Professional Documents
Culture Documents
Use Steel
above: 2 1/2
PIPE INNER DIAMETERS
I.D. " Unit Total
Length Size Type L STD WT Volume Volume
(ft.) COPPER STEEL (gals/ft) (gals)
1/2 0.55 0.622 0.0121 0.0
3/4 0.79 0.824 0.0252 0.0
1 1.03 1.049 0.0429 0.0
1 1/4 1.27 1.38 0.0653 0.0
1 1/2 1.51 1.61 0.0925 0.0
2 1.99 2.067 0.1609 0.0
2 1/2 2.47 2.469 0.2489 0.0
3 2.945 3.068 0.3843 0.0
4 3.905 4.026 0.6617 0.0
5 4.875 5.047 1.0399 0.0
6 5.845 6.065 1.5017 0.0
8 7.725 7.981 2.6004 0.0
10 9.625 10.02 4.0988 0.0
12 11.565 12 5.8787 0.0
14 13.25 7.1673 0.0
16 15.25 9.4942 0.0
18 17.25 12.1478 0.0
20 19.25 15.1280 0.0
24 23.25 22.0682 0.0
26 25.25 26.0282 0.0
30 29.25 34.9279 0.0
SubTotal 0.0
Total
Volume
(gals)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0 Total 0.0
Insert rows for each potentially critical piece of equipment.
Elevation below
the top of the
system (ft).
Should be
Pressure rating (PSI) positive number Difference (PSI)
Boiler 90 90
Air Separator 150 150
Control valve 300 300
Pump 250 250
Other 300 300
Other 300 300
Other 300 300
MINIMUM 90
The CPP is the location on discharge side of the pump of the highlighted equipment above
ted equipment above
LEGEND
INPUT
RESULT
NOTES
System Type HW Sets default values for minimum
Find pressure required to maintain pump NPSH This step can be skipped f
1. NPSHr = ft From pump manufacturer data
0.0 PSIG
2. Pv = -7.1 PSIG The gauge saturation vapor pres
3. Ps, Tank -> Suction = 0.0 ft Elevation difference from the ta
0.0 PSIG
4. Pf, Tank -> Suction = 0.0 ft Frictional pressure drop from the
0.0 PSIG
5. PV, Tank -> Suction = 0.0 ft Difference in velocity pressure a
0.0 PSIG
5. Pf, PRV -> Tank = 0.0 ft Frictional pressure drop from the
0.0 PSIG
Selection (manufacturer/model):
Notes
s default values for minimum and maximum water temperature in rows 55 and 56. Override these if necessary
tional pressure drop from the tank to the LPP. Ignored if the tank is downstream of LPP.
is step can be skipped for all but high temperature (>~210degF) hot water systems and sy
m pump manufacturer data
e gauge saturation vapor pressure of the fluid at its maximum expected temperature. Blue line on chart --> is cu
vation difference from the tank to the pump suction.
erence in velocity pressure at the point of tank connection to the point of suction at the pump. Typically neglig
s is almost always less than Pi, boiling. If you calculated it, you probably didn't have to (see row 18).
s is the required initial pressure of the tank (aka the Precharge Pressure). It's equal to the larger of Pi, boiling, Pi
ault precharge from the factory so it is the minimum for convenience.
ssure rating of the equipment at the Critical Pressure Point (CPP) aka the "weakest link". See CPP tab.
vation difference from the CPP to the PRV. Positive if CPP is above PRV (Pressure Relief Valve).
tional pressure drop from CPP to PRV. Ignored if PRV is upstream of CPP.
tional pressure drop from the PRV to the tank. Ignored if tank is upstream of PRV.
rease in water volume from min. temperature to max. temperature. Tank "Acceptance Volume" must be to thi
al tank volume, equal to the volume of water expansion plus the air cushion necessary to maintain pressure bet
rride these if necessary for your specific system.
t always be the highest point of the return line just after it drops down to the pump.
ater systems and systems where ET and pump suction are very far apart (e.g. campus)
olume" must be to this value. Not an issue for "Full Acceptance" tanks.
to maintain pressure between Pi and Pmax. "Tank Volume" must be to this value.
e.g. campus)