You are on page 1of 27

Los Angeles Fire Department

CHIEF’S
REGULATION #4
PROCEDURES
Revision 02-28-06
LOS ANGELES FIRE DEPARTMENT

CHIEF’S REGULATION NO. 4

TESTING OF FIRE PROTECTION EQUIPMENT

TABLE OF CONTENTS

SECTION 1 – SCOPE ...........................................................................................................................R4-3

SECTION 2 – DEFINITIONS .................................................................................................................R4-3

SECTION 3 – GENERAL REQUIREMENTS.........................................................................................R4-6

A. Testing Intervals:........................................................................................................R4-6
B. Fire Department Notification: ....................................................................................R4-7
C. General Test Information:..........................................................................................R4-7
D. Repair: .........................................................................................................................R4-8
E. Fire Hose Connections: .............................................................................................R4-8
F. Gauges: .......................................................................................................................R4-8
G. System Tagging:...........................................................................................................R4-8

SECTION 4 – GENERAL TEST PROCEDURES ..................................................................................R4-9

A. Central Station Signaling Systems:..........................................................................R4-9


B. Communication Systems (Firefighter and Building): .............................................R4-9
C. Elevators, Automatic (Phase I and II): ....................................................................R4-10
D. Emergency and Standby Power Systems:.............................................................R4-12
E. Fire Escape Assemblies: .........................................................................................R4-12
F. Fire Hydrants (Private) .............................................................................................R4-12
G. Fire Protection Assemblies: Automatic Closing ...................................................R4-13
H. Fire Protective Signaling Systems: ........................................................................R4-14
I. Fire Pumps:...............................................................................................................R4-15
J. Gas Detection System: ............................................................................................R4-15
K. Pressure Regulating Valves: ...................................................................................R4-16
L. Refrigerant Discharge Systems: .............................................................................R4-17
M. Smoke Management Systems:................................................................................R4-17
N. Sprinkler Systems, Automatic: ...............................................................................R4-19
O. Standpipe Systems and Fire Pump fuction Test:....................................................R4-20

SECTION 5 – APPLICATION............................................................................................................R4-23

R4-2
SECTION 1 – SCOPE approving equipment, an installation, or a
The provisions of this regulation shall govern procedure.
the minimum requirements for the periodic 7. Automatic Closing Device:
testing and repair of Fire Protection Equipment. A device attached to a fire protection assembly
The types of equipment addressed by this that allows the assembly to close when
regulation include, but are not limited to activated as a result of either heat, smoke, or
Automatic Fire Sprinkler Systems, Central other products of combustion.
Station Signaling Systems, Elevator Emergency 8. Automatic Fire Extinguishing System:
Service, Emergency and Standby Power An approved self-contained system of devices
Systems, Fire Department Communication and and equipment, which automatically detects a
Emergency Voice Alarm Signaling Systems, Fire fire and discharges an approved fire
Escape Assemblies, Fire Hydrants, (Private) extinguishing agent onto or in the area of a fire.
Fire Protection Assemblies, Fire Protective As regulated by Division 5 and 141 of the Los
Signaling Systems, Fire Pumps, Gas Detection Angeles Fire Code (Except Automatic Sprinkler
Systems, Pressure Regulating Valves, Systems).
Refrigerant Discharge Systems, Smoke 9. Automatic Fire Sprinkler Systems:
Management Systems, and Standpipe Systems. An approved integrated system of piping, valves,
The intent is to ensure that this equipment is devices, automatic sprinkler heads and water
maintained in proper operating condition supply which automatically detects a fire and
according to proper installation, and in discharges water in the area of the fire.
accordance with generally accepted practices
and the code in effect at the time of installation. (a) Dry pipe: A system containing air or
It is not the intent of this regulation to limit or nitrogen under pressure, the release of
restrict the use of other testing or maintenance which permits the water pressure to open
programs that provide an equivalent level of a valve known as a dry pipe valve. The
system integrity and performance as detailed in water then flows into the piping system
this regulation. and out the opened sprinklers.
(b) Pre-action: A system containing air that
may or may not be under pressure, with a
SECTION 2 – DEFINITIONS supplemental detection system installed
1. Addressable System: in the same areas as the sprinklers.
A Fire Alarm System with discrete identification Actuation of the detection system opens
that can have its status individually identified, or the valve that allows water to flow into the
that is used to individually control other piping and to be discharged from any
functions. sprinklers that are open.
2. Alarm Signal: (c) Deluge: A system employing open
A signal initiated by a fire alarm initiating device sprinklers attached to a piping system
indicating an emergency requiring immediate connected to a water supply through a
action, such as a signal indicative of fire. valve that is opened by the operation of a
3. Analog System: detection system installed in the same
A system that transmits and receives signals areas as the sprinklers. When the valve
indicating varying degrees of condition as opens, water flows into the system and
contrasted with a conventional initiation device, discharges water from all sprinklers
which can only indicate an on/off condition. attached to the piping.
4. Annunciator:
A unit containing two or more indicator lamps, 9. Automatic Initiating Device:
alphanumeric displays, or other equivalent A device designed to detect the presence of fire
means in which each indication provides status or smoke and initiate immediate action.
information about a circuit, condition, or location. 10. Building Description:
5. Approved: Detailed information necessary to identify the
Acceptable to the "authority having jurisdiction." size, use, occupancy type, and construction type
6. Authority Having Jurisdiction: of a building.
The "authority having jurisdiction" is the 11. Building Fire Control Room/Station:
organization, office, or individual responsible for A specific room or area designated as the

R4-3
principal point of annunciation for the Fire after failure of the normal electrical
Protective Signaling System and all associated supply.
equipment, systems and devices.
12. Central Station Signaling System: [1] Electrically driven fire pumps
A system consisting electrically operated circuits [2] Smoke management systems
and equipment, which transmits alarms, trouble [3] Elevators designated for fire
and supervisory signals automatically to a department and emergency use
approved Central Station Service having [4] Lighting circuits supplying elevator
competent and experienced servers and operators lobbies, Building Fire Control
who, upon receipt of a signal shall take such Room/Station, generator, and fire
action as required by the code. Such service is to pump rooms
be controlled and operated by a person, firm, or [5] Exterior window washing equipment,
corporation whose business is to provide, including equipment listed in
maintain, and monitor supervised fire protection Emergency Power Systems
systems.
13. Certification: NOTE: Not all buildings have this
A systematic program using approved testing and equipment. Check single line diagram for
inspection procedures of the accepted systems, proper equipment.
which allows the certified tester to verify that a fire
protection system complies with all the 17. Fire Department Connection:
requirements of the code as installed in A connection through which the Fire Department
accordance with the code in effect at the time if can pump water into a Standpipe or Automatic
installation. Sprinkler System.
14. Elevator, Automatic: 18. Fire Escape Assembly:
Elevators with automatic operation and power- A secondary exit attached to the exterior wall of
operated hoistway doors and equipped with a building that is two or more stories in height
firefighter Emergency service. and which provides emergency egress from the
15. Elevator Lobby Locking System: building. Fire escape assemblies shall include
An approved fail-safe method of locking elevator stairs, railings, landings, ladders and all
lobby doors leading out of an elevator lobby. associated safety equipment.
16. Emergency and Standby Power 19. Fire Hydrant (Private):
Systems: A connection to a water main for the purpose of
Special electrical wiring and equipment, which supplying water to fire hoses or other fire
are required to be operational during protection apparatus.
interruptions of the normal electrical supply to 20. Fire Protection Assembly, Automatic
the building, classified as follows: Closing:
A rated fire assembly, which is maintained in a
(a) Emergency Power System: The normally open position including all required
wiring, fixtures, equipment and hardware, anchorage, frames, sills, and is
luminaries in or on a building, which are equipped with an automatic closing device.
required to be automatically energized 21. Fire Protection Assembly, Self-closing:
from an alternate on-site electrical A rated fire assembly, which is maintained in a
supply within 10 seconds after failure of normally closed position and is equipped with an
the normal electrical supply. approved device to ensure closing and latching
after having been opened for use.
[1] Exit signs and exit illumination 22. Fire Protective Signaling System:
[2] Elevator car lighting A system of electrical devices and circuits, or
[3] Fire protective signaling systems mechanical devices, installed, arranged and
maintained to monitor and transmit, or emit, an
(b) Standby Power System: The part of audible and/or visual signal indicating an
the normal electrical system which is emergency requiring immediate action to
required to be automatically transferred safeguard life and property from fire.
to, and energized from, an alternate on- 23. Fire Pump:
site electrical supply, within 60 seconds An assembly that provides water flows and

R4-4
pressure to Fire Protection Equipment. The fire occupancy and is subject to the provisions of
pump assembly includes the water supply, Title 24 of the California Code of Regulations
suction and discharge piping, valves, pump and and Division 118 of the Los Angeles Fire Code.
pump driver, fire pump controller, and all [Such building will generally have been
auxiliary equipment appurtenant thereto. constructed after July 1, 1974.]
24. Fire Pump Controller: 30. Maintenance:
The cabinet, motor, starter, circuit breaker and Repair and service, including periodically
disconnect switch, and other control devices for recurrent inspections and tests, required to keep
the control of electric motors and internal the Fire Protection Equipment in operative
combustion engines that drive fire pumps. condition at all times.
25. Firefighter Communication Systems: 31. Manual Pull Station:
A manually operated device used to initiate an
(a) Fire Department Communication alarm to a fire protective signaling system.
System: A two-way sound-powered 32. Pressure Regulating Device:
telephone system capable of A device designed for the purpose of reducing,
communicating between the building fire regulating, controlling, or restricting water
control room/station and all required pressure. Examples include pressure reducing
locations. valves, pressure control valves, and pressure
(b) Emergency voice Alarm Signaling restricting devices.
System: A one-way system providing 33. Refrigerant Discharge System:
communication between the building fire A system designed for manual discharge of a
control room/station and all areas of the refrigerant agent into the atmosphere or a sewer
building where provided. system.
(c) Required Telephone: A telephone for 34. Sequence of Operation:
fire department use with controlled An approved series of functions to the Fire
access to the public telephone system. Protection Systems of a building caused by the
initiation of a fire alarm initiating device.
26. Foam-Water Sprinkler System: (See Figure No. 1 in Section 4.)
A foam-water sprinkler system is a special 35. Shall:
system that is pipe connected to a source of Indicates a mandatory requirement.
foam concentrate and to a water supply and 36. Should:
equipped with appropriate discharge devices for Indicates a recommendation or that which is
discharging an extinguishing agent over the advised but not required.
area to be protected.
27. Gas Detection Systems: 37. Smoke Management Systems:
A system with all associated equipment and
devices capable of continuous monitoring for the (a) Airflow Method: A method of
presence of a hazardous gas, and containing an controlling smoke from migrating
audible alarm capable of alerting occupants that through fixed openings between smoke
a hazardous atmosphere exists. control zones using high air velocity
28. High-Rise Building, Existing: through the opening(s) towards the fire
A building more than 75 feet (23m) in height. zone of origin.
Building height shall be measured from the (b) Building Emergency Smoke
lowest level of Fire Department access to the Evacuation System: A ventilation
floor of the highest level used for human system capable of providing exhaust
occupancy and is subject to the provisions of from specified areas of a building at a
Title 24 of the California Code of Regulations. rate of not less than six changes of air
[Such building will generally have been per hour and releasing directly to the
constructed prior to July 1, 1974.] outside atmosphere without re-
29. High-Rise Building, New: circulating exhaust to other areas of the
A building more than 75 feet (23m) in height. building.
Building height shall be measured from the (c) Exhaust Method: A method of
lowest level of Fire Department access to the controlling smoke in large spaces, such
floor of the highest level used for human

R4-5
as malls and atria through the use of reducers.
mechanical smoke removal systems. (d) Combined: A system of piping directly
(d) Mechanically Ventilated Smoke-proof connected to a water supply which
Enclosure: An enclosed stairway with serves 2½-inch hose outlets equipped
vestibules equipped with a ventilation with 2½-inch by 1½-inch reducers for
system designed to maintain a smoke- use by Fire Department or trained
free atmosphere. personnel and also supplies water to an
(e) Pressurization Method: A method of Automatic Sprinkler System.
controlling smoke by containing it within (e) Class H: A standpipe system directly
the zone of fire origin by maintaining a connected to a water supply equipped
minimum 0.05 inch water gauge positive with 1½-inch hose outlets with hose and
pressure differential between adjacent nozzle located on two sides of a
zones and the zone of fire origin. helicopter landing site intended for use
(f) Pressurized Stair-shaft Ventilation by Fire Department or trained personnel
System: An enclosed stairway in fighting fires on helicopter landing
equipped with a ventilation system sites.
designed to maintain a uniform air
velocity discharging to the outside 39. Supervisory Signal:
atmosphere while maintaining a positive A signal is indicating the need for action in
pressure in the stair-shaft relative to the connection with an abnormal condition of a Fire
adjacent areas during fire conditions. Protection System.
40. System Description:
38. Standpipe Systems: The concise and approved description of a
A wet or dry system of piping, valves, hose system, equipment or device as described by
outlets, and allied equipment installed in a the Manufacturer's Operating Manual.
building or structure with outlets located in such 41. Trouble Signal:
a manner that water can be discharged through A signal initiated by the Fire Alarm System,
hose and nozzles. Standpipe systems are indicative of a fault or abnormal condition of a
classified as follows: monitored circuit or component.

(a) Class I: A standpipe system with or


without a direct connection to a water SECTION 3 – GENERAL REQUIREMENTS
supply equipped with 2½-inch hose A. Testing Intervals:
outlets for use by Fire Department or
trained personnel. (1) Yearly:
(b) Class II: A standpipe system directly Tests of the following systems, equipment, and
connected to a water supply and equipped devices shall be conducted at least each year:
with 1½-inch hose outlets with hose and
nozzle intended for use by building (a) All Buildings
occupants.
[1] Central Station Signaling
Systems.
[2] Elevators, Automatic, Phases I
(c) Class III Combination: A combination and/or II.
standpipe system directly connected to [3] Emergency and Standby Power
a water supply and equipped with both Systems.
1½-inch hose outlets with hose and [4] Emergency Voice Alarm Signaling
nozzle intended for use Systems.
by building occupants and 2½-inch [5] Fire Department Communication
hose outlets for use by Fire Systems.
Department or trained personnel. Hose [6] Fire Escape Assemblies.
connections for Class III Systems may be [7] Fire Hydrants (Private).
made through 2½-inch hose valves with [8] Fire Protective Signaling
easily removable 2½-inch by 1½-inch

R4-6
Systems. fire protection equipment or system
[9] Fire Pumps. that was determined to be inoperable.
[10] Gas Detection Systems. Subsequently, written documentation
[11] Pressure Regulating Valves shall be submitted to the Chief within
(Maintenance Test Only). seven working days on approved Fire
[12] Smoke Management Systems. Department forms.
[13] Pre-action, Deluge, Dry pipe and (3) When it is determined that the fire
Foam valves of Automatic protection equipment, system, or
Sprinkler Systems (Trip Test device is operable, the test person
Only). shall attest to its condition to the Chief
using approved Fire Department
forms within seven working days after
(b) Buildings Over 75 Feet (23m) in initial test or retest.
Height (high-rise Buildings)
C. General Test Information:
[1] Fire Protection Assemblies, (1) Notification:
Automatic Closing (Sections 4-G-
1 through 8). (a) Notify all concerned agencies prior to
and at the conclusion of all testing of
(2) Every Five Years: all supervised fire protection
Tests of the following systems, equipment and equipment, systems, or devices.
devices shall be conducted at least once every (b) Notify all building occupants prior to,
five years: during and at the conclusion of all
testing of all supervised fire
(a) All Buildings protection equipment, systems, or
devices, which may cause concern to
[1] Fire Protection Assemblies, such occupants.
Automatic Closing.
[2] Refrigerant Discharge Systems. (2) Fire/Life Safety System Description
[3] Sprinkler Systems. Procedures: Used to determine the
[4] Standpipe Systems. status of a system as intended
according to the approved design
[5] Pressure Regulating Valves (Flow
standard for that particular system,
Test).
equipment or device as may be
necessary to carry out the purpose
(3) The Chief has the authority to require
and intent of this regulation. Building
a test at shorter intervals when an
owners shall submit a fire life safety
inspection by the Chief indicates there
system description manual to the Fire
is substantial reason to believe that
Department for approval. The Chief
the equipment, system, or device
shall be consulted and approval
would fail to operate properly in an
obtained for any alternative programs
emergency.
or procedures.
(3) Fan Motors: When testing systems,
B. Fire Department Notification:
equipment, or devices that will
activate fans of emergency smoke
(1) The Chief shall be notified by the
management systems, determine
concerned building owner or owner's
proper automatic operation by
agent at least two working days prior
actuation of each type of device in
to the performance of any required
each zone, then disconnect power to
test or retest in order that the Chief or
fans and continue testing. Constant
his representative may observe the
on/off operation of fans could damage
test.
motors. At conclusion of testing,
(2) At the conclusion of the test, the Chief
return fan motors to their normal
shall be notified within 24 hours of any
mode.

R4-7
(4) Electrical Thermal Links: Test Standard hose coupling screw threads
electrical thermal links for continuity as specified in NFPA - 1963,
only. "Standard for Screw Threads and
(5) Fire Pumps: When testing water flow Gaskets for Fire Hose Connection,"
alarms or pressure regulating devices unless approved by the Chief.
on systems equipped with fire pumps,
fire pumps may be placed in the on
position to keep pumps from cycling (2) All Fire Department inlets and outlets
on and off. At the conclusion of the shall be equipped with approved plugs or
test, return pumps to the automatic caps.
mode.
F. Gauges:
Gauges shall be replaced when defective or
every 5 years. Gauges shall tested by
D. Repair: comparison with a calibrated gauge. Gauges not
When it is determined that any fire protection accurate to within 3 percent of the full scale
equipment, system, or device is inoperable or shall be re-calibrated or replaced.
defective, the owner or the owner’s agent shall
commence repairs of the deficiencies forthwith. G. System Tagging:
Such repair shall be completed as soon as System tags shall be placed on all systems
possible, but in every case within 30 days of the certified by the Certified tester, and shall bear
initial test. At the completion of repairs, the the following information machine printed on
equipment, system, or device shall be re-tested them.
to determine that it is fully operable.
(1) The words “Do not Remove by order of
The Chief shall be notified of the repair and the Fire Chief”
retest within seven days on approved Fire (2) Concern Name
Department forms. (3) Concern Address
(4) Contractors license number or State
NOTE: A permit from the Department of Fire Marshals “A” license number
Building and Safety or the Fire Department (5) Certificate of Fitness Number
may be required for repairs of equipment, (6) Date system was certified
systems or devices in accordance with the (7) Signature of certified tester
Los Angeles Building and Fire Codes. A (8) Seal of the City of Los Angeles
licensed contractor with the appropriate (9) Type of system tested
license shall perform all required work.
The system tags shall be five and one-half
E. Fire Hose Connections: inches (5-1/2) in length and two and three-
fourths inches (2-3/4) in width. The following
(1) All fire hose connections shall be sample shall be used for all tags.
equipped with American National

JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
2005 2006 2007 2008 2009
DO NOT REMOVE

AUTO SPRINKLERS
ANNUAL COMPANY NAME___ STANDPIPE CLASS_____
5-YEAR COMBINED SYSTEM
ADDRESS/PHONE #
FIRE PUMP
STATE LIC. # FIRE ALARM
THE FIRE MARSHAL

CENTRAL STATION
E-POWER
BY ORDER OF

SMOKE SYSTEM
ELEVATORS
FIRE DOORS
REG 4 NO. Signature FIRE ESCAPES

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27 28 29 31
30

R4-8
SECTION 4 – GENERAL TEST PROCEDURES (a) Test clarity of voice communications
A. Central Station Signaling Systems: between floors, the building fire control
room/station and other locations
(1) Test all fire protection equipment, where provided.
systems, and devices, which are (b) Determine that a minimum of six
supervised by an approved central approved sound-powered telephone
station monitoring company for their sets are available at the building fire
proper operating condition, supervision control room/station.
and maintenance in Accordance with (c) Check telephone jacks for proper type,
NFPA-72. loose connections, corrosion, and
(2) Determine that the transmitter panel is proper installation.
operating properly and the approved
system description, sequence of (2) Emergency Voice Alarm Signaling
operation and operating instructions Systems:
are available.
(3) Notify the central station monitoring (a) Determine that voice evacuation panel
company and building occupants prior is operating properly and approved
to conducting tests. operating instructions are available.
(4) Actuate each water flow alarm device (b) New buildings: Determine system
by use of the Inspector's test valve. reliability by testing clarity of voice
(5) Actuate all other fire alarm devices, communication between the fire
supervisory devices and transmitters control room/station and all areas
for proper operation and supervision. within the structure include outside
(6) Determine that the system has two patios and balconies above the first
approved methods of transmitting the floor. Audibility shall not be less than
signal to the Central Station monitoring 15db minimum above the average
company. ambient sound level.
(7) At the conclusion of the test notify the (c) Existing buildings: Determine
central station monitoring company, system reliability by testing clarity of
determine that the central station voice communication between fire
properly supervised and received all control room/station and all areas
test signals by maintaining a where provided. Audibility shall not be
chronology of all testing. Return less than 10db above the average
system to the normal mode, and notify ambient sound level.
building occupants that the test is (d) Determine that the voice override on
complete. voice evacuation systems operates
properly. With fire alarm audible
B. Communication Systems (Firefighter and signals operating, press down on the
Building): microphone button and speak into
Determine that all equipment is in proper operating microphone. At that time, fire alarm
condition and well maintained in accordance with audible tones shall discontinue to
NFPA-72. Check system reliability as follows: sound and voice sound shall be 15db
minimum above average ambient
(1) Fire Department Communication sound level.
Systems.
NOTE: Systems installed prior to 1993 may

R4-9
have an audible signal a minimum of 10db [a] Determine that the elevator door
above the average ambient sound level. retraction safety devices (except
mechanical safety edges) are
(e) Systems equipped with A.D.A. strobes immediately deactivated.
may continue to flash when voice [b] Determine that the "Emergency
evacuation system is activated or Stop Switch" is rendered
audible signals are silenced. inoperative as soon as the doors
are closed and the elevator car
(3) Required Public Telephone: To be starts towards the designated
located in the building fire control room recall level. A moving car,
as regulated by Section 403 of the traveling to or away from the
California Building Code. designated level shall have its
"Emergency Stop Switch"
(a) Determine that Fire Department rendered inoperative immediately.
telephone number is posted. [c] Determine that elevator cars are
(b) Determine that telephone is connected not subject to calls from other
to the telephone system and is sources; i.e., corridor call buttons
operational. and car floor selection buttons.
[d] Determine that each elevator car
C. Elevators, Automatic (Phase I and II): returns nonstop to the
Test shall determine that all features of Phases I designated main recall floor and
and Phase II (if provided) of fire emergency remains there with the doors
service are in proper operating condition in open.
accordance with Title 8, Section 3041 of the [e] Determine that the elevator shunt
California Code of Regulations. trip smoke detector operates
properly and shuts power to the
(1) Phase I (Recall) elevator equipment.

(a) Elevator Lobby Smoke Detectors (b) Designated Main Recall Floor
Switch
[1] Determine that all landings served
by each elevator or each group of [1] Determine that the proper
elevators, except the designated designated main floor recall switch
main recall floor, are provided with is provided for each elevator or
smoke detectors. each group of elevators. The
[2] Determine that smoke detectors designated main floor recall switch
located in the elevator machine shall be a three-position ("on," "off,"
room and at top of elevator shaft and "bypass") key-operated switch.
recalls elevators in that bank to The key shall not be removable in
designated main recall floor. the "bypass" position. Determine
that keys to operate the designated
EXCEPTION: main floor recall switch and in-car
The main recall floor may be equipped with elevator switch are keyed alike and
elevator lobby smoke detectors, provided they are readily available for firefighter
recall the elevator car to an alternate floor use. Keys shall be located in the
approved by the Chief. Fire Department lock-box or other
location approved by the Chief.
[3] Recall function - Actuate the [2] Turn the designated main floor
elevator lobby smoke detector on recall switch to the “on” position.
each landing. Check for Phase I Determine that the recall function is
activation and interconnection of the same as described in Section 4-
circuit with the fire alarm system, if C-1 Phase I Recall Function, except
provided: the alarm system, if provided, shall
not activate.

R4-10
position, the elevator car shall remain in
(c) Designated Fire Control Phase II if the lobby switch is turned to the
Room/Station Switch "off" position until the car returns to the
designated recall floor and the doors fully
[1] Turn the designated fire control open.
room/station switch to the on
position, if provided. Determine that (d) Phase II Override Function: Turn the
the recall function is the same as designated main floor switch to the on
described in Section 4-C-1 Phase I position, then turn the in-car switch of
Recall Function except the fire each elevator car to the on position.
alarm system, if provided, shall not Test the override function of each car
activate. This switch shall be a two- as follows:
position ("on" and "off") key-
operated switch. [1] Determine that each elevator car is
operable only by a person in that
NOTE: If a three-position switch is used, the car. The car shall not respond to a
main floor switch shall override the bypass call from any other source.
position in the fire control room if activated. [2] Actuate a floor selection button in a
normal manner. Close the doors by
(d) Elevator Status Panel: Check for continuous pressure on the "door
proper function of the elevator status close" button. If not provided, close
panel. the doors by continuous pressure
on the floor selection button. If the
button that closes the doors is
(2) Phase II (Override): released prior to the doors reaching
the fully closed position, the doors
(a) Determine that the proper in-car shall automatically reopen.
switch is provided in each elevator [3] Determine that, if multiple floor
car. The in-car switch shall be a two- selection buttons have been
position ("on" and "off") key-operated actuated, the elevator car will stop
switch, keyed identically with the at the first of the selected floors that
designate main floor switch. The key it reaches. At that time, all other
shall not be removable in the "on" selections shall cancel. The doors
position. shall remain closed.
[4] Open the doors by continuous
NOTE: Elevator cars equipped with a three- pressure on the "door open" button.
position “off, hold, on,” key switch, the key is If not provided, open door by
removable in any position. continuous pressure on floor
selection button. If the button is
(b) Determine that keys are readily released prior to the doors reaching
available for firefighter operation of the the fully open position, the doors
Phase II override function. There shall shall promptly and automatically re-
be a separate key for each elevator car close.
in addition to the key for the designate [5] Where more than one operating
main floor switch. Keys shall be located panel is provided in an elevator car,
in the Fire Department lock-box or other determine that both panels will
location approved by the Chief. correctly operate the override
(c) Determine that the in-car phase II function.
switch in each elevator car is [6] In elevators where key switches or
operative only when the elevator is in programming characteristics are
the Phase I recall mode. provided to prevent the elevator
from stopping at one or more
NOTE: If Phase I was activated by the lobby landings while in normal service,
key switch and the in-car switch is in the "on" determine that fire emergency

R4-11
service overrides such features.
[7] Determine that the "Emergency NOTE: A proper test of unit lighting shall be
Stop Switch" is operative during the conducted by using the main breaker, or with
time the elevator is in the Phase II the approval of the Chief, the circuit breaker
override function. that supplies power to the fixtures and not by
[8] Cars equipped with a three position pressing the test button.
“off, hold, on,” key switch shall
operate in phase II in the “on” (7) Emergency Lighting Systems:
position. Shall stay stopped at their Determine that all Emergency Lighting
designated landing in the “hold” has been restored within 10 seconds.
position And return to phase I in to All areas requiring Emergency Lighting
“off” position causing the car to shall be checked for adequate lighting.
return non stop to the main recall Ensure a reading of not less than one
floor. foot-candle power for exit path lighting
[9] Return all systems and key measured at the floor level and a
switches to their normal positions. reading of not less than five foot-candle
power for exit and directional signs
D. Emergency and Standby Power Systems: measured at the sign. A light meter
may be used. The emergency
(1) Determine that all equipment is in generator or battery system must
proper operating condition and well supply power to all emergency lights for
maintained in accordance with NFPA- the duration of the test.
70 and 110. (8) Return all systems and equipment to
(2) Determine that the generator has not their normal position.
been started within 12 hours to ensure
a cold start and that all systems and NOTE: Testing of emergency lighting levels
equipment powered by emergency should be conducted during hours of
power are operating prior to load darkness when necessary in order to
transfer from normal power to accurately measure the required candle-
emergency power. power simulating worst case scenario. A
(3) Use the main breaker for load transfer single line diagram shall be provided for each
from normal power to emergency system tested.
power.
E. Fire Escape Assemblies:
EXCEPTION:
With the approval of the Chief, other methods (1) Determine that fire escape stairs,
of load transfer may be conducted. landings, ladders, guards, rails, and
safety chains are in good repair.
(4) Determine that the load transfers in the (2) Determine that all landings are
required time. accessible from inside the building and
provided with proper signage.
(a) Emergency power requirement is 10 (3) Operate the ladder release mechanism.
seconds. The release mechanism must operate
(b) Standby power requirement is 60 easily. The ladder must travel to the
seconds. ground without hesitation. It must be
stable and firm in its position after
(5) Determine that emergency current reaching the ground. This procedure
supplies power to all required systems shall be conducted twice.
and equipment as per building single (4) Return ladder to its normal position.
line diagram.
(6) Conduct a load test on battery systems F. Fire Hydrants (Private)
to ensure proper battery life. Batteries Determine that hydrant is in proper operating
supplying power to unit lighting shall condition and well maintained in accordance with
have sufficient power for 90 minutes. Los Angeles Fire Code Division 9, NFPA-25 and

R4-12
NFPA-291 (1) Swinging Fire Door: Release the
hold-open device by unfastening the
(1) Outlets: Determine that outlets are not most distant fusible link or by de-
damaged and are provided with proper energizing the smoke-actuated hold-
caps. Only 1-1/4 or 1-3/4 pentagonal open device. The door must close the
nuts shall be accepted. opening completely and latch.
(2) Flow: Hydrant shall be opened fully (2) Sliding Doors on an Inclined Track:
and water flowed until all foreign Unfasten the most distant fusible link to
material has cleared. Flow shall be release the suspended weight to allow
maintained for not less than one (1) the door to travel down the inclined
minute (care should be given to avoid track to the closed position. The door
flooding and property damage). must close completely and be held
(3) One hydrant closest to the main is firmly in place by the binders. Doors in
chosen to be the residual hydrant at pairs must butt together without gaps or
which the normal static pressure will be excessive offset from each other.
observed with the other hydrants in the (3) Sliding Doors on a Level Track:
system closed. The residual pressure Unfasten the most distant fusible link
will be observed with the other hydrants supporting the closing weight. As the
flowing. closing weight drops, the door must
(4) When the required GPM’s are flowing, cover the opening completely.
a minimum residual pressure of 20 psi (4) Rolling Steel Doors: Unfasten the
shall be maintained at the residual restraining cable or most distant fusible
hydrant. Record the residual pressure link and drop the restraining trigger
with the required GPM’S flowing from quickly. The door must cover the
the furthest hydrant in the system. The opening completely.
required flow shall be in accordance (5) Telescoping Vertically Sliding
with Los Angeles Fire Code Division-9 Doors: Unfasten the small
counterweight. The large
counterweight must operate the door,
covering the opening completely.
NOTE: To obtain satisfactory test results, (6) Vertical Sliding Doors: Unfasten the
sufficient discharge should be achieved to most distant fusible link that supports
cause a drop in pressure at the residual the suspended weight. The door must
hydrant of at least 25%. For hydrants with a cover the opening completely.
static pressure of less than 40 psi, hydrants (7) Stair-shaft Door Locks: Determine
should be rated at one-half the static that the locks release when:
pressure.
(a) The building loses normal electrical
G. Fire Protection Assemblies: Automatic power; doors will remain locked when
Closing transferred to emergency power.
(b) Any fire protective signaling system-
NOTE: The following Automatic Closing Fire initiating device is actuated.
Assemblies shall be tested by persons (c) Initiated manually from building fire
qualified to do work in order to determine their control room/station or other location
proper operating and reset condition in approved by the Chief.
accordance with NFPA-80. The closing speed
for all fire doors shall be not less than six (8) Initiating Devices: Ascertain that all
inches per second nor more than twenty-four initiating devices, e.g., smoke detectors
inches per second. and manual pull stations that are
interconnected to a fire protection
signaling system will actuate the hold-
open device and release the fire
protection assembly to which they are
connected.

R4-13
operating instructions for the Fire
NOTE: Single Station - stand alone smoke Protective Signaling System shall be
detectors connected to fire doors in multiple posted in or adjacent to the building fire
residential occupancies that are not part of a control room/station. A systematic
fire alarm system shall be tested every six checklist of all fire and life safety
months by the building owner or by the initiating devices with a simplified floor
owner's representative. A record of the test plan of the location and type of each
shall be maintained and made available for initiating device shall be provided in or
inspection upon request by the Chief. adjacent to the building fire control
room/station.
(9) Ventilation and Air Duct Dampers in (3) Sequence of Operation: An approved
non-sprinklered buildings: sequence of operation shall be posted
Disconnect the fusible link or actuating in or adjacent to the building fire control
device to the damper control. The room/station showing the operation of
damper must automatically travel to a all auxiliary functions of the fire
position that closes the opening protective signaling system. (See
completely. Attachment No. 1)
(4) Trouble Signal: Disconnect fire alarm
NOTE: Dampers in sprinklered buildings AC power. The audible trouble signal
shall be tested when first installed, or when and trouble light or lights must operate.
major improvements to an area are made. Operate the trouble signal-silencing
switch. Restore power and trouble light
(10) Laundry and Rubbish Chute Doors: switch to normal position. If a ring-back
Operate the door assemblies. The doors system is provided, the trouble light
must close and latch either by means of switch must be reset.
a counterbalance or spring-load (5) Supervision of Initiating Device
mechanism. Circuits: Disconnect a fire alarm
(11) Dumbwaiter Doors, Access Doors, initiating device. Audible trouble signal
and Fire Windows: Determine that the and light or lights on fire alarm
automatic operation of these annunciator panel must operate.
assemblies will function by releasing (6) Supervision of Audible Fire Alarm
the weights or by actuation of any Device Circuits: Disconnect a
initiating device. Opening or closing the notification appliance. At that time,
contacts, whichever is applicable, will either an audible trouble signal and/or
actuate electrically operated devices. light on fire alarm annunciator panel
Determine that they close the opening must operate.
completely when activated. (7) Supervision of Control Valve
(12) Fire Shutters: When these assemblies Circuits: Movement of the valve from
are automatic or self-closing, determine its normal position shall initiate a
that they close the opening completely distinctive signal at the fire alarm panel.
when activated. The off-normal supervision signal
(tamper) shall remain until the valve is
H. Fire Protective Signaling Systems: restored to its normal position. The off-
normal supervision signal shall be
NOTE: Prior to testing any Fire Protective obtained by two revolutions or 1/5 the
Signaling System, the system shall be clear of travel distance of the control valve
all supervision, trouble, tampers, and alarm apparatus, whichever is less from its
signals. normal position.
(8) Initiating Device Function Test: Test
(1) Determine that all equipment is in all fire alarm initiating devices.
proper operating condition and well Actuation of an initiating device shall
maintained in accordance With NFPA- indicate a signal on the fire alarm panel
72 and/or the annunciator panel, indicating
(2) Operating Instructions: Approved the type of device and zone of

R4-14
actuation if provided. Actuation of (2) Determine the rated capacity and
initiating devices shall also sound an pressure of the pump from the pump plate
audible signal that is a minimum 15 db attached to the pump. Determine the
above the ambient noise level. required flow and the number of test
outlets required by multiplying the rated
EXCEPTION: capacity of the pump (gpm) by 250 (gpm).
Systems installed prior to 1993. An audible To determine the 50, 100 and 150
tone of 10db above normal ambient sound percent required flow of the pump. An
level is acceptable. approved method shall be used to
measure both gpm and psi.
(9) In buildings regulated by the provisions (3) Determine that the fire pump starts
of Title 24-California Code of automatically and manually in
Regulations and Division 118-Los accordance with manufacturer
Angeles Fire Code, shall have all fire specifications by decreasing system
alarm, trouble and supervision signals pressure for automatic starts and using
transmitted to a 24-hour continuously the start switch for manual starts.
supervised Building Fire Control (4) Operate the fire pump for seven
Room/Station or to a UL approved minutes with all Fire Department
remote Central Station Service. discharge outlets in the closed position
(10) Sprinkler System Flow Switch: Open (except for a minimum flow of water to
the Inspector's test valve(s) for each ensure proper pump cooling). Record
riser or floor valve, causing the water churn pressure.
flow switch to be actuated. This (5) After the fire pump has been operating
actuation shall indicate an alarm within for seven minutes, open the correct
20 to 60 seconds. In addition, the number of test outlets and record the
outside sprinklers alarm bell (if pump discharge at 50, 100, and 150
provided) will sound within 90 seconds. percent of the rated capacity of the
(11) Determine that subsequent alarms pump for a minimum of three minutes
reactivate audible signals; i.e., at each percent. At peak flow (150%),
resounding of alarms from one floor to the fire pump shall not perform less
the next. than 65 percent of its rated capacity.
(12) Verify that all ADA strobes are (6) If the fire pump is fed directly from city
activated by initiating devices and flash mains, ensure that the residual
at a rate of 60 to 120 per minute. pressure on the supply side of the
Strobes may continue to flash when the pump does not drop below 20 psi
voice evacuation system is activated or during the flow test. A reading below 20
when the fire warning system is psi could damage city mains.
silenced. (7) At the conclusion of the pump test,
restore all valves and controls to their
NOTE: ADA strobe shall be synchronized normal operating condition.
when more than two strobes are visible from
any location.

I. Fire Pumps:
J. Gas Detection System:
(1) Determine that the fire pump, fire pump (1) Methane Gas
controller, remote status panel, water
supply, fire pump test header, a. Verify that the gas detection system
approved signs and all other and all associated components are in
associated components are in proper proper operating condition and
operating condition and maintained in maintained in accordance with F.P.B.
accordance with NFPA-20 and NFPA- Requirement No. 71, Chapter 71 of
25. the Los Angeles Building Code and

R4-15
Division 123 of the Los Angeles Fire activation and dispatch.
Code.
b. Verify that the control panel is in proper i. Verify that the electrical circuit breakers
operating condition and the approved supplying normal electrical power are
system description, sequence of equipped with a lockout device.
operation, operating instructions and
emergency telephone number of j. Verify that sensors located in the vent
company responsible for servicing risers do not place the system in alarm
system is posted at or adjacent to the and do not cause a fire department
control panel and the annunciator dispatch. These sensors shall only
panel. send a supervisory signal.
c. Verify that emergency power is capable
of supplying power for 24 hours in the k. Verify that all sensor identification
standby mode and 5 minutes in full addresses correspond with the same
alarm after 24 hours in the standby information as the control panel.
mode.
d. For methane systems, test all sensors K. Pressure Regulating Valves:
in the system using 10% to 25% L.E.L. The following procedure applies to every 2-1/2-
and 50% to 60% L.E.L. Methane Test inch standpipe outlet equipped with pressure
Gases for proper activation of alarm regulating valves, to determine their proper
system and proper annunciation at the operating condition and maintenance in
status panel. The drift (difference) accordance with NFPA-14 and 25.
between the sensor and the test gas
shall not exceed +or- 5% LEL when Fire pump(s) must be operating when
using 50% test gas. Verify that system measurements are taken. Perform test procedure
goes into pre-alarm between 10% and in the following sequence:
24% L.E.L. and into full alarm at 25%
L.E.L. (1) Attach approved flow and pressure
e. Verify that all audible devices sound an measuring devices to the pressure-
alarm a minimum of 15db above the reducing valve.
ambient noise level but not less than (2) Attach an approved 2-1/2 inch shut-off on
75db and not more than 120db and are the discharge side of the measuring
distinctive from all other alarm signals. devices.
Visual devices shall be visible and (3) Attach an approved water drainage system
shall be synchronized when more than on the discharge side of the 2-1/2 inch shut-
two devices are visible off.
f. All devices shall be identified with the (4) Open the outlet fully; regulate the water
word “METHANE” written on then. for the required maintenance flows
g. Verify that all mechanical air ventilation from the 2-1/2 inch shut-off.
systems (if applicable) operate (5) Determine that the outlet delivers at
properly when system is activated at or least 300-gpm.
below 10% L.E.L. and an exchange of (6) With 300-gpm flowing, ensure that the
air occurs at a rate of not less than four residual pressure on the discharge side
(4) changes of air per hour and of the outlet is at least 80-psi and not
exhausted directly to the outside. more than 125-psi. Document residual
Verify that vent risers are not damage pressure with 300-gpm flowing on
or obstructed and maintain a 10’ foot approved Fire Department forms. If
clearance around point of discharge. adjustments are needed a residual
h. Verify that all methane alarm, pressure of 100-psi is recommended.
supervision and trouble signals are
transmitted to a 24-hour continuously EXCEPTION:
supervised location or a UL Laboratory For buildings built after 1994, required flow is
approved remote central station 300-gpm between 100 and 125-psi.
service. Verify for proper type of

R4-16
(7) Ensure that static pressure on the Smoke Ventilation Systems are tested
discharge side of the outlet is a for proper automatic operation by
maximum of 175-psi. Document static actuation of a fire protective signaling
pressure on approved Fire Department system-initiating device.
forms.
(a) Mechanical Ventilation: Building air-
EXCEPTION: handling equipment (HVAC) designed
For buildings built after 1994, static pressure to remove smoke shall exhaust at a
shall be 175-psi maximum. rate of not less than six changes of air
per hour and exhaust directly to the
(8) Close outlet and remove test exterior of the building without re-
equipment. circulating to other locations in the
building. Mechanical ventilation
equipment controls shall be located in
the fire control room/station and have
L. Refrigerant Discharge Systems: the capability of controlling one or all
floors for smoke evacuation.
(1) Systems Providing For Manual (b) Below Grade Levels: All areas below
Discharge of Refrigerant to the grade equipped with mechanical
atmosphere: smoke ventilation shall be tested for
proper automatic operation by
(a) Determine that the emergency actuation of a fire protective signaling
refrigerant control box is plainly system-initiating device. System shall
marked: exhaust at a rate of not less than six
“FOR FIRE DEPARTMENT ONLY – (6) changes of air per hour, and
(REFRIGERANT) CONTROL VALVE.” exhaust directly to the exterior of the
(b) Determine that the high and low- building.
pressure valves in box are indicated. (c) Smoke Removal: Mechanical Smoke
(c) Operate the high and low-pressure Control systems. Check system
valves to assess proper working reliability as follows:
condition.
[1] Actuate all initiating devices
(2) System Provided With A Fire designed to operate fans, blowers,
Department Diffuser Consisting of A 2 and smoke control dampers to
½” Hose Connection To A Sewer: determine proper automatic
function of system.
(a) Determine that the emergency [2] When fans, blowers, and smoke
refrigerant control box and valves are control dampers are interconnected
properly labeled as per (a) and (b) to the building fire control
above. room/station, ensure that remote
(b) With water flowing through 2 ½” hose control from that location is
to Fire Department diffuser, open the operable and proper status is
high and low-pressure valves to indicated on the smoke control
assess proper working condition. panel. Verify that all lights are
functional when the lamp test
button is depressed.
[3] Perform a visual inspection of all
fans, blowers, and smoke control
dampers to verify proper operation
M. Smoke Management Systems: in the smoke removal mode.
[4] Verify that smoke control systems
(1) Building Emergency Smoke supplied by emergency power
Management Systems: Ensure that systems, operate properly when
areas equipped with Mechanical normal power is lost. Secondary

R4-17
power shall be from an approved
emergency standby power source (d) Performance Test, Stair-shaft: Use
complying with the electrical code. this procedure:

(2) Mechanically Ventilated Smoke- [1] With the system operating and all
proof Enclosure: doors closed, measure the stair-
shaft static pressure at three floors
(a) Doors: Open all doors in the system located in the top, center, and
and determine if they are held open by bottom thirds of the stair-shaft. This
smoke-actuated hold-open devices. pressure is to be measured
(b) Initiating Devices: Actuate any between the stair-shaft and
initiating device on each floor and hallway, at the floors selected, with
determine: the comfort air handling (HVAC)
turned off.
[1] That all-magnetic hold open
devices release and all fire rated EXCEPTION: Determine that the minimum
doors in the system properly closes pressure within the vestibule with the doors
and latch. closed is 0.05-inch water gauge (12.44 PA)
[2] That the comfort air handling positive pressure relative to the fire floor and
system (HVAC) has shutdown. 0.05-inch water gauge (12.44 PA) negative
[3] That the vestibule ventilation pressure relative to the exit enclosure. No
system is activated and the supply pressure difference is required relative to the
and exhaust dampers open. exit enclosure.
[4] That the stair-shaft ventilation
system is activated. (3) Pressurized Stair-shaft System:
[5] That the fire control panel properly Inspect the system for proper status
indicates the status of the fire prior to activating system. Activate any
protective signaling system. fire alarm initiating device to
[6] That all fire alarm audible and automatically activate the system.
visual devices operate on Inspect the status panel in the building
appropriate floor. fire control room/station for proper
[7] That the smoke control panel, if operation. Determine that the system
provided, operates properly in both has the minimum airflow requirement.
manual and automatic modes and This is done by multiplying a typical
proper status is indicated on the cross-sectional area in the stair-shaft in
panel. square feet by 50 linear feet per
minute. With all doors closed using an
(c) Performance test, vestibule: Use approved anemometer at the exhaust
this procedure: point, determine that the system meets
90 percent of the minimum required
[1] Actuate any fire alarm initiating CFM while maintaining a positive
device. pressure.
[2] Open the doors from the vestibule (4) Door Test: Test pressure is obtained
to the stair-shaft, on any three by using an approved door-testing
consecutive floors. device applied in a direct vertical line
[3] Ensure that the system meets the above the axis of the door knob/lever.
following requirements:
(a) Test 1: With the system on and all
[a] 2500-cfm minimum is flowing at doors closed, the maximum allowable
the stair-shaft exhaust opening. pressure that is required to open that
[b] The flow from the exhaust of each door should be 30 lbs. That door must
of three vestibules shall be 2500- close and latch when released.
cfm minimum per vestibule with all (b) Test 2: With the system on and one
three flowing simultaneously. other door open, the maximum

R4-18
allowable pressure to open the door static reading may indicate a closed
shall be 15 lbs. Door must close and valve or obstructions in water supply
latch when released. In Tests 1 and lines.
2, stair-shaft doors that swing outward (4) Gauge Tests: Connect a test gauge at
must close and latch after being the test gauge opening to determine
opened and released. the reliability of existing gauges.
(c) Test 3: With the system off all doors in (5) On-site Water Supply:
stair-shaft must close and latch after
being opened and released. (a) Determine that filling for on-site water
supply, if provided, operates when
N. Sprinkler Systems, Automatic: flow test is conducted.
Determine that all equipment is in proper operating (b) Determine that the air pressure and/or
condition and well maintained in accordance with water supply gauges on dry, pre-
NFPA-13 and NFPA-25. action, and deluge systems are in
proper working condition.
(1) Inlets: Determine that appropriate inlet
connections with approved signs have NOTE: Tests of these systems will be done
been provided and are in operable by using the bypass connection.
condition.
(2) Flush the Fire Department Inlet (6) Inspect system for proper sprinkler
Connection and Piping: Use the head placement, orientation, type,
following method to remove proper hangers, seismic braces, and
obstructions and/or debris from the Fire signs of corrosion, paint, physical
Department inlet connection and damage, and proper signage.
piping:
NOTE: Sprinklers protecting spray-coating
(a) Back Flush: areas shall be protected against over-spray
residue. Sprinklers shall be protected using
[1] With the main system shut-off valve plastic bags having a maximum thickness of
closed and the piping to the Fire 0.003 inches, [0.076mm] or with small paper
Department connection drained, bags. Coverings shall be replaced when
disassemble and inspect the check deposits or residue accumulate.
valve, then remove, reverse, or
block open the clapper in the check (7) Inspect spare sprinkler heads box for
valve. Reassemble check valve. correct number and type of sprinkler
[2] Open the main system shut-off and heads and proper wrench. The number
flow adequate water back through of spare sprinkler heads shall be as
to the Fire Department connection follows:
inlet to assure that all debris is
cleared from the inlet piping and (a) Up to 300 heads - not less than 6
Fire Department connection. sprinklers heads.
Restore system to normal. (b) 300 to 1,000 heads - not less than 12
sprinklers heads.
NOTE: This is the preferred method of (c) Over 1,000 heads - not less than 24
clearing the Fire Department connection. sprinklers heads.

(3) Main Drain Test: With the main drain (8) Sprinkler heads in operation over 50
valve closed, note pressure reading on years and sprinkler heads known to
the gauge. Fully open the main drain have an abnormally high failure rate
valve with water flowing, note the listed by the Chief shall have a
residual reading on the pressure representative sample of not less than
gauge. Close main drain valve and four sprinklers or 1 percent, whichever
note pressure gauge reading. A slow is greater tested by an approved testing
return on pressure gauge to original laboratory for evaluation. (If one

R4-19
sprinkler fails, all sprinklers in the be secured in their normal position using a
system shall be replaced.) This testing break-a-way lock and chain.
procedure shall be repeated at 10-year
intervals.
(13) Automatic Sprinkler Systems other
Exception No. 1: than wet: Automatic sprinkler systems
Sprinkler heads manufactured prior to 1920 equipped with Pre-action, Deluge or
shall be replaced. Dry Pipe systems shall have their
Exception No. 2: water-control valves and their
Fast response sprinkler heads that have been automatic and manual tripping means
in service for 20 years shall be tested. They tested annually as required by
shall be re-tested at 10-year intervals. approved manufacturer's testing
Exception No. 3: procedures and the Chief.
Representative samples of solder-type
sprinklers with a temperature classification of EXCEPTION:
Extra High {325 degrees (163 degrees C)} or This regulation shall not apply to junior
greater that are exposed to continuous sprinkler systems of less than 21 sprinkler
maximum allowable ambient temperature heads and sprinkler systems designed and
conditions shall be tested at five-year installed in accordance with NFPA-13D,
intervals. standard for the installation of sprinkler
systems in one and two family dwellings and
(9) Sprinkler systems with static pressures manufactured homes.
in excess of 175 psi shall be equipped
with approved pressure regulating (14) Foam-Water Sprinkler Systems:
devices. Testing of foam water sprinkler
(10) Operation Test: Open the Inspector's systems shall be conducted to ensure
test valve at the topmost or most that the foam-water system(s) operates
remote location from the main control as designed, both automatically and
valve in the system. The alarm must manually. Testing procedures shall
sound within 90 seconds for water simulate anticipated emergency events
motor-type alarms and within 20 to 60 so the response of the foam-water
seconds for electrically monitored water system can be evaluated in accordance
flow switches. with NFPA 16, 16A, 25 and
(11) Valves: Operate, inspect, and recommended test procedures as per
lubricate post indicator valves, manufacturer’s specifications.
underground gate valves, OS&Y
valves, and one-way check valves to O. Standpipe Systems:
determine that they are in good Determine that all equipment is in proper operating
operating condition and do not leak. condition and well maintained in accordance with
Return all valves to their normal NFPA-14 and NFPA-25.
position. Check tamper supervision
circuits by moving valve from its normal (8) Class I and III Standpipes:
position two revolutions or 1/5 the
travel of the valve whichever is less. (a) Fire Department Connections:
This shall initiate a distinctive signal at Ensure that appropriate inlet
the fire alarm panel, if provided. connections are provided with
(12) Sprinkler Wrench: A special sprinkler approved signs and are in operable
wrench[s] shall be provided and kept in condition. Flush Fire Department
the cabinet to be used in the removal connection and piping using an
and installation of sprinklers. A approved method to remove
sprinkler wrench[s] shall be provided obstructions and/or debris from the
for each type of sprinkler installed. inlet connection and piping as stated
in Section 4-N-2.
NOTE: Valves that are not supervised shall (b) Air Test: Air test dry systems to a

R4-20
maximum of 25 psi for 30 minutes to greater than 275 feet shall flow a minimum of
determine if the system leaks. This is 1000-gpm at 65 psi at the roof.
to avoid water damage to the building
if piping has been damaged or NOTE: A separate flow test shall be
disconnected. conducted for each Fire Department
connection and riser.
NOTE: Air test not required on outside
piping. (f) Fire Department Outlets:

(c) Hydrostatic Test: Fill the system [1] Check each Fire Department outlet
completely with water and note the for any signs of corrosion and
static pressure (head) on a test gauge leakage.
installed on the lowest inlet [2] Inspect and operate each outlet
connection. Hydrostatically test the valve in the system to determine
system at a pressure 50 PSI greater that it will function properly. Close
than the head pressure but in no case valve and replace cap.
less than 200 PSI for two hours. [3] Where the static pressure at a hose
(d) Flow Test: Flow a minimum of 500- connection exceeds 175 psi, an
gpm for the first standpipe through the approved pressure-regulating
most remote Fire Department outlets device shall be provided to limit the
plus 250-gpm for each additional static pressure to 175 psi. The
standpipe with the total supply not to pressure-regulating valve shall
exceed 1,250-GPM. The system shall provide a residual pressure
maintain a residual pressure of not between 80 and 125 psi with 300-
less than 65 PSI for three minutes. gpm flowing. Buildings built after
Test gauges shall be used to measure 1994 shall have a residual pressure
residual pressures and a pitot gauge between 100 and 125 psi with 300-
or approved flow meter used to gpm flowing.
measure water flow quantities. [4] Flow water from each Fire
Alternate test procedure: Department outlet not equipped
Flow 100 GPM of water through the with pressure regulating valves in a
standpipe at the topmost outlet. Using manner that will indicate the valve
a flow meter and pressure gauge, is fully operable and that there is
measure the flow and residual appropriate water pressure at that
pressure. Install a pressure gauge at outlet.
the lowest inlet connection, with 100 [5] Check automatic drip connections,
GPM flowing at the topmost outlet if provided, for proper function.
measure the residual pressure at the
topmost outlet and the inlet pressure. (g) On-site Water Supply:
Determine that the friction loss in the
system does not exceed 15 PSI. [1] Determine that filling for on-site
Subtracting the combined static water supply, if provided, operates
pressure (head) and residual pressure when flow test is conducted.
from the inlet pressure determines the [2] Determine that air pressure and/or
friction loss. FL=IP- (SP+RP) water supply gauges, if provided,
(e) Gauge Test: Connect a test gauge at are in proper working condition.
the test gauge opening to determine
the reliability of existing gauges. (h) Hose:

EXCEPTION:
Existing retrofit buildings as regulated by
section 91.8604 of the Los Angeles Building
Code 75 feet to 275 feet shall flow a minimum
of 750-gpm at 65 psi at the roof. Buildings

R4-21
Disconnect hose, from Fire Installed prior to 1996: Shall have
Department outlet (if provided). a residual pressure of 108 psi on
Examine full length of hose section for each riser with 90-gpm flowing.
mildew, cuts, abrasions, and other [7] Class H Standpipe Systems
deterioration. Check hose couplings, Installed after 1996: Shall have a
gaskets, and nozzle for damage and residual pressure of not less than
obstruction. Hydrostatic testing of fire 65 psi on each riser with 100-gpm
hose shall be conducted in flowing.
accordance with NFPA 1962, Chapter
5. (b) On-site Water Supply:

(2) Class II (Wet) Standpipes: [1] Determine that filling for on-site
water supply, if provided, operates
(a) Flow Test: Determine that the system when flow test is conducted.
and its water supply will meet one of [2] Determine that air pressure and/or
the following standards according to water supply gauges, if provided,
the date of its installation. Test gauges are in proper working condition.
shall be used to measure residual
pressures and an approved flow meter (c) Outlets:
shall be used to measure water flow
quantities. The required water flow [1] Check each outlet for signs of
must be maintained for at least 30 corrosion and leakage.
seconds from systems supplied by [2] Where the residual pressure at a 1-
street mains or gravity tanks and at 1/2 inch outlet exceeds 100 psi, an
least two minutes from systems approved pressure-regulating
supplied by booster pumps or device shall be provided to limit the
pressure tanks: residual pressure to 100 psi.
[3] Flow water from each outlet in the
[1] Systems Installed Prior to 1948: system in a manner that will
Shall have residual pressures of not indicate the valves are fully
less than 8 psi at the topmost outlet operable and that there is water
on each riser with 20-gpm flowing. pressure at that outlet.
[2] Systems Installed from 1948 to
1959: Shall have residual (d) Hose: Inspect hose at each outlet.
pressures of not less than 12 psi at Examine full length of hose section for
the topmost outlet on each riser mildew, cuts, abrasions, and other
with 35-gpm flowing. deterioration. Check hose couplings
[3] Systems Installed from 1960 to for gaskets, damage and obstructions.
1971: Shall have residual Check for proper nozzles. Unlined
pressures of not less than 15 psi at hose shall be equipped with
the topmost outlet on each riser smoothbore nozzles; lined hose shall
with 35-gpm flowing. be equipped with adjustable spray
[4] Systems Installed from 1971 to nozzles.
1982: Shall have residual
pressures of not less than 30 psi at (e) Service Testing: Hydrostatic testing
the topmost outlet on each riser of fire hose shall be conducted in
with 70-gpm flowing. accordance with NFPA-1962 Chapter
[5] Systems Installed after 1982: 5.
Shall have a residual pressure of
not less than 65 psi at the topmost EXCEPTION:
outlet on each riser with 100-gpm Unlined hose shall not be hydrostatically
flowing. tested. Hose shall be replaced with lined hose
[6] Class H Standpipe Systems when replacement is necessary.

R4-22
(3) Combined Standpipe Systems:

(a) Inlets: Determine that proper inlet


connections with approved signs have
been provided and are in operable
condition.

Flush Fire Department Inlet


Connection and Piping using an
approved method to remove
obstructions and/or debris from Fire
Department inlet connection and
piping as stated in Section 4-N-1.

(b) Fire Pump Test: Follow Fire Pump SECTION 5 – APPLICATION


test procedures as stated in Section 4- The provisions of this regulation do not
I. supersede, nullify, or in any manner abrogate
(c) Flow Test: Follow Class I and III any other provision of the Los Angeles City
standpipe test procedure as stated in Fire Code. Compliance with the provisions of
Section 4-O-1-d. this regulation does not relieve any person
(d) On-site Water Supply: Follow Class I from compliance with applicable provisions of
and III standpipe test procedure as any County, State, or Federal Law.
stated in Section 4-O-1-g.
(e) Automatic Sprinkler System: Follow
Automatic Sprinkler System test
procedure as stated in Section 4-N.
(f) Fire Department Outlets: Follow
Class I and III standpipe and pressure
regulating valve test procedure as
stated in Section 4-O and 4-K 1-8.

NOTE: Combined Standpipe Systems


equipped with looped standpipe risers shall
be flow tested by shutting down one side of
the system at a time and flowing water from
the open side. Fire alarm initiation shall take
place within 20 to 60 seconds. After both
sides have been individually tested, a flow
test with both flow valves open shall be
conducted. Tamper valves shall be tested by
moving valve from its normal position two
revolutions or 1/5 the travel of the valve
whichever is less. This shall initiate a trouble
signal at the fire alarm panel.

NOTE: A separate flow test shall be


conducted for each Fire Department
connection and riser.

R4-23
Los Angeles City Fire Department
Chief’s Regulation No. 4 Requirements
GUIDELINES FOR SEQUENCE OF OPERATION FOR LIFE SAFETY SYSTEMS IN HIGH-RISE BUILDINGS

Elevator Return Air Elevator Sprinkler Sprinkler Special


Area Building
Manual Pull Lobby Duct Shaft Water Valve Extinguishi
Smoke Power
Station Smoke Smoke Smoke Flow Tamper ng
Detector Failure
Detector Detector Detector Switch Switch System
Annunciate @ FCR (alarm
and trouble) Yes Yes Yes Yes Yes Yes Yes Yes Yes

Annunciate @ 24-hour
attended remote location Yes Yes Yes Yes Yes Yes Yes Yes Yes
(alarm and trouble)
Activate Audible Alarm
Signal on floor of alarm Yes Yes Yes Yes No Yes No Yes No

Shut Down All Air Handling


(HVAC) on floor of alarm Yes Yes Yes Yes No Yes No Yes No

Release All
Electromagnetically Held Yes Yes Yes Yes No Yes No Yes Yes
Doors on floor of alarm
Activate Smoke Evacuation
System on floor of alarm Yes Yes Yes Yes No Yes No No No

Recall All Elevators serving


floor of alarm No Yes No No Yes No No No Yes

Release All Stair Shaft Door


Locks in building Yes Yes Yes Yes No Yes No Yes Yes

Activate All Stair Shaft


Pressurization Fans in Yes Yes Yes Yes No Yes No Yes No
building
Open Elevator Shaft Smoke
Damper No No No No Yes No No No No

Release Approved Elevator


Security Door Locks Yes Yes Yes Yes Yes Yes No Yes Yes
R4-27

You might also like