person or animal can experience when they inadvertently get between an electrically
energized point and ground can be something of a mystery. Stories are told of cows that
won't give milk, dogs that avoid metallic grates and manhole covers, and folks getting an
unusual wake-up call when they step into their hot tub or backyard pool. However, despite
the esoteric nature of nuisance shocking, the science necessary for understanding it and
mitigating it has advanced significantly in recent years. Also, the various mechanisms that
can lead to nuisance shocking are now better recognized. This article provides insights on the
utility distribution system aspects of nuisance shocking, first defining the sources of these
voltages and then discussion of both traditional and new techniques for mitigating the
problem once it has been identified.
Each of these terms is defined in the following paragraphs, along with some insight into their
most common causes. With an understanding of the terminology and what causes each
condition, useful mitigation techniques can be discussed.
Remote earth is defined as an earthing or grounding point that is at the same voltage potential
as other points on the earth in the surrounding area. Electrical current flowing through
grounding or neutral conductors, or even through earth itself, will cause voltage variation
from point to point. The remote earth point is hypothetically beyond or outside of the
influence of these current paths. Thus, the remote earth point is at zero potential with respect
to the voltage source and provides a consistent and repeatable reference point.
Stray voltage from intentional actions. The U.S. Department of Agriculture Publication 696
defines stray voltage as a small voltage (less than 10 V) that can develop between two
possible contact points. Contact points are generally considered to be points close enough
between the voltage source and a remote earth path that would allow a current to flow
through any human, animal or other object that contacts both points simultaneously. Another
important note about Publication 696 is that the document summary states: While stray
voltage cannot totally be eliminated, it can certainly be reduced to an acceptable level. While
this definition focuses primarily on NEV sources, which result from the intentional grounding
of the power system neutral conductor, many cases have been identified where improper
wiring and load faults on the customer side of the meter contribute to the measured voltages.
Stray voltage from unintentional actions. The New York Public Utility Commission uses the
term stray voltage to describe the unintentional or accidental energization of manhole
covers, street lamps and other urban street-level metallic objects. This definition focuses
on MOEV sources such as contact with the power system phase conductor, or in some cases as
the result of induced voltages from electric fields.
While the previous two definitions have created some confusion, the common element is that
stray voltage could be considered an undesirable voltage potential across any two points that
can be simultaneously contacted by an animal or a human. In summary, to develop a stray
voltage we can consider the following sources: 1) currents flowing on primary and secondary
neutral conductors; 2) faulted-phase conductors; and 3) induced voltages from currents
flowing through power lines.
Remediation
There is a distinct difference between the causes of an elevated NEV concern and the causes of
an energized metallic object concern. For energized metallic objects, there are obviously no
mitigation techniques, as the objective is to identify and isolate the problem and remove or
repair the source of the energization. Research is presently underway in this area to develop
consistent and repeatable measurement protocols to determine where energized objects are
present so monitoring and protection devices can detect the problem using new diagnostic
instruments such as pen lights and electric field detectors.
For higher-than-acceptable NEV, the mitigation solutions are well understood but can be
challenging to ascertain. Each method has its proven success stories as well as potential
shortcomings. Traditional mitigation techniques include: load balancing, resizing neutral
conductors, isolation, improved grounding techniques and equipotential planes.
Isolation A simple and effective means of keeping stray voltage from getting to animal and
human contact points would be to not jumper the primary and secondary neutral conductors
at the service transformer. If there is no metallic connection, there can be no voltage and no
opportunity for current flow from the primary neutral. The key considerations in removing
the primary to secondary neutral jumper would be the adverse effect on protection of the
load-side of the transformer in the event of a lightning strike, system fault or wiring error.
Therefore, isolation is best accomplished through the use of a separate isolation transformer
or use of neutral isolation products that allow voltages greater than 10 V to be equalized via
low-voltage clamping devices.
Equipotential planes. Similar to the ground-reference structures used for computer rooms
and the ground mats that minimize step potentials at utility substations,
the equipotential plane is a useful means of minimizing nuisance shocking at animal contact
points. An equipotential plane typically consists of a conductive wire mesh installed under the
area where nuisance shocking has been reported, and attaching most (if not all) conductive
materials in the area directly to the mesh. The technique does not reduce NEV levels, but
rather moves the problem away from areas where animals are likely to insert themselves into
the conducting path.
While the traditional mitigation techniques discussed above have been successfully and
consistently applied in specific applications, two experimental techniques are noteworthy.
These include distribution level harmonic filters and insulated five-wire distribution systems.
Passive harmonic filters A recent area of research into NEV concern relates
to triplen harmonic currents flowing on distribution system neutral conductors. These odd
multiples of the fundamental 60-Hz current add instead of canceling out on the neutral
conductor, thereby creating harmonic NEV levels. The causes of these harmonic currents
include harmonic generating equipment owned by the end user and circuit resonances created
by distributed capacitor banks. Harmonics due to customer loads is expected to increase over
time as more equipment such as variable frequency drive washers and air conditioning
equipment proliferate and as more televisions, PCs and other home entertainment equipment
use increases.
While filters for harmonic load mitigation is not necessarily a new concept, applying passive
harmonic filters to mitigate NEV impacts on the entire utility distribution circuit is new. In
under an ongoing research project, EPRI is working with some U.S. electric utilities to
determine how well filters tuned to the third harmonic reduce NEV levels on circuits where
the neutral-to-earth voltages have been found to be nearly all harmonic in makeup. The
approach used is to convert existing distribution capacitor banks to filter banks by employing
a combination of capacitors and one or more inductors. Modeling results demonstrate up to a
fivefold improvement with installation of harmonic filters in conjunction with grounding
modifications. Harmonic filters appear to be a promising way to reduce NEV impacts on the
entire utility distribution circuit instead of at the traditional single point of interest.
The so-called five-wire design is a concept that has been demonstrated to evaluate the
potential to reduce stray voltages and magnetic fields and also make high impedance faults
more easily detectable. The first four wires of this system are the familiar three-phase
conductors plus a neutral. The fifth wire is a new isolated neutral that carries all of the
unbalanced return current, relieving the original neutral of this burden.
The multigrounded ground wire continues to perform the safety functions associated with
a multigrounded system. The five-wire system was tested by EPRI at New York State Electric
and Gas (NYSEG), which converted a section of a circuit in Cooperstown, New York, U.S., to a
five-wire configuration. Benefits included reductions in stray voltages and magnetic fields
along with promising results that high-impedance faults could be detected. Drawbacks
included lack of ability to convert underground systems to the five-wire topology, concerns
that an open neutral would cause overvoltages for customer and utility system equipment, and
the inability to control stray voltage unless the entire circuit is converted over to the five-wire
design.
Although utilities, the government and research organizations have accomplished much to
minimize undesirable voltages with respect to remote earth, additional research and
development will promote a better understanding of the effects of stray voltages and the
methods to minimize these phenomena. To help further this research and to supply credible
and unbiased information on the subject, EPRI has identified a number of different concerns
and topics of interest to include:
Animal contact areas' health and productivity concerns
Residential contact concerns for swimming pools, hot tubs and metallic objects
Contributions of transmission lines to elevated NEV levels at human and animal contact areas
Impacts of nonlinear voltage waveforms and voltage magnitudes on humans and animals
Better understanding of the voltage levels that warrant investigation and remediation.
Of these concerns, the majority can be distilled down into four areas of research related to:
Measurement devices and measurement protocols
Work at EPRI is presently ongoing in each of these areas to supplement and support the needs
of utilities and end users. The largest challenges to date are not in understanding the issues
but in prioritizing the concerns and funding the research. Stray-voltage issues are analogous
to power-quality-related concerns in that when problems are identified, limited resources are
applied to investigate and resolve the concerns. The IEEE has started a working group under
the power engineering society that will be focused on instrumentation and measurement
protocols to standardize efforts in these areas. For more information on the ongoing efforts,
visit http://strayvoltage.epri-peac.com.