
capacitor banks to the network
capacitorbankstothenetwork.
Alldevicesthatcontainacoil,acapacitor ora
transformeratthepowersupplyinlet:relays,
contactors,televisionsets,printers,computers,
electricovens,filters,etc.
62
31
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Theseovervoltages havethesamefrequencyas
thenetwork(50,60or400Hz).
63
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Phase/frameorphase/earthinsulatingfaultsona
networkwithaninsulatedorimpedanceneutral,
network with an insulated or impedanceneutral
orbythebreakdownoftheneutralconductor.
Whenthishappens,singlephasedeviceswillbe
suppliedin400V insteadof230V.
Acable breakdown.Forexample,amedium
voltagecablewhichfallsonalowvoltageline.
g g
Thearcing ofahighormediumvoltageprotective
sparkgapcausingariseinearthpotentialduring
theactionoftheprotectiondevices.
64
32
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Inadryenvironment,electricalchargesaccumulate
andcreateaverystrongelectrostaticfield.
and create a very strong electrostatic field.
Forexample,apersonwalking oncarpetwith
insulatingsoleswillbecomeelectricallychargedtoa
voltageofseveralkilovolts.Ifthepersonwalksclose
toaconductivestructure,hewillgiveoffan
electricaldischargeofseveralamperesinavery
shortrisetimeofafewnanoseconds.
Ifthestructurecontainssensitiveelectronics,a
computerforexample,itscomponentsorcircuit
boardsmaybedamaged.
65
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Primary protectiondevices(protectionof
installationsagainstlightning).
i t ll ti i t li ht i )
Secondary protectiondevices(protectionof
internalinstallationsagainstlightning).
66
33
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Thepurposeofprimaryprotectiondevicesisto
protectinstallationsagainstdirectstrokesof
protect installations against direct strokes of
lightning.
Theycatchandrunthelightningcurrentintothe
ground.Theprincipleisbasedonaprotectionarea
determinedbyastructurewhichishigher thanthe
rest.
Therearethreetypesofprimaryprotection:
Lightningconductors
Overheadearthwires
ThemeshedcageorFaradaycage
67
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Thelightningconductoris
a tapered rod placed on
ataperedrodplacedon
topofthebuilding.Itis
earthedbyoneormore
conductors(oftencopper
strips).
68
34
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Thesewiresarestretchedoverthestructuretobe
protected.Theyareusedforspecialstructures:rocket
launchpads,militaryapplicationsandlightningprotection
cablesforoverheadhighvoltagepowerlines.
69
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Thisprincipleisusedfor
very sensitive buildings
verysensitivebuildings
housingcomputeror
integratedcircuit
productionequipment.
Itconsistsin
symmetrically multiplying
symmetricallymultiplying
thenumberofdownstrips
outsidethebuilding.
70
35
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Thesehandletheeffectsofatmospheric,
operating
ti orindustrialfrequencyvoltage
i d t i lf lt
surges.
Theycanbeclassifiedaccordingtotheway
theyareconnectedinaninstallation:serialor
parallel p
p protection.
71
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Thisisconnectedinseriestothepowersupply
i f th t t b t t d
wiresofthesystemtobeprotected.
72
36
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Transformers
Theyreducevoltagesurgesbyinductoreffectandmake
They reduce voltage surges by inductor effect and make
certainharmonicsdisappearbycoupling.This
protectionisnotveryeffective.
Filters
Basedoncomponentssuchasresistors,inductance
coilsandcapacitorstheyaresuitableforvoltagesurges
causedbyindustrialandoperationdisturbance
db i d i l d i di b
correspondingtoaclearlydefinedfrequencyband.This
protectiondeviceisnotsuitableforatmospheric
disturbance.
73
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Waveabsorbers
Theyareessentiallymadeupofairinductancecoils
whichlimitthevoltagesurges,andsurgearresters
whichabsorbthecurrents.Theyareextremely
suitableforprotectingsensitive electronicand
computingequipment.
74
37
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Networkconditionersandstaticuninterrupted
powersupplies(UPS)
power supplies (UPS)
These devices are essentially used to protect highly
sensitive equipment, such as computer equipment,
which requires a high quality electrical power supply.
They can be used to regulate the voltage and frequency,
stop interference and ensure a continuous electrical
power supply even in the event of a mains power
failure (for the UPS).
UPS)
On the other hand, they are not protected against
large, atmospheric type voltage surges against which it
is still necessary to use surge arresters.
75
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Theparallelprotectionisadaptedtoany
i t ll ti l l Thi t f
installationpowerlevel.Thistypeof
overvoltage protectionisthemostcommonly
used.
76
38
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Maincharacteristics
Theratedvoltageoftheprotectiondevicemust
The rated voltage of the protection device must
correspondtothenetworkvoltageattheinstallation
terminals.
Whenthereisnovoltagesurge,aleakagecurrent
shouldnotgothroughtheprotectiondevicewhichison
standby.
Whenavoltagesurgeabove theallowablevoltage
threshold of the installation to be protected occurs the
thresholdoftheinstallationtobeprotectedoccurs,the
protectiondeviceabruptlyconductsthevoltagesurge
current totheearth bylimitingthevoltagetothe
desiredprotectionlevel,Vp.
77
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
Whenthevoltagesurgedisappears,theprotection
devicestopsconductingandreturnstostandby
device stops conducting and returns to standby
withoutaholdingcurrent.ThisistheidealU/I
characteristiccurve:
Theprotectiondeviceresponsetime(tr)mustbeasshort
aspossibletoprotecttheinstallationasquicklyas
possible.
Theprotectiondevicemusthavethecapacitytobeable
Th t ti d i th th it t b bl
toconducttheenergycausedbytheforeseeablevoltage
surgeonthesitetobeprotected.
Thesurgearresterprotectiondevicemustbeableto
withstandtheratedcurrent,In.
78
39
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
(1)Voltagelimiters
They are used in MV/LV/
substations at the
transformer output, in
IT earthing scheme.
They can run voltage
surges to the earth,
especially industrial
frequency surges.
79
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
(2)LVsurgearresters
Lowvoltagesurgearresterscomeintheformof
modulestobeinstalledinsideLVswitchboard.
Theyensuresecondaryprotectionofnearby
elementsbuthaveasmallflowcapacity.
Someareevenbuiltintoloadsalthoughthey
Some are even built into loads although they
cannotprotectagainststrongvoltagesurges.
80
40
28/11/2012
BEX42803/BEF33203/BEE4213 UtilisationofElectricalEnergy
(3)Lowcurrentsurgearresters
Theseprotecttelephone orswitchingnetworks
againstvoltagesurgesfromtheoutside
(lightning),aswellasfromtheinside(polluting
equipment,switchgearswitching,etc.).
Lowcurrentvoltagesurgearrestersarealso
Low current voltage surge arresters are also
installedindistributionboxesorbuiltinto
loads.
81
41