Storage tanks are often used when the total loop volume of the
distribution network is less than the minimum requirements of the chiller
manufacturer. Storage tanks increase the effective volume of the
system.
Niles Steel Tank is a Bradford White subsidiary and their buffer tanks
are designed for use with commercial and process chilled water
systems which may have insufficient water volume to maintain optimum
operating temperature control. Niles offers gallon capacities of 130,
210, 300, 400, 528, 850, 1040, as well as custom. Tanks are
constructed under the A.S.M.E., Section VIII, Division I code. Vertical
and horizontal tank designs are available with center baffle plate.
Optional closed cell spray foam insulation has an R16 insulation rating.
Minimum Loop Volume Requirements by Chiller Model
Manufacturer & Model Cooling Capacity Comfort Cooling Low Ambient (<32F)
(tons) Minimum System or Process Cooling
Volume (gal/ton) Applications (gal/ton)
Multiaqua MAC 3 8.3 8.3
Multiaqua MAC 4 6.3 6.3
Multiaqua MAC 5 10 5 5
Carrier 30RAP 10 15 12 12
Carrier 30RAP 18 30 6 10
Carrier 30RAP 35 40 4 8
Carrier 30RAP 45 55 3 6
Carrier 30RAP w/ 10 60 3 3
Digital Scroll
Carrier 30MP 15 30 3 6 10
Carrier 30MP 40 45 2.1 6 10
Carrier 30HX 70 265 3 6 10
Carrier 30RB 60 390 3 6 10
Carrier 30XW 150 400 3 6 10
Carrier 30XA 80 500 3 6 10
Carrier 23XRV 300 550 3 6 10
Carrier 19XR 200 1500 3 6 10