You are on page 1of 16

MiCOM P441 P442

Distance Protection
Relays

MiCOM P441 and P442


Distance Protection Relays

T&D
Protection & Control
MiCOM P441 and P442
Full Scheme Distance Protection Relays

Introduction Current reversal guard protection Monitoring


and parallel line compensation
MiCOM Distance Protection Relays Trip circuit monitoring
provide flexible and reliable Power swing blocking
Breaker state monitoring
integration of protection, control, Switch-On-To-Fault and zone-
Breaker condition monitoring
monitoring and measurement selectable Trip-On-Reclose protection
functions.
Other Protection Communications
Extensive functionality provides
complete protection and control for a Functions A choice of protocols
wide range of overhead lines and Directional/non-directional phase Front and rear communication ports
underground cables from distribution overcurrent
to transmission voltage levels. Stub bus protection
Diagnostics
Emergency overcurrent on VT failure Power-up diagnostics
Models Available Continuous self monitoring
Directional/non-directional earth
P441 Distance Protection Relay, fault Test facilities
three phase tripping logic and three-
pole autorecloser, 8 opto inputs, Channel-aided directional earth fault
User Friendly Interface
14 output relays with option for Directional/non-directional negative
synchronism check. sequence overcurrent Liquid crystal display with backlight
P442 Distance Protection Relay, Under/overvoltage Programmable LED indications
single and three-phase tripping logic Broken conductor Password protection
and one and three-pole autorecloser. Circuit breaker failure Optional secondary front cover
This version has 16 opto-inputs and
Voltage transformer supervision
21 output relays. Software Support
In addition to the synchronism check Current transformer supervision
In conjunction with MiCOM S1,
option, IRIG-B time synchronisation is
Control provided separately:
available as is a fibre optic interface
for rear port IEC60870-5-103 Settings editor
Four shot autoreclose (1 and/or
communication option. 3-pole) with or without synchronism Programmable scheme logic editor
check Viewing of fault diagnostics and
Distance Protection Circuit breaker control measurements
Dual distance protection algorithms Programmable scheme logic Disturbance recorder viewer
Typical operating time 1.25 cycles Programmable inputs and outputs Application
Five independent zones of protection Four setting groups
Zone 1 extension scheme MiCOM P441 and P442 Numerical
Measurements Distance Relays provide
Independent quadrilateral comprehensive distance protection for
characteristics for phase-to-phase Comprehensive range of the following applications: lines,
and phase-to-earth faults measurement values including cables, tapped lines, lines with
Range of pre-programmed channel instantaneous and derived values. multiple zero sequence sources,
aided schemes and user-definable non-homogeneous lines, series
channel aided scheme logic Post Fault Analysis compensated lines and parallel lines.
Weak infeed and echo logic Fault location The resistive reach coverage allows
Loss of load protection application to short lines and cable
Event and fault records
protection. It provides complete
Disturbance records protection of solidly earthed systems
from distribution to transmission
voltage levels.

2
Using well-proven, patented techniques
3Y
to directionalise, and making full use
of digital memory, the relays can be 3Y

applied in situations that can cause MiCOM P441/ P442


85
classic distance implementations to 59

maloperate (cross-country faults, 46 46 50 50 50 / 51 VTS/ 21P 78 67 50 / 21G 67N 50N/


27
BC BF 51 FF CTS 27 51N
close-up faults, etc.).
The MiCOM P441 and P442 are 1
complete with a library of scheme 25 /
79
logic applications as well as user
21G Ground distance protection, 67/46 Negative sequence overcurrent VTS Voltage transformer supervision
programmable scheme logic, 3 forward elements, 1 reverse 50/27 Switch onto fault and trip on CTS Current transformer supervision
metering, logging, oscillography and element,1 selectable element, reclose
quadrilateral zones 50BF Breaker failure and backtrip
advanced communication abilities. 50/51 Phase overcurrent, DT or IDMT 46BC Broken conductor detection
21P Phase distance protection,
Many back up functions are also 3 forward elements,1 reverse 50/51N Ground over current, DT or IDMT 25 Check synchroniser
selectively available. Windows-based element,1 selectable element, 51FF Fuse failure overcurrent 79 Autorecloser
software tools are provided to ease quadrilateral zones 67 Phase directional overcurrent 59 Overvoltage
85 Channel-aided protection
setting, view data from the relays, and 67N DEF , communication aided 27 Undervoltage
50 Phase overcurrent,High set,for 78 Power swing detection,used to
analyse faults. Stub bus application selectively permit or block tripping
A range of communication protocols
allows connection with many external
devices thus providing remote Figure 1: Protection line diagram
programming, control and extraction
of information.
Figure 1 is a single line diagram Enhanced reliability for all faults The impedance calculations are
giving the protection functions of the through two different measurement performed on each waveform sample
MiCOM P441 and P442 relays. techniques. for all six loops AN, BN, AB, BC and
For clarity, current related functions are The software tools contained in S1 CA making this a true full scheme
shown in red circles, voltage related allow intuitive interface to the relay, numerical distance relay.
functions in green squares, and greatly lessen training and
current/voltage related functions in Delta algorithms
documentation commitment. The post
brown octagons. The Delta algorithms are based on
fault analysis capabilities allow
transient components. This is a
Operations personnel to make
Benefits of Use informed decisions about relay and
patented technique with 10 years
MiCOM relays offer fast, secure experience in various relays.
system operation.
clearing for any type of fault. The current and voltage values are
The unique distance and continuously predicted, based on the
Distance Protection
directionalising implementations last two cycles, and the predicted
Functions values are compared with the values
provide an optimum mix of speed,
selectivity and security for difficult fault Three phase tripping with faulted actually measured. A fault is detected
types and application situations. phase indication is provided for all if the predicted and measured values
In addition, the P441 and P442 offer protection functions. are different (I and V).
the following benefits: In addition model P442 allows single- Faulted phase selection is made by
Standardised relay selection for all phase tripping for the distance comparing the superimposed currents
applications. protection and the channel-aided DEF for each phase.
protection. The directional elements use the fault-
Simplified spares holding with dual
rated CT inputs. generated changes in the voltage and
Dual distance protection current signals at the relay location,
No need for additional equipment algorithms referred to as the superimposed
(voltage protection, current
The operation of the MiCOM relays is signals, to determine the direction of a
protection, autorecloser, synchronism
based on the combined use of two fault. During a fault the voltage signal
check, disturbance recorder,
types of fault detection: changes by V and the current signal
measurement devices).
Calculation of the superimposed changes by I.
Simple system integration through a
current and voltage values that are
choice of protocols.
characteristic of the fault ("Delta"
Faster fault diagnosis with fault algorithms).
information, disturbance and event
Measurement of impedance values
records.
("Conventional" algorithms).
Maximise protection availability
This dual algorithm principle offers
through extensive self-monitoring
dependable detection of all types of
and self-test, system supervision
faults occurring on the network. Proven
(CT, VT, trip circuit monitoring)
quadrilateral distance characteristics
issue the trip command to clear any
fault.

3
Voltage: Current:
F
If If
Vf
Vf
(i) Faulted

Ip F
Vp Ip

(ii) Unfaulted Vp VP
(predicted)

I F
V I
ZS
V t=0
t=0 t=0

(iii) Superimposed

Figure 2: Relationship between the superimposed and the faulted power system

Figure 2 illustrates that the faulted continuously. On fault inception, the when the channel associated with
power system can be considered to tripping logic criteria are started to an aided scheme has failed.
consist of two parts: the unfaulted provide secure, fast tripping. Zone 2 forward directional
system and the superimposed system. time-delayed trip zone.
The superimposed system defines the Distance to fault
Zone P forward or reverse
changes caused by the fault. The distance to the fault is measured
programmable directional time
by discriminating between the voltage
The directional elements process the delayed trip zone.
drop on the line and that caused by
signals V and I obtained from the Zone 3 forward directional
the fault. This removes the error due to
superimposed system (see Figure 2(iii)) time delayed trip zone.
the fault resistance irrespective of the
and calculate the sign of the Zone 4 reverse directional
load current. A least squares method is
superimposed energy: time delayed trip zone.
used to get the algorithms to converge
for a forward fault V and I are of rapidly. Four independent earth fault residual
opposite polarity (sign of energy: compensation coefficients are
negative) and Quadrilateral characteristics provided for non-homogeneous line
for a reverse fault V and I are of Two independently settable impedance protection, or the back-up protection of
the same polarity (sign of energy: characteristics (for earth faults and transformers.
positive). phase faults) provide five zones of
The directional and phase selection protection each as shown in Figure 4. Power swing blocking
elements will change their decision if They are: Power swing is detected when the
required, for example during evolving Zone 1 forward directional instant- impedance passes through the R and
or cross-country faults. aneous or time-delayed trip zone X zone in more than 5 ms.
and Any of the zones (Z1/Z1X, Z2, Z3 or
Conventional algorithms
Zone 1X forward directional used in Zp) can be selectively blocked.
Conventional algorithms in the relays Zone 1 extension schemes with Three separate elements can be set to
use impedance measurement criteria autoreclosure, or as a time-delayed override the power swing blocking in
with quadrilateral-shaped trip zone. Zone 1X can be enabled case of major faults.
characteristics. This algorithm is used
for the time-delayed zones when the
superimposed delta quantities have X
disappeared. Phase selection is X
Zone 3, T3
enhanced for high current faults by Zone P, Tp
utilising current phase selection. If the Figure 3: Impedance characteristic
fault current is low, impedance phase
Zone 2, T2
selection is used. Zone 1X, T1
Zone 1, T1
A fault is detected when the
R1Ph R2Ph RpPh R3Ph R
impedance crosses the starting R1G R2G RpG R3G
characteristic (see Figure 3). R
Power- swing
Zone P, Tp boundary
reverse
Both algorithms independently monitor
Zone 4, T4
the system, measuring the impedance Starting characteristic
(fault detection)
loops and calculating delta values

4
Switch-on-to-fault (SOTF)/ Other Protection Negative sequence
Trip on reclose (TOR) Functions overcurrent
The Switch-On-To-Fault and Trip On Directional comparison scheme Negative sequence overcurrent
Reclose protection offers fast fault protection can be set as either
The programmable scheme logic (PSL)
clearance immediately following circuit non-directional or directional
provides many scheme possibilities.
breaker closure. TOR can be (forward/reverse), and can operate
An example of this is to create a
configured to trip only for faults in for remote phase-phase and phase-
directional comparison scheme
selected zones so as to make sure the earth faults even with delta-star
integral to the relay.
fault is on the protected line. They can transformers present.
also be directionalised by distance
schemes. 21 forward Earth fault elements
to remote
An overcurrent threshold (I>3) is from remote Two functions of earth fault protection
available to accelerate the trip on high are available. They operate from a
fault current. residual current that is derived
internally from the summation of the
The SOTF protection is blocked when Directional three phase currents.
2nd harmonic is detected in order to t
comparison

avoid maloperation due to transformer The directionality of the earth fault


magnetising inrush. elements is provided by either zero
The PSL can be used to initiate an
sequence voltage or negative
external signal send when a forward
Channel-aided scheme logic sequence voltage.
fault directional decision is made.
The relay is fitted with a The relay at the other end can use this Channel-Aided Directional Earth Fault
comprehensive selection of IEC and signal receive with its own forward ("Aided DEF")
ANSI/IEEE compatible channel-aided fault decision to initiate a trip thus Directional comparison protection
schemes for 2 terminal feeders: creating a unit protection of the whole operates in conjunction with one or
Permissive Underreach Protection, line. two remote end relays. The Aided DEF
Accelerating Zone 2 (PUP Z2), protection is able to trip single or
Phase overcurrent three-pole using permissive or blocking
Permissive Underreach Protection
Tripping via Forward Start Four independent stages are available scheme logic. The transmission
(PUP forward), for the phase overcurrent protection. channels may be the same as those
Two stages (I>1 and I>2) may be used by the distance protection or may
Permissive Overreach Protection with
selected as non-directional or be independent.
Overreaching Zone 1
(POP Z1), directional (forward/reverse).
Stand-by Earth Fault ("SBEF")
Permissive Scheme Unblocking logic All stages have definite time (DT)
delayed characteristics, two of the There are two stand-by earth fault
(Loss of Guard, Loss of Carrier) elements. Both can be set directional
stages (I>1 and I>2) may also be
Blocking Overreach Protection with or non directional. Each can be set
independently set to one of nine
Overreaching zone 2 (BOP Z2), either DT or IDMT time-delayed.
inverse definite minimum time (IDMT)
Blocking Overreach Protection with curves (IEC and IEEE). The IDMT Stand-by earth fault elements always
Overreaching zone 1 (BOP Z1), stages have a programmable reset trip three pole and have an optional
Weak Infeed and Echo logic. timer for grading with timer hold facility on reset. They may
For double circuit lines, current electromechanical relays and to be enabled at the same time providing
reversal guard logic is available to reduce clearance times where discriminative directional earth fault
prevent tripping of a healthy line. intermittent faults occur. protection and back-up standby earth
The I>1 and I>2 stages are also fault protection in the same device.
In addition to the pre-programmed
schemes, the relays allow the creation used for emergency overcurrent To maintain operation during periods
of customised channel-aided schemes. protection in case of a VT of VT malfunction, a back-up VTS fail
malfunction (MCB trip or fuse definite time function can be applied
failure). to both elements. On VTS pick-up both
Loss of load accelerated tripping
The I>3 DT stage is used as part of are forced to non-directional operation
The loss of load logic provides fast and are subject to a revised DT time
fault clearance for faults over the the SOTF/TOR elements and to
detect close-up faults. delay, user set to mimic distance zone
whole of a double end fed protected time delays.
circuit for all types of fault, except The I>4 DT stage is used for Stub
three phase. It does not require a Bus protection in 11/2 circuit breaker Under/overvoltage
signalling channel but can be enabled feeding arrangements.
Under/overvoltage protection may be
when the channel associated with an The phase fault elements direction is configured to operate from either
aided scheme has failed. (Loss of load provided by the distance algorithms. phase-phase or phase-neutral voltage
schemes are applicable only where Overcurrent elements operate correctly elements. Two independent stages with
three pole tripping is employed.) for close-up three phase faults as they definite time elements are available,
use the superimposed Delta elements one of the stages can also be
for the directional decision. configured to an inverse characteristic.

5
Broken conductor
The broken conductor protection
detects unbalanced conditions caused
by broken conductors, maloperation of
single phase switchgear or by single
phasing conditions.

Supervisory Functions
Circuit breaker failure protection
Circuit breaker failure protection may
be used for backtripping upstream
circuit breakers, and/or for retripping
via a second breaker trip coil when a
local breaker failure is detected.
The circuit breaker failure logic may
also be initiated externally from other
protection devices if required.

Voltage transformer supervision


(VTS)
Figure 4: Programmable scheme logic (MiCOM S1)
Voltage transformer supervision is
provided to detect loss of one, two or
three VT signals, providing indication Autoreclose with synchronism illustrated in Figure 4. The required
and inhibition of voltage dependent check logic is drawn as shown and is then
protection elements. An opto-input may The P441 provides three pole multi- downloaded directly into the relay.
also be configured to initiate the shot (up to 4 shots) autoreclose with The total scheme operation is shown
voltage transformer supervision alarm optional synchronism check. clearly and there is no need for
and blocking when used with MCBs or complex Boolean formulas. The logic
other external forms of voltage The P442 provides one and three pole
may also be uploaded from the relay
transformer supervision. multi-shot (up to 4 shots) autoreclose
and then modified using MiCOM S1.
with optional synchronism check.
The logic is as follows:
For both models, the user may select a MiCOM Z-Graph
single, two, three or four shot MICOM Z-Graph allows downloading
U0 autoreclose cycle, with independently distance protection settings from the
settable dead times and reclaim time. relay and displaying the tripping
I0
IMAX & 1 or 2 VT signals
failed
The check synchroniser offers
independent settings for manual
characteristic for all 4 groups.
The user can modify the distance
I2 closing and autoreclosing. (Check settings and upload the new
synchronism is an optional extra which configuration into the relay.
should be specified at the time of Conversion to Rio format is also
ordering). available.
U<
I
& 3 VT signals failed
Programmable scheme logic
Programmable scheme logic allows the
user to customise the protection and
Current transformer supervision control functions. It is also used to
(CTS) program the functionality of the opto-
Current transformer supervision is inputs, relay outputs and LED
provided to detect loss of phase CT indications.
signals and inhibit the operation of The programmable scheme logic
current dependent protection elements. comprises 256 gate logic and 8
This is achieved by detecting the general purpose timers. The gate logic
presence of residual current in the includes OR, AND and majority gate
absence of residual voltage. functions, with the ability to invert the Independent protection
inputs and outputs, and provide
setting groups
Control feedback. The system is optimised to
evaluate changes to the scheme logic The settings are divided into two
Circuit breaker control
signals and thus avoid unnecessary categories; protection settings, and
Circuit breaker control is available control and support settings.
from the front panel user interface, signal processing.
Four setting groups are provided for
opto-inputs and remotely via the The programmable scheme logic may the protection settings to allow for
substation communications. be configured using the graphical different operating conditions and
MiCOM S1 PC based software, as adaptive relaying.

6
Measurement and
Recording Facilities
The P440 series is capable of
measuring and storing the values of a
wide range of quantities. All events,
fault and disturbance records are time
tagged to a resolution of 1ms using an
internal real time clock. An IRIG-B port
is also provided in the P442 relay for
accurate time synchronisation.
A lithium battery provides a back-up
for the real time clock and all records
in the event of supply failure.
This battery is supervised and easily
replaced from the front of the relay.

Measurements
The measurements provided, which
may be viewed in primary or
secondary values, can be accessed by Figure 5: Disturbance record analysing (MiCOM S1)
the back-lit liquid crystal display, or
the communications ports. Event records Disturbance records can be extracted
Phase notation is user definable. from the relay via the remote
Up to 250 time-tagged event records
are stored in non-volatile memory, and communications and saved in the
Instantaneous measurements COMTRADE format.
can be extracted using the
Phase voltages Van Vbn Vcn communication ports or viewed on the These records may be examined using
Line voltages Vab Vbc Vca front panel display. MiCOM S1 or any suitable software
Neutral voltage Vn program.
Busbar voltage Fault records
Records of the last 5 faults are stored Switchgear Supervision
Phase currents Ia Ib Ic
in non-volatile memory. Trip circuit monitoring and
Neutral current In
The information provided in the fault supervision
Mutual current Im record includes: Monitoring of the trip circuit in both
Sequence currents and voltages Indication of faulted phase breaker open and closed states.
Frequency Protection operation Supervision of the trip circuit using the
Single and three phase power factor programmable scheme logic.
Active setting group
Active power Wa Wb Wc Fault location Circuit breaker state monitoring
Wtotal
Relay and CB operating time An alarm will be generated if there is
Reactive power VAra VArb VArc
Currents, voltages and frequency a discrepancy between the open and
VArtotal
closed contacts of the circuit breaker.
Apparent power VAa VAb VAc
Disturbance records
VAtotal Circuit breaker condition
The internal disturbance recorder
records: monitoring
Derived values The circuit breaker condition
8 analogue channels,
Peak and average demand: monitoring features include:
W VAr 32 digital channels
monitoring the number of breaker
1 time channel. trip operations
Post Fault Analysis Data is sampled 24 times a cycle. recording the sum of the broken
Fault location 20 disturbance records. current quantity Ix, 1.0 x 2.0
A fault location algorithm provides Maximum duration of each record: monitoring the breaker operating
distance to fault in miles, kilometres, 10.5 seconds. time
ohms or percentage of line. Non-volatile memory. monitoring the number of breaker
A mutual compensation feature is All channels and trigger sources user operations within a predetermined
provided to eliminate the effect of zero configured. period.
sequence mutual coupling from
parallel lines.

7
Direction of forward current flow
P2 P1
A J11
S2 S1 Relay failed
J12
B Watchdog

Power supply
J13
C Relay healthy
A J14
+ J7
48V field voltage
IA C1 J9
5A
Main Processor &

board
A B C C2
C B + J8
C3 1A
48V field voltage
Phase rotation
User Interface J10
N C4 + J2
IB 5A board Auxiliary voltage
n C5 J1
See note 3.
1A See note 5.
See note 4. C6 - fixed scheme logic
a b c C7 - programmable scheme

- analogue quantities acquisition and filtering


IC 5A
C8 logic

IRIG-B board
IRIG-B input
C9 1A - communications (optional)
C10 - user interface Fibre optic
See note 1. IM 5A TX
Communication
C11 for IEC60870-5-103
1A RX (optional)
C12
Direction of for ward current flow
See note 6.
P2 P1 A
A
S2 S1 Input

- thresholds calculation
- protection algorithms
kA, kV , Hz LEDs
B 1 4 0 0
kW , kVA , kV
C C B
Phase rotation
module kW , kV , rh
Sequence compon ents
Fixed LEDs
Measurements
Parallel line - transformer
Protection I
N
> 1 St ON
- 16 bit ADC 250
Event
00:12:00 01/01/99
LEDs
Trip A B C ON
records
12:01 01/01/99
C19
User
5 Fault A-B - C 15ms
Ia = 1000 A programmable LEDs
Fault
VA reports Ib = 1000 A
Ic = 1000 A

C20
Front por t
Co-processor board

20 RS232 Courier
Disturbance
VB records
Rear por t
C21
F18
Courier or
No. trips = 100
VC Breaker Modbus or
monitoring
SUM I2 = 1000 kA F16
C22
CB opt time = 100 ms
RS485 SCN IEC60870-5-103

C23
Notes:
V BUSBAR F1
RL15 F2
1. I M input is for optional mutual See note 2.
C24

Relay output board


F3
compensation of fault locator. Programmable scheme logic RL16 F4
2. V BUSBAR only required if check RL17 F5
synchronism function enabled. D2 F6
L1
D1 F7
3. C.T. connections are shown 1A F8
D4 RL18
connected and are typical only. L2 F9 User
D3
F10 programmable
4. All C.T. connections have integral D6
L3 RL19 F11
shorting. These contacts are made D5 F12
before the internal C.T. circuits are D8
L4 F13
disconnected. F14
User D7 RL20
5. The bridge rectifier is not present on D10 F15
programmable
L5 F16
the 24-48Vdc version. D9
F17
D12 RL21 F18
6. Additional hardware for P442 only
. L6
D11
7. ANSI CODES: D14
L7
21N Ground distance protection, D13 VTS/ G1
3 forward elements, D16 21P 21G RL8
1 reverse element, L8 CTS G2
Relay output board

D15 G3
1 selectable element, RL9
quadrilateral zones 46 50 G4
46
21P Phase distance protection, BC BF RL10 G5
3 forward elements, G6
1 reverse element, 51 G7
1 selectable element, E2 50 50/ G8
RL11 User
quadrilateral zones E1
L9 51 FF G9
programmable
85 Distance protection, E4 G10
L10
communication aided
E3 85 50N/ 50/ RL12 G11
G12
50 Phase overcurrent, High set, E6 51N 27
for Stub bus application L11 G13
E5 RL13 G14
67/46 Negative sequence
overcurrent E8 67 67N 78 G15
User L12
50/27 Switch onto fault and trip on E7 G16
programmable E10 G17
reclose RL14 G18
50/51 Phase overcurrent, DT or See note 6. E9
L13
59 27 25/
IDMT E12 79
50/51N Stand-by Earth fault, DT or L14
E11 H1
IDMT F14 RL1
H2
51FF Fuse failure overcurrent L15 See note 7.
Relay output board

E13 H3
67 Phase directional overcurrent RL2
E16 H4
67N Directional Earth fault, L16
E15 H5
communication aided RL3 H6
78 Power swing detection, used H7
to selectively permit or block H8
tripping Opto input RL4
H9 User
programmable
VTS Voltage transformer H10
supervision board RL5 H11 See note 6.
CTS Current transformer H12
supervision H13
50BF Breaker failure and backtrip H14
RL6
H15
46BC Broken conductor detection
H16
25 Check synchroniser H17
RL7
79 Autorecloser H18
59 Overvoltage
27 Undervoltage

Figure 6: System overview of the P442 relay

8
Local and Remote of reliability. The results of the self-test User Interface
functions are stored in non-volatile
Communications The front panel user interface
memory. Test features available on the comprises:
Two communication ports are user interface provide examination of
available; a rear port providing input quantities, states of the digital 1
remote communications and a front inputs, relay outputs and selected 6
port providing local communications. internal logic. A local monitor port
providing digital outputs, selected from 3
Remote communications
a prescribed list of signals, including
The remote communications are based 2
the status of protection elements, may
on RS485 voltage levels. Any of the 5
be used in conjunction with test
protocols listed below can be chosen
equipment. These test signals can also
at the time of ordering, for easy 4
be viewed using the Courier and
system integration such as
Modbus communications ports.
MiCOM S10, PSCN, SPACE 2000 7
and other SCADA or integrated 8
Hardware Description
protection control packages.
All models within the MiCOM P440
series include: (1) A 2 x 16 character back-lit liquid
Courier/K-Bus
crystal display.
The Courier language is a protocol A back-lit liquid crystal display
which has been developed specifically (2) Four fixed function LEDs.
12 LEDs
for the purpose of developing generic An optional IRIG-B port (3) Eight user programmable LEDs.
PC programs that will, without An RS232 port (4) Menu navigation and data entry
modification, communicate with any An RS485 port keys.
device using the Courier language. (5) "READ" ; and "CLEAR" C keys
A download/monitor port
A battery (supervised) - time function for viewing and acknowledging
Modbus
only alarms.
Modbus is a master/slave protocol,
whereby the master must have N/O and N/C watchdog contacts (6) An upper cover identifying the
knowledge of the slave's databases Supervised 48V field voltage product name.
and addresses. The MiCOM P440 1A/5A dual rated CTs The cover may be raised to
series is implemented in Modbus RTU provide access to the product
The case variations between the model number, serial number
mode. MiCOM P441 and P442 models are: and ratings.
IEC 60870-5-103 (7) A lower cover concealing the
P441 P442
The relay is compliant with the front RS232 port, down
transmission protocol defined by the Opto-inputs 8 16 load/monitor port and battery
specification IEC 60870-5-103. Relay outputs 6 N/O 9 N/O compartment.
8 C/O 12 C/O
An optional fibre optic interface is The front of the cover displays
available for this protocol. the name of the product, but may
The opto-inputs, relay outputs and 8 of
The standardised messages based on also be customised to display a
the LEDs are preconfigured as a
the VDEW communication protocol are user defined name.
default, but may be re-programmed by
supported. the user. The opto-inputs are (8) Facility for fitting a security lead
independent and may be powered seal.
Local communications
from the 48V field voltage available
The front serial communications port from the relay. The relay outputs may
has been designed for use with be configured as latching or self reset.
MiCOM S1 software, which fully All CT connections have integral
supports functions within the relay by shorting.
providing the ability to program the
settings off-line, configure the System
frequency
Other default
displays Three-phase
voltage
programmable scheme logic, extract Alarm
messages
Date and
and view event, disturbance and fault time

records, view the measurement


information dynamically and perform
control functions. ALSTOMs PAS&T Column 1 Column 2
Column n
Group 4
System data Other column
can also be used with the local Figure 7: Menu structure View records
headings
Distance Elts

communications port. Data 1.1 Data 2.1 Data n.1


Language Last record Line Setting
MiCOM S1 and PAS&T softwares are Note:

provided separately. Data 1.2 Data 2.2


The C key will return
to column header Data n.2
Password Time and date from any menu cell Line Length

Diagnostics Other setting Other setting Other setting


cells in cells in cells in
Automatic tests performed including column 1 column 2 column n

power-on diagnostics and continuous Data 1.n


Password
Data 2.n
Reset Data n.n
kZm Angle
Indication
self-monitoring ensure a high degree level 2

9
The user interface and menu text are Outputs: Digital inputs
available in English, French, German Field voltage supply Optically isolated inputs may be
and Spanish as standard. Labels 48V dc (current limit: 112mA) energised from the supervised 48V
supplied with the device allow field voltage provided or an external
customised descriptions of the LEDs. Burdens battery.
A user selectable default display DC auxiliary voltage Operating voltage >30V dc
provides measurement information, 15VA typical (P441)
18VA typical (P442) Max. input voltage 60V dc
time/date, protection functions and
plant reference information. The ability AC auxiliary voltage AC immunity 50V rms
to customise the menu text and alarm 16W typical (P441) Contacts
descriptions is also supported. 19W typical (P442)
Contact ratings:
Optically isolated inputs Make: 30A and carry for 3s
Password protection 0.24W per input at 48V
Carry: 5A continuous
Password protection may be Nominal voltage circuit
independently applied to the front user Break: dc 50W resistive
Un 100 120V <0.03VA at 110V
interface, front communications port 25W inductive
Nominal current circuit (L/R = 40ms)
and rear communications port.
Phase and neutral
Two levels of password protection are ac 1250VA resistive
<0.04VA at 1A
available providing access to the <0.4VA at 5A ac 1250VA inductive
controls and settings respectively. (P.F. = 0.5)
Thermal withstand Subject to maxima of 5A and 300V
Technical Data AC current inputs Watchdog contact ratings
4.0 In continuous dc 30W resistive
Operating time 30 In for 10s dc 15W inductive
Distance protection: 100 In for 1s
(L/R = 40ms)
18ms minimum AC voltage inputs ac 375W inductive
22ms typical at 60Hz 2 Vn continuous
(P.F. = 0.7)
25ms typical at 50Hz 2.6 Vn for 10s
Durability:
Drop-off time 18ms at 60Hz Current transformer Loaded contact
22ms at 50Hz requirements 10,000 operations minimum
Overcurrent protection: For Class X current transformers : Unloaded contact
10ms minimum Vk = IF (1 + X/R)(RB + RCT + RL) 100,000 operations minimum
Breaker failure protection: Where:
Rear communications port
Reset time <15ms IF = The maximum secondary
Connection
fault current at the relay
Accuracy Multidrop (32 units)
Zone 1 reach point.
Distance protection: 5% Cable type
X/R = The primary system ratio.
Screened twisted pair
Fault locator: 3% RB = The relay burden.
Cable length 1000m max
Ratings RCT = The CT secondary winding
Connector Screw terminals
resistance.
Inputs: Signal levels RS485
RL = The resistance of the cable
AC current (In) connection the relay to the Isolation SELV
1A - 5A dual rated ac rms CTs, (lead and return for Remote access
AC voltage (Vn) earth faults, lead only for Transmission rate:
80 - 140V rms phase faults.) 9600, 19200 or 38400 bits/s.
nominal phase-phase For IEC class 5P protection current
transformers: Protocols supported
Rated frequency 50/60Hz
[(VA.ALF)/In] + [RCT.ALF.In)> Courier
Operative range 45Hz to 65Hz
IF(1 + X/R)(RB + RCT + RL) Modbus
Auxiliary voltage (Vx)
Where:
IEC 60870-5-103
VA = burden
Note: An interface to an optical
Nominal ALF = accuracy limit factor
Operative range fibre, type 850nm, BFOC 2.5
(V) connector is available for
dc dc ac IEC 60870-5-103.
24 - 48 19 to 65
48 - 110 37 to 150 24 to 110
110 - 250 87 to 300 80 to 265

10
Front communications port High voltage impulse Electrostatic discharge
Connection Point to point IEC 60255-5: 1977 IEC 60255-22-2: 1996 Class 4
Cable type Multi-core Three positive and three negative 15kV discharge in air to user
impulses of 5kV peak, 1.2/50s, interface, display and exposed
Cable length 15m max
0.5J between all terminals and all metal work.
Connector RS232 DTE
9 pin D-type female terminals and case earth. IEC 60255-22-2: 1996 Class 3
Protocol Courier This is not applicable to the front 8kV discharge in air to all
RS232 and download/monitor communication ports. 6kV point
Isolation ELV
ports. contact discharge to any part of the
Local access front of the product.
Transmission rate: Electrical environment
Surge immunity
9600, 19200 or 38400 bits/s. DC supply interruption
IEC 61000-4-5: 1995 Level 4
IRIG-B Port IEC 60255-11: 1979
4kV peak, 1.2/50s between all
Carrier signal The unit will withstand a 20ms groups and case earth.
Amplitude modulated interruption in the auxiliary supply,
in its quiescent state, without de- 2kV peak, 1.2/50s between
Cable type terminals of each group.
energising.
50 ohm coaxial cable EMC compliance
Connection BNC AC ripple on dc supply
Isolation SELV IEC 60255-11: 1979 89/336/EEC
The unit will withstand a 12% ac
Internal battery ripple on the dc supply. Compliance to the European
Commission Directive on EMC is
Battery type: 1/
2 AA, 3.6V AC voltage dips and short claimed via the Technical
Battery life: >5 years interruptions Construction File route.
With auxiliary supply removed: IEC 61000-4-11: 1994 Generic Standards were used to
1 year 20ms interruptions/dips. establish conformity:
High frequency disturbance EN50081-2: 1994
Download/monitor port EN50082-2: 1995
IEC 60255-22-1: 1988 Class III
This is a 25 pin D-type female At 1MHz, for 2s with 200 source Product safety
connector located on the front user impedance:
interface and is specifically 73/23/EEC
designed for test purposes and 2.5kV peak between independent
software download. circuits and independent circuits Compliance with European
and case earth. Commission Low Voltage Directive.
Isolation ELV
1.0kV peak across terminals of the Compliance is demonstrated by
Local access same circuit. reference to generic safety
High voltage withstand Fast transient disturbance standards:
Dielectric withstand IEC 60255-22-4 : 1992 Class IV EN61010-1: 1993/A2: 1995
IEC 60255-5: 1977 4kV, 2.5kHz applied directly to EN60950: 1992/A11: 1997
2kV rms for 1 minute between all auxiliary supply Atmospheric environment
case terminals connected together 4kV, 2.5kHz applied to all inputs.
Temperature
and the case earth.
Surge withstand capability IEC 60255-6:1988
2kV rms for 1 minute between all
IEEE/ANSI C37.90.1 (1989) Operating 25C to +55C
terminals of independent circuits
with terminals on each independent 4kV fast transient and 2.5kV Storage 40C to +70C
circuit connected together. oscillatory applied directly across
Transit 25C to +70C
each output contact, optically isolated
ANSI/IEEE C37.90-1989 (r1994) IEC 60068-2-1: 1990/A2:1994
input and power supply circuit.
1kV rms for 1 minute across the Cold
open contacts of the watchdog Radiated immunity
IEC 60068-2-2: 1974/A2:1994
relays. C37.90.2: 1995 Dry heat
1kV rms for 1 minute across open 25MHz to 1000MHz, zero and
Humidity
contacts of changeover output 100% square wave modulated.
relays. IEC 60068-2-3: 1969
Field strength of 35V/m.
1.5kV rms for 1 minute across 56 days at 93% RH and +40C
Conducted immunity
open contacts of normally open Enclosure protection
output relays. IEC 61000-4-6: 1996 Level 3
IEC 60529: 1989
10V, 150kHz to 80MHz at 1kHz
80% am IP52 Protection (front panel) against
dust and dripping water at 15 to
the vertical.

11
Mechanical environment
23.30 155.40 8 off holes Dia. 3.4
Vibration
A B BA
IEC 60255-21-1: 1996 Sealing strip
177.0
Response Class 2 159.00 168.00 (4U)
Endurance Class 2 AB BA

Shock and bump 10.35 181.30 483 (19 rack)


202.00
IEC 60255-21-2: 1995 Flush mounting panel
A = Clearance holes
Shock response Class 2 B = Mounting holes
Panel cut-out detail
Shock withstand Class 1
200.00 Note: If mounting plate
Seismic is required use flush
IEC 60255-21-3: 1995 Class 2 mounting cut out dimensions

Cases All dimensions in mm

P441 MiCOM 40TE


P442 MiCOM 60TE
Secondary cover (when fitted)
Weight Front view 240.00
Incl. wiring
P441 c.7.7 kg
P442 c.9.4 kg
177.00 157.5 max
Additional information
MiCOM P441 & P442 Side view
206.00 30.00
Service Manual SM1.1671
(TG1.1671
+
OG1.1671) Figure 8: Case size P441 (40TE)
Courier Communications R4113
MiCOM S1 User Manual R8610
Midos Parts Catalogue Sealing
116.55 142.45 12 off holes Dia. 3.4
and Assembly Instructions R7012 23.25 strip

PAS&T R8514 AB A B BA
168.00

177.0
159.00 (4U)
Case
AB B A BA
The MiCOM P440 series relays are
10.30 155.40 129.50
housed in a specially designed case 483 (19 rack)
305.50
providing a high density of A = Clearance holes
functionality within the product, a B = Mounting holes
303.50
customisable user interface, additional
functions and information concealed
by upper and lower covers. All dimensions in mm
Physical protection of the front panel
user interface and prevention of casual
access is provided by an optional
transparent front cover, which can be Secondary cover (when fitted)
fitted or omitted according to choice, 240.00
Front view Incl. wiring
since the front panel has been
designed to IP52 protection against
dust and water.
177.00 157.5 max
The case is suitable for either rack or
panel mounting as shown in Figures 8
and 9. Side view
309.60 30.00

Figure 9: Case size P442 (60TE)

12
MiCOM P442 Specification Time-tagged event, fault and A complete software package shall
disturbance records shall be stored in be able to provide support for local
An integrated distance protection and non-volatile memory. The internal and remote programming, and
autoreclose scheme shall provide one disturbance recorder shall have a extraction of records from the device.
and three phase protection for two capacity to store 20 records, each
and three terminal applications, with record shall store sampled data from
faulted phase and fault value 8 analogue and 32 digital channels
indications. An integral four shot, one over a period of 10 seconds.
and three pole autorecloser shall
support synchronism check. The relay
must have a five zone characteristic
with an independent settable earth
fault coefficient per zone. Resistance Information Required with Order
reach for phase and earth fault
protections shall be independently
settable with provision being made
Relay type MiCOM P 4 4 1 A 0 0 0 0 A
for non-homogeneous lines or
Distance Protection Relay
transformer protection.
Relay operating time for faults in the
Version
pilot zone or for faults within zone 1 3 pole tripping/reclosing, 1
reach shall be less than 1.5 cycle. 8 opto inputs, 14 relay outputs, no IRIG-B
Distance phase selection and 1 & 3 pole tripping/reclosing, 16 opto inputs,
2
21 relay outputs, IRIG-B & Fibre optic converter options
directionality shall operate correctly
for evolving faults between phases, Vx auxiliary rating
between forward and reverse 24 - 48V dc 1
directions and between parallel lines 48 - 110V dc (30 - 100V ac) 2
(cross-country faults). 110 - 250V dc (100 - 240V ac) 3

In addition to distance protection, the Hardware options


relay shall include instantaneous Standard version 1
overcurrent protection for close-up IRIG-B input (P442 only) 2
fault, stub bus protection, SOTF/TOR Fibre optic converter (IEC 60870-5-103) (P442 only) 3
protection, under/overvoltage IRIG-B input & Fibre optic converter (IEC 60870-5-103) (P442 only) 4
protection, breaker failure protection, Software options
power swing selective blocking, Without check synchronising A
parallel line compensation, and a With check synchronising B
comprehensive range of IEC and
Protocol options
ANSI/IEEE compatible pilot schemes
K-Bus 1
for distance and DEF, and back-up
Modbus 2
including a comprehensive selection
of IEC and ANSI/IEEE compatible IEC 60870-5-103 (VDEW) 3

IDMT characteristics for phase and


earth fault overcurrent protection. Software type MiCOM S 1 A0 A
Maximised protection availability Setting software
shall be provided through extensive
self-monitoring, self-test and CT/VT Options
supervision. Internal three-phase VT Base version (Settings editor, Monitoring, PSL editor, Menu text editor) 1
supervision shall be provided. Base version + Disturbance Analyser and Archiver 2
Flexible programmable scheme logic Note : Our policy is one of continuous product development.
shall be provided in order to allow The order code for MiCOM S1 may be subject to change.
the user to customise the protection
and control functions, using a
Please quote
graphical interface software. Accessories
on order
Programming of the device shall be
Rack frame (in accordance with CEI 60297). FX0021 001
possible using a front panel user
Case to rack sealing gaskets are available to improve the overall IP rating
interface, local and remote of the panel, (10 per order) GN2044 001
communications ports. The front panel
M4 90 pre-insulated ring terminals:
user interface shall provide Blue - Wire size 1.04 to 2.63mm 2 (100 per order) ZB9124 900
independent keys for the viewing and Red - Wire size 0.25 to 1.65mm 2 (100 per order) ZB9124 901
acknowledgement of alarms. Secondary cover: P441 Size 40TE GN0037 001
A comprehensive range of P442 Size 60TE GN0038 001
measurement values shall be Blanking plates: Size 10TE GJ2028 002
available for viewing on the user Size 20TE GJ2028 004
interface and the communication Size 30TE GJ2028 006
Size 40TE GJ2028 008
ports.

13
Protection Setting Ranges
1000 100
Distance protection element

Setting Setting range Step size


Line setting 100

Line Length 0.3 km (0.2 mile) 0.010 km 10

- 1000 km (625 miles) (0.005 m)

Operating time (s)

Operating time (s)


Line Impedance 0.001 - 500 0.001 10
Line Angle 90 - + 90 1 UK LTI

Zone setting
IEC SI 1
Zone Status Bit 0: Z1X Enable, Bit 1: Z2 IEEE MI

Enable, Bit 2: Zp Enable, Bit 3: Z3 1 IEEE VI


IEC VI
Enable, Bit 4: Z4 Enable. US CO2

KZ1 Res Comp 0-7 0.001 US CO8


IEC EI IEEE EI
KZ1 Angle 180 - +180 0.1
0.1 0.1
Z1 0.001/In - 500/In 0.001/In 1 10 100 1 10 100

Z1X 0.001/In - 500/In 0.001/In I


Current (Multiple of s) I
Current (Multiple of s)

R1G 0 - 400/In 0.01/In IEC/UK curves IEEE/US curves


R1Ph 0 - 400/In 0.01/In
TMS = 1 TD = 7
tZ1 0 - 10s 0.002s 0.14 TD 0.0515
IEC Standard inverse t = TMS x IEEE Moderately t= x 0.02
+ 0.114
KZ2 Res Comp 0-7 0.001 I
0.02
1 inverse 7 I 1
Is Is
KZ2 Angle 180 - +180 0.1
Z2 0.001/In - 500/In 0.001/In 19.61
13.5 TD
R2G 0 - 400/In 0.01/In IEC Very inverse t = TMS x IEEE Very inverse t=
7
x
I
2
+ 0.491
Is 1
I
Is 1
R2Ph 0 - 400/In 0.01/In
tZ2 0 - 10s 0.01s
80 TD 28.2
KZ3/4 Res Comp 0-7 0.001 IEC Extremely inverse t = TMS x 2
IEEE Extremely t= x 2
+ 0.1217
I inverse 7 I
KZ3/4 Angle 180 - +180 0.1 Is 1 Is 1
Z3 0.001/In - 500/In 0.001/In
R3G - R4G 0 - 400/In 0.01/In UK Long time inverse t = TMS x
120
US CO8 Inverse t=
TD
x
5.95
+ 0.18
2
7
R3Ph - R4Ph 0 - 400/In 0.01/In I
Is 1
I
Is 1
tZ3 0 - 10s 0.01s
Z4 0.001/In - 500/In 0.001/In TD 0.02394
US CO2 Short t= x 0.02
+ 0.01694
tZ4 0 - 10s 0.01s time inverse 7 I
Is 1
Zone P Direct. Forward or Reverse
KZp Res Comp 0-7 0.001
KZp Angle 180 - +180 0.1 Figure 10 - IDMT curves
Zp 0.001/In - 500/In 0.001/In
RpG 0 - 400/In 0.01/In
Setting Setting range Step size Setting Setting range Step size
RpPh 0 - 400/In 0.01/In
tZp 0 - 10s 0.01s Distance carrier None, Permissive Z1, Loss of Load
receive Permissive Z2, Permissive Forward, Mode Status Disabled or Enabled
Fault Locator
Block Z1, Block Z2. Chan. Fail Disabled or Enabled
KZm Mutual Comp 0 - 7 0.001
Tp 0 - 1s 0.002s I< 0.05 x In - 1 x In 0.05 x In
KZm Angle 180 - +180 0.1
tReversal Guard 0 - 0.15s 0.002s Window 0.01s - 0.1s 0.01s
TOR-SOTF Mode Bit 0: TOR Z1 Enabled,
Channel-aided schemes
Bit 1: TOR Z2 Enabled, Power swing blocking
Setting Setting range Bit 2: TOR Z3 Enabled, Setting Setting range Step size
Distance Schemes Bit 3: TOR All Zones Enabled,
Bit 4: Dist. Scheme Enabled, Delta R 0 - 400/In 0.01/In
Program Mode Standard Scheme, open Scheme Delta X 0 - 400/In 0.01/In
Bit 5: SOFT All Zones,
Standard Mode Basic + Z1X, POP Z1, IN> Status Disabled or Enabled
Bit 6: SOFT Level Detectors.
POP Z2, PUP Z2, PUP Fwd,
BOP Z1, BOP Z2. Z1 Ext. /Chan. Fail Disabled or Enabled IN> (% Imax) 10% - 100% 1%
Weak Infeed Imax line> Status Disabled or Enabled
Fault Type Phase to Ground, Phase to Phase,
Both Enabled. Mode Status Disabled, Echo, Trip & Echo. Imax line> 10% - 100% 1%

Trip Mode Force 3 Poles, Single Pole Trip Disabled or Enabled I Phase>Status Disabled or Enabled
1 Pole Z1 & Carrier receive, V< Thres. 10V - 70V 5V I Phase > 1 x In - 20 x In 0.01 x In
1 Pole Z1 Z2 & Carrier receive. Trip Time Delay 0 - 1s 0.002s Unblock. Delay 0 - 30s 0.1s
Signal Send Zone None, CsZ1, CsZ2, CsZ4. Blocked Zones Bit 0: Z1&Z1X Block, Bit 1: Z2
Block, - Bit 2: Z3 Block, Bit 3: Zp
Block.

14
Overcurrent Protection Voltage transformer supervision
Setting Setting range Step size Setting Setting range Step size Setting Setting range Step size
I>1 Function DT or IDMT (see Figure 8) IN>2 VTS Block Block or Non directional VTS Time Delay 1 - 20s 1s
I>1 Direction Non-Directional, Forward, Reverse IN>2 Current Set 0.08 x In - 32 x In 0.01 x In VTS I2> & I0> 0 - 1 x In 0.01 x In
I>1 VTS Block Block or Non directional IN>2 Time Delay 0 - 200s 0.01s Inhibit
I>1 Current Set 0.08 x In - 4.0 x In 0.01 x In IN>2 Time VTS 0 - 200s 0.01s Detect 3P Enabled or Disabled
I>1 Time Delay 0 - 100s 0.01s IN> Directional Threshold 3P U< 10 - 70V 1V
I>1 Time VTS 0 - 100s 0.01s IN> Char Angle 95 - +95 1 Delta I> 0.01 - 5A 0.01A
I>1 TMS 0.025 - 1.2 0.025 Polarisation Zero Sequence or Negative Sequence
I>1 Time Dial 0.5 - 15 0.1 Current transformer supervision
I>1 Reset Char DT or Inverse Channel-aided D.E.F. Setting Setting range Step size
I>1 tReset 0 - 100s 0.01s Setting Setting range Step size CTS Status Enabled or Disabled
I>2 Function DT or IDMT (see Figure 8) Aided DEF Status Disabled or Enabled CTS VN< Inhibit 0.5 - 22V 0.5 V
I>2 Direction Non-Directional, Forward, Reverse Polarisation Zero Sequence or Neg. Sequence CTS IN> Set 0.08 x In - 4 x In 0.01 x In
I>2 VTS Block Block or Non directional V>Voltage set 0.05 - 20V 0.05V CTS Time Delay 0 - 10s 1s
I>2 Current Set 0.08 x In - 4.0 x In 0.01 x In IN Forward> 0.05 x In - 4 x In 0.01 xIn
I>2 Time Delay 0 - 100s 0.01s Time Delay 0 - 10s 0.1s Check synchronisation
I>2 Time VTS 0 - 100s 0.01s Scheme Logic Shared, Blocking or Permissive Setting Setting range Step size
I>2 TMS 0.025 - 1.2 0.025 Tripping Three Phase or Single Phase C/S Check Bit 0: Live Bus / Dead Line,
I>2 Time Dial 0.5 - 15 0.1 Scheme for A/R Bit 1: Dead Bus / Live Line,
I>2 Reset Char DT or Inverse Voltage protection Bit 2: Live Bus / Live Line.
I>2 tRESET 0 - 100s 0.01s C/S Check Bit 0: Live Bus / Dead Line,
Setting Setting range Step size
I>3 Status Disabled or Enabled Scheme for Man Bit 1: Dead Bus / Live Line,
V< & V> Mode Bit 0: V<1 Trip, Bit 1: V<2 Trip,
I>3 Current Set 0.08 x In - 32 x In 0.01 x In CB Bit 2: Live Bus / Live Line.
Bit 2: V>1 Trip, Bit 3: V>2 Trip
I>3 Time Delay 0s - 100s 0.01s V< Dead Line 5 - 30V 1V
Undervoltage
I>4 Status Disabled or Enabled V> Live Line 30 - 120V 1V
Setting Setting range Step size
I>4 Current Set 0.08 x In - 32 x In 0.01 x In V< Dead Bus 5 - 30V 1V
V< Measurt Mode Phase-Phase or Phase-Neutral
I>4 Time Delay 0s - 100s 0.01s V> Live Bus 30 - 120V 1V
Diff Voltage 0.5 - 40V 0.1V
V<1 Function Disabled, DT or IDMT
Negative sequence overcurrent Diff Frequency 0.02 - 1Hz 0.01Hz
V<1 Voltage Set 10 - 120V 1V
Setting Setting range Step size Diff Phase 5 - 90 2.5
V<1 Time Delay 0 - 100s 0.01s
I2> Status Disabled, Enabled Bus-Line Delay 0.1 - 2s 0.1s
V<1 TMS 0.5 - 100 0.5
I2> Directional Non-Directional, Forward, Reverse V<2 Status Enabled or Disabled
I2> VTS Block, Non-Directional Autoreclose
V<2 Voltage Set 10 - 120V 1V
I2> Current Set 0.08In - 4In 0.01In V<2 Time Delay 0 - 100s 0.01s Setting Setting range Step size
I2> Time Delay 0s - 100s 0.01s V<2 Poledead Inh Enabled or Disabled 1P Trip Mode 1, 1/3, 1/3/3, 1/3/3/3.
I2> Char Angle 95- +95 1 Overvoltage 3P Trip Mode 3, 3/3, 3/3/3, 3/3/3/3.
V> Meast Mode Phase-Phase or Phase-Neutral 1P Rcl - DT 1 0.1 - 5s 0.01s
Broken conductor detection 3P Rcl - DT 1 0.1 - 60s 0.01s
V>1 Function Disabled, DT or IDMT
Setting Setting range Step size V>1 Voltage Set 60 - 185V 1V Dead Time 2 1 - 3600s 1s
Broken Conductor Enabled/Disabled V>1 Time Delay 0 - 100s 0.01s Dead Time 3 1 - 3600s 1s
I2/I1 0.2 - 1 0.01 V>1 TMS 0.5 - 100 0.5 Dead Time 4 1 - 3600s 1s
I2/I1 Time Delay 0s - 100s 0.1s V>2 Status Enabled or Disabled Reclaim Time 1 - 600s 1s
V>2 Voltage Set 60 - 185V 1V Close Pulse 0.1 - 10s 0.01s
Earth fault protection V>2 Time Delay 0 - 100s 0.01s A/R Inhibit Wind 1 - 3600s 1s
Autoreclose Lockout
Setting Setting range Step size
Circuit breaker failure Block A/R Bit 0: At tZ2,
IN>1 Function DT or IDMT (see Figure 8)
Bit 1: At tZ3,
IN>1 Direction Non-Directional, Forward, Reverse Setting Setting range Step size Bit 2: At tZp,
IN>1 VTS Block Block or Non directional Breaker Fail Bit 3: LoL Trip,
IN>1 Current Set 0.08 x In - 4.0 x In 0.01 x In CB Fail 1 0 - 10s 0.005s Bit 4: I2> Trip,
IN>1 Time Delay 0 - 200s 0.01s CB Fail 2 0 - 10s 0.005s Bit 5: I>1 Trip,
IN>1 Time VTS 0 - 200s 0.01s CBF Non I Reset I< Only, CB Open & I<, Bit 6: I>2 Trip,
IN>1 TMS 0.025 - 1.2 0.025 Prot Reset & I< Bit 7: V<1 Trip,
IN>1 Time Dial 0.5 - 15 0.1 CBF Ext Reset I< Only, CB Open & I<, Bit 8: V<2 Trip,
IN>1 Reset Char DT or Inverse Prot Reset & I< Bit 9: V>1 Trip,
Bit 10: V>2 Trip,
IN>1 tRESET 0 - 100s 0.01s Undercurrent
Bit 11: IN>1 Trip,
IN>2 Status Disabled or Enabled I<Current set 0.05 x In - 3.2 x In 0.01 x In
Bit 12: IN>2 Trip,
IN>2 Direction Non-Directional, Forward, Reverse
Bit 13: Aided DEF Trip.

15
TRANSMISSION & DISTRIBUTION Protection & Control, HQ, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex, France
Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: pcs.enquiries@tde.alstom.com Internet: www.alstom.com

2000 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
Other names mentioned, registered or not, are the property of their respective companies.

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication N1 1671C 110020 CPS Printed in England

You might also like