Certified Drawing CD: WSCWDC-MTII-WIRE-2

Job Name: Group: Chiller


Type: WSC/WDC
Supercedes: January 2005
Tag / Item No.: Effective: May 2005

WSC/WDC MicroTech II Field Wiring Diagram


MICROTECH CONTROL
BOX TERMINALS
(115V) (24V)

PE 54
GND
85
POWER
* NOTE 7
86
NEUTRAL
* NOTE 10 70
H
80
* COOLING O 55
TOWER C4 74 H
A
FOURTH O
86
STAGE
STARTER EP2
A C
86

* NOTE 10
H 79
* COOLING O
TOWER C3 73
A H
THIRD O
STAGE
STARTER EP1
A C
78

77
* NOTE 10
H 76
* COOLING O
TOWER C2 75
A
SECONDH
STAGE
STARTER
H
O

* NOTE 10 A C
H CP2
* COOLING O
C1 T3-S
TOWER A
FIRST EF
STAGE
STARTER CF

81
COMMON
82(NO) ALARM RELAY
A (NOTE 4)
83(NC)

84
POWER

H
52
O
COOLING TOWER
71
BYPASS VALVE 1-10 VDC CP1
A C
71
1-10 VDC
COOLING TOWER VFD 53

MICROTECH STARTER LOAD SIDE TERMINBALS


COMPRESSOR CONTROL VFD
- FOR DC VOLTAGE AND 4-20 MA
L1 L2 L3
BOX TERMINALS CONNECTIONS (SEE NOTE 3)
U V W
CTB1
NOTE 2 - FOR DETAILS OF CONTROL REFER
115 VAC
GND T1 T6 T2 T4 T3 T5 TO UNIT CONTROL SCHEMATIC
PE COMPRESSOR TERMINALS 330342103
CP1 L1
STARTER LOAD SIDE TERMINBALS
CP2 L2 WYE-DELTA - COMPRESSOR CONTROL
23(5A) 23 T1 T2 T3
T4 T5 T6 SCHEMATIC 330342203
COMPRESSOR 24(5) 24
- LEGEND: 330343003
MOTOR 25 25
T1 T2 T3 T4 T5 T6
STARTER COMPRESSOR TERMINALS * FIELD SUPPLIED ITEM
(NOTE 1) 1 1
STARTER LOAD SIDE TERMINBALS
2 2 SOLID STATE
NOTE 12
T1 T2 T3
3 3

4 4

6 11 T1 T6 T2 T4 T3 T5
COMPRESSOR TERMINALS
11 11

12 12
STARTER LOAD SIDE TERMINBALS
22 22 MEDIUM AND HIGH VOLTAGE

T1 T2 T3
-LOAD- NOTE 2 LESS
THAN
30V
OR T1 T2 T3
24VAC COMPRESSOR TERMINALS 330387901-0A

Page 1 of 3
Certified Drawing CD: WSCWDC-MTII-WIRE-2

Job Name: Group: Chiller


Type: WSC/WDC
Supercedes: January 2005
Tag / Item No.: Effective: May 2005

Field Wiring for Optional Display

Page 2 of 3
Certified Drawing CD: WSCWDC-MTII-WIRE-2

Job Name: Group: Chiller


Type: WSC/WDC
Supercedes: January 2005
Tag / Item No.: Effective: May 2005

WSC/WDC MicroTech II Wiring Diagram Notes


NOTES:
1. Compressor motor starters are either factory mounted and wired or shipped separate for field mounting and wiring.
If provided by others starters must comply with McQuay specification 359AB99. All line and load side power
conductors must be copper.
2. If starters are free standing, then field wiring between the starter and the a terminal block located in the compressor
motor terminal box is required. Minimum wire size for 115 Vac is 12 Ga. For a maximum length of 50 feet. If greater
than 50 feet refer to McQuay for recommended wire size minimum. Wire size for 24 Vac is 18 Ga, all wiring to be
installed as NEC Class 1 wiring system. All 24 Vac wiring must be run in separate conduit from 115 Vac wiring.
Main power wiring between starter and motor terminal is factory installed when units are supplied with unit mounted
starters. Wiring of free-standing starter must be wired in accordance with NEC and connection to compressor motor
terminals must be made with copper wire and copper lugs only.
When unit mounted starters are shipped loose for mounting on the unit in the field, a pre-wired control cable will be
factory installed on the unit for connection to the starter in the field.
3. For optional sensor wiring see unit control diagram. It is recommended that dc wires be run separately from 115
Vac wiring.
4. A Customer furnished 24 or 120 vac power for alarm relay coil may be connected between utb1 terminals 84 power
and 81 neutral of the control panel. For normally open contacts wire between 82 & 81. For normally closed wire
between 83 & 81. The alarm is operator programmable, maximum rating of the alarm relay coil is 25va.
5. Remote on/off control of unit can be accomplished by installing a set of dry contacts between terminals 70 and 54.
6. Evaporator and condenser paddle type flow switches or water pressure differential switches are required and must
be wired as shown. WDC dual compressor units require DPDT switches. If field supplied pressure differential
switches are used then these must be installed across the vessel and not the pump.
7. Customer supplied 115 Vac 20 amp power for optional evap and cond water pump control power and tower fans is
supplied to unit control terminals (UTBI) 85 power / 86 neutral, PB equipment ground.
8. Optional customer supplied 115 Vac 25 VA maximum coil rated chilled water pump relay (EP 1 & 2) may be wired
as shown. This option will cycle the chilled water pump in response to building load.
9. The condenser water pump must cycle with the unit. A customer supplied 115 Vac 25 VA maximum coil rated
condenser water pump relay (CP1 & 2) is to be wired as shown.
10. Optional customer supplied 115 Vac 25 VA maximum coil rated cooling tower fan relays (CL - C4) maybe wired as
shown. This option will cycle the cooling tower fans in order to maintain unit head pressure.
11. Auxiliary 24 Vac rated contacts in both the chilled water and condenser water pump starters must be wired as
shown.
12. For VFD, Wye-Delta, and solid state starters connected to six (6) terminal motors. The conductors between the
starter and motor carry phase current and selection shall be based on 58 percent of the motor rated load amperes
(RLA). Wiring of free-standing starter must be in accordance with the NEC and connection to the compressor motor
terminals shall be made with copper wire and copper lugs only. Main power wiring between the starter and motor
terminals is factory installed when chillers are supplied with unit mounted starters,
13. Terminals 3 and 4 are for VFD only.

NOTE: Voltage unbalance not to exceed 2% with a resultant current unbalance of 6 to


10 times the voltage unbalance per NEMA MG-1, 1998 Standard.