You are on page 1of 10

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO.

1, JANUARY 2014 43

Medium-Voltage 12-Pulse Converter: Output Voltage


Harmonic Compensation Using a Series APF
Mostafa S. Hamad, Mahmoud I. Masoud, Senior Member, IEEE, and Barry W. Williams

AbstractIn this paper, compensation of the dc-side voltage The configuration in [5] uses a two-winding nine-phase
harmonics of a medium-voltage (MV) 12-pulse ac/dc converter front-end transformer feeding an 18-pulse diode rectifier. Con-
is achieved using a series active power filter (APF). The output ventional passive filters are used to suppress harmonic distor-
voltage harmonics are dependent on the converter firing delay
angles and, consequently, on the specific power locus followed tion. However, passive filters have limitations [6].
by the ac/dc converter. This power locus ensures minimum fifth In [7] and [8], the output voltage RF is improved by using
and seventh harmonics (total rms) in the input current which a pulse multiplication technique, where higher pulse operation
provides minimum input current total harmonic distortion when is obtained based on a six-pulse converter, with additional
the reactive power is less than 0.5 p.u. The series APF is connected circuitry. This adds auxiliary thyristors, two transformers, and
between the load and the converter output via a magnetic amplifier
to eliminate the dc current from the APF inverter, thus reducing passive elements to the main circuit. The addition of a complex
inverter losses. Voltage harmonic compensation using a series APF, active injection circuit in the converter dc side [8], [9] reduces
with and without a magnetic amplifier, is examined with both resis- the harmonic distortion in both the ac and dc sides. Other
tive and inductive loads. The simulation results for compensating a harmonic current injection methods are based on injecting
3.3-kV MV 12-pulse converter system are experimentally verified ripple into the converter dc side [10], [11], but the RF improve-
using a scaled prototype 12-pulse converter with a series APF.
ment is limited and does not guarantee compensation if used
Index TermsActive power filters (APFs), dc-side compensa- with controlled rectifiers. For higher voltage applications, the
tion, magnetic amplifiers, medium-voltage (MV) rectifiers, series passive elements of these circuits must be designed to withstand
APF, 12-pulse converters.
the maximum voltage. Because of power quality issues, more
importance is now being given to compensation using active
I. I NTRODUCTION power filters (APFs), made possible because of semiconductor
improvements, such as increased switching frequency, ratings,
C ONTROLLED ac/dc converters provide high reliabil-
ity, low complexity, and low power loss and minimize
the number of series-connected switches for high-voltage or
and cost, and also the availability of microelectronics and
measurement sensors [12], [13]. The APF overcomes classical
medium-voltage (MV) applications [1], [2]. One drawback of passive filters drawbacks; moreover, it can be durable and
these converters is the generation of voltage harmonics which reliable [14]. AC-side compensation using a shunt APF has
affects the power quality on the dc side [3], [4]. Controlling the been investigated and well documented, with recent publi-
converter phase angle impacts on the output voltage harmonics, cations dealing with performance improvement and control
which are assessed by using individual harmonic distortion design [15][22]. However, dc-side compensation has received
and the ripple factor (RF) [2]. Methods have been used to less attention even though the output voltage waveform has
minimize the output voltage waveform distortion, and a mul- a direct impact on the load. A series APF could be a candi-
tipulse configuration can be used in MV systems to improve date for dc-side compensation. When a series APF is used to
the power quality. Converters utilize a front-end phase-shifting compensate the output voltage harmonics [23], [24], the APF
transformer feeding a number of six-pulse converters connected inverter switches have to conduct the full-load current including
in parallel for high-current applications or in series for high- the principal dc component. The shunt APF is used to inject
voltage applications [3]. the compensating current necessary to cancel the output current
harmonics, therefore improving its RF [25][27]. To overcome
the problem of the APF inverter switches conducting the dc
load current, the series APF is connected into the converter dc
side via a magnetic amplifier coupled circuit which also isolates
Manuscript received August 9, 2012; revised November 19, 2012 and
the series APF from the power circuit. This allows lowering of
January 5, 2013; accepted February 13, 2013. Date of publication February 22, the APF switch ratings and voltage matching and minimizes
2013; date of current version July 18, 2013. inverter losses.
M. S. Hamad is with the Arab Academy for Science, Technology and Maritime
Transport, Alexandria 21532, Egypt (e-mail: eng_mostafa99@yahoo.com).
The objective of this paper is to compensate the 12-pulse
M. I. Masoud is with the Department of Electrical and Computer Engineer- controlled converter output harmonics using a series APF
ing, College of Engineering, Sultan Qaboos University, Muscat 123, Oman, and connected via a magnetic amplifier. This converter follows
also with the Electrical Engineering Department, The Faculty of Engineering,
Alexandria University, Alexandria 21544, Egypt (e-mail: m.masoud@ieee.org).
a specific power locus [28][30]. The insertion of the series
B. W. Williams is with the University of Strathclyde, Glasgow, G1 1XQ, APF improves the RF, consequently minimizing the necessary
U.K. (e-mail: barry.williams@eee.strath.ac.uk). smoothing inductance.
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. The remainder of this paper is organized into five sections
Digital Object Identifier 10.1109/TIE.2013.2248337 and the conclusion. Section II gives a brief introduction to the

0278-0046/$31.00 2013 IEEE


44 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 1, JANUARY 2014

power locus used. Section III explains the harmonic analysis


of the 12-pulse converter. Section IV shows the effect of
harmonic current injection on the flux distribution. Section V
introduces the series APF, either directly inserted or inserted
via a magnetic amplifier. Section VI shows the output voltage
after compensation using both simulation and experimentation.
Discussion and observations of the systems are introduced in
Section VII, which is followed by the conclusion.

II. P OWER L OCUS


The output voltage of the series 12-pulse converter Vo is the
sum of the output voltages of the two series-connected six-pulse
converters where
3Vmax Fig. 1. Operating power locus.
Vo = (cos 1 + cos 2 ). (1)

six-pulse converter [5]
By multiplying (1) by the converter output current (Io ), the
active and reactive powers are given by Vo = Vo1 + Vo2 (5)

P = Pmax (cos 1 + cos 2 ) where Vo1 is the output voltage of the upper six-pulse converter
Q = Pmax (sin 1 + sin 2 ) (2) and Vo2 is the output voltage of the lower converter. Hence, the
output voltage Fourier series is the sum of the Fourier series of
where each output, which are given by (6), shown at the bottom of the
3Io Vmax page, where
Pmax = . (3)    
cos(6n+1) 1
cos(6n1)1

6n+1 6n1
If 2Pmax is considered the base power, the active and reactive 6n(1) = n+tan1    
sin(6n+1)1 sin(6n1)1
powers can be represented in terms of per-unit values as
   6n1 
6n+1

P = 1/2(cos 1 + cos 2 ) cos(6n+1)2


6n+1 cos(6n1)
6n1
2

1     .
Q = 1/2(sin 1 + sin 2 ). (4) 6n(2) = n+tan
sin(6n+1)2 sin(6n1)2
6n+1 6n1
Constant-active-power operation can be achieved via different (7)
combinations of the firing angles 1 and 2 , with the converter
absorbing different amounts of reactive power, which affects By substituting (6) into (5), the total output voltage can be
the power factor [28][30]. This means that P and Q can expressed in terms of 1 and 2 by
produce a power locus which affects the converter performance. 3Vmax
The specific power locus shown in Fig. 1 achieves a maximum vo =

absorbed reactive power of 0.5 p.u. and compromises between


a symmetrical firing power locus, an asymmetrical firing power cos 1 +cos 2
loci, and a constant-VAr power locus [28][30]. Specifically,
this locus ensures minimum fifth and seventh harmonics (total 1 1 2 cos 21
+ + 2 sin(6t+6(1) )
rms) in the input current which provides minimum input current 5 2 7 57
total harmonic distortion when the reactive power is less than 1 1 2 cos 22
0.5 p.u. + 2
+ 2 sin(6t+6(2) )
5 7 57
1 1 2 cos 21
III. S ERIES -C ONNECTED 12-P ULSE C ONVERTER + 2
+ 2 sin(12t+6(1) )
11 13 1113
H ARMONIC A NALYSIS
1 1 2 cos 22
+ + sin(12t+6(2) )+ .
The output voltage of a series-connected 12-pulse converter 112 132 1113
is the vectorial sum of the output voltages generated by each (8)




3Vmax 1 1 2 cos 21
vo1 = cos 1 + + sin(6nt + 6n(1) )
n=1
(6n 1)2 (6n + 1)2 (6n 1)(6n + 1)



3Vmax 1 1 2 cos 22  
vo2 = cos 2 + + sin 6(nt /6) + 6n(2) . (6)
n=1
(6n 1)2 (6n + 1)2 (6n 1)(6n + 1)
HAMAD et al.: MV 12-PULSE CONVERTER: OUTPUT VOLTAGE HARMONIC COMPENSATION USING A SERIES APF 45

Fig. 3. Basic control technique used with the series APF.

V. S ERIES APF C ONNECTION


Series compensation is classified according to how the series
APF is coupled into the converter dc side. The series APF
can be connected into the converter dc side either directly or
transformer coupled via a magnetic amplifier.

Fig. 2. Harmonic factors and RF of the 12-pulse converter output voltage.


A. Configuration #1: Series APF Directly Inserted Into
In the case of 1 = 2 (symmetrical firing), the 6th, 18th, the Converter DC Side
. . ., harmonic voltages generated by each six-pulse converter
In configuration #1, the series APF (an H-bridge inverter) is
are 180 out of phase and therefore are canceled. The dc-
inserted directly into the dc side, as illustrated in Fig. 3. The
side harmonics of the 12-pulse converter are generated at 12p
load current Idc is blocked by the filter capacitor and thus flows
times the fundamental line frequency, where p = 1, 2, 3, . . ..
through the APF inverter switches and the passive filter induc-
This means that the ripple, and hence the RF, of the combined
tor. This inverter dc current is the major disadvantage of this
output voltage is reduced. When the 12-pulse converter follows
configuration, particularly in high-power applications, as the
the operating power locus introduced in [28] and [29], as shown
APF requires high-current inverter switches which introduce
in Fig. 1, the 12-pulse converter is asymmetrically controlled
(1 = 2 ), and the dc-side harmonics are generated at 6p high power losses. Moreover, the APF inverter is not isolated
times the fundamental line frequency. The variation of the four from the ac/dc converter.
dominant voltage harmonic factors and the RF, for the per-
unit active power range, is shown in Fig. 2, for the converter B. Configuration #2: Series APF Inserted Into the Converter
following the proposed power locus. DC Side via a Magnetic Amplifier
The APF can be coupled into the converter dc side using
IV. E FFECT OF H ARMONIC C URRENT I NJECTION
a single-phase high-bandwidth transformer used in a manner
ON F LUX D ISTRIBUTION
similar to that employed in dc current measurement transducers
The APF is inserted in series into the converter dc side and [31], which isolates the inverter from the power system and
acts as a voltage source that injects voltages equal but opposite matches the voltage and current ratings of the H-bridge inverter
in polarity to the harmonic vectors generated by the converter. to those of the power system [23]. Since the load current
The objective is to make the dc-side output voltage harmonic consists mainly of a dc component, a transformer core saturates
free [23]. The basic control algorithm concept is shown in [32]. Configuration #2 is proposed to solve this saturation
Fig. 3. The harmonic voltage Vo is extracted from the converter problem, where the series APF is coupled into the converter
output voltage using a low-pass filter (LPF) and scaled to dc side using the magnetic amplifier circuit shown in Fig. 4.
form the filter reference voltage. The APF inverter produces The magnetic amplifier has a tightly coupled three-winding
a modulated output voltage with contents proportional to the single-phase transformer with turns Nm1 : Nm2 : Nm3 , as
reference voltage. A passive filter (Lf and Cf ) is connected shown in Fig. 5(a). The converter-side winding of Nm1 turns
to the output of the series APF inverter, as shown in Fig. 3, is inserted into the converter dc side, which is designed
to eliminate the switching harmonics due to the pulsewidth according to
modulation (PWM). The filter output is connected into the d
converter dc side between its output and the load and injects vcs = Nm1 (9)
dt
the compensation voltage that cancels the harmonic voltage Vo
produced by the converter. The voltage across the load terminal where vcs is the instantaneous voltage and is the magnetic
VL becomes purely a dc voltage Vo . flux linking each turn of the coil. The APF-side winding of
46 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 1, JANUARY 2014

Fig. 6. Current-controlled dc chopper circuit.

measured load current average Idc is used to control the auxil-


iary current source which produces the control winding current
Ich required to achieve a dc ampere-turn balance between the
converter-side winding and the control winding
Fig. 4. Configuration #2: Coupling of the series APF via a magnetic amplifier.

Nm3 Ich = Nm1 Idc . (11)

Therefore, the current Ich cancels the effect of the dc current


Idc , preventing the APF transformer from saturating [33], [34].
With this arrangement, the load current Idc tends to saturate
the core material where no further magnetization is induced by
increasing the field intensity (H). However, the control winding
current Ich counters the load current effect by demagnetizing
the core and forces the operating point away from the saturation
region, as illustrated in the BH curve in Fig. 5(b). The series
APF is now isolated from the power system, and no dc cur-
rent is induced across the transformer APF-side winding from
the other two windings. An auxiliary dc source is necessary
in the APF inverter dc side. According to the given voltage
reference, the APF produces the required harmonic voltage,
which is transferred to the transformer converter-side winding,
and cancels the converter voltage harmonics. The number of
turns Nm3 is low in the low-voltage (LV) prototype; however,
a high number of turns can be used in an MV system to lower
the control winding current Ich . The transformer turn ratio is
chosen so that the inverter dc-side voltage source can match
the dc-side voltage of the shunt APF connected to the input
side. A common dc link can be used for both a three-phase
shunt APF and the series APF (and the source for the dc
compensating winding). That is, the proposed series APF can
be designed to be back-to-back coupled to the controlled dc
bus of a shunt APF connected to the converter ac side. This
saves cost and reduces complexity. This coupling technique to
Fig. 5. (a) Series APF transformer and (b) BH curve and effect of the
control winding current.
form a unified power flow controller is the subject of subsequent
publications.
Nm2 turns is connected to the APF, where each injected series Different controlled current sources can be used to generate
voltage harmonic contributes the control winding current Ich . For simplicity, a current-
controlled class A chopper, shown in Fig. 6, is used. A
En = 4.44fn Nm2 AB (10) bidirectional dc chopper is needed for fast dc current reduction
(determined by the time constant Lch /Rch ) and bidirectional
where En is the nth rms voltage of the winding, fn is the power flow in systems that reverse the current direction as
injected harmonic frequency, A is the core cross-sectional area, opposed to reversing the voltage.
and B is the flux density. The harmonic components accumu- According to the closed control loop, variation of the chop-

late, adding to the flux. The dc control winding of Nm3 turns per reference current level Ich changes the reference voltage

is connected to an auxiliary controlled dc current source. The level vr . Consequently, the duty cycle changes so as to
HAMAD et al.: MV 12-PULSE CONVERTER: OUTPUT VOLTAGE HARMONIC COMPENSATION USING A SERIES APF 47

Fig. 7. Twelve-pulse converter follows the proposed power locus with the series APF inserted into the dc side via a magnetic amplifier.

guarantee that the control winding current Ich tracks the ref- the converter load current may represent the dc-link current of
erence current. Based on the transformer configuration and an invertermotor set. The power given to the motor can be
winding arrangement for the converter-side winding and the controlled by controlling the inverter modulation index while
control winding (11), this current prevents the magnetic am- maintaining a constant dc-link current or by controlling the dc-
plifier from saturating. Since power flow in this application is link current while the inverter operates at a constant modulation
unidirectional, a single-quadrant dc chopper is used with the index. Both possibilities are catered for with the system block
magnetic amplifier as an LV high-current controlled current diagram shown in Fig. 7. The average load current is used in the
source which circulates the chopper output current in the low- two controlling loops, namely, a control winding current loop
resistance control winding. This load resistance determines and a constant-load-current control loop. In the load current
the maximum steady-state chopper current when 1. The control loop, irrespective of the load type, the actual load
switching frequency fch is 10 kHz, and a smoothing inductance current should track a given reference, and the proposed power
Lch of 10 mH is used to ensure continuous Ich with low ripple locus algorithm is applied to generate the required firing angles
current [35]. Also, this inductance presents high impedance to change the converter output voltage and keep the load current
(required of a current source) to current changes in the other constant. Hence, varying the reference load current changes
two windings. The current source response, determined by the the converter firing angles, in compliance with the proposed
dc source and inductance and time constant Lch /Rch , should be power locus, and proportionally changes the control winding
better than the dc current response required of the main ac/dc current.
converter. DC-side compensation of the 12-pulse converter using the
series APF with a magnetic amplifier is initially investigated
using MATLAB. The system has a static inductive load of
VI. O UTPUT VOLTAGE C OMPENSATION OF A 12-P ULSE
100 mH and a variable resistance. The reference load current
C ONVERTER U SING A S ERIES APF W ITH
Idc is 100 A. The turn ratio of the series APF transformer Nm1 :
A M AGNETIC A MPLIFIER
Nm2 : Nm3 is 2 : 1 : 2. The chopper (< 5% of the 12-pulse
The series APF with a magnetic amplifier is used to com- converter voltampere rating) is controlled to achieve a con-
pensate the 12-pulse converter output voltage harmonics. The trol winding current Ich of 100 A. For a supply voltage of
steady-state performance of the dc-side-compensated converter 3.3 kV, the dc-bus voltage of the series APF inverter Vdc(s)
is investigated while the converter tracks the power locus in is 1000 V (half the maximum peak of the converter harmonic
Fig. 1. This power locus is based on a constant and ripple- voltage). The magnetic amplifier reduces the series APF in-
free load current for the required active power range. The verter current by eliminating the dc component. This allows
load may be either static or dynamic. A dynamic load may an increased switching frequency fsw(s) limit for the same
draw either constant or variable dc current. As an example, inverter dc-side voltage and consequently improves the filtering
48 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 1, JANUARY 2014

TABLE I
O UTPUT VOLTAGE AND L OAD VOLTAGE H ARMONIC P ROFILE

voltage (VL ) are shown in Fig. 8(a)(c), respectively. The


frequency spectra of Vo and VL are shown in Fig. 8(d) and
(e), respectively. After the compensation, the load voltage RF
improves from 41.5% to 3.6%. The individual harmonic factors
for the four dominant harmonic components are improved, as
illustrated in Table I. The actual load current Idc waveform
after activating the series APF is shown in Fig. 8(f). The
control winding current is controlled at 100 A, as shown in
Fig. 8(g). This configuration requires a low APF current, as
shown in Fig. 8(h). The series APF with the magnetic amplifier
achieves the compensation objectives by mitigating the out-
put voltage harmonic, improving the RF with minimum APF
current.
Fig. 9 shows some simulation results for a step change in
the operating point (Pp.u. , Qp.u. ) from (0.866 p.u., 0.5 p.u.) to
(0.5 p.u., 0.5 p.u.) without a smoothing inductance. The firing
angles (1 and 2 ), in accordance with the proposed power
locus, change from (30 and 30 ) to (90 and 0 ), respectively.
Fig. 9(a) shows the converter output voltage (Vo ), Fig. 9(b)
shows the load voltage, and Fig. 9(c) illustrates the load current.
Fig. 8. DC-side compensation of a 12-pulse converter using a series APF.
(a) Converter output voltage Vo , (b) compensation voltage vcs , (c) compensated The converter output voltage and load voltage harmonic profile
load voltage VL , [(d) and (e)] load voltage spectra before and after compensa- for a load step change are given in Table II.
tion, (f) load current Idc after activating the series APF, (g) control winding Fig. 9 shows that the series APF can follow the load variation
current Ich , and (h) APF current ics .
and improves the RF of both the load voltage and load current.
efficiency [14], [35]. The switching frequency fsw(s) of the Also, the results confirm that the series APF minimizes the
APF H-bridge inverter is 5 kHz. The required passive filter at required smoothing inductance. However, as the firing angle
the APF inverter output to filter the switching harmonics and to increases to 90 , the voltage harmonic factors and RF pro-
pass the compensating dominant harmonic orders is designed gressively increase, as indicated in Table II [37]. The series
using compensation effects on the harmonic factors and RF of the
12-pulse converter dc side, operating in the rectification mode,
1 are shown in Fig. 10(a) and (b). The load is modeled as a current
ff =  . (12)
2 Lf C f source controlled at 100 A, and the firing angles are generated
according to the proposed power locus. The improvement of
In this study, the passive filter elements Lf and Cf are the four dominant individual harmonic factors is shown in
15 mH and 0.3 F, respectively, to give a break frequency ff of Fig. 10(a). The series APF improves the load voltage RF as
2.37 kHz. shown in Fig. 10(b).

A. Simulation Results B. Experimental Results


The load resistance is adjusted to 22.3 while the reference A 2-kVA 415-V three-winding
star/star/delta transformer,
load current is set at 100 A. From the load current loop, the with a turn ratio of 2:1: 3, functions as the front-end trans-
generated firing angles (1 and 2 ), according to the pro- former of the 12-pulse system which is implemented to
posed power locus, are 90 and 0 , respectively. This loading emulate the simulated MV system. The supply voltage vs
condition represents the operating point of (Pp.u. , Qp.u. ) = is 170 V, and the converter with the series magnetic am-
(0.5 p.u., 0.5 p.u.) on the power locus. The simulation results plifier APF feeds an inductive dc load of Idc = 1 A. The
are shown in Fig. 8(a)(h). The converter output voltage (Vo ), auxiliary dc-source voltage Vdc(s) is 110 V. The test-rig picture
the compensation voltage (vcs ), and the compensated load appears in the Appendix. The experimental results when the
HAMAD et al.: MV 12-PULSE CONVERTER: OUTPUT VOLTAGE HARMONIC COMPENSATION USING A SERIES APF 49

Fig. 9. DC-side compensation of a 12-pulse converter using a series APF with a unit step load change. (a) Converter output voltage Vo , (b) compensated load
voltage VL , and (c) load current.

TABLE II dependent on the load type. When feeding an invertermotor


O UTPUT VOLTAGE AND L OAD VOLTAGE H ARMONIC
P ROFILE FOR A L OAD S TEP C HANGE set, it is mandatory to have Ldc large enough to minimize
the ripple in the dc-link current and to decouple the two
converter systems. The series APF can minimize the dc-link
current ripple without a smoothing inductance, as shown in
Figs. 8 and 11, where the load voltage ripple is minimized as
indicated in Table I, which reflects on the load current ripple;
hence, compensation minimizes the inductance necessary to
decouple the two systems. The converter-side winding leakage
inductance can be designed to be the required decoupling
inductance (at the expense of converter underlap increase).
In this case, the transformer parameters may affect (delay
and/or attenuate) the compensation voltage to be injected;
consequently, voltage harmonic miscancellation takes place and
deteriorates the compensation quality. This can be avoided
converter operates at 1 = 90 , 2 = 0 , and (Pp.u. , Qp.u. ) = if another control loop is added, as shown in Fig. 12. The
(0.5 p.u., 0.5 p.u.) are shown in Fig. 11(a)(d). Fig. 11(a) shows actual compensation voltage measured across the converter-
the converter output voltage Vo , the injected compensation side winding is compared with the compensation reference
voltage vcs , and the compensated load voltage VL . Fig. 11(b) voltage, and the error is used to produce the PWM modulating
shows the load current Idc , the control winding current Ich , signal.
and the APF current ics . The frequency spectra of the load An open-loop control technique can be used to control the
voltage before and after compensation are shown in Fig. 11(c) series APF. The system can be offline trained under all load-
and (d), respectively. After compensation, the load voltage ing conditions to determine the harmonic modulating signal
RF improves from 41% to 10%. The practical results tend information, i.e., magnitudes and phase angles, required to
to verify the simulation results, but harmonic miscancellation achieve proper voltage harmonic compensation. Moreover, the
is introduced due to signal processing delays. The individual signal information can account for all delay source effects in
harmonic factors indicated in Fig. 11(d) illustrate the effects the compensation system. The determined modulating signal
of the delay sources on the compensation quality, particularly information can be used for lookup tables to an artificial neural
for higher harmonic orders, where a fixed delay represents an network control system.
increasing phase angle error.

VIII. C ONCLUSION
VII. R ESULTS , D ISCUSSION , AND O BSERVATIONS
Thyristor ac/dc converters generate output voltage harmonics
The existence and the size of the dc-link smoothing inductor inversely dependent on the firing delay angle. Compensation of
Ldc in the ac/dc converter output and the load current are both the output voltage harmonics of a 12-pulse converter following
50 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 1, JANUARY 2014

Fig. 10. Performance parameters before and after compensation using a series APF: (a) Four dominant harmonic factors and (b) voltage RF. (----) Before
compensation and () after compensation.

the proposed power locus has been investigated with a series RFs, allowing the use of a smaller converter dc-link inductance.
APF inserted into the converter dc side. The series APF is The series APF can be connected either directly or through a
controlled to inject a compensation voltage that cancels the transformer. In the case of APF direct connection, the full-load
voltage harmonics in the converter dc side, thereby indirectly current flows in the APF inverter switches, which increases the
compensating load current harmonics. This improves the load power losses and requires switches of high current rating. The
HAMAD et al.: MV 12-PULSE CONVERTER: OUTPUT VOLTAGE HARMONIC COMPENSATION USING A SERIES APF 51

Fig. 12. Configuration #2: Coupling the series APF with a magnetic amplifier.

Fig. 13. Test rig photograph.

A PPENDIX
See Fig. 13.

R EFERENCES
[1] N. Akagi, Large static converters for industry and utility applications,
Proc. IEEE, vol. 89, no. 6, pp. 976983, Jun. 2001.
[2] B. K. Bose, Power Electronics and AC Drives. Englewood Cliffs, NJ,
USA: Prentice-Hall, 1986.
[3] B. Wu, High Power Converters and AC Drives. Piscataway, NJ, USA:
IEEE Press, 2006.
[4] P. E. Aqueveque, E. P. Wiechmann, and R. P. Burgos, On the effi-
ciency and reliability of high-current rectifiers, in Proc. IEEE PESC,
Jun. 1519, 2008, pp. 45094516.
[5] L. Wei, N. Guskov, R. A. Lukaszewski, and G. Skibinski, Miti-
gation of current harmonics for multi-pulse diode front end rectifier
Fig. 11. Practical results of series APF compensation: (a) Voltage waveforms, systems, in Conf. Rec. 14th IEEE IAS Annu. Meeting, Oct. 26, 2005,
(b) current waveforms, (c) spectrum of the converter output voltage Vo , and vol. 1, pp. 129137.
(d) spectrum of the load voltage VL after compensation. [6] H. Akagi, New trends in active filters for power conditioning, IEEE
Trans. Ind. Appl., vol. 32, no. 6, pp. 13121322, Nov./Dec. 1996.
APF can be inserted via a three-winding magnetic amplifier [7] N. Vazquez, H. Rodriguez, C. Hernandez, E. Rodriguez, and J. Arau,
Three-phase rectifier with active current injection and high efficiency,
transformer which does not saturate, which minimizes the IEEE Trans. Ind. Electron., vol. 56, no. 1, pp. 110119, Jan. 2009.
APF inverter current and power loss. The filter-side voltage [8] S. Choi, New pulse multiplication technique based on six-pulse thyristor
can be reduced according to the step-down ratio of the APF converters for high-power applications, IEEE Trans. Ind. Appl., vol. 38,
no. 1, pp. 131136, Jan./Feb. 2002.
isolating transformer. With this configuration, an auxiliary dc [9] I. A. Vargas, A. J. Forsyth, and F. J Zabalza, Capacitor voltage balancing
voltage source is required in the APF inverter dc side, and an techniques for a multi-pulse rectifier with active injection, in Proc. 24th
auxiliary controlled dc current source is required to inject an IEEE APEC, Feb. 1519, 2009, pp. 383389.
[10] J. F. Baird and J. Arrilaga, Harmonic reduction in D.C.-ripple reinjec-
antisaturation current into the control winding of the magnetic tion, Proc. Inst. Elect. Eng.Gener., Transm. Distrib., vol. 127, no. 5,
amplifier. pp. 294303, Sep. 1980.
52 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 61, NO. 1, JANUARY 2014

[11] J. Arrillaga and M. Villablanca, 24-pulse HVDC conversion, Proc. [34] K. Harada, Y. Ishihara, and T. Todaka, A novel high power factor con-
Inst. Elect. Eng.Gener., Transm. Distrib., vol. 138, no. 1, pp. 5764, verter using a magnetic amplifier, IEEE Trans. Magn., vol. 32, pt. 2,
Jan. 1991. no. 5, pp. 50135015, Sep. 1996.
[12] W. Ping, C. Houquan, and Z. Zhixiong, Three-phrase active power fil- [35] M. H. Rashid, Power Electronics: Handbook. Don Mills, ON, Canada:
ter based on DSP for power distribution systems, in Proc. APPEEC, Academic, 2001.
Mar. 2731, 2009, pp. 15. [36] K. H. Ahmed, S. J. Finney, and B. W. Williams, Passive filter design for
[13] P. Wei, Z. Zhan, and H. Chen, A DSP-based active power filter for three- three-phase inverter interfacing in distributed generation, Elect. Power
phase power distribution systems, in Proc. ICCET, Jan. 2224, 2009, Qual. Util. (EPQU) J., vol. 13, no. 2, pp. 4959, May 2007.
vol. 1, pp. 210214. [37] G. K. Dubey, Thyristorised Power Controllers. New Delhi, India: Wiley
[14] A. M. Massoud, S. J. Finney, and B. W. Williams, Practical issues Eastern, 1986.
of three-phase, three-wire, voltage source inverter-based shunt active
power filters, in Proc. IEEE Int. Conf. Harmon. Qual. Power, 2004,
pp. 436441.
[15] S. Rahmani, N. Mendalek, and K. Al-Haddad, Experimental design of
nonlinear control technique for three-phase shunt active power filters,
IEEE Trans. Ind. Electron., vol. 57, no. 10, pp. 33643375, Oct. 2010.
[16] A. Bhattacharya and C. Chakraborty, A shunt active power filter with Mostafa S. Hamad received the B.Sc. and M.Sc. de-
enhanced performance using ANN-based predictive and adaptive con- grees from The Faculty of Engineering, Alexandria
trollers, IEEE Trans. Ind. Electron., vol. 58, no. 2, pp. 421423, University, Alexandria, Egypt, in 1999 and 2003,
Feb. 2011. respectively, and the Ph.D. degree in electrical engi-
[17] M. Odavic, V. Biagini, P. Zanchetta, M. Sumner, and M. Gegano, One- neering from the Faculty of Engineering, University
sample-period-ahead predictive current control for high-performance ac- of Strathclyde, Glasgow, U.K., in 2009.
tive shunt power filters, IET Power Electron., vol. 4, no. 4, pp. 414423, Since January 2010, he has been an Assistant
Apr. 2011. Professor with the Arab Academy for Science,
[18] H. Akagi and K. Isozaki, A hybrid active filter for a three-phase 12 Technology and Maritime Transport, Alexandria.
pulse diode rectifier used as the front end of a medium-voltage mo- His research interests include motor drives, power
tor drive, IEEE Trans. Power Electron., vol. 27, no. 1, pp. 6977, quality, flexible ac transmission systems, and
Jan. 2012. renewable energy systems.
[19] S. Rahmani, A. Hamadi, and K. Al-Hadad, A Lyapunov-function-based
control for a three-phase shunt hybrid active filter, IEEE Trans. Ind.
Electron., vol. 59, no. 3, pp. 14181429, Mar. 2012.
[20] X. Du, L. Zhou, H. Lu, and H. Tai, DC link active power filter for three-
phase diode rectifier, IEEE Trans. Ind. Electron., vol. 59, no. 3, pp. 1430
1442, Mar. 2012.
[21] J. Liu, P. Xanchetta, M. Degano, and E. Lavopa, Control design and Mahmoud I. Masoud (SM12) was born in
implementation for high performance shunt active filters in aircraft power Alexandria, Egypt, in 1974. He received the B.Sc.
grids, IEEE Trans. Ind. Electron., vol. 59, no. 9, pp. 36043613, (top of class with honors) and M.Sc. degrees from
Sep. 2012. The Faculty of Engineering, Alexandria Univer-
[22] Z. Chen, Y. Luo, and M. Chen, Control and performance of a cascaded sity, Alexandria, in 1996 and 1999, respectively,
shunt active power filter for aircraft electric power system, IEEE Trans. and the Ph.D. degree from HeriotWatt University,
Ind. Electron., vol. 59, no. 9, pp. 36143623, Sep. 2012. Edinburgh, U.K., in 2003.
[23] E. H. Watanabe, P. G. Barbosa, and J. A. Santisteban, Shunt-series active From 2003 to 2007, he was a Lecturer with the
power filter for rectifiers AC and DC sides, Proc. Inst. Elect. Eng.Elect. Electrical Engineering Department, The Faculty of
Power Appl., vol. 145, no. 6, pp. 577584, Nov. 1998. Engineering, Alexandria University. From February
[24] E. H. Watanabe and L. A. S. Pilotto, Series active power filter for the DC 2007 to August 2009, he was a Research Fellow
side of an HVDC transmission systems, in Proc. IPEC, Tokyo, Japan, with the Power Electronics and Energy Conversion Group, Department of
1990, pp. 10241030. Electronic and Electrical Engineering, University of Strathclyde, Glasgow,
[25] Y. Wang, G. Joos, and H. Jin, DC-side shunt-active power filter for phase- U.K. Since June 2009, he has been an Associate Professor with the Electrical
controlled magnet-load power supplies, IEEE Trans. Power Electron., Engineering Department, The Faculty of Engineering, Alexandria University.
vol. 12, no. 5, pp. 765771, Sep. 1997. From 2009 to 2011, he was with Beirut Arab University, Beirut, Lebanon.
[26] P. Hao, W. Zanji, and C. Jianye, Study on the control of shunt active He is currently with the Department of Electrical and Computer Engineering,
DC filter for HVDC systems, IEEE Trans. Power Del., vol. 23, no. 1, College of Engineering, Sultan Qaboos University, Muscat, Oman. His research
pp. 396401, Jan. 2008. interests include renewable energy systems, power electronics applications, and
[27] Z. Dongyuan, C. Jianye, W. Zanji, and Y. Wang, The active DC filter electrical machine drives.
in HVDC resolved by the multiple PWM inverters, in Proc. 35th IEEE
PESC, Jun. 2025, 2004, vol. 5, pp. 38893893.
[28] M. S. Hamad, M. I. Masoud, S. J. Finney, and B. W. Williams, Medium
voltage series connected 12-pulse compensated current source controlled
rectifier with novel front end transformer configuration, in Proc. 4th IET
Int. Conf. PEMD, York, U.K., Apr. 24, 2008, pp. 2732.
[29] M. S. Hamad, M. I. Masoud, S. J. Finney, and B. W. Williams, A new Barry W. Williams received the M.Eng.Sc. de-
power locus for the pq operation of series connected 12-pulse current gree from The University of Adelaide, Adelaide,
source controlled converter, in Proc. 39th IEEE PESC, Rhodes, Greece, Australia, in 1978 and the Ph.D. degree from the
Jun. 1519, 2008, pp. 22642270. University of Cambridge, Cambridge, U.K., in 1980.
[30] M. S. Hamad, M. I. Masoud, B. W. Williams, and S. Finney, Medium After seven years as a Lecturer with Imperial Col-
voltage 12-pulse converter: AC side compensation using a shunt active lege London, University of London, London, U.K.,
power filter in a novel front end transformer configuration, IET Power he was appointed Chair of Electrical Engineering
Electron., vol. 5, no. 8, pp. 13151323, Sep. 2012. with HeriotWatt University, Edinburgh, U.K., in
[31] High precision current transducers: LEM solutions for high precision 1986. He is currently a Professor with the University
current measurements, 2012. [Online]. Available: http://www.lem.com/ of Strathclyde, Glasgow, U.K., where he is also the
docs/marketing/LDK%20leaflet%20complete%20web.pdf Head of the Power Electronics and Energy Conver-
[32] W. Enright, J. Arrillaga, A. R. Wood, and F. P. Hidalgo, The smoothing sion Group, Department of Electronic and Electrical Engineering. His teaching
transformer, a new concept in DC side harmonic reduction of HVDC covers power electronics (on which topic he has authored a textbook) and
schemes, IEEE Trans. Power Del., vol. 11, no. 4, pp. 19411947, drive systems. His research activities include power semiconductor modeling
Oct. 1996. and protection, converter topologies, soft-switching techniques, and application
[33] C. W. Lufcy, A survey of magnetic amplifiers, Proc. IRE, vol. 43, no. 4, of application-specified integrated circuits and microprocessors to industrial
pp. 404413, Apr. 1955. electronics.

You might also like