BALDOR -RELIANCE FRAME HP TYPE PHASE HERTZ RPM

MODEL NUMBER

KGPEM50804L-2340 5012 750 P 3 60 1792

VOLTS AMPS DUTY AMBoC INSUL S.F. NEMA DESIGN

2300 / 4000 167 / 96.0 CONT 40 F 1.15 ---

CODE ENCL. ROTOR WK2 STATOR RES.@25oC


LETTER (lb-ft2) OHMS (BETWEEN LINES) TYPICAL
DATA
G TEFC 350 0.12127 / 0.36380

PERFORMANCE

LOAD HP AMPERES RPM % %


POWER FACTOR EFFICIENCY

NO LOAD 0 25.7 1800 6.0 0.0


1/4 188 36.2 1798 60.4 92.3
2/4 375 53.2 1796 79.7 95.2
3/4 563 73.6 1794 85.8 95.8
4/4 750 96.0 1792 87.8 95.8
5/4 938 120.1 1789 87.9 95.6
6/4 1125 146.5 1787 87.0 95.1

SPEED TORQUE

RPM TORQUE TORQUE AMPERES


% FULL LOAD LB-FT

LOCKED ROTOR 0 107 2351 601.4


PULL UP 144 93 2043 596.6
BREAKDOWN 1761 250 5486 310.6
FULL LOAD 1792 100 2198 96.0
AMPERES SHOWN FOR 4000 VOLT CONNECTION(S). IF OTHER VOLTAGE CONNECTIONS ARE AVAILABLE, THE AMPERES WILL
VARY INVERSELY WITH THE VOLTAGE.

CATALOG NO EM50804L-2340 RERATE #10

REVISION 0
DR. BY C. Evans
CK. BY D. Harrell A-C MOTOR VGPM804E4K
APP. BY J. Ernest PERFORMANCE
DATE 4/14/2016 ISSUE DATE: 4/14/2016
REL M.N. KGPEM50804L-2340 HERTZ 60 AMBoC 40 CODE LETTER G
FRAME 5012 RPM 1792 INSUL F ENCLOSURE TEFC
HP 750 VOLTS 2300 / 4000 S.F. 1.15 STATOR RES.@25oC 0.12127 / 0.36380
TYPE P AMPS 167 / 96.0 NEMA DESIGN --- OHMS (BETWEEN LINES)
2 2
PHASE 3 DUTY CONT ROTOR WK (lb-ft ) 350 TYPICAL DATA

6000 700

5400 630
1

4800 560

4200 490
TORQUE IN LB-FT AT 4000 VOLTS (2)

3600 420
AMPS AT 4000 VOLTS (1)

3000 350

2400 280 2

1800 210

1200 140

600 70

0 0
0 180 360 540 720 900 1080 1260 1440 1620 1800
SPEED IN RPM
AMPERES SHOWN FOR 4000 VOLT CONNECTION, IF OTHER VOLTAGE CONNECTIONS ARE AVAILABLE, THE AMPERES WILL VARY
INVERSELY WITH THE VOLTAGE. REVISION 0
DR. BY C. Evans A-C MOTOR
CK. BY D. Harrell VGPM804E4K
APP. BY J. Ernest
PERFORMANCE
DATE 4/14/2016 CURVES ISSUE DATE: 4/14/2016
REL M.N. KGPEM50804L-2340 HERTZ 60 AMBoC 40 CODE LETTER G
FRAME 5012 RPM 1792 INSUL F ENCLOSURE TEFC
HP 750 VOLTS 2300 / 4000 S.F. 1.15 STATOR RES.@25oC 0.12127 / 0.36380
TYPE P AMPS 167 / 96.0 NEMA DESIGN --- OHMS (BETWEEN LINES)
2 2
PHASE 3 DUTY CONT ROTOR WK (lb-ft ) 350 TYPICAL DATA

1800 100 150


3

1798 90 135 4

1796 80 120

1794 70 105
PF (2) AND EFF (3) . IN PERCENT

1792 60 90 2
SPEED IN RPM (4)

AMPS (1)

1790 50 75

1788 40 60

1786 30
45

1784 20 30

1782 10
RATED LOAD

15

1780 0
0
0 120 240 360 480 600 720 840 960 1080 1200
HORSEPOWER

AMPERES SHOWN FOR 4000 VOLT CONNECTION, IF OTHER VOLTAGE CONNECTIONS ARE AVAILABLE, THE AMPERES WILL VARY
INVERSELY WITH THE VOLTAGE. REVISION 0
DR. BY C. Evans A-C MOTOR
CK. BY D. Harrell VGPM804E4K
APP. BY J. Ernest
PERFORMANCE
DATE 4/14/2016 CURVES ISSUE DATE: 4/14/2016
REL M.N. KGPEM50804L-2340 HERTZ 60 AMBoC 40 CODE LETTER G
FRAME 5012 RPM 1792 INSUL F ENCLOSURE TEFC
HP 750 VOLTS 2300 / 4000 S.F. 1.15 STATOR RES.@25oC 0.12127 / 0.36380
TYPE P AMPS 167 / 96.0 NEMA DESIGN --- OHMS (BETWEEN LINES)
2 2
PHASE 3 DUTY CONT ROTOR WK (lb-ft ) 350 TYPICAL DATA

THERMAL LIMIT CURVES


1000
900
800 Motor Initial Temperature:
700 40C Cold 120C Hot
600
500
400

300
Overload

200

100
90
80
70
60
Breakdown

50
Time (Seconds)

40
Acceleration
30 Locked Rotor

20 Cold
Hot

10
9
8
7
6
5
4

3
Rated Voltage

1
0 100 200 300 400 500 600 700
Percent Full Load Current
REVISION 0
DR. BY C. Evans
CK. BY D. Harrell A-C MOTOR VGPM804E4K
APP. BY J. Ernest PERFORMANCE
DATE 4/14/2016 ISSUE DATE: 4/14/2016
REL M.N. KGPEM50804L-2340 HERTZ 60 AMBoC 40 CODE LETTER G
FRAME 5012 RPM 1792 INSUL F ENCLOSURE TEFC
HP 750 VOLTS 2300 / 4000 S.F. 1.15 STATOR RES.@25oC 0.12127 / 0.36380
TYPE P AMPS 167 / 96.0 NEMA DESIGN --- OHMS (BETWEEN LINES)
2 2
PHASE 3 DUTY CONT ROTOR WK (lb-ft ) 350 TYPICAL DATA

EQUIVALENT CIRCUIT DATA


(Per Unit, Per Phase)

FULL LOAD LOCKED ROTOR


R1 0.00832 X1 0.07328 R1 0.00673 X1 0.06474
R2 0.00398 X2 0.11638 R2 0.02011 X2 0.06683
RM 0.08720 XM 3.07308 RM 0.17270 XM 2.73523
BASE OHMS 28.59700 BASE VOLTS 2309
SC Time Constant 0.088 Sec X" = XS 0.13157
OC Time Constant 2.126 Sec X/R Ratio 13.18

R1 X1 X2

RM
R2/SLIP
XM

Parallel Equivalent
FL RM' pu 108.3879 LR RM' pu 43.49339
FL XM' pu 3.07555 LR XM' pu 2.74613
R1 = Stator dc resistance X1 = Stator leakage reactance
R2 = Rotor resistance X2 = Rotor leakage reactance
RM = Core loss resistance XM = Magnetizing reactance
SC = Short circuit FL = Full load
OC = Open circuit LR = Locked rotor
X" = XS = Subtransient reactance
REVISION 0
DR. BY C. Evans A-C MOTOR
CK. BY D. Harrell VGPM804E4K
APP. BY J. Ernest
PERFORMANCE
DATE 4/14/2016 CURVES ISSUE DATE: 4/14/2016
REL M.N. KGPEM50804L-2340 HERTZ 60 AMBoC 40 CODE LETTER G
FRAME 5012 RPM 1792 INSUL F ENCLOSURE TEFC
HP 750 VOLTS 2300 / 4000 S.F. 1.15 STATOR RES.@25oC 0.12127 / 0.36380
TYPE P AMPS 167 / 96.0 NEMA DESIGN --- OHMS (BETWEEN LINES)
2 2
PHASE 3 DUTY CONT ROTOR WK (lb-ft ) 350 TYPICAL DATA

Recommended Winding and Bearing Temperatures

Stator Winding Class B Class F

Maximum Running Total Temperature 130 C 155 C


Alarm Total Temperature 135 C 160 C
Trip Total Temperature 145 C 170 C

Sleeve Bearings - Oil Lubricated Bearing Oil

Typical Running Total Temperature 93 C 60 C


Alarm Total Temperature 96 C 70 C
Trip Total Temperature 98 C 75 C

Anti-Friction Bearings - Grease Lubricated Bearing Grease

Typical Running Total Temperature 90 C 80 C


Alarm Total Temperature 110 C 100 C
Trip Total Temperature 120 C 110 C

Recommended Vibration Settings for Standard Motors

Speed (rpm) Shaft Vibration (mils) Bracket Vibration (mils)


Alarm Shutdown Alarm Shutdown
3600 2.50 3.00 1.00 1.50
1800 3.00 3.50 2.00 2.50
1200 3.00 3.50 2.00 2.50
900 & Lower 3.00 3.50 2.00 2.50
Bracket Vibration
(in/sec pk)
Alarm Shutdown
All Speeds 0.20* 0.30*
* 0 to 1000 Hz Spectrum

REVISION 0
DR. BY C. Evans A-C MOTOR
CK. BY D. Harrell VGPM804E4K
APP. BY J. Ernest
PERFORMANCE
DATE 4/14/2016 CURVES ISSUE DATE: 4/14/2016
REL M.N. KGPEM50804L-2340 HERTZ 60 AMBoC 40 CODE LETTER G
FRAME 5012 RPM 1792 INSUL F ENCLOSURE TEFC
HP 750 VOLTS 2300 / 4000 S.F. 1.15 STATOR RES.@25oC 0.12127 / 0.36380
TYPE P AMPS 167 / 96.0 NEMA DESIGN --- OHMS (BETWEEN LINES)
2 2
PHASE 3 DUTY CONT ROTOR WK (lb-ft ) 350 TYPICAL DATA

A-C MOTOR
CONNECTION DIAGRAM
STANDARD 6 LEAD ( DELTA / STAR { Y } CONNECTED )
DUAL VOLTAGE ( LOW VOLTS / HIGH VOLTS )

DELTA STAR { Y }
T1
T6 T1

T4
T6 T5

T3 T4
T5 T2 T3 T2

LOW VOLTS HIGH VOLTS

( DELTA ) ( STAR )
T6 T4 T5
T6 T4 T5

T1 T2 T3 T1 T2 T3
L1 L2 L3 L1 L2 L3
LOW VOLTS LINE HIGH VOLTS

( N.P. 1767-CC )

REVISION 0
DR. BY C. Evans A-C MOTOR
CK. BY D. Harrell VGPM804E4K
APP. BY J. Ernest
PERFORMANCE
DATE 4/14/2016 CURVES ISSUE DATE: 4/14/2016
RESISTANCE TEMPERATURE
CONNECTION DIAGRAM

WINDING
100 OHM @ 0C

BEARING
N/A
RTD
BLACK
OR
WHITE
RED

TD1 TD2 TD3

DR. BY Chris Stockton


CK. BY Chris Stockton A-C MOTOR G30_GP
APP. BY Joe Hillhouse AUXILARY SHEET 1 OF 2
DATE 3/5/2014 CONNECTIONS
SPACE HEATER CONNECTION

VOLTS 120/240 AMPS 2.9/1.46 WATTS 350/350


PHASE 1 HZ. 60

H1 H2 H3 H4

HEATER CONNECTIONS

LOW VOLTAGE - PARALLEL


L1 - H1 & H2
L2 - H3 & H4

HIGH VOLTAGE - SERIES


L1 - H1
L2 - H2
CONNECT H3 TO H4

DR. BY Chris Stockton A-C MOTOR


CK. BY Chris Stockton G30_GP
APP. BY Joe Hillhouse AUXILARY SHEET 2 OF 2
DATE 3/5/2014 CONNECTIONS
8 7 6 5 4 3 2 1

616158-807

GENERAL PURPOSE STOCK ALTERNATING CURRENT MOTORS


ENCLOSURE: TOTALLY ENCLOSED SQUIRREL-CAGE INDUCTION COOLING: FAN COOLED F
F MOUNTING: FOOT 1800 RPM MAX ANTI-FRICTION BEARINGS
FRAME G5012L ENGLISH HARDWARE
(FIELD CONVERTIBLE COUPLE/BELT BELT/COUPLE)
INCLUDES G5011L FRAME MOUNTING HOLES OVERSIZE MAIN CONDUIT BOX

90.97 29.64

19.00 17.50 (2)

E E
9.50 9.48 16.50 (4) 16.19

.63

17.25
(2)
AIR INLET (9)
(5) (9) 8.25 19.19
(4)

D
40.27 D
8.00
KEY 1.00
SQUARE

(6) 34.39
8.60
5.31
+.000
4.125 - .001
3.06
10.00 +.00
12.50 - .06

C
10.75 60 C

4.12 (7)
4.12 (8)
(3)
8.94 15/16 FOOT MTG HOLES 1.39
W/ 1.75 SPOTFACED
3.07
2.00 (1) (1)1.75 6.07

11.30 20.00 19.50 10.00 10.00

36.00 26.00

40.00
B B

NOTES:
1. (4) 3/4-10 JACKSCREW HOLES
2. 2.0 NPT FOR WINDING TEMPERATURE DETECTOR LEADS
3. 11/32 DOWEL PIN PILOT HOLES, 1 HOLE EACH FOOT WEIGHT (LBS): 6600 (MAXIMUM)
4. 3/4 NPT FOR MOTOR SPACE HEATER LEADS DIMENSIONS ARE IN INCHES
5. WALL OR OBSTRUCTION MUST NOT ENCROACH ON AIR INLET SPACE
6. CUSTOMER TO PROVIDE HOLE FOR MOTOR POWER LEADS
7. TWO GROUND PADS DIAGONALLY OPPOSITE EACH OTHER, TAPPED 1/2-13
8. 1/8 NPT PROVISIONS FOR BEARING TEMPERATURE DETECTOR LEADS.
9. GREASE POINT
A
A

616158-807
CONDUIT BOX LOCATED ON OPPOSITE SIDE WHEN F-2.
IF MOUNTING CLEARANCE DETAILS ARE REQUIRED, CONSULT FACTORY. CUSTOMER IS RESPONSIBLE FOR DETERMINING THAT BALDOR'S PRODUCT WILL PERFORM SUITABLY IN THE INTENDED APPLICATION

MAXIMUM PERMISSIBLE SHAFT RUNOUT WHEN MEASURED AT END OF CATALOG #'S REV. DESC: OMITTED TO 5 INCH DIAMETER FROM SHAFT EXT. NOTE
STANDARD SHAFT EXTENSION IS .003" T.I.R. REV: D VERSION: 04 REVISED: 11:13:55 11/25/2015 TDR: 000000951349
M50804L-4 MODEL NO. 616158-807 REF:
616158-807
M50804L - 2340 G5012L,TEFC,L/N,CONV.,1800,A/F,F1,19X19X12,U=4.125,XBA=19.50
BY: RSNGKW Material: C
8 7 6 5 4 3 2 1

You might also like