Model EC-25
Extended Coverage Upright Sprinklers
K-Factor 25.2 (360)
General NOTICE
The Model EC-25 Sprinklers described
Description herein must be installed and main-
tained in compliance with this docu-
TYCO Model EC-25 Extended Cover- ment, as well as with the applicable
age Upright Sprinklers are UL Listed standards of the National Fire Pro-
standard response, extended cover- tection Association, in addition to the
age sprinklers for Storage Protection standards of any other Authorities
(Area/Density) and FM Approved quick Having Jurisdiction (for example, FM
response, extended coverage sprin- Global). Failure to do so may impair
klers for storage and non-storage ap- the performance of these devices.
plications. Their use is especially ad-
vantageous as a means of decreasing The owner is responsible for maintain-
the number of required sprinklers to ing their fire protection system and
protect occupancies requiring an area/ devices in proper operating condition.
density application of water. The installing contractor or sprinkler
manufacturer should be contacted
These sprinklers offer a maximum with any questions.
coverage area of 196 ft (18,2 m),
which is almost double the area of-
fered by standard coverage sprinklers Model/Sprinkler
used for similar applications.
The Model EC-25 Sprinklers comply Identification Physical Characteristics
Frame Brass
with the criteria for the protection of
retail stores as described in the 2010 Number (SIN) Deflector Copper
Compression Screw Stainless
Edition of NFPA 13, Section 20.3. TY9128 Steel
Where the FM Approval is utilized, the
Model EC-25 Sprinkler has success-
fully undergone full-scale fire testing at
Technical Hook Monel
Strut Monel
FM Global for ceiling-only storage ap-
plications. When used in conformance
Data Link Assembly Solder, Nickel
Button Brass
with applicable FM Global Property Approvals
UL and C-UL Listed Sealing Assembly. . . . . . . . . Beryllium
Loss Prevention Data Sheets, the
Nickel w/TEFLON
Model EC-25 Sprinkler provides low FM Approved
hydraulic demand, the spacing ad- NYC under MEA 355-01-E Ejection Spring Inconel
vantages of extended coverage, and Deflector Nut Brass
the obstruction benefits of an upright (Approvals only apply to the service
sprinkler. conditions indicated in the Design Cri-
teria section.)
For more information on applications
and benefits of the Model EC-25 Sprin- Maximum Working Pressure
kler, refer to the available white papers 175 psi (12,1 bar)
at www.tyco-fire.com. Pipe Thread Connection
1 inch NPT
ISO 7-R1
IMPORTANT
Discharge Coefficient
Always refer to Technical Data
K=25.2 GPM/psi1/2 (362,9 LPM/bar1/2)
Sheet TFP700 for the INSTALLER
WARNING that provides cautions Temperature Ratings
with respect to handling and 165F (74C)
installation of sprinkler systems and
214F (101C)
components. Improper handling
and installation can permanently Maximum Coverage Area
damage a sprinkler system or its 196 ft (18,2 m)
components and cause the sprinkler
to fail to operate in a fire situation or Finish
cause it to operate prematurely. Natural Brass

Page 1 of 4 JUNE 2012 TFP213


TFP213
Page 2 of 4

3 TEMPERATURE 2-9/16" DIA.


10 RATING (65,0 mm)
2

1- Frame
2- Deflector
4
3- Compression Screw 3-3/4"
4- Hook (95,3 mm)
5
5- Strut
6- Link Assembly 6 9/16"
7- Button (14,3 mm)
8- Gasketed Spring Plate 9 WRENCH NOMINAL
9- Ejection Spring FLATS MAKE-IN
10- Deflector Nut 8

7
1" NPT
1

FIGURE 1
MODEL EC-25 EXTENDED COVERAGE
UPRIGHT SPRINKLER

Operation The maximum coverage area per


sprinkler is 196 ft. (18,2 m).
Ordinary and intermediate tem-
perature rated Model EC-25 Sprin-
The fusible link assembly is com- klers have been investigated for use
The maximum distance between
prised of two link halves that are in high-piled storage occupancies
sprinklers is 15 feet (4,6 m) when the
joined together by a thin layer of sol- at the hydraulic demand normally
coverage area does not exceed 144
der. When the rated temperature is associated with high temperature
ft. (13,4 m), and the maximum dis-
reached, the solder melts and the sprinklers. As such, the Model EC-
tance between sprinklers is 14 feet
two link halves separate, allowing the 25 Sprinklers are listed storage
(4,3 m) when the coverage area
sprinkler to activate and flow water. sprinklers having a K-factor greater
does not exceed 196 ft. (18,2 m).
than 11.2 (161,4) and having ordi-
Design Criteria The minimum distance between
sprinklers is 8 feet (2,44 m).
nary and intermediate temperature
ratings (that is, 165F or 74C and
The minimum flow requirement is 214F or 101C). Consequently, the
UL AND C-UL LISTING based on the design density applied Model EC-25 Sprinklers, in accor-
CRITERIA over the actual coverage area per dance with NFPA 13, may be used in
The TYCO Model EC-25 Extended sprinkler. conjunction with the density curves
Coverage Upright Sprinklers (TY9128) for high temperature sprinklers.
are UL and C-UL Listed for installation For example: when sprinkler spacing
is 14ft. x 12ft.-6in. (4,3 m x 3,8 m) or NFPA obstruction rules for Extended
in accordance with the extended cov- Coverage Sprinklers must be utilized.
erage upright spray sprinkler require- 175 ft (16,3 m), and the design
ments of NFPA 13 or other applicable density is 0.6 GPM/ft (24,4 mm/
min), the sprinkler design flow rate System Type
NFPA standards when used in con- Wet pipe, dry pipe, and preaction sys-
junction with the following guidelines: is 105 GPM (397 LPM) and the re-
quired design pressure is 17.4 psi tems are acceptable.
Suitable for the protection of extra (1,2 bar).
hazard and high-piled storage occu-
pancies where area/density design The minimum clearance between
criteria are provided. the deflector and the top of storage
is 36 inches (0,9 m). For clearances
Suitable for unobstructed or of 36 inches (0,9 m) up to 48 inches
noncombustible obstructed (1,21 m), the minimum design pres-
construction. sure is 22 psi (1,52 bar). For clear-
The Model EC-25 Sprinklers hav- ances of 48 inches (1,21 m) and
ing been specifically tested and greater, the minimum design pres-
listed for noncombustible obstruct- sure is established by the minimum
ed construction are suitable for use flow requirement. However, the
within trusses or bar joists hav- pressure can never be less than 7
ing noncombustible web members psi (0,5 bar).
greater than 1 inch (25.4 mm) when
applying the 4 times obstruction cri-
teria rule defined under Obstruc-
tions to Sprinkler Discharge Pattern
Development.
TFP213
Page 3 of 4

FM APPROVAL CRITERIA
The TYCO Model EC-25 Extend-
Installation
ed Coverage Upright Sprinklers The TYCO Model EC-25 Upright
(TY9128) are FM Approved to be uti- Sprinklers are to be installed in accor- WRENCH
lized in accordance with the following dance with the following instructions: RECESS
guidelines. Damage to the fusible Link Assembly
during installation can be avoided by
Application handling the sprinkler using only the
The Model EC-25 Extended Coverage frame arms and the appropriate sprin-
Upright Sprinklers are FM Approved kler wrench. Do not grip or apply any
ceiling-level Storage Sprinklers for force to the Fusible Link Assembly.
storage occupancy hazards and oth- Damaged sprinklers must be replaced
er similar high heat release type fires. immediately. "FITTING SIDE"
When compared with other FM Ap- TOWARDS SPRINKLER
proved Storage Sprinklers, the Model A leak-tight 1 inch NPT sprinkler joint FITTING
EC-25 Sprinkler provides low hydraulic should be obtained by applying a min-
demand, the spacing advantages imum-to-maximum torque of 20 to 30
of extended coverage, and the FM ft.lbs. (26,8 to 40,2 Nm). Higher levels
obstruction benefits of an upright of torque may distort the sprinkler in-
sprinkler. let with consequent leakage or impair-
ment of the sprinkler. FIGURE 2
Model EC-25 Sprinklers should be
used in conformance with applicable 1. Install the Model EC-25 Sprinkler W-TYPE 1
FM Global Property Loss Prevention in the upright position. SPRINKLER WRENCH
Data Sheets. 2. With pipe-thread sealant applied,
hand-tighten the sprinkler into the
Hydraulic Design
To determine the hydraulic design for
sprinkler fitting. Do not apply any Care and
force to the Link Assembly, and
the Model EC-25 Sprinkler refer to the
applicable FM Global Property Loss
handle the Model EC-25 Sprinkler Maintenance
only by the Frame arms. The TYCO Model EC-25 Sprinkler
Prevention Data Sheet.
3. Wrench-tighten the Model EC-25 must be maintained and serviced
System Type Sprinkler using only the W-Type 1 in accordance with the following
Wet-pipe systems only. Sprinkler Wrench (Figure 2) and by instructions.
fully engaging (seating) the wrench Before closing a fire protection system
Sprinkler Spacing on the sprinkler Wrench Flats. main control valve for maintenance
The maximum coverage area per 4. After installation, inspect the Link work on the fire protection system
sprinkler is 196ft (18,2m). The mini- Assembly of each Model EC-25 that it controls, obtain permission to
mum coverage area per sprinkler is Sprinkler for damage. In particu- shut down the affected fire protection
100ft (9,3m). The maximum distance lar, verify that the Link Assem- system from the proper authorities
between sprinklers is 14 ft. (4,3 m). The bly and Hook are positioned as and notify all personnel who may be
minimum distance between sprinklers illustrated in Figure 1, and that affected by this decision.
is 10 ft. (3,05 m). the Link Assembly has not been Inspection, testing, and maintenance
Note: When a wall or obstruction bent, creased, or forced out of must be performed as indicated be-
makes a minimum spacing of 10 ft. its normal position in any way. low and in accordance with the local
(3,05 m) impossible, consult FM Glob- Damaged sprinklers must be re- requirements and/or national codes.
al Property Loss Prevention Data placed immediately. Any impairment must be immediately
Sheet 2.0 for applicable guidelines. corrected.
Sprinkler Location The owner is responsible for the in-
Locate sprinklers with respect to the spection, testing, and maintenance of
ceiling/roof in accordance with FM their fire protection system and devic-
Global Property Loss Prevention Data es in compliance with this document,
Sheet 2.0. as well as with the applicable stan-
dards of any authorities having juris-
Obstructions diction. Contact the installing contrac-
Follow the obstruction requirements tor or product manufacturer regarding
as detailed in FM Global Property Loss any questions.
Prevention Data Sheet 2.0. Automatic sprinkler systems are rec-
ommended to be inspected, tested,
Other Details and maintained by a qualified Inspec-
All other design details should be in tion Service in accordance with local
accordance with FM Global Property requirements and/or national codes.
Loss Prevention Data Sheet 2.0 as well
as any other applicable FM Global
Data Sheet.
TFP213
Page 4 of 4

Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product description and Part
Number (P/N).

Sprinkler Assemblies with 1-Inch


NPT Connections
Specify (temperature rating), natural
brass, Model EC-25 Extended Cov-
erage Upright Sprinkler (TY9128), and
P/N (below).
165F (74C) . . . . . . . . . . . . . . P/N 58-450-1-165
214F (101C) . . . . . . . . . . . . . P/N 58-450-1-214
Special Order
Sprinkler Assemblies with ISO 7/1
Thread Connections
Specify (temperature rating), natural
brass, Model EC-25 Extended Cov-
erage Upright Sprinkler (TY9128) with
thread connection per ISO 7/1, and
P/N (below).
165F (74C) . . . . . . . . . . . . . . . P/N 58-451-1-165
214F (101C) . . . . . . . . . . . . . . P/N 58-451-1-214

Sprinkler Wrench
Specify W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025.

Copyright 2011 Tyco Fire Protection Products. All rights reserved.