LIEBERT eXM 3-PHASE UPS: 10-100KVA/KW, 60HZ, 208-220VAC, SINGLE & DUAL INPUT - SITE PLANNING DATA

BYPASS DISTRIBUTION CABINET

* System MBB (Optional AC Output 208V


AC Input BIB MIB Distribution) 4 Wire + GND
3 Wire + GND See Note 5 Notes:
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. UPS system input and output cables must be run in separate conduits.
Local Grounding 4. Control wiring must be run in separate conduits.
Electrode 5. Optional 54 pole 400A or two 225A subfeed breakers.
Static Bypass See Note 1 6. Transformer available: 208, 220, 480, 600V input.

BIB - Bypass Isolation Breaker


MBB - Maintenance Bypass Breaker
MIB - Maintenance Isolation Breaker
UPS * External Overcurrent Protection By Others
Field-Supplied Wiring
BATTERY

Notes for Tables


1. Nominal (Nom) current is based on full rated output load at nominal input voltage. 11. Top or bottom cable entry through removable access plates. Punch plate to suit conduit
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge size, then replace.
conditions. 12. Control wiring and power wiring must be run in separate conduit.
3. UPS input and bypass cables must be run in separate conduit from output cables. 13. Dimensions shown include an internal battery (40kVA frame only).
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. 14. Weights shown do not include an internal battery nor optional cabinets or features.
5. For Single Input units only. For Dual Input units, see Electrical Data Specification 15. When a Liebert Bypass Distribution Cabinet is not used, the customer must supply the
Sheet, Dual Input 10-100kVA, Liebert eXM. input circuit breaker with a 120VAC shunt trip on the bypass feed only. The shunt trip
6. Nominal rectifier AC input current (considered continuous) is based on full rated drive capability is 8A.
output load. Maximum current includes nominal input current and maximum Additional Notes
battery recharge current (considered non-continuous). Continuous and non-
If site configuration includes a backup emergency generator, it is recommended that the
continuous currents are defined in NEC 215.
engine generator set be properly sized and equipped for a UPS application. Generator
Nominal AC output current (considered continuous) is based on full rated output
options would typically include an isochronous governor (generator frequency regulation)
load. Output breakers are either supplied by the customer or by using the optional
and a UPS-compatible regulator (generator voltage regulation). Consult generator
Liebert Bypass Distribution Cabinet.
manufacturer for required generator options and sizing.
7. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground
If site configuration includes an automatic transfer switch, refer to Liebert Power Line titled
conductors are recommended. Neutral conductors to be sized for full capacity per
Criteria for Application of Automatic Transfer Switches (ATS) With Uninterruptible Power
NEC 310-15 (b)(4). References are per NEC 2008..
Supply (UPS) Systems, publication 91K-PLT-48-02. It is also recommended that the
8. Wiring requirements: AC Input: 3-phase, 4-wire, plus ground transfer switch be equipped with auxiliary contacts to provide a UPS on generator signal.
AC Output: 3-phase, 3- or 4-wire, plus ground Consult transfer switch manufacturer for required transfer switch options and sizing.
9. All wiring is to be in accordance with national and local electric codes. If site configuration requires an external isolated maintenance bypass circuit, it should be
10. Minimum access clearance is 36" (914mm) front; ventilation clearance is noted that utility AC input might not be in phase with the UPS AC output. Consult an
24" (610mm) above and 0-5" (127mm) in the rear, depending on anchoring method. Emerson sales representative or applications engineer.

1
Table 1 Site planning data - 10-100kVA, 60Hz, 208VAC, single input
UPS
Rating Voltage AC Input Battery AC Output Mechanical Data
Current, A Current, A Unit Weight, lb. (kg)
Rec. Nom. Max. Dimensions 40 kVA 100 kVA Heat Dissipation, Cooling Air
kVA kW Input Output Nom. Max OPD VDC Discharge Nom. OPD WxDxH, in. (mm) Frame Frame BTU/hr (kWH) CFM (m3/hr)
10 10 208 208 30 34 45 288 47 28 40 604 (274) NA 1535 (0.45) 67.8 (115)
15 15 208 208 45 51 70 288 70 42 60 604 (274) NA 2303 (0.675) 67.8 (115)
20 20 208 208 59 68 90 288 93 56 70 604 (274) NA 3071 (0.9) 67.8 (115)
30 30 208 208 89 102 150 288 140 83 110 23-5/8 x 39-3/8 x 78-3/4 678 (307.5) NA 4606 (1.35) 135.6 (231)
40 40 208 208 119 136 175 288 187 111 150 (600 x 1000 x 2000) 678 (307.5) NA 6142 (1.8) 135.6 (231)
60 60 208 208 178 205 300 288 280 167 225 NA 807 (307.5) 9213 (2.7) 203.4 (346)
80 80 208 208 237 273 350 288 373 222 300 NA 881 (399.6) 12284 (3.6) 271.2 (462)
100 100 208 208 297 341 450 288 467 278 350 NA 955 (433.2) 15354 (4.5) 339 (575)
Refer to Table 5 for dimensions and weights for options.

Table 2 Site planning data - 10-100kVA, 60Hz, 208VAC, dual input


UPS
Rating Voltage AC Input Battery AC Output Mechanical Data
Rectifier Bypass
Current, A Current, A Current, A Unit Weight, lb. (kg)
Heat
Rec. Rec. Nom. Max. Dimensions 40 kVA 100 kVA Dissipation, Cooling Air,
kVA kW Input Output Nom. Max OPD Nom. OPD VDC Discharge Nom. OPD WxDxH, in. (mm) Frame Frame BTU/hr (kWH) CFM (m3/hr)
10 10 208 208 30 34 45 28 40 288 47 28 40 604 (274) NA 1535 (0.45) 67.8 (115)
15 15 208 208 45 51 70 42 60 288 70 42 60 604 (274) NA 2303 (0.675) 67.8 (115)
20 20 208 208 59 68 90 56 70 288 93 56 70 604 (274) NA 3071 (0.9) 67.8 (115)
30 30 208 208 89 102 150 83 110 288 140 83 110 23-5/8 x 39-3/8 x 78-3/4 678 (307.5) NA 4606 (1.35) 135.6 (231)
40 40 208 208 119 136 175 111 150 288 187 111 150 (600 x 1000 x 2000) 678 (307.5) NA 6142 (1.8) 135.6 (231)
60 60 208 208 178 205 300 167 225 288 280 167 225 NA 807 (307.5) 9213 (2.7) 203.4 (346)
80 80 208 208 237 273 350 222 300 288 373 222 300 NA 881 (399.6) 12284 (3.6) 271.2 (462)
100 100 208 208 297 341 450 278 350 288 467 278 350 NA 955 (433.2) 15354 (4.5) 339 (575)
Refer to Table 5 for dimensions and weights for options.

2
Table 3 General specifications
INPUT OUTPUT
Voltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus ground Voltage 208/120, 220/127VAC, 50/60Hz, 3-phase, 4-wire plus ground
Voltage Range Voltage
+15%, -20%
without derating Adjustment 5%
Frequency Range 40-70Hz Range
THDi Voltage 1% for balanced load
5% maximum reflected THD at full load
(Current Distortion) Regulation 5% regulation for unbalanced load
Power Factor 0.99 full load, 0.98 half load Dynamic 5% deviation for 100% load step
Regulation 1% for loss or return of AC input
Sustains input surges w/o damage, per criteria in IEC 1000-4-5
Surge Protection
(w/ surge suppressor option ANSI C62.41 (IEEE 587) CAT A3 & B3 Transient
Recover to 5% of output voltage within 1/2 cycle
ENVIRONMENTAL Response Time
Operating UPS: 32 to 104F (0-40C) For linear loads, 2% THD; Less than 5% THD for 100% nonlinear
THDv
Temperature Battery: 68 to 86F (20-30C) loads without kVA/kW derating
Non-Operating Phasing 120 1 for balanced load
-4 to 158F (-20 to 70C)
Temperature Balance 120 1.5 for 100% unbalanced load
Relative Humidity 0-95% non-condensing Frequency
0.1% to 0.25%
Operating Altitude Up to 3,300 ft. (1,000m) without derating Regulation
Less than 59 dBA typical (100kVA) Acoustical Noise, Load Power
Acoustical Noise 0.5 lagging to 0.9 leading without derating
at 55 in. (1.4m) Factor Range
100% load, continuous
Listed to UL 1778 UPS standards, and CSA certified. Meets
STANDARDS Overload 110% load, 60 minutes; 125% load, 10 minutes;
current requirements for safe, high performance UPS operation.
150% load, 60 seconds, with true sinusoidal waveform

Table 4 Battery specifications and run times


Battery Time, Minutes
Battery Added Battery
Model Code 10kVA 15kVA 20kVA 30kVA 40kVA Weight, lb. (kg)
HX 100-FR F 22 12 8 528 (240)
HX 150-FR H 36 21 14 8 768 (348.3)
HX 205-FR M 52 32 22 13 9 1032 (468.1)
HR 1500 G 26 16 11 6 576 (261.3)
HR 2000 L 46 27 18 10 5 924 (419.1)

3
Table 5 Variations to weights and dimensions for optional equipment
Rated Power, kVA 10-40 60-100
Dimensions, WxDxH, in. (mm)
23-5/8 x 39-1/2 x 78-3/4 23-5/8 x 39-1/2 x 78-3/4
UPS (600 x 1000 x 2000) (600 x 1000 x 2000)
47-1/4 x 39-1/2 x 78-3/4 47-1/4 x 39-1/2 x 78-3/4
UPS w/BDC (1200 x 1000 x 2000) (1200 x 1000 x 2000)
Weight, lb (kg
No Distribution 525 (239) 550 (250)
225A Panelboard 625 (284)
400A Panelboard 660 (300)
No Distribution and 480V Transformer 1110 (505) 1522 (692)
No Distribution and 600V Transformer 1125 (511) 1507 (685)
225A Panelboard and 480V Transformer 1210 (550)
225A Panelboard and 600V Transformer 1225 (557)
400A Panelboard and 480V Transformer 1632 (742)
400A Panelboard and 600V Transformer 1617 (735)
Two 225A Subfeed Breakers 660 (300)
Two 225A Subfeed Breakers and 480V Transformer 1632 (742)
Two 225A Subfeed Breakers and 600V Transformer 1617 (735)

2014 Liebert Corporation Technical Support / Service United States


All rights reserved throughout the world. Specifications subject to change without notice.
Liebert is a registered trademark of Liebert Corporation. 800-543-2378 1050 Dearborn Drive
All names referred to are trademarks or registered trademarks of their respective owners. powertech@emersonnetworkpower.com P.O. Box 29186
SL-25645_REV0_01-15 DRAFT Web site: www.liebert.com Columbus, OH 43229