Air System Design Load Summary for SF - AHU-06 w heat/humidifier

Project Name: DG Affairs- Office rev. 1 08/27/2011


Prepared by: abc 07:42AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1200 HEATING DATA AT DES HTG
COOLING OA DB / WB 48.1 C / 29.6 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 22 m 2936 - 22 m - -
Wall Transmission 161 m 2539 - 161 m 867 -
Roof Transmission 343 m 25150 - 343 m 3757 -
Window Transmission 22 m 1721 - 22 m 655 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 110 m 1434 - 110 m 0 -
Partitions 360 m 3984 - 360 m 0 -
Ceiling 6 m 173 - 6 m 0 -
Overhead Lighting 5429 W 6349 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4860 W 5228 - 0 0 -
People 35 3081 2127 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 15% / 15% 7889 319 0% 0 0
>> Total Zone Loads - 60484 2446 - 5278 0
Zone Conditioning - 64774 2446 - -1498 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 5384 L/s 0 - 402 L/s 0 -
Ventilation Load 363 L/s 10371 10048 27 L/s 179 -48
Supply Fan Load 5384 L/s 3020 - 402 L/s -822 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 605 - 1% 53 -
>> Total System Loads - 78769 12494 - -2088 -48
Central Cooling Coil - 78769 12504 - -4415 -48
Central Heating Coil - 0 - - 2327 -
Humidification Load - - 0 - - 0
>> Total Conditioning - 78769 12504 - -2088 -48
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads