You are on page 1of 6

IX International Symposium on

Lightning Protection
26th-30th November 2007 Foz do Iguau, Brazil

HOW TO VERIFY LIGHTNING PROTECTION EFFICIENCY FOR


ELECTRICAL SYSTEMS?
TESTING PROCEDURES AND PRACTICAL APPLICATIONS

Birkl Josef Zahlmann Peter


DEHN + SOEHNE DEHN + SOEHNE
Josef.Birkl@technik.dehn.de Peter.Zahlmann@technik.dehn.de
Hans-Dehn-Strasse 1, D-92318 Neumarkt, Germany

Abstract There are increasing numbers of applications,


installing Surge Protective Devices (SPDs), through which
partial lightning currents flow, and highly sensitive, Testing of a SPD Testing the surge immunity of equipment
electronic devices to be protected closely next to each other according to IEC 61643-1 according to IEC 61000-4-5

due to the design of electric distribution systems and -


i Imax
switchgear installations which is getting more and more CWG CWG Coupling Umax
Umax DUT
compact. In these cases, the protective function of the SPDs 1.2/50 // 8/20 SPD 1.2/50 // 8/20 network
W EUT

has to be co-ordinated with the individual immunity of the


equipment against energetic, conductive impulse voltages Voltage protection level Up < Test level

and impulse currents. In order to verify the immunity


Combined system test:
against partial lightning currents of the complete system Testing the SPD and equipment to be protected
laboratory tests on a system level are a suitable approach.
Imax*
The proposed test schemes for complete systems have been Imax < Imax*
DUT Umax*
U max < Umax*
successfully performed on various applications. Examples CWG SPD
WEUT*
WEUT < W EUT*
will be presented.

1 INTRODUCTION Fig. 1 - Protective criterion for the co-ordination SPD and


equipment to be protected.
The protective effect of SPDs is verified in tests
according to the relevant product standard such as IEC The voltage protection level UP, of an upstream SPD has
61643-1 and IEC 61643-21 [1], [2]. The verification of to be below the verified immunity level of the equipment
immunity or surge immunity against conductive impulse to be protected. UP should be also co-ordinated with the
voltages or impulse currents of electrical and electronic withstand voltage of the equipment Uw according to IEC
devices is carried out according to IEC 61000-4-5 [3]. 60664-1 [4]. However, when applying this basic
However, the tests described in these two standards protective principle, not only the maximum voltage level
mainly refer to the SPD itself or the equipment to be Umax to be expected across the terminals of the SPD has to
protected. The necessity to combine both test levels be compared as generally assumed. Furthermore, a
within one system level test is stated by both parties. number of additional parameters might be relevant for
Figure 1 shows the basic protective criterion for the co- ensuring effective protection of equipment by means of
ordination of the individual surge immunity of a external SPDs:
equipment and the "protective performance of SPDs". Maximum impulse current Imax flow into equipment
Maximum energy Wmax transfered into equipment
In general, the protective performance of a SPD is
described by stating the voltage protection level UP, Maximum voltage-time integral u dt at equipment,
which is determined according to the test procedures Maximum voltage change du .
specified in IEC 61643. dt
The immunity of equipment from voltage and current In order to evaluate the above parameters following basic
surges is described by the magnitude of the applied questions are to be taken into account and will be
voltage test level (installation class). Considering the discussed further on:
protection of equipment by means of an upstream SPD, Different protection performance of SPDs depending
the following basic criteria applies: on the functional principle of individual SPDs
Comparability of different test parameters according
to IEC 61000-4-5 and IEC 61643
2 LIMITATION PERFORMANCE OF SPDs ]
Iimpedance

Depending on their design SPDs are subdivided MOV MOV

according IEC 61643-1 into following three functional


principles: Impulse current
Voltage switching type SPD: "can have a sudden generator External Voltage-limiting component
voltage-limiting SPD in equipment to be protected
change in impedance to a low value in response to a i[kA]
U [V]
voltage surge". Typical examples of such 1.2
total current 800
voltage across equipment
components are spark-gap-based SPDs.
voltage across SPD
Voltage limiting type SPD: " will reduce impedance 0.6
current into SPD
400
continuously with increased surge current and surge current into equipment

voltage". Typical examples are MOVs or diodes. 0


0
0 40 80 120 t[s] 0 40 80 120 t[s]
Combination type SPD: " incorporates both voltage
switching type and voltage limiting type components"
Figure 2.2 - Protection of equipment by an external MOV
The protection performance of SPDs may significantly
differ depending on the design features described. In
When assessing whether equipment can be protected by
Figure 2.1 and 2.2, this matter is outlined based on two
an upstream SPD, the protection performance,
basic examples. In both examples it is assumed, that the
considering also let-through energy and voltage-time
equipment to be protected contains a MOV directly at the
integral, which depends o the functional principle of the
equipment input terminal. Furthermore it is supposed that
SPD, may be decisive factors.
the equipment is protected by an upstream SPD at a
voltage protection level of UP = 1,5kV. In example 2.1, Table 1: Comparison of load parameters for the calculation
the SPD is designed as spark gap, in figure 2.2 a MOV examples in figures 2
type SPD is assumed. Based on a total load of 1kA
10/350s, the two pictures show the impulse current, Load Parameter at Voltage- Voltage-limiting
which flows into the equipment, and the voltage across equipment switching SPD SPD
equipment. In this simplified examples the primary values Maximum voltage < 800V < 800V
Imax and Umax have almost the same value. However, when Umax
comparing the integral values Wmax and u dt , it is
Maximum current < 200A < 200A
obvious that the let-through energy generated in the Imax
equipment to be protected and the voltage-time integral at Voltage-time 350mVs 1000mVs
the equipment may differ considerable in value when
using two different SPDs which have the same voltage
integral u dt
Maximum energy 2 Ws 70 Ws
protection level Up, but different functional principles. A
Wmax transfer
varistor-based SPD did result in a higher let-through
engery, especially at impulse currents with a long time to 3 COMPARISON OF TEST PROCEDURES
half-value, such as the 10/350s current waveshape. ACCORDING TO IEC 61000-4-5 AND IEC 61643
However at a spark-gap-based SPD it can be expected
that the load on the equipment to be protected is reduced In the scope of IEC 61000-4-5 it is clearly stated, that
due to the switching performance particularly if impulse direct lightning strikes, are not considered.
currents with a long time to half-value occur [6]. Furthermore the difference of equipment level immunity
and system level immunity is pointed out: "The
Impedance manufacturer should test his equipment to confirm the
equipment level immunity" and those responsible for the
Spark gap MOV
installation should then apply measures necessary to
ensure that the interference voltage caused by lightning
Impulse current
generator External Voltage-limiting componet in
- strokes does not exceed the chosen immunity level.
voltage-switching type SPD equipment to be protected Comparability of the parameters determined in various
i[kA] tests is a basic requirement that equipment with a specific
u[V]
1.2 800 immunity according to IEC 61000-4-5 can be protected
total current
voltage across SPD
current into SPD
by a SPD with specific voltage protection level according
0.6 400 to IEC 61643. Comparability is in some cases difficult
voltage at equipment due to different test philosophies and test methods, on
current into equipment
0 which the two standards are based. Some of the basic
0
0 40 80 120 t[s] 0 40 80 120 t[s]
differences between these two standards are described
Figure 2.1 - Protection of equipment by an external spark gap below.
3.1 Different source impedances 3.2 Different waveforms and threat values

Equipment immunity according to IEC 61000-4-5 is IEC 61000-4-5 specifies different installation classes
determined with a Combination Wave Generator (CWG) based on the installation conditions. Vlass 4 installations
with an internal impedance of 2 , a short circuit current are defined as power installation which can be subjected
of wave form 8/20s and an open-circuit voltage of wave to inteference voltages generated by the installation itself
form 1.2/50s. When testing SPDs Type III, which are or by lightning. The AC-power supply input of
mainly used for the protection of equipment, such a CWG equipment in installation class 4 will be tested with a
is also required according to IEC 61643-1. However, hybrid impulse of the waveshape 1.2/50s (8/20s).
when testing the immunity of equipment, different Whereas partial lightning currents are simulated in a
coupling elements are used. For example, when testing laboratory by means of an energetic current impulse with
low-voltage power supply lines against earth, an the waveform 10/350s according to the primary threat
additional resistor of 10 is connected in series. values, which are part of the lightning current standards
Therefore, SPDs ClassI, often called lightning current
The example in Figure 3 shows that different parameters arresters, are used for this purpose. These are installed
might be obtained from both tests due to this additional where cables enter buildings for protection against
series impedance. In the assumed example a MOV based lightning currents. These SPDs, are tested according to
SPD is tested according to IEC 61643-1 with an open- IEC 61643-1 with this energetic 10/350s test impulse. A
circuit voltage UOC =10kV. In this example, a voltage comparison of the different waveshapes, as given in
protection level of UP=1kV is achieved. An equipment figure 4, shows that a general statement whether
immunity of 2kV was determined according to IEC equipment can be protected by an external SPD also in
61000-4-5. In order to ensure this surge withstand it is case of lightning currents with a long current wave is
assumed that varistor is integrated inside the equipment. sometimes difficult, due to the different current
This MOV is charged with a total energy of 1 Joule when waveforms. As pointed out above, spark-gap-based SPDs
testing immunity according the EMC-standard. However, with a wave-breaking performance reduce the actual
if the SPD and equipment to be protected are tested in stress parameters for the equipment, due to its switching
combination with a 2-CWG of 10kV 1.2/50s, the characteristics. The remaining stress for the equipment
energy produced in the internal MOV of the equipment is then corresponds to the current waveform used to
20 times higher due to the different source impedance. evaluate the test level of the EMC-surge immunity test.
This may result in an energetic overload of this
component although the basic criterion, i.e. the immunity i [kA]
100
level of equipment has to be greater than the maximum
voltage protection level of the SPD, is met in this
example.

Case 1: Test of a single SPD according to EN 61643-1 50


U [kV] I [kA]
1.0 4.0
i
0.5 2.0 u
0
voltage above SPD
0
test voltage
10 kV
SPD
Partial lightning current 10/350
current through SPD
20
0 10 20 30 t [s] 40
Umax = 1 kV, Imax = 4 kA
Wmax = 60 J
Short circuit current
of a CWG 8/20
Case 2: Test of a single SPD according to EN 61000-4-5
U [kV] I [A]
0.8 100 200 1000 t [s]
10 9F i
0.4 50 DUT u
voltage above terminal equipment test voltage
0
current in terminal equipment
0 2 kV Figure 4 - Comparison of different wavevforms
0 10 20 30 t [s] 40
Umax = 600 V, Imax = 100 A
Wmax = 1 J
for 10/350 partial lightning current and 8/20 surge current
Case 3: System test of an SPD in combination with the terminal equipment
U [kV] I [kA]
1.0
i*
3.3 Adoption of the various test philosophies
1
0.5 DUT U*
voltage above terminal equipment test SPD
0
current in terminal equipment
0 voltage
10 kV For several years, experts of the IEC 77B and IEC 37A
Umax* = 850 V, Imax* = 1.1 kA
0 10 20 30 t [s] 40 Wmax* = 20 J committees responsible have been trying to adapt the
various test philosophies, on which the installation and
device regulations are based [5]. A description of this
problem of different test procedures was added to the
Figure 3 - Comparison of the threat values when co-ordinating
latest standard version of IEC 61000-4-5 Ed. 2.0 in an
SPD and equipment to be protected
additional informative annexe. In this article, possible test
procedures for such a cross-standard system test are
outlined based on practical examples.
4 SYSTEM TEST under operating conditions is to combine the standard test
philosophy of an immunity test according to IEC 61000-
In general the following statement of IEC 61000-4-5 4-5 with the increased requirements of an impulse current
applies: "In order to ensure system level immunity, a test test or lighting current test according to IEC 61643-1.
at the system level is recommended to simulate the real
installation. Therefore, when carrying out a system test, 4.3 Example I: Protection of a central inverter for
the actual installation conditions have to be simulated as solar power plants
realistically as possible. A test installation set up in the
laboratory includes for example the following: Figure 5 shows the basic circuit diagram of the individual
SPDs required surge protection measures for a solar power plant. There
Additional protective equipment installed, such as are two possible ways how lightning currents and surges
overcurrent protective devices and RCDs can couple into the central DC-AC-converter in the
Actual length and type of the connecting cables operation building: The collectors and their connecting
between the individual system components cables with the DC-input of the DC-AC-converter form a
Equipment and terminal equipment which have to be wide conductor loop. In this conductor loop high impulse
protected against surges currents will be induced even at distant strikes. If,
however, the DC-conductors are run in a steel conduit
The response of upstream SPDs result in secondary only a low energy impulse current loading have to be
effects such as change of wave form. Carrying out a taken into account. In such cases the installation of Class
system test also verifies that these effects do not have II SPDs according IEC 61643-1 directly at the DC-input
impermissible effects on the function of the equipment. of the DC-AC-converter and close to the solar generator
is necessary and sufficient [8]. In the operation building,
which includes the DC-AC-converter all metal systems
4.1 Energetic coordination shall be connected directly and all systems under
operating voltage shall be connected indirectly via Class I
It has to be observed that immunity of the total system SPDs to the lightning equipotential bonding.
cannot be increased by means of uncoordinated adding of
SPDs. Moreover, it has to be ensured in all cases that the
Surge protective components installed in the terminal
Central building with
equipment do not make the high-performance, upstream DC-AC-converter
SPDs ineffective. This "Blind Spot" can be verified in the
laboratory by carrying out tests, which are referred to as
"coordination tests". The test current has to be increased Partial lightning
currents in AC-low-
voltage-power-supply
gradually for the most critical case of this coordination Induced surge into
DC-input of converter
test is often not the maximum impulse current load to be
expected. In case of maximum test current, low line Earthing
impedance of the connecting cable often results in
sufficient coupling. The high current steepness di/dt
ensures that the upstream SPD is activated before the Figure 5 Basic protection scheme of the surge protection
surge protection integrated in the terminal equipment to for a solar power plant
be protected is overloaded. For reproducable coordination
tests special requirements for the test generators apply. Testing procedure:
Impulse current generators with a "fictive" internal In the following an example of such a system level test,
impedance 10 have proven to be sufficient. Thus, the called "lightning current test under service conditions"
requirement that lightning currents are to be regarded as will be presented. The DC-AC-converter to be protected
"ideal" power source is met with adequate accuracy [7]. is tested under operating conditions, i.e. the device will be
loaded with lightning partial currents at live state while
being connected with a DC supplying voltage. Figure 6
4.2 Lightning current test of SPD and equipment shows the basic circuit diagram of this system level test.
under real service conditions This circuit diagram shows how 8/20s impulse currents
are coupled into the DC input of the DC-AC-converter
The protection of equipment in the case of a direct under operating conditions. It has also been verified that
lightning strike can be verified by means of carrying out a during and after the feeding of lightning partial currents
Lightning current test under real operating conditions. of wave form 10/350 into the AC connection of the DC-
Equipment and SPDs are tested in a combined system test AC-converter via an AC supply transformer, electrical
under operating conditions, which have to be as real as energy has been supplied into the general low-voltage
possible. The basic idea of such a lightning current test mains.
S2

~ DC - AC-converter
~ 25 A-DC AC-power-transformer
L1 L1 S1 230 / 400 V 50 Hz

+
~ L2 L2
L3 L3

A N

PEN IAC A
IImpuls + IImpuls -
V

IDC
A
- -
A
DC-Power supply 600 V
Wh
Impuls current
Uprotect

generator 8/20
N L1 L2 L3
A
Multipole surge arrester External Lightning current arrester
Itotal - Class II SPD- for PV system - Class I SPD - for AC-power supply

Figure 6 Circuit diagram lightning current test of a central DC-AC-converter under real operating conditions

4.4 Example II: Lightning and surge protection of electromagnetic field generated by lightning currents. The
electrical systems in nacelle and hub of a windturbine resulting induced impulse currents within the cabling of
The verification of the effectiveness of lightning and the complete system were monitored. The characteristic
surge protection for electrical and electronic systems in values Imax, QStroke and W/R of the lightning currents were
the nacelle and hub of wind turbines by laboratory determined for every test impulse. The functional
testing, will be described on the example of a pitch drive endurance of the pitch drive system during the injection
control system. Pitch systems in the rotor hub are used for of direct lightning currents into the mounting plate was
adjusting the rotor blades. If the wind exceeds a critical monitored in order to verify any influence of conducted
value, the turbine will be moved out of the wind. interference to the control unit caused by effects of close-
by lightning currents. Figure 7 shows the laboratory test
Description of pitch drive control system set-up for this test series.
The examined pitch drive system did include several AC-
motors, AC converter, for communication a serial link
Measurement of Impulse current generator
(Profibus DP) and several multi turn position sensors. All impulse currents 200 kA 10/350
power-supply lines were protected by Class 2 SPDs
according IEC 61643-1. The data lines were protected by
multi-stage data line protectors tested according IEC
61643-21. These type of arresters include in the first stage
a powerful gapped arrester and downstream of the
decoupling element a diode element, ensuring the low Distribution board
including control system
protection level.

Lightning current parameters


It is assumed that the pitch drive control system is located Injection of impulse
current into metal frame
with Lightning Protection Zone 1, that means no direct
lightning currents but surge currents are flowing in the
electrical lines within the system. Furthermore the Figure 7 System test of a wind turbine pitch control system
complete pitch drive system, consisting of a control unit,
AC-motors, position sensors and the complete cabling
between these different components is also stressed by B) Impulse test 8/20 of low voltage power supply and
the magnetic field, which is generated by direct lightning Surge immunity test of data line
currents flowing in the surrounding metallic hub. Impulse currents 8/20 were injected directly both into the
power supply and into the data line conductors in order to
A) Induction effects due to lightning check the surge withstand of the connected equipment.
Impulse currents up to 100kA (10/350) were injected into During this test also the co-ordination of the installed
a defined metal, mounting plate, in order to examine the external SPDs both for data lines and power lines and
behavior of the complete system within an surge protection components, installed already inside the
connected equipment was verified. In the described D) Proof of continuity of supply
example the test of the surge current carrying capability The above test sequences mainly focussed on the
onto the power supply of the pitch drive control unit lightning current behaviour of the systems. But also the
under service conditions was performed with discharge the reliability of the low-voltage AC power supply are
currents up to 40 kA 8/20. The impulse current was becoming more important for the user. Therefore an
injected in this case in the line conductor to PEN- additional test for the selectivity of backup fuses and
conductor, while the system was connected with 255 V SPDs was included. This was done by laboratory testing
mains voltage. using the basic test procedure of a duty-cycle test,
Additionally a surge immunity test of the data line type described in the SPD-standard, but selecting the real
Profibus DP under service conditions has been overcurrent protective element, prospective short-circuit
performed. It was the aim to examine the interference on current and system voltage for the specific application.
the connection lines of the Profibus system as they are The frequency of follow currents and the follow current
caused by effects of lightning. Therefore 8/20 impulse limitation of a lightning current arrester are the decisive
currents up to 5kA have been directly injected into the parameters for a reliable power supply of a system.
data bus. The injection of the 8/20 discharge currents has It was ensured that low-energy overvoltages are
been done in two different coupling modes: suppressed to a low protection level without leading to
Line-to earth-coupling any 50Hz-mains follow currents. Should impulse currents
Screen-to-earth-coupling arise with higher energies and possibly lead to follow
currents, these should be limited to ensure that an
During the test the pitch drive system was running in test upstream overcurrent protective element will not respond.
mode. The data transfer between the pitch controller and
an external computer has been monitored. The correct 5 SUMMARY
function of the complete pitch control system could be
successfully verified during and following the complete It is not possible in every case to compare all parameters
test series. No data interruption or any damage to determined due to different test philosophies specified in
connected the pitch drive control system has been standards concerning immunity tests of terminal
observed. equipment and test requirements specified in the product
standards for SPDs.
C) Lightning current withstand of pre-wired connection Therefore, the system test presented in this article is a
unit for low voltage power supply method for verifying immunity on system level, which
This test is used to check for the cumulative effects that has been tried and tested in various applications.
occur when multiple modes of protection of a multi-pole
SPD conduct at the same time. The basic test procedure 6 REFERENCES
of the total discharge current test for multiple SPDs
according IEC 61643-1 is applied. The distribution of the [1] IEC 61643-1 Ed. 2: 2005-03 Low-voltage surge protective
impulse currents and it's characteristic parameters, such as devices - Part 11: Surge protective devices connected to
peak current Ipeak, total charge Q and specific energy W/R low-voltage power systems; Requirements and tests.
are monitored during the test, as IEC 61643-1 assumes a [2] IEC 61643-21 Ed. 1.0: 2000-09 Low voltage surge
protective devices - Part 21: Surge protective devices
balanced impulse current distribution. In the laboratory,
connected to telecommunications and signalling networks -
this balanced current distribution is ensured by series Performance requirements and testing methods
inductances and resistances. Assuming a balanced surge [3] IEC 61000-4-5 Ed. 2.0: 2005-11 Electromagnetic
current distribution amongst the phase lines and the Compatibility (EMC)- Part 4-5: Testing and measurement
neutral line represents a "worst-case" analysis. Different techniques - Surge immunity test
earthing practices in different parts of the world have a [4] IEC 60664-1: 2002 Insulation coordination for
very huge influence onto the actual lightning current equipment within low-voltage systems- Part 1:
distribution. However surge-protection systems tested Principles requirements and tests
under these conditions can be applied in all applications [5] H. Bachl "berspannungsschutz Koordination Gerte -
regardless the specific earthing conditions at the SPDs; IEC/EN 61000-4-5 versus IEC/EN 61643-11" [Surge
individual site. Additionally the equipment to be protection coordination devices; IEC/EN 61000-4-5 versus
protected has been connected to the output terminals of IEC/EN 61643-11] on the occasion of the D-A-CH
conference 08/2004, Rostock Wannemnde, Germany
the surge protective unit. So this test combines again the
[6] IEC 62305-4: 2006: Protection against lightning - Part 4:
stress parameter of the lightning protection standard with Electrical and elctronic systems within structures
the immunity verification of equipment and therefore [7] J.Birkl, P. Hasse "EMV-Testverfahren zur
exceeds the standardized requirements considerably. Ableiterkoordination" [EMC test procedures for
However, it offers the user of the SPDs the most realistic coordination of SPDs], in EMC Kompendium 1998
proof about the actual lightning current carrying [8] H. Pusch., B. Schulz "Blitz- und berspannungsschutz fr
capability and the protection of downstream equipment. Solarkraftwerke" in TAB 7-8/2003, S. 79-83

You might also like